FM2. Economical and compact feeder protection for low voltage feeders. Digital Energy Multilin. Monitoring & Metering. Protection and Control

Similar documents
GE Power Management. MMII Intelligent MCC Controller

FM2. Feeder Manager 2 INSTRUCTION MANUAL. GE Industrial Systems

www. ElectricalPartManuals. com l Basler Electric MPS100 MOTOR PROTECTION SYSTEM ADVANTAGES WINDOWS SOFTWARE ADDITIONAL INFORMATION

Multilin MM200. Low Voltage Motor Protection and Control. Protection and Control. Metering & Monitoring. Communications. EnerVista Software

MIN II. Complete numerical ground directional protection. Digital Energy Multilin. Protection and Control. Monitoring and Metering.

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...

Earth-fault Relay SPAJ 110 C. Product Guide

Protection Relays PHASE & RESIDUAL OVERCURRENT

www. ElectricalPartManuals. com Protective Relays HIGHLIGHTS PROTECTIVE FUNCTIONS ixp-420 Transformer Protection Relay

www. ElectricalPartManuals. com Protective Relays PROTECTION AND CONTROL FUNCTIONS ADVANCED CAPABILITIES

PowerLogic power-monitoring units. Power Meter PM500. Technical data sheet 2006

LM10 to MM200 Retrofit

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

DIAC/DIFC/DSFC. Single Phase Digital O/C. Single phase or ground overcurrent protection for industrial and utility power systems.

g Energy Multilin Voltage Regulator Controller DGCV KEy BENEFITS APPLICATIONS FEATURES Metering & Monitoring Voltage Regulation Communications

Function permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100%

DGC-2000 DIGITAL GENSET CONTROLLER

The PCI Series. Precise power control for complex SCR applications. Phase Angle Fired SCR Power Controls AMPS VAC

PowerLogic power-monitoring units. PM1000 series power meter. Technical data sheet

FP-5000 Feeder Protection

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

Contact protection relay

HID. GE Consumer & Industrial Multilin. High Impedance Differential Module Instruction manual GEK Copyright 2005 GE Multilin

Bus Bar Protection Relay B-PRO 4000

BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

www. ElectricalPartManuals. com .Basler Electric BE1-878 HIGH IMPEDANCE BUS DIFFERENTIAL RELAY ADVANTAGES ADDITIONAL INFORMATION APPLICATION Page2

PGR-2601 MANUAL DC GROUND-FAULT RELAY

For Transmission, Distribution and Machinery protection.

SED2 Variable Frequency Drives with Electronic (E) Bypass Options

D64RP18 INSTRUCTION MANUAL N.O. N.C V AC/DC TEST/ RESET

Iso DIN. User Manual. 1 channel Earth Fault Monitoring

Data Sheet. Digital Multifunctional Power Meter with LCD Display and Optional Modules WPM D

Bulletin 290/291 ArmorStart LT Distributed Motor Controllers Specifications

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

EM6400 series Multi-Function meters

PowerLogic power-monitoring units. DM6000 series digital panel meters. Technical data sheet

Voltage Transducer UMT516 / MT516

MIC-2 MKII, Multi-instrument DATA SHEET

Quantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III

MIC-2 Multi-instrument DATA SHEET

Feeder protection relay SPAA 121 C. Product Guide

SORDS ELECTRIC ~ MA7200. Sensorless Vector AC Inverter.

Motor protection relays

Residual overvoltage relay

RT4F-120V/20A-WAC RECTIFIER

OVERLOAD RELAYS POWER & ACTUATION PROVEN. series

How to control and monitor up to 16 Motor Insight motor protection relays via an HMi and Modbus serial

MM300. Integrated automation and protection for low voltage motors. Digital Energy Multilin. Metering & Monitoring. Protection and Control

Phase loss monitor CM-PBE Phasemonitor for over and undervoltage CM-PVE Ordering details

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box

Protection relay for secondary distribution

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

A drive dedicated to variable speed control for HVAC applications

EPM g Energy. Multilin BUILDING AUTOMATION POWER METER. BACnet /IP Communications and Energy Measurement KEY BENEFITS APPLICATIONS FEATURES

SE-701 MANUAL GROUND-FAULT MONITOR

SED2 Variable Frequency Drives Conventional Bypass (C-Bypass) Options

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

PROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL

FP-5000 Series Multi-functional Microprocessor-based Feeder Protective Relay

2 Table of Contents 1. TABLE OF CONTENTS. 1. Table of Contents Introduction Wiring Diagram Terminals Review...

Multifunction Transducer MT440

InteliPro. Protection Relay for Parallel Applications. Technical Specification

E1 Plus Electronic Overload Relay

CURRENT PROTECTION RELAY SMPR-1

MIC-2 MKII & MIC-2 MKII DIN, Multi-instrument DATA SHEET

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

One relay for safety and process continuity

GE Multilin 350 Feeder Protection Relay Specifications

BNS SERIES - COMPATIBLE SERIES AES SAFETY CONTROLLERS SELECTION CHART AVAILABLE STANDARD MODELS

SACE Emax 2 Specification guide

ATV340D75N4E variable speed drive - 75kW- 400V - 3 phases - ATV340 Ethernet

Feeder/ Motor Protection Relay VAMP 40

RT4F-110V/25A RECTIFIER

IPS INTELLIGENT PUMP STARTER

F650 - More than Feeder Protection & Control. GE Consumer & Industrial Multilin

PFC-10 Power Factor Controller

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

RT4B-110V/12A RECTIFIER

2C138. Sensitive Earth Fault Relay. Features. Application. Operation

Maximize process uptime with the SEL-patented motor thermal model.

ASCO 920 Remote Control (RC) Switches

SmartOnline 240/208/120V 8kVA 5.6kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, Split-Phase input, Bypass Switch

Metering Devices, Protective Relays, Software and Connectivity. Pre-Wired Control Power, Voltage and CT Inputs

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

SIA-B. Overcurrent & Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered / Standard CTs. Main characteristics

160 AA02SF1 AF DS-D17

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

NPW800R RETROFITTING. Power and Volatge Protection Relay

PDI Modular Compact Remote Power Panel

Testing Instruments Manufactured by

RM4JA01F current measurement relay RM4-J - range ma V AC

PowerLogic power-monitoring units. EM1000 series power meter. Technical data sheet

ICS Regent. Relay Output Modules. Low Power and High Power (T3446L and T3446H) PD-6017

ATV212WU40N4 variable speed drive ATV212-4kW - 5hp - 480V - 3ph - EMC class C2 - IP55

SYMAP R Plug in Variants FI, MI, 87M, TI Technical data

SIA-C. Overcurrent and Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered. Main characteristics

Transcription:

Key Benefits FM2 FEEDER Protection System Economical and compact feeder protection for low voltage feeders Comprehensive low voltage feeder management system - Integrated feeder protection and process control in a small package Cost effective solution - Low cost modular design Small footprint and compact design - With or without display, fits into standard Power Control Center buckets Ease of use - EnerVista compatible Remote monitoring - via serial communications, Modbus RTU Easy installation and integration - Door mount option Reduced number of devices - Replaces of bi-metal overload elements, integrates timers, relays, meters, switches, indicators Integrated trip pushbutton Easy to read two line display Applications Feeder protection and management system for low voltage distribution feeders Integrated process and electrical control Specifically designed for Power Control Centre applications Features Protection and Control Thermal overload protection Current unbalance Ground fault protection Open contactor/welded contactor Under voltage autoreclose Outputs: 2 fixed, 1 programmable and 1 emergency shutdown Inputs: 6 fixed, 10 programmable Monitoring & Metering Display phase current, ground current, current unbalance, voltage, power, energy, etc. Trip record and pre-trip values Maintenance information Communications RS485 ModBus, 1200-19,200 bps Front Panel 11 LEDs, key pad, and 2x20 LCD display Front Panel control push buttons Includes EnerVista software EnerVista Software EnerVista software - an industry leading suite of software tools that simplifies every aspect of working with GE Multilin devices EnerVista Integrator providing easy integration of data in the FM2 into new or existing monitoring and control systems g Digital Energy Multilin 359

FM2 Feeder Protection System Protection and Control The FM2 is available with a variety of protection and control features. FM2 can be used for fuse contactors feeders or feeders with breakers having built in trip units. Thermal Overload Thermal overload trip occurs when the thermal capacity value equals 100%. Thermal capacity used is calculated from accumulated I 2 t value and chosen overload curves. True RMS current sensing ensures correct response to the heating effect of harmonics. One of 3 different I 2 t time overcurrent overload curves may be selected from standard IEC curves. After an overload trip, the thermal capacity value decreases exponentially to model the load cooling characteristic. An overload trip can be reset when the thermal capacity value decreases to 15%. Ground Fault Aging and thermal cycling can cause cable and equipment insulation to break down, resulting in ground faults. Ground faults can be detected by either from the residual connection of the phase s or from the zero sequence. The FM2 can trigger a trip or an alarm if the ground fault pickup level is exceeded. A time delay may be entered for time coordination of systems with several levels of ground fault detection. Contactor/Circuit Breaker Failure The FM2 monitors the contactor/circuit breaker while performing close and open commands. If the contactor does not change status an open control circuit or welded contactor alarm is triggered. If circuit breaker doesn t change status a breaker failed to close or breaker failed to open alarm is generated. Additional Alarms The FM2 has programmable alarms to warn of a number of abnormal conditions. These include: contactor inspection, and process interlock switch open. Undervoltage Autoreclose The feeder can be automatically reclosed after a momentary power loss when this feature is enabled. When the control voltage drops below the dropout voltage the contactors are de-energized. The FM2 can initiate timers to reclose selected feeder upon the return of supply voltage. It has one instantaneous and two delayed reclose settings. If control voltage is restored within the programmed reclose time, the feeder will be reclosed immediately. If the control voltage takes longer to be restored, the FM2 can be programmed to attempt a reclose after a programmed time delay. Outputs The FM2 has two output relays (A and B). Relay A and Relay B can be controlled independently for controlling a breaker. Relay A is used as close contact and Relay B is used as a trip contact for the breaker. There is also a programmable relay available on the FM2, which can be assigned to any one of the relay functions. FM2 has an emergency shutdown (ESD) relay, which can be energized externally by applying 24VDC. Switched Inputs The FM2 has six fixed control inputs. These are used for close A and B, open, test status, and contactor A and B status. The FM2 also has 10 programmable switch inputs. Each input can have one of a number of interlock functions assigned to it. A function can be assigned to one interlock input. Monitoring and Metering The FM2 offers advanced monitoring and metering which includes: Metering The FM2 meters and displays: RMS current of each phase Ground fault leakage current Phase current imbalance (%) Power (kw) Energy (kwhr) Functional Block Diagram BREAKER 415-12000 VOLTS BUS 52 ANSI Device Numbers & Functions Device Number Function 49/51 overload - welded/open contactor 50G earth fault 79 undervoltage autoreclose *see ANSI Standard in catalog for a complete list Voltage Trip Record When the FM2 issues a trip command a record is generated which includes the cause and pre-trip current values. Statistics and Maintenance FUSE CONTAOR PHASE/LINE VT PHASE CB RELAY A RELAY B 79 49 51 50G PROG. RELAY ESD RELAY CONTROL INPUTS 24VDC INPUT PROCESS PLC The FM2 records statistical data about relay and feeder operation, allowing the user to set the interval at which routine maintenance tasks should be performed. When the times are exceeded an alarm is generated. This includes: Contactor inspection: number of contactor/breaker operations after which contactor contacts must be inspected for wear LOAD FM2 FEEDER PROTEION SYSTEM 848700A1.DWG RS485 REMOTE MUNICATE 1200-19200 BAUD 360

AUTO MANUAL CLOSE A CLOSE B SETPOINT AUAL RESET STORE MESSAGE VALUE RUNNING STOPPED TRIPPED ALARM FAULT RELAY A RELAY B PROG RELAY ESD RELAY Multilin FM2 Feeder Manager 2 FM2 Feeder Protection System User Interfaces The user can communicate with the FM2 through a variety of interfaces: Display and Control Keys single communication channel. The FM2 supports operation at 1200 to 19,200 bps. A RS232/485 converter module may be used to connect a personal computer to the FM2. The panel mount model has a large user key which opens feeder contactor/breaker. The panel mount model comes with a two-line 40 character display and additional control keys. The display and keypad can be used for local programming, showing information on alarms and trips, and displaying monitoring and metering values. Indicator LEDs The panel mount FM2 has nine status LEDs and has two additional LEDs which indicate auto mode or manual control mode. Communications The FM2 uses a ModBus RTU RS485 connection for communication. Up to 32 FM2s can be daisy-chained together on a Models Mounting Configurations The FM2 can be ordered in either chassis mount or panel mount with display. The chassis mount model comes with any of the option models. Setpoints are loaded through the RS485 port. The panel mount with display model may be ordered with any option model. It is mounted on the front panel of the PCC with its two by 20 alphanumeric display, full keypad, and 11 status LEDs exposed to the operator for complete local viewing and setpoint programming. The setpoints can also be loaded into the relay through the RS485 communications port. Models Model 712: 120V, 50 or 60Hz AC VT input and switch input voltage rating Model 722: 240V, 50 or 60Hz AC input and switch input voltage rating The panel mount with display model is the Top of the Line FM2. EnerVista Software A single PC setup software package is required to access, configure, and monitor the FM2 relay. The EnerVista FM2 Setup Software extracts the model number, version, and configuration parameters from the connected relay to display only the relevant data and options for the relay it is communicating with. This eliminates having to manually configure the relay within the software and provides a simple and easy to use operator user interface. The FM2 relay is supplied with Windows based EnerVista FM2 Setup Software. EnerVista software may be run on a PC with any Windows based operating system. The program may be used locally on the RS232 front port or remotely on the RS485 port. It provides full access to the relay data with the following features: View relay status and actual values The chassis mount model is the black box version of the FM2. It is mounted inside the power control center (PCC). Cost Effective PCC Wiring with FM2. View/edit settings on-line/off-line View event recorder for trouble-shooting Configure inputs, outputs and LEDs through configurable logic REPEAT FOR EACH CONTAOR/BREAKER CONVENTIONAL PCC SUPERVISORY CONTROL SYSTEM CLOSE CLOSED TRIPPED MULTIWIRE CONTROL CABLE REMOTE CONTROL REPLACED BY PCC WITH FEEDER MANAGER 2 SUPERVISORY CONTROL SYSTEM TWO WIRE CONTROL CABLE Utilize a configurable protection curve Relay firmware programming for upgrades In addition, all status information such as target messages and digital input/output states may be viewed with EnerVista FM2 Setup Software. 120/240 VAC CLOSE CONTAOR CONTAOR TRIP CONTAOR LOAD SENSOR LOCAL PCC TO OTHER CONTAORS IN PCC 120/240 VAC DIGITAL CONTROL/ MONITOR RS485 TWISTEDPAIR FEEDER MANAGER 2 O/L E / F TRIP FIELD STOP CONTAOR 807680A7.cdr 361

FM2 Feeder Protection System Features Front View DISPLAY: 2 line, 40 character illuminated display communicates all messages in simple English for easy interpretation by users unfamiliar with unit. control KEYS: Auto: Selects operation of close via communication port. Manual: Selects manual operation of feeder using close key. CLOSE A: Energize contactor A. CLOSE B: Energize contactor B. : De-energize contactors. relay indicators: Relay A: Contactor A energized. Relay B: Contactor B energized. prog relay: User programmable relay 1 energized. esd relay: ESD Relay energized. program KEYS: AUAL VALUES: Press to enter actual values mode to display actual feeder values such as current, earth leakage, voltage, power, energy. SETPOINTS: Press to enter setpoint mode to alter or examine setpoints. Store: Save a newly entered setpoint. RESET: Reset the FM2 after a trip. Message: Move to the desired setpoint or actual value message. VALUE: Increment or decrement currently displayed setpoint value. status INDICATORS: CLOSED: Contactor is energized and feeder is closed. : Contactor is not energized and motor is not running. TRIPPED: Contactor is not energized. Feeder is open. The FM2 has tripped the feeder due to a fault. Normally a cause of trip message will be displayed. ALARM: One or more alarm conditions are present. Normally a cause of alarm message will be displayed. Fault: An internal fault or abnormal condition has been detected. The FM2 may need to be replaced or serviced. Supply voltage required to power thefm2. Rear View communications RS485 2 wire serial communication port operates at 1200 19,200 bps for remote commands, monitoring and setpoint store. ModBus RTU protocol. switch inputs Opto-isolated 120 VAC live inputs for various interlock functions. The interlock inputs are fully programmable and can be assigned to such functions as setpoint access, plant interlock, test, and various others. Control Power 120/240 VAC supply voltage selector switch and fuse access door. Earth safety and surge. voltage input Phase R voltage input for voltage and power monitoring. phase Ct inputs 3 isolated phase inputs that accept 1 amp or 5 amp. 4 relays Relay A: Relay B: User programmable relay (PROG RELAY 1) Emergency Shutdown Relay (ESD) EARTH FAULT ct input 5 amp or 50:0.025 earth fault input for residually connected phase s or separate core balance (zero sequence). 362

RUNNING STOPPED TRIPPED ALARM FAULT CONTAOR A CONTAOR B AUX 1 AUX 2 FM2 Feeder Protection System Typical Wiring PHASE R RESIDUAL GROUND CONNEION PHASE Y PHASE B PHASE R TWO PHASE CONNEION PHASE B DIRE CONNEION 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 50: 5A 1A 5A 1A 5A 1A 5A 0.025 5A 1A 5A 1A 5A 8 9 10 11 12 1A 5A 50: 0.025 1 2 3 4 5 5A 1A 5A 1A 6 7 8 9 5A 1A B Y PHASE R 415V R Y R B PHASE Y ISOLATOR SWITCH PHASE B CONTAOR A L1 A L2 A L3 415V 120V OR 240V * See Note 4 Vry VT 15 EARTH 16 1 2 3 PHASE R 4 5 PHASE Y 6 7 8 PHASE B CORE BALANCE ( ZERO SEQUENCE ) PHASE R PHASE Y PHASE B 9 10 EARTH EARTH 11 12 PHASE R L1 L2 L3 PHASE Y LOAD PHASE B 5A 1A 5A 1A 5A 1A 5A 50: 0.025 VT VT PHASE R PHASE Y PHASE B EARTH CLOSE A 50 * 51 * 41 42 43 44 45 46 47 48 49 52 53 54 55 56 INPUT 10 INPUT 9 INPUT 8 INPUT 7 INPUT 6 INPUT 5 INPUT 4 INPUT 3 INPUT 2 INPUT 1 CLOSE A CLOSE B TEST STATUS NO CONTAOR A STATUS NO CONTAOR B STATUS NO PROGRAMMABLE SWITCH INPUTS FIXED SWITCH INPUTS SERIAL EARTH SERIAL 485 + SERIAL 485 Multilin FM2 g Feeder Protection System 38 39 40 RS485 57 SWITCH MON 58 SWITCH MON EARTHING CONTROL VOLTAGE RELAY A SAFETY SURGE L NO NO 1NC 1 13 14 36 37 34 35 32 33 26 27 N RELAY B PROGRAMMABLE RELAY 1NO 2NC 2 2NO 28 29 30 31 ESD RELAY 24VDC COIL NC NO + - 23 24 25 21 22 PCC EARTH BUS L AC CONTROL VOLTAGE 120/240 VAC N CONTAOR A 848704A1.DWG NOTES: 1) RELAY CONTA STATE SHOWN WITH CONTROL POWER NOT APPLIED. 2) TERMINALS MARKED WITH " " MUST BE CONNEED BEFORE FEEDER IS CLOSED 3) DIRE CONNEION WITH NO s CAN BE USED FOR FEEDER FULL LOAD CURRENT BELOW 10 AMPS (TYPICALLY LESS THAN 10 HP). NOTE: TERMINALS RATED FOR 600V. 4) 240VAC INPUT CAN BE GIVEN TO FM2-722* MODELS ONLY * Dimensions PANEL MOUNT FRONT VIEW PANEL MOUNT SIDE VIEW PANEL MOUNT CUTOUT Inches CHASSIS MOUNT SIDE VIEW CHASSIS MOUNT CUTOUT (mm) 7.10" 7.50" 7.36" 1.0" 3.95" 4.13" (187) 0.10" (180) 6.90" 0.13" (191) (25) (100) PANEL (105) 7.24" PANEL (2.5) (175) (3) (184) 0.35" (9) 0.30" (7.5) FM2 Feeder Manager 2 4.35" (111) CUTOUT 1.15" (29) 2.31" (59) 3.47" (88) 4.17" (106) 6 x 0.218" Dia. HOLES (6) BASE PLATE PROFILE 1.73" (44) 3.47" (88) 4.07" (103) 8 x 0.078" R (2) 807629C5.dwg 363

FM2 Feeder Protection System FM2 Technical Specifications PROTEION IEC OVERLOAD CURVES IEC A, IEC B, IEC C Trip time: ±200 ms up to 10 sec Accuracy: ±2% of trip time over 10 sec Detection level: ±1% of primary amps ground Fault Trip time Accuracy: -0 ms, +50 ms, 0.0 = <50 ms UNDERVOLTAGE supply voltage Undervoltage: 65% of nominal (120 VAC or 240 VAC) immediate reclose for maximum dip time of 0.1 0.5 sec or OFF delay 1 reclose for maximum dip time of 0.1-10.0 sec/unlimited time delay 2 reclose for maximum dip time of 0.5-60.0 min/off Delay reclose range: 0.2 300 sec Delay restart accuracy: ±0.2 sec monitoring Voltage input/power reading Conversion: True RMS, sample time: 12 samples/cycle for 50Hz 10 samples/cycle for 60Hz Voltage full scale: 1.5 x VT primary Voltage accuracy: ±2% of VT primary or ±2% of reading (whichever is greater) Power accuracy: ±5% of nominal or ±5% of reading (whichever is greater) Power range: -12500kW to +12500kW Input voltage: Nominal: 120 VAC or 240 V Max: 150 VAC for 712 model 300 VAC for 722 model VT burden: 0.01 VA Phase IMbalance Range: Greater than 30% U/B trip, alarm 15% Accuracy: ±2 percentage points Trip delay: 5 sec, ±1 sec Calculation method: If I AV Ž I flc : IM - IAV x 100 I AV If I AV < I flc : IN - IAV x 100 I flc Where:I AV = average phase currents I M = current in a phase with maximum deviation from I AV I flc = motor full load current setting METERING PHASE CURRENT INPUTS Conversion: True RMS, sample time: 12 samples/cycle for 50Hz 10 samples/cycle for 60Hz Range: 0.1 8 x phase primary amps setpoint Full scale: 8 x phase primary amps setpoint Accuracy: ±2% of Phase primary amps setpoint or ±2% of reading, whichever is greater ground FAULT CURRENT INPUT Conversion: True RMS, sample time: 12 samples/cycle for 50Hz 10 samples/cycle for 60Hz Range: 0.1 to 1.0 x Phase primary amps setpoint (5 A secondary ) 0.5 to 15.0 amps (2000:1 ) Full scale: 1.5 x primary amps setpoint (5 A secondary ) (15 A (2000:1 ) Accuracy: 5 A secondary: ± 2% of full scale 2000:1 : ± 0.10A (0.0 to 3.99 A) ± 0.20 A (4.00 to 15.00 A) OUTPUTs RELAY CONTAS FM2 Contactor A & B and ESD relay VOLTAGE MAKE/carry make/carry break CONTINUOUS 0.2 sec 30 Vdc 10 A 30 A 10 A Resistive 125 Vdc 10 A 30 A 0.5 A 250 Vdc 10 A 30 A 0.3 A 30 Vdc 10 A 30 A 5 A Inductive 125 Vdc 10 A 30 A 0.25 A (L/R = 7ms) 250 Vdc 10 A 30 A 0.15 A Resistive 120 Vac 10 A 30 A 10 A 250 Vac 10 A 30 A 10 A Inductive 120 Vac 10 A 30 A 10 A (PF = 0.4) 225 Vac 10 A 30 A 8 A Configuration Contactor A & B Form A ESD Relay form C Contact Material Silver alloy (AgCdO) Max operating voltage 280 VAC, 250 VDC Minimum permissible load 5 VDC, 100 ma FM2 Prog relay 1 output VOLTAGE MAKE/carry make/carry break 0.2 sec Resistive 30 Vdc 5 A 15 A 5 A 125 Vdc 5 A 15 A 0.25 A Inductive 30 Vdc 5 A 15 A 2.5 A (L/R = 7ms) 125 Vdc 5 A 15 A 0.1 A Resistive 120 Vac 5 A 15 A 5 A 250 Vac 5 A 15 A 5 A Inductive 120 Vac 5 A 15 A 5 A (PF = 0.4) 225 Vac 5 A 15 A 3 A Configuration Aux relay 1 dual form C Contact Material Silver alloy (AgCdO) Max operating voltage 280 VAC, 125 VDC INPUTs inputs input Burden (A) (VA) (ž) 1 0.009 0.01 Phase (1 A) 5 0.2 0.01 20 3.5 0.01 5 0.04 0.002 Phase (5 A) 25 0.9 0.002 100 16 0.002 5 0.04 0.002 Earth (5 A) 25 1.1 0.002 100 17 0.002 Sensitive Earth 0.025 0.07 116 Fault (50:0.025) 0.1 1.19 119 0.5 30.5 122 Withstand 1 sec x 5 sec x continuous x Phase (1 A) 100 40 3 Phase (5 A) 100 40 3 Earth (5 A) 100 40 3 50:0.025 EARTH FAULT Input Withstand Continuous 150 ma Maximum 12 A for 3 cycles 50:0.025 input can be driven by a GE Multilin 50:0.025 Digital Inputs Inputs: Input Type: 6 fixed & 10 configurable inputs optically isolated. Dry contact POWER SUPPLY supply voltage AC nominal: Frequency: Power consumption: 120 VAC, range 108 135 VAC 240 VAC, range 216 250 VAC 50/60 Hz 25 VA (Maximum) 7 VA (Nominal) *CE units limited to 250 V unless external fuse rated to 300 V is used. communications Type: Baud rate: Protocol: Functions: environmental type tests UL: Transients: Impulse: RFI: Static: Hipot: fuse type/rating 0.5 A 250 V Fast blow, high breaking capacity installation WARNING: HAZARD may result if the product is not used for its intended purpose Ventilation requirements: None Cleaning requirements: None certification RS485 2 wire, half duplex 1,200 19,200 bps ModBus RTU Read/write setpoints, read actual values, execute commands, read coil status, read device status, loopback test Pollution degree: 2 Overvoltage category: 2 Insulation voltage: 300 V Operating temperature range: 0 C to 60 C Dust and moisture rating: NEMA Type 12+12K PACKAGING E83849 ANSI/IEEE C37.90.1 oscillatory/ fast risetime transients IEC 255-22-4 electrical fast transient/burst requirements IEC 255-5 5 kv impulse voltage test IEC 255-22-3 5 v/m with portable transmitter IEC 255-22-2 electrostatic discharge 1500 V, 1 min all input >30 V Max weight: 4 lbs (1.8 kg) Shipping dimensions: 8.3" x 5.625" x 5.8" (211 mm x 143 mm x 147 mm) : IEC 61010-1 culus: E83849 UL listed for USA & Canada *Specifications subject to change without notice. Ordering FM2 * - * - * - * Base Unit FM2 Product Family Model 712 120V AC VT and Switch input voltage 722 240V AC VT and Switch input voltage PD Panel mount with Display C Chassis mount (Black box) Visit www.gemultilin.com/fm2 to: View Guideform specifications Download the instruction manual Review applications notes and support documents Buy a FM2 online View the FM2 brochure 364 0306-v3