This Datasheet for the IC660BBA103. Block 115Vac/125Vdc Thermocouple Input 6 Channels.

Similar documents
This Datasheet for the IC660BBA026. Block 24/48Vdc Analog Current Source 6 Inputs.

This Datasheet for the IC660BBA104. Block 115Vac/125Vdc Analog Current Source 4 Inputs / 2 Outputs

This Datasheet for the IC660BBA101. Block 115Vac/125Vdc RTD Input 6 Channels.

This Datasheet for the IC660BBA020. Block 24/48Vdc Analog 4 Inputs / 2 Outputs.

This Datasheet for the IC660BBA020. Block 24/48Vdc Analog 4 Inputs / 2 Outputs.

This Datasheet for the IC660BBD110. Block 115Vac Input 16 Circuits.

This Datasheet for the IC660BBD025. Block 5/12/24Vdc Sink I/O 32 Circuits.

This Datasheet for the IC660BBR100. Block Relay Output Normally Closed 16 Circuits.

This Datasheet for the IC660BBD101. Block 115Vac I/O Low Leakage 8 Circuits.

This Datasheet for the IC660BBD022. Block 24Vdc Source I/O 16 Circuits, 2/3 Wire Sensor Compatible

This Datasheet for the IC660BBS103. Block 115Vac/125Vdc Low Leak Isolated I/O, w/o Failed SW Diagnostics, 8 Circuit.

This Datasheet for the IC670ALG310. Analog Output Voltage, 8 Channel, +/-10V, 0 to 10V.

This Datasheet for the IC670GBI002 24VDC BUS INTERFACE UNIT.

Analog Input, 16-Bit Thermocouple Module

VersaMax* Analog Input, 16-Bit Thermocouple Module


This Datasheet for the IC697CHS790. Rack, 9 Slots, Rear Mount.

This Datasheet for the IC660BSM120. BUS Switching Module 115Vac/125Vdc.

Shown with terminal block Supports diagnostic point fault contacts in the logic program

5504 Thermocouple Analog Input Module

This Datasheet is for the IC693ALG390. Memory Backup and Backup Battery.

PV Rapid Shutdown device

PACSystems* RX3i and Series 90*-30 IC694ALG223 and IC693ALG223

CONTROL MICROSYSTEMS Thermocouple Analog Input Module. Hardware Manual

GE Fanuc IC694ALG221. Rx3i PacSystem

ALS c en Alspa CE80 20 N80 Bus Interface Unit User s Manual

Analog Current Input - 16 Channel IC693ALG223. Current Ranges. Power Requirements and LEDs. Location in System. Analog Input Modules

GFK-2415A March Type of sensor connection

GE Fanuc IC694ALG391. Rx3i PacSystem

General Specifications. P2-08THM Analog Input

PACSystems RX3i IC695PSA140

PACSystems* RX3i IC695PSA140

This Datasheet for the IC670MDL VDC 2A Output Pos. Logic 8 Pt. Electronic Short Circuit Protect

PACSystems* RX3i IC694ALG232

This Datasheet for the IC693BEM331. Genius Bus Controller (Supports I/O and Datagrams)

PACSystems* RX3i and Series 90*-30 IC694ALG442-CC and IC693ALG442-EC

Power Supply. Users Guide PRODUCT MANUAL. WESTELL.COM Westell Technologies MNL rd

PLC Racks IC697CHS782/783

ICS Regent. Thermocouple Input Assembly. Input Module, Mux, Termination Panel and Cable (T3431-IM, T3431-Mux, T3431-TP and T3431-CA) PD-6024

This Datasheet for the IC697BEM733. Series Genius Remote I/O Scanner.

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

This Datasheet for the IC670MDL VAC 16 Pt. Input Grouped.

PACSystems* RX3i IC694ALG233

Analog Voltage Combination Module

PACSystems* RX3i IC695PSA040

GE Fanuc IC695ALG708. Rx3i PacSystem

TCP A3. Description. Module with 3 thermocouple inputs. Datasheet

S66 Series Electronic Fan Speed Control

This Datasheet for the IC670MDL VAC 8 Pt. Isolated Input.

Digital ac/dc (24V) Input Module

Current: 0 to 20mA, 4 to 20mA. Voltage: ±10V, 0 to 10V. Isolated +24 VDC Power

This Datasheet for the IC670MDL VDC Pos/Neg Logic Input 16 Pt. Grouped.

Analog Input Installation Manual

INSTALLATION MANUAL SLI 50 INVERTER

Tempco Instruction Manual

Dell SC7020 Storage Controller Getting Started Guide

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

This Datasheet for the IC697BEM721. I/O Link Interface Module for the Series

OPTICAL HEADEND PLATFORM OTOHP-CH 3RU CHASSIS OTOHP-PS POWER SUPPLY MODULE OTOHP-BP BLANK PANEL INSTRUCTION MANUAL

Applications: Power generator sets and control systems for industrial engine applications.

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

Analog Monitor Installation Manual

Mitsubishi Electric Automation Instruction Manual FR-A5AC-01

This Datasheet for the IC670MDL /24VDC 0.5A Output Pos. Logic 16 Pt. Grouped.

Junos WebApp Secure 5.0 Hardware Guide

MODEL SST3-MV INSTALLATION INSTRUCTIONS FOR FEDERAL MODEL SST3-MV SELECTABLE SIRENTONE-MULTI VOLT

This Datasheet is for the IC693PWR332. High Capacity Power Supply, 12 VDC Input.

PACSystems RX7i IC698CHS009/119

CTI 2551-A 8-CHANNEL ISOLATED THERMOCOUPLE INPUT MODULE INSTALLATION AND OPERATION GUIDE. Version 1.3 CTI Part # * *

Non-Isolated Analog Output Module with HART Communications, IC695ALG728-DC Non-Isolated Analog Output Modules, IC695ALG704-DC, IC695ALG708-DC

AWP-24-3 Wave Height Gauge User's Guide

This Datasheet for the IC670MDL VDC Pos/Neg Logic Input 16 Pt. Grouped.

Site Preparation CHAPTER

IC693 PLC IC693ACC350, IC693ACC340/341

ICS Regent. Relay Output Modules. Low Power and High Power (T3446L and T3446H) PD-6017

Dual-Feed 80A Auto Low Voltage Disconnect Panel - 80LVD02

Table of Contents. Introduction... 2 Description...2 Specifications...3 Installation.. 5 Calibration.. 6 General Maintenance...7

Rhino Redundancy Module PSM24-REM360S. Operating Instructions

TPE 1464 Series Pressure Transducer

User's Guide. Model W 3-in-1 Switching DC Power Supply

Power Supply and Fan Module Installation

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

This Datasheet for the IC697BEM731. Series Genius I/O Bus Controller.

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

EL1142 Series. IEC / IEEE 1613 Hardened 2-Port 10/100BASE-TX to 2-Port 100BASE-FX Media Converter. User s Guide

Dell MD1280 Storage Enclosure Getting Started Guide

CRAGG RAILCHARGER Instruction Manual for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V

Dell Networking S4810 Open Networking (ON) Getting Started Guide

16-Channel Digital Output Module 120Vac/dc

VECTOR INVERTER -INSTRUCTION MANUAL- HIGH RESOLUTION ANALOG INPUT / EXTRA CONTACT INPUT / THERMISTOR INTERFACE FR-V5AX

Instructions to printer DO NOT PRINT THIS PAGE

Lightning Stitch Assembly

PACSystems* RX3i Genius* Communications Gateway, IC695GCG001. Quick Start Guide, GFK-2891C August 2016

Quick Start. This document describes how to install the Juniper Networks PTX5000 Packet Transport

Trident and Trident X2 Digital Process and Temperature Panel Meter

ADC7520 SERIES. 1600W Battery Chargers and Power Supplies

Mini Probe. user manual. DM Models

Chassis Power Supplies

SmartBlock I/O Module HE579MIX577/977 Isolated 4/8 Analog Inputs 2/4 Analog Outputs

PanelView Plus/VersaView CE Terminals and Display Modules

Transcription:

This Datasheet for the IC660BBA103 Block 115Vac/125Vdc Thermocouple Input 6 Channels http://www.qualitrol.com/shop/p-14424-ic660bba103.aspx Provides the wiring diagrams and installation guidelines for this GE Series 90-30 module. For further information, please contact Qualitrol Technical Support at 1-800-784-9385 support@qualitrol.com

Description Thermocouple Input Blocks are primarily used for monitoring temperature, with standard thermocouple types connected to the inputs. They can also be used for measuring low-level voltage input signals. Two Thermocouple blocks are available: 115 VAC/125 VDC Thermocouple block (IC66*BBA103) 24/48 VDC Thermocouple block (IC66*BBA023) They are the same except for the power supply. DC+ DC- +BSM -BSM +TC1 -TC1 +TC2 -TC2 +TC3 -TC3 +TC4 -TC4 +TC5 -TC5 +TC6 -TC6 Thermocouple Input (24/48VDC) (.4A Max) Features A Thermocouple block has six input circuits, in three isolated groups. +/-10 V common mode voltage (maximum) allowed between 2 points in a group. Each group has two thermocouple input circuits and two remote cold junction compensation inputs. Group to group isolation is 300 volts. Each input can interface to type J, K, T, E, B, R, S, and N (#14 AWG Nicrosil vs. Nisil) thermocouples. The block provides cold junction compensation for all thermocouple input measurements. Each channel can be configured to use an internal sensor, an external sensor, or a user-defined value ( in the range of +/- 327.67mV) for cold-junction compensation. An external signal from a remote junction can be either a voltage (XJV) or a current (XJI) analog of temperature. The XJV input is scaled for 1.0mV per degree Centigrade and the XJI input is scaled for 1.0uA per degree Kelvin. After compensation, the block linearizes each thermocouple input measurement according to the NBS monograph for the thermocouple type in use. Each input measurement can be adjusted up to +/-100.0 degrees C or +/-100.0 degrees F for greatest accuracy. An output is provided to drive a Bus Switching Module (version IC66*BSM021 only). Thermocouple blocks perform the following diagnostics: Internal fault detection Open Wire detection Overrange and underrange input indication High and low input alarms Specifications Catalog Numbers 115 VAC/125 VDC Thermocouple Block IC66*BBA103 Terminal Assembly Electronics Assembly IC66*TBA103 IC66*EBA103 24/48 VDC Thermocouple Block IC66*BBA023 Terminal Assembly Electronics Assembly Block Specifications IC66*TBA023 IC66*EBA023 Size (height x width x depth) 8.83 (22.44cm) x 3.34 (8.48cm) x 3.91 (9.93cm) Weight 4 lbs. (1.8 kg) LEDs (I/O Block) Unit OK, I/O Enabled Block to Block Isolation 1500V Group to Group Isolation 300V Heat Dissipation 9W maximum Block Power 115VAC 125VDC 24/48VDC Power supply voltage (@9W) 93-132 VAC 47-63 Hz 105-145 VDC 10% max. ripple Power supply dropout time 1 cycle 10ms 10ms Input Specifications Voltage measurement: Accuracy (at 25 C)* Bandwidth of input amplifier filter Internal Cold Junction Measurement: Offset at 25 C Linearity Temperature coefficient External Cold Junction Measurement: Scale factors Accuracy Input update time (all channels): Open wire detection response: Diagnostics 18-56 VDC 10% max. ripple -25.0mV to +150mV Less than +/-4 µv. Less than +/-10µV error typ, +/-20µV max. 8 Hz +/-2µV per C typical 0 to 60 C +/-2 C typ. Adjustable to zero at any temperature. +/-0.15 C Less than +/-0.01 C +/-0.05 per C -25.0 C to +150.0 C 1.0 C per millivolt, 1.0 K per microampere Less than +/-0.01 C +/-0.1 C 2.0 seconds (typ), 3.0 seconds (max) less than 5.0 seconds Open Wire, Overrange, Underrange, High Alarm, Low Alarm, Internal Fault Refer to GFK-0867 for product standards and general specifications. * In the presence of severe RF interference (IEC 801-3, 10V/m), accuracy may be degraded to +/1 (0.5% of full-scale reading plus 0.5% or reading). Using this Datasheet This datasheet summarizes information about block installation, configuration, and diagnostics. Your primary reference should be the Discrete and Analog Blocks User s Manual. It includes detailed instructions for block installation and configuration. For additional information about systems and communications, including bus specifications, refer to the I/O System and Communications Manual. 1

Compatibility Thermocouple blocks are compatible with: For an IC697 series PLC, the CPU must be rel. 2 (IC697CPU731 or 771) or later. The Bus Controller must also be: rel 2 (IC697BEM731) or later. The programming software must be rel 2.02 or later. For an IC600 series PLC, the CPU must be rev. 105 or later. For an IC600 series Plus PLC, the CPU must be rev. 110 or later. The Bus Controller must be model IC66*CBB902 or 903. The programming software must be rel. 4.02 or later. For an IC550 series PLC. the CPU must be rev. 3.0 or later. The programming software must be rel. 2.01 or later. Hand-held Monitor model IC66*HHM501D (version 3.5) or later can be used with these blocks. However, HHM version 3.7 or later is required for full configuration capability. If a Bus Switching Module is connected directly to the block, it must be the 24/48 VDC version (IC66*BSM021). Installation Instructions Carefully inspect all shipping containers for damage. If any equipment is damaged, notify the delivery service immediately. Save the damaged shipping container for inspection by the delivery service. After unpacking the equipment, record all serial numbers. Save the shipping containers and packing material in case it is necessary to transport or ship any part of the system. Block Mounting Genius I/O blocks are considered "open equipment" and therefore must be installed within a protective enclosure. They should be located in an area that is clean and free of airborne contaminants. There should be adequate cooling airflow. For best performance, it is recommended that this block be mounted in such a manner as to minimize the change in ambient temperature to which it is exposed. The block can be mounted right side up, or upside down. Leave at least 2 inches of space between blocks. Mount the block by drilling two screw or bolt holes for 8-32 hardware. Position the block so that the notches in the upper and lower flanges line up with the mounting holes. Mount the block using 8-32 screws. Use star washers to provide ground integrity. Grounding The block s mounting screws must not be used as the only means of grounding the block. Connect the green ground screw on the block to a reliable ground system using a short wire lead, minimum size AWG #12 (avg 3.3mm 2 in cross-section). WARNING: If mounting screws do not make good ground connection and the ground screw is not connected to a reliable ground, the block is not grounded. Electrical shock hazard exists. Death or personal injury may result. Removing an Electronics Assembly The block s Electronics Assembly can be replaced with a compatible model without removing field wiring or reconfiguring the block. Retaining Screws (Qty. 2) Terminal Assembly Electronics Assembly Connector Pins 1. Unscrew the retaining screws at the top and bottom of the block. 2. Using a Block Puller (IC660BLM507), engage the tabs in the first vent slots. Move the tool to the center of the block and squeeze the handle. 3. Pull the Electronics Assembly upward. WARNING: If power is applied to the field terminals, power is also exposed on the connector pins at the base of the Terminal Assembly, and electrical shock hazard exists. Do not touch the connector pins! Death or injury may result. Inserting an Electronics Assembly 1. Align the Electronics Assembly in the guides and push down firmly. CAUTION: Do not exert excessive force; it may damage the block. 2. If unusual resistance is met, remove the Electronics Assembly. If power is applied to the block, DO NOT TOUCH THE CONNECTOR PINS! Inspect the Terminal Assembly, connector receptacle, and connector edge board (on the Electronics Assembly). Be sure the keying matches. Remove any obstacles and reinsert the Electronics Assembly. Pay close attention to the alignment of the guide pins. 3. Secure the Electronics Assembly with the screws on the top and bottom of the Terminal Assembly. Note: If the Electronics Assembly has been removed from a block for some length of time, contaminants may have built up on the exposed connector pins. After the block is reassembled, these contaminants could affect the accuracy of measurements. When reassembling the block, push the Electronics Assembly in and out a few times to assure a fresh mating surface. 2

Block Wiring Do not overtorque the terminal screws. Recommended torque for all terminals is 6 in/lb (.678 N/M). Serial Bus Wiring Using one of the cable types recommended in the System and Communications User s Manual, connect the serial bus to terminals 1-4. If a Bus Switching Module will be connected to the block, see below instead. Terminals 1 to 4 are for the serial bus. These terminals accept one AWG #12 wire (avg 3.3mm 2 cross-section) or two AWG #14 wires (each avg 2.1mm 2 in cross-section). The minimum recommended wire size is AWG #22 (avg.36mm 2 in cross-section). Terminals 1-4 can also accommodate spade or ring terminals up to 0.27 inch (6.85mm) wide with a minimum opening for a #6 screw, and up to 0.20 inch (5.1mm) depth from the screw center to the back barrier. Be sure unshielded wire ends are not longer than 2 inches (5 cm). 1 2 3 4 SERIAL 1 SERIAL 2 SHIELD IN SHIELD OUT If the block is at either end of the bus, connect a terminating resistor of the appropriate type (see the System and Communications User s Manual for details) across its Serial 1 and Serial 2 terminals. Terminating Resistor Serial 1 Serial 2 Shield In Shield Out Start of Bus Installing a Bus Switching Module End of Bus Terminating Resistor Serial 1 Serial 2 Shield In Shield Out If a Bus Switching Module will be connected directly to the block, install it at the block s serial bus terminals, as shown in the diagram on the next page. Connect the bus cables to the BSM. Connect either of the BSM pigtail wires to terminals 7. Connect the other to terminal 8. Field Wiring Terminals 5 to 32 are for field devices. They take a single wire up to AWG #14 (avg 2.1mm 2 in cross-section). Minimum recommended size is AWG #20 (avg.54mm 2 in cross-section). Wiring for Block Power For block power, connect an appropriate power source to terminals 5 and 6. For the 115 VAC/125 VDC block version, connection can be of either polarity. For the 24/48 VDC version, the polarity should be observed as marked, although protection is provided against accidental reversed input polarity. Wiring for Thermocouples Thermocouple wires should be connected to the six channels observing the proper polarity. For American color coding, connect the red wire to the (-) terminal. For the smaller gauge thermocouple wires, connector-type crimp pins of the same alloy are recommended to make installation easier. TC3 TC4 Remote Cold Junction T SENSE 1uA/1 K TC5 TC6 BSM NOTE: Heavy lines ( ) represent copper wires T SENSE 1mV/1 C Remote Cold Junction 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 H or +DC N or -DC +BSM -BSM +TC1 -TC1 +TC2 -TC2 +TC3 -TC3 +TC4 -TC4 +TC5 -TC5 +TC6 -TC6 LEDs The block's Unit OK and I/O Enabled LEDs show its operating status: Unit OK I/O Meaning Enabled ON ON Block functioning, CPU communicating ON OFF Block functioning No CPU communications for 3 bus scans ON Blinking Block functioning, Circuit forced Blinking ON Circuit fault, CPU communicating Blinking OFF Circuit fault No CPU communications for 3 bus scans Alternate Blinking Circuit fault, Circuit forced Synchronous Blinking No CPU communications - block number conflict OFF Blinking Electronics/Terminal Assembly mismatch OFF OFF No block power, or block faulty 3

Block Operation A Thermocouple Input Block has three isolated pairs of inputs. Transformers isolate power and optical couplers provide signal isolation. For each pair of inputs: 1. After filtering, each signal input is sequentially switched into a common amplifier whose output is applied to a voltage to frequency converter. The output signal frequency of the VFC is applied to a frequency counter via an optical coupler. The output frequency is counted for a 400 millisecond gate time, which provides rejection of line frequency pickups. 2. The multiplexer intersperses other inputs between the two main thermocouple input times. These other inputs come from the cold junction sensors and from internal references. The cold junction inputs are measured and stored for later compensation of the normal thermocouple input measurement errors. 3. To detect and correct for any gain or offset drift in the amplifier or VFC, the block takes new readings of factory-calibrated internal reference levels during operation. These new measurements are compared to reference values stored by the block. 4. The processor converts the cold junction temperature value to a voltage for the thermocouple type in use. This voltage is then added to the thermocouple measurement before converting to thermal units. To compensate for small differences between the cold junction temperature measurement and the actual cold junction temperature, an offset adjustment can be entered using a Handheld Monitor. Diagnostics Block diagnostics are listed below. Fault messages can be cleared from the Hand-held Monitor or the CPU. High Alarm: Input over its high alarm limit Low Alarm: Input under its low alarm limit Open Wire: Missing or faulty connection to a thermocouple input, XJV input, or XJI input. Overrange or Underrange: Reported only if engineering units of degrees are selected. Indicates one of the following conditions: Input temperature exceeds the expected range for the thermocouple type in use. The expected range for each thermocouple type is listed in the Discrete and Analog Blocks User s Manual. Overrange: Cold junction sensor reading above +150 C (may be caused by an open wire if XJV sensor is in use). Underrange: Cold junction sensor reading below -50 C (may be caused by an open wire if XJI sensor is in use). Internal Channel Fault: One or more of the block s internal references is faulty. While the fault is present, input data of 0 is reported for each channel using the faulty reference(s). Configuration First, the block must be configured with a Hand-held Monitor to: Enter its Device Number (serial bus address). Enter its Reference Number (required only for IC600 and IC550 series PLCs only). Note: If a block is configured offline, it must be properly grounded and have a 75 Ohm resistor installed across its Serial 1 and Serial 2 terminals. See the Discrete and Analog I/O Blocks User s Manual for instructions. The rest of the features can be configured either using a Hand-held Monitor, or by sending a Write Configuration datagram to the block from the host. Feature Circuit Factory Selections or Block Setting Device Number Block null 0 to 31 (a number must be selected) Reference Address Block none Depends on host CPU type Baud Rate Block 153.6 std 153.6 std, 153.6 ext, 76.8, 38.4 Kbd Channel Active Circuit yes yes, no Report Faults Circuit yes yes/no Units Block C C, F, mv, counts Thermocouple type Compensation method Comp. value (for user-supplied method) Circuit Type J J, K, T, E, B, R, S, N or (L)inear Circuit Internal Internal, Ext. voltage, Ext. current, user-supplied Circuit 0.00mV +/-326.67mV Offset value Circuit 0.00 +/-100.0 C or+/-100.0 F Low Alarm Circuit -250 C -32,767 to +32,767 or 0 to +65,535 High Alarm Circuit +1400 C -32,767 to +32,767 or 0 to +65,535 BSM Present Block no yes, no BSM Controller Block no yes, no Configuration Protection Block disabled enabled, disabled 4