The 3 kw Models will accept 200*/230 VAC single phase and 200*/208 VAC three phase input power.

Similar documents
Sorensen DLM 600 Series W V 2 75 A. Half Rack Programmable DC Power Supply

Sorensen DLM 600 Series W V 2 75 A. Half Rack Programmable DC Power Supply

M133 / M135 / M136 Disconnect Polarity Relay Option. M9 / M130 Remote Programming

M130/M131 Ethernet Option for DLM600 and DCS Series Programming Manual

Sorensen XT Series W A. 60 Watt Linear Performance DC Power Supply V. Low noise and ripple. Excellent line/load regulation

Sorensen SG Series - Water Cooled kw V A. Programmable Precision High Power DC Power Supply

Sorensen SG Series kw V A. Programmable Precision High Power DC Power Supply

DCS-E 1kW Series, DLM-E 3kW & 4kW Power Supplies

Sorensen XT Series W A. 60 Watt Linear Performance DC Power Supply V

Applications Electronic Design/Development Battery Charging Launch Control Rackmount ATE Systems. DLM 600 Near Linear 600W DC Power Supply

GENERAL DESCRIPTION. A bright, easy to read, 0.55" Plasma Display makes the unit an easy to read instrument even in bright light.

Internal GPIB Interface for LHP Series Power Supplies

Series Watt DC Power Supplies

How to Convert from a Sorensen DLM to an Agilent N5700

Programmable Digital Controlled DC Power Supplies

Features. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors. Output Connectors. Overvoltage Protection. Over Temperature Protection

Features. Conducted Emission. Radiated Emission. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors.

Features. Conducted. Emission. Line Regulation. Load Regulation. Safety. Cooling. Input Connectors. Overvoltage Protection. Phase Loss.

Programmable DC Power Supplies For Laboratory & System Integration

Features. LXI Compliant LAN. Power W GEN V 0 55A 3300W GEN V 0 42A 3300W GEN V 0 33A 3300W GEN V 0 22A 3300W

Features. LXI Compliant LAN. Power GEN V 0 65A 5200W GEN V 0 50A 5000W GEN V 0 34A 5100W GEN V 0 25A 5000W

GEN W SERIES. LXI Compliant LAN. Laboratory Power Supplies: 750 ~ 1500W. Features. Programming Options: How to order:

THURLBY THANDAR INSTRUMENTS. PL & PL-P Series. Laboratory Power Supplies. Standard and Programmable models, 35 watts to 240 watts

Features. LXI Compliant LAN. Power GEN V 0 40A 2400W GEN V 0 30A 2400W GEN V 0 24A 2400W GEN V 0 16A 2400W

Sorensen XEL & New XEL-P Series

How to Convert from a Xantrex XFR to an Agilent N5700

Stocked Electro-Mechanical Switches. SP2T SEM Series

PROGRAMMABLE DC POWER SUPPLIES MODEL:62000P SERIES

capability for accurate voltage and cur- readings of the UUT s input parameters. 8 bit TTLs, DC-ON, fault output signal and

An ISO 9001 Company. KLP POWER SUPPLY

Programmable DC Power Supplies XLN Series

PROGRAMMABLE DC POWER Supply MODEL 62000P SERIES MODEL 62000P SERIES. Programmable DC Power Supply PFC

User's Guide. Programmable DC Power Supply 200 Watt (40 Volts / 5 Amps) Model Introduction

Advanced Test Equipment Rentals ATEC (2832)

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS

NEW! ZERO-UP. Control Flexibility for Worldwide Applications 200W/400W/800W. Built-in RS232 & RS485 Interface with GPIB optional.

Overview: Functional Description:

16AIO Bit Analog Input/Output Board. With 16 Input Channels and 8 Output Channels

Keysight Technologies How to Convert from a Sorensen DLM to a N5700. Application Note

Genesys TM. Programmable DC Power Supplies 10/15kW in 3U Built in RS-232 & RS-485 Interface Parallel Current Summing Optional Interfaces: Compliant

BOARD LEVEL PRODUCTS OEM GPIB<->RS-232 INTERFACE BOARD GPIB

Series MV2000 MEDIUM VOLTAGE HIGH CURRENT POWER SUPPLIES

Control Flexibility for Worldwide Applications

BRC SERIES 20kW High Voltage Power Supply

PAS 9715/AO ENGINEERING SPECIFICATION

PC104P-16AIO Bit Analog Input/Output PC104-Plus Board

AP SERIES SYSTEMS POWER SUPPLIES. Autoranging power supplies for bench or systems use FEATURES

Improved. Specifications

XT Series Programmable DC Power Supply. Operation Manual

transient waveforms. This capability allows devices to be tested to DC voltage dropouts, simulation, battery automated charging,

Programmable DC Power Supplies

BOARD LEVEL PRODUCTS GPIB<->RS-422/RS-485 INTERFACE BOARD

R&S HMC804x Power Supply 100 W and 1, 2 or 3 Channels

Agilent E3640A E3649A Programmable DC Power Supplies. Data Sheet

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors

DP700 Series. Programmable Linear DC Power Supply. Batter Fly s.r.l. - Tel

Modular Power System 1200 W per mainframe GPIB

Test and Measurements Automated Systems Component Device Testing Semiconductor Processing & Burn-in Aerospace & Satellite Testing

HERCULES-5000 INSTRUCTION MANUAL

Agilent E363xA Series Programmable DC Power Supplies. Data Sheet

Agilent 66000A 1200 W DC Modular Power System, GPIB

AD-8923-BCD. Remote Controller (BCD) INSTRUCTION MANUAL 1WMPD

AMPLIFIER PARALLEL INTERFACE SPECIFICATION

Programmable Dual-Range DC Power Supplies 9170 & 9180 series

MODULAR DC POWER SUPPLY MODEL 62000B SERIES MODEL 62000B SERIES. Modular DC Power Supply. Ethernet. Key Features :

Agilent E363xA Series Programmable DC Power Supplies

16-Channel 16-Bit PMC Analog I/O Board

PMC-16AIO 16-Bit Analog Input/Output PMC Board With 32 Input Channels, 4 Output Channels and 16-Bit Digital I/O Port

Single-output and dual-output power supplies. TOE 8840 up to 160 W TOE 8850 up to 320 W. In-phase regulation

LT900SERIES. 1xN Multi-Channel Switch Operation Manual

Programmable D.C. Electronic Load

Keysight U8030 Series Triple-Output DC Power Supplies

A. Advanced Features. Configurable High Power Solution

PC104P66-18AISS6C: 18-Bit, 6-Channel, 550KSPS Analog Input Module. With Six Simultaneously Sampled Analog Inputs and 8-Bit Digital I/O Port

Mobile Communications DC Sources W

Vorne Industries. Model 77/232 Serial Input Numeric 3" Display User's Manual

ADR7700. RS232 / Data Acquisition Interface USER MANUAL V 1.0

Programmable Dual-Range DC Power Supplies 9170B & 9180B Series

DSP240-LPI Inverter Controller Card. Technical Brief

Series. Programmable DC Power Supplies 200W/400W/600W/800W in 2U Built-in USB, RS-232 & RS-485 Interface

Control via Front Panel Touchscreen & Encoder or available digital control interfaces.

16AIO 16-Bit Analog Input/Output Board With 32 Input Channels, 4 Output Channels and 16-Bit Digital I/O Port

ECS ecompass Series. ECS ecompass Series. Strap down Electronic Compass. General Description. Features. Making Sense out of Motion

Agilent E3632A DC Power Supply

Programmable DC Power Supplies 750W/1500W in 1U Built in RS-232 & RS-485 Interface Advanced Parallel Operation Optional Interface:

Release Note. How to Use the OptoCon Connection Module. 1 Introduction. Option C Revision 4 Revised 8/13/98

E36300 Series Triple Output Bench Power Supply DATA SHEET

99 Washington Street Melrose, MA Phone Toll Free Visit us at

Swift Responses with Accurate Measurement

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

HPD Series Programmable DC Power Supply. Operation Manual

MDK. Accelnet Module DevKit. Provides Mounting & Connections for Accelnet CANopen Servoamplifiers FEATURES

GE Energy. ACE184 Series Power Shelf Main Output: 600A; Standby output: 8A. Preliminary Data Sheet. Features. Applications.

CDN502 HIGH DENSITY I/O ADAPTER USER GUIDE

ISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) OPERATION MANUAL. Total System Manager

2U/5U. AC + DC Power Solutions. Transient Generation for Disturbance Tests. only. High Performance Programmable AC Power Source

360W and 720W Programmable DC Power Supplies

D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide

PCIe-20AO8C500K. 20-Bit 8-Output 500KSPS Precision Wideband. PCI Express Short-Card Analog Output Module

12-Channel, 12-Bit PMC Analog Input/Output Board

Transcription:

Sorensen DLM 3 & 4 kw Series DC Power Supply 3 4 kw 5 600 V 5 450 A 208 230 208 400 480 The Sorensen DLM 3kW and 4kW Series programmable DC power supplies are designed to provide highly stable, continuously variable output voltage and current for a broad range of applications in a compact 2U ( 3½ high) chassis. Both the 3 kw and 4 kw models have output voltages from 0-5 VDC to 0-600 VDC and a current range from 0-5A to 0-450A. The output rms noise is as low as 10 mv. The output will recover to 1% of its steady-state voltage within 1 ms for a step load change of 100% to 70% or 70% to 100%. The front panel layout makes the series extremely easy to use. Control switches include: power on, enable/ standby and local/ remote. Displays and indicators show programmed set points and operational control status. The programmed voltage, current and overvoltage set points are displayed with two large 3½ digit LED displays. Operational Status LEDs indicate power on, shutdown, over temperature, overvoltage, constant current and voltage mode status. Control Status LEDs indicate front panel lockout, remote control and standby status. IEEE- 488.2 control LEDs indicate error, service request and remote address status. The 3 kw Models will accept 200*/230 VAC single phase and 200*/208 VAC three phase input power. The 4 kw Models will accept 200*/208 VAC, three phase or optional 400 or 480 VAC three phase input power. *Operating temperature below 40 C With compliments Helmut Singer Elektronik www.helmut-singer.de info@helmut-singer.de fon +49 241 155 315 fax +49 241 152 066 Feldchen 16-24 D-52070 Aachen Germany AMETEK Programmable Power 9250 Brown Deer Road San Diego, CA 92121-2267 USA 858.458.0223 sales.ppd@ametek.com 10252013 61

DLM 3 & 4 kw Series : Product Specifications Common Environmental Physical Output Input 3 kw 4 kw 62 www.programmablepower.com

DLM 3 & 4 kw Series : Product Specifications 3 4 kw Output : Voltage and Current 3 kw Model Voltage Current 4 kw Model Voltage Current Model Voltage (VDC) Output Ratings Regulation Line and Load Meter Accuracy Current (ADC) Voltage (0.05% of Vmax + 2 mv) Current (0.1% of Imax) Voltage (0.5% of Vmax + 1 count) Current (0.75% of Imax + 1 count) * 22V Model available as 4kW With compliments Helmut Singer Elektronik www.helmut-singer.de info@helmut-singer.de fon +49 241 155 315 fax +49 241 152 066 Feldchen 16-24 D-52070 Aachen Germany 858.458.0223 sales.ppd@ametek.com 63

DLM 3 & 4 kw Series : Product Specifications Model Preview Accuracy Voltage (05% of Vmax +1 count) Current (1.0% of Imax +1 count) OVP Adjustment Range (6% to 110% Vmax) Ripple & Noise Stability Temp Coefficient Maximum Total Ripple (rms)* Noise (p-p) Voltage (0.05% of Vmax) Current (0.05% of Imax) Voltage (0.02% C of Vmax) Current (0.03% C of Imax) J3 Connector * 22V Model available as 4kW Remote Sense Drop 64 www.programmablepower.com

DLM 3 & 4 kw Series : Diagram 3 4 kw Top View Input Connections Front View Chassis Ground Connection Output Connections 5V to 80V 150V to 600V Rear View 858.458.0223 sales.ppd@ametek.com 65

DLM 3 & 4 kw Series Model Number Description DLM 32 125E (MXX) Series Options Voltage Current Options and Accessories With compliments Helmut Singer Elektronik www.helmut-singer.de info@helmut-singer.de fon +49 241 155 315 fax +49 241 152 066 Feldchen 16-24 D-52070 Aachen Germany 2009 AMETEK Programmable Power All rights reserved. AMETEK Programmable Power is the trademark of AMETEK Inc., registered in the U.S. and other countries. Elgar, Sorensen, California Instruments, and Power Ten are trademarks of AMETEK Inc., registered in the U.S. 66 www.programmablepower.com

SECTION 1 FEATURES, FUNCTIONS, AND SPECIFICATIONS 1.1 Introduction This manual covers the M9 Remote Programming Option for the DCS, PRO-T, and DLM Series power supplies. The M9 interface card enables you to operate your Sorensen power supply from a computer via the IEEE-488.2 GPIB or RS-232 interface, allowing full remote programming control and monitoring of your power supply. The M9 is compatible with both the M9A (which it replaces) and SCPI languages. The M9 supports the control of up to 30 auxiliary power supplies from a single GPIB/RS232 interface using the Extended Interface Bus (EIB), which uses RS-485, with the M85 option. 1.2 Features and Functions Features 12-bit programming and 12-bit readback of voltage and current Programmable overvoltage protection with reset IEEE-488.2 and SCPI compliant command set User-programmable signals including Local/Remote Sense, External Polarity, and Disconnect Relay Drive User selectable Constant-Voltage/Constant-Current or Foldback mode, with reset Voltage Ramp and Current Ramp functions Field-upgradable firmware via RS-232 Attachment of up to 30 supplies via EIB interface with the M85 option Soft calibration Rear panel IEEE-488.2 and RS-232 control interface Rear panel User Control Signal interface Rear panel configuration switch M9 Programming Manual 1-1

Features and Functions Sorensen DCS, DLM, PRO-T Series Programmable Functions Output voltage and current Soft limits for voltage and current Overvoltage protection Output enable/disable Maskable fault interrupt Hold and trigger External relay control Full calibration Readback Functions Actual measured voltage and current Voltage and current settings Soft voltage and current limits Overvoltage protection setting Status and Accumulated Status registers Programming error codes Fault codes Manufacturer, power supply model, and firmware version identification 1.3 Specifications (SUBJECT TO CHANGE WITHOUT NOTICE) Programming Resolution Voltage: 0.03% of full scale Current: 0.03% of full scale Overvoltage Protection: 0.03% of full scale (full scale is 110% of max output voltage.) Programming Accuracy Voltage: ± (0.1% + 0.1% of maximum output voltage) Current: ± (0.1% + 0.4% of maximum output current)* Overvoltage Protection: ± (0.5% + 0.5% of max output voltage) Readback Resolution Voltage: ± 0.03% of full scale Current: ± 0.03% of full scale Readback Accuracy Voltage: ± (0.1% + 0.15% of full scale output voltage) Current: ± (0.1% + 0.4% of full scale output current)* * After 30 minutes operation with fixed line, load, and temperature. Note: Refer to the power supply manual for effects of line regulation, load regulation, and temperature on accuracy specifications. 1-2 M9 Programming Manual

SECTION 2 CONFIGURATION The M9 is installed into the supply at the factory. Use the Setup Procedure described below to configure the M9 for your system and application. 2.1 Setup Procedure This procedure is a quick reference for the configuration requirements. Refer to Section 2.2 for detailed information on the rear panel switches. 1. Set the rear panel Remote/Local switch to Remote (On or 1). 2. Set the rear panel Power On Service Request switch to No Service Request (Off or 0). 3. Set the rear panel Master/Auxiliary (M9/M85) to Master (M9) (On or 1). Note: This switch applies only to the DCS and Pro-T Series of power supplies. It is not used on other models. 4. Set the GPIB/EIB address switches to the desired address. Note: Valid GPIB addresses are 1-30. Valid EIB addresses are 2-31. 5. Connect the GPIB or RS232 Interface Cable to the supply. 6. Connect power to the unit and turn on the unit. Verify that the green REMOTE LED on the front panel is ON. 7. Configure the controller to match the supply identification and configuration. Use one of the available programs such as IBCONF from National Instruments for GPIB, or set the RS232 baud rate to 19200, 8 data bits, no parity, and 1 stop bit. 8. Test the communication interface by issuing a *IDN? Command. This returns the supply s model and firmware versions and does not affect the output of the supply. M9 Programming Manual 2-1

Configuration Sorensen DCS, DLM, PRO-T Series 2.2 Rear Panel Configuration Switch The DIP switch is accessible from the rear panel to allow configuration of the supply with the installed M9/M85 for the user s particular system and application. The following figures show the configuration, as set up in Section 2.1, and with GPIB address set to five (5). Note: Two types of DIP switches are utilized; toggle and rocker. For toggle switches, the shading indicates the position of the toggle switch. For rocker switches, the shading indicates the depressed side. Figure 2 1 DCS and Pro-T Configuration Switch Figure 2 2 DLM Series 3kW & 4kW Configuration Switch Figure 2 3 DLM Series 600W Configuration Switch 2-2 M9 Programming Manual

Sorensen DCS, DLM, PRO-T Series Configuration 2.2.1 Remote/Local Selection Set the rear panel Remote/Local switch to select remote or local operation. REMOTE/LOCAL SWITCH Switch Position Description ON Remote operation selected. * OFF Local operation selected. Front panel control is enabled. Unit will switch to remote operation upon the first GPIB or RS-232 command. * For DCS firmware prior to version 2.07, and DLM firmware prior to version 1.04 In the ON position, the power hardware and GPIB card initialize to the remote state on power turn on. Initially, control is accessible only though GPIB or RS232. Note that control may still revert to front panel control if the appropriate command is sent, or the REN of the GPIB is disabled. For DCS firmware version 2.07 and above, and DLM firmware version 1.04 and above In the ON position, the power hardware and GPIB card initialize to the remote state on power turn on. In addition, front panel control remains disabled regardless of the state of the REN line, or the GTL command. The special command SYST[n]:LOCAL <on/off> is now permitted as a means to revert to front panel control if desired. Powering up in remote mode will result in the following operating conditions. REMOTE MODE POWER-ON CONDITIONS Condition Voltage Current Soft Voltage Limit Soft Current Limit OVP Trip Voltage Delay Foldback Protection Output Hold Unmask Service Request Capability Default 0 Volts (initial power on voltage). Also see CAL:INIT:VOLT 0 Amps (initial power on current). Also see CAL:INIT:CURR Model maximum voltage Model maximum current Model maximum voltage +10% (initial power on OVP). See CAL:INIT:VOLT:PROT 0.5 seconds OFF ON OFF NONE OFF M9 Programming Manual 2-3

Configuration Sorensen DCS, DLM, PRO-T Series 2.2.2 Power-On GPIB Service Request (PON SRQ) Selection Set the rear panel PON SRQ switch to ON to cause a GPIB service request to be sent to the computer controller when the supply is turned on. The front panel SRQ LED will also turn on. You may clear the service request and turn off the SRQ LED by issuing a serial poll. POWER-ON GPIB SERVICE REQUEST (PON SRQ) SWITCH Switch Position ON OFF Description Power-On SRQ selected No Power-On SRQ selected Refer to your specific GPIB controller card manual for further details on serial polling. 2.2.3 Master/Auxiliary Selection [Applies to DCS and PROT series only!] For the M9, set the rear panel Master/Auxiliary switch to ON to configure the supply to be the master. The address selection for a master is the GPIB address (1-30). For the M85, set the Master/Auxiliary switch to OFF to configure the supply to be an auxiliary unit. The address selection for an auxiliary unit is the channel number of that device (2-31). Refer to Section 2.2.4 for more details regarding address selection. MASTER/AUXILIARY SWITCH Switch Position ON OFF Description Master unit (M9 only) Auxiliary unit (M85 only) 2.2.4 Address Selection The address selection is binary with switch A0 as the LSB and A4 as the MSB. The rear panel switch illustration in Section 2.2 shows the address selection 00101 in binary (5 decimal). The address selection for a master unit is the GPIB address of that device (1-30). The address selection for an auxiliary unit is the channel number of that device (2-31). Channel selections 0 and 1 are invalid for an auxiliary device because SCPI reserves channel 0 as the global channel to address all channels and channel 1 as the default master channel to address the master unit. ADDRESS SWITCHES Switch Position Description ON 1 OFF 0 2-4 M9 Programming Manual

Sorensen DCS, DLM, PRO-T Series Configuration 2.3 External User Control Signal Connector An 8-pin Molex or 9-pin Subminiature-D connector located at the rear panel provides external auxiliary control signals to increase the user s operating control of the supply. The mating receptacle for the 8-pin connector is Molex 43025-0800 with 8 female terminals 43030-0003. The Molex terminals accommodate wire sizes from #20 - #24. The relay outputs, when active, connect the POLARITY, SENSE, and ISOLATION pins of the connector to the relay COMMON pin. The relays are rated at 120VAC/125VDC @ 1A; for DLM Series 600W, maximum ratings are 60V(PK), 30VA, and 1A. Any change in output (voltage, current, etc.) initiated by the user from the RS-232 or GPIB interface will cause a 10ms synchronization pulse to be generated at the rear panel User Control Signal Connector of the master unit (Sync Signal). EXTERNAL USER CONTROL SIGNAL CONNECTOR PINOUT Sub-D Pin Molex Pin Description 1 1 FOLDBACK output signal, open collector, active-low. Asserted when in foldback mode. 2 3 FAULT output signal, open collector, active-low. Asserted when a fault is recorded in the fault register. 3 6 POLARITY output signal, relay contacts. Asserted (contacts close to COMMON) when a negative voltage is programmed. (e.g., SOURce:VOLTage -5.0) 4 7 ISOLATION output signal, relay contacts. Asserted (contacts close to COMMON) when the output relay is programmed OFF. (e.g., OUTPut:ISOlation OFF) 5 8 SENSE output signal, relay contacts. Asserted (contacts close to COMMON) when the sense relay is programmed OFF. (e.g., OUTput:SENse OFF) 6 2 SHUTDOWN TTL input signal, active-high. Allows the user to immediately shutdown the unit by a TTL input signal. 7 5 COMMON for all signals and relay contacts. 8 4 SYNC output signal, open collector, active-low. Pulsed for 10 ms when a change in the output occurs. 9 COMMON for all signals and relay contacts. Figure 2 4 External User Connector Designation (8-pin Molex) M9 Programming Manual 2-5

Configuration Sorensen DCS, DLM, PRO-T Series Figure 2 5 Example of Open Collector, TTL Input, and Relay Output Circuits CAUTION The relays must not be hot-switched; ensure that the voltage across the relay contacts and the current through them is zero prior to changing the relay states. 2-6 M9 Programming Manual

Sorensen DCS, DLM, PRO-T Series Configuration 2.4 Remote Programming Via RS-232 The M9 s RS-232 interface operates at 19.2Kbaud with 8 data bits, no parity, and 1 stop bit. All M9 commands are supported at the RS-232 interface with the exception of the Service Request (SRQ) function which is a GPIB-specific function requiring the dedicated Service Request line of the IEEE-488.2 interface. In this case, the SRQ function has no effect. The RS-232 interface is accessible through the rear panel 6-pin RJ-11 connector; on DLM Series 600W, the connector is labeled RS232(485). Figure 2 6 RS-232 Rear Panel RJ-11 Connector Pinout Figure 2 7 M9 to PC RS-232 Connection (RJ-11 to DB-9) M9 Programming Manual 2-7

Configuration Sorensen DCS, DLM, PRO-T Series 2.5 Extended Interface Bus (EIB) with the M85 Option The M85 option is an auxiliary controller used in conjunction with the M9 to provide multiple sources controlled by a single GPIB address or via a single RS-232 connection. Up to 30 power supplies can be attached to a single M9 via the EIB(RS-485) bus connection at the rear panel of the M9. The EIB(RS-485) is accessible through the rear panel 6-pin RJ-11 connector. Figure 2 8 EIB(RS485) Rear Panel RJ-11 Connector Pinout Figure 2 9 M9 to M85 EIB Connection (RJ-11 to RJ-11) With compliments Helmut Singer Elektronik www.helmut-singer.de info@helmut-singer.de fon +49 241 155 315 fax +49 241 152 066 Feldchen 16-24 D-52070 Aachen Germany 2-8 M9 Programming Manual