Tarleton State University. Specifications

Similar documents
COMPUTER NETWORK WIRING SYSTEMS FOR PLCs

A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

Network Construction Guide Specification Telecommunications Infrastructure Standards V 2.6

The six major components of a structured wiring system are:

f) Telecommunications Equipment Rooms

Communications. UNM IT/Telecommunications Guide Specification Communications

Computer Network Design Guide Existing Systems 1 / 6

Division 27 Master Specification for

Government of Prince Edward Island Structured Cabling Standards August 24, 2009

Copper Riser And Intrabuilding Cabling

Data Cabling / Low Voltage Technology Specifications

Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING

SPECIFICATION STANDARD

Target Interface / Construction Compliance Inspection Checklist

SECTION COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING

SECTION TELEPHONE AND COMPUTER CABLING

The University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS

ANSI/TIA/EIA-568-B Cabling Standard

SECTION TELECOMMUNICATIONS TESTING AND DOCUMENTATION

SECTION COMMUNICATIONS BACKBONE CABLING

LACCD IT Design Standards

TIA/EIA 568A Sub-system HORIZONTAL CABLING

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS

COMMON WORK RESULTS FOR COMMUNICATIONS

INTERIM COMMUNICATIONS INFRASTRUCTURE PLANNING GUIDELINES

UMass Lowell. October 1, Network and Voice Infrastructure Specifications Prepared by Network Engineering and Network Project Management

E. Numbering and Labeling Pathway components. In general, pathway components are not labeled.

PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY

v2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017.

Communication

Cabling Infrastructure

Addendum No. 1 January 7, 2015

Wirewerks Datacenters Becoming More Common in Our Workplace, Next Step Solution

ANSI/TIA/EIA-568-B Cabling Standard

AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM. Welcome!!! Instructor : Nicholas Yeo

Los Angeles Community College District Design Standards

Communications Updated April

BROWARD COUNTY AVIATION DEPARTMENT INSIDE PLANT INFRASTRUCTURE SPECIFICATIONS

ELLIS COUNTY COURTS AND JAIL EXPANSION. SECTION Communications Cabling Infrastructure ADDENDUM #4. Table of Contents

SECTION 2 DIVISION 27 UNC CHARLOTTE ITS DEPARTMENT. ITS Telecommunications Standards - Specifications Manual for Construction and Renovations

Classroom WiFi Network Infrastructure Plan

AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT)

Technology Standards

PANGEN SYSTEM WARRANTY. Warranty Guide

PIONEERS OF The Structured Cabling Systems

SPOS (Station Point of Sale) 200. SFTP (Station Fare Transaction Processor) 35. CQD (Card Query Device) 35. HCR (Handheld Card Reader) Cradles 120

UNIVERSITY OF CALICUT (Purchase Division)

Structured Cabling Guidelines

Cable Certification. General Testing Criteria (Applies to all cable certification testing) Attachment F Cable Certification

Design Guidelines for Facilities Construction:

University of Arkansas at Little Rock

Telecommunications Structured Cabling Systems

Optimization and Speed: Two Critical Standards Enabling Next Generation Networks. Stephanie Montgomery, TIA Brett Lane, Panduit

SUSQUEHANNA COMMUNITY SCHOOL DISTRICT BID REQUEST FOR THE INSTALLATION OF FIBER OPTIC CABLE CAPABLE OF A 10 GIGABIT

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling

AT&T Dedicated Internet (ADI formerly known as MIS) and Private Network Transport (PNT)

BUILDING NETWORK SOLUTIONS GUIDE

FiberSolutions. Fiber Optic Cable & Assembly Solutions

ELLIS COUNTY COURTS AND JAIL EXPANSION. SECTION Communications Cabling Infrastructure ADDENDUM #2. Table of Contents

SECURE NETWORK INFRASTRUCTURE POLICY

STRUCTURED CABLING GUIDELINES. for PALM BEACH STATE COLLEGE

OMEGA MODULAR PATCH PANEL EMPTY ENCLOSURE

FIBER OPTIC HARDWARE STEVE PAULOV

ANSI/BICSI , Information Transport Systems Design Standard for K-12 Educational Institutions

Peter Sharp RCDD IBI Group

CERTIFICATION PLUS SM

Structured Cabling Guidelines For The State Of Oregon

Connectix Specification Guide for Category 6 U/UTP and Optical Fibre Cabling System Architecture

Master Format Division 27 - Communications

AT&T Switched Ethernet Service SM

COUNTY OF SAN JOAQUIN

PoP ROOM: INSIDE AND OUTSIDE PLANT RULES & REGULATIONS

The 5500 Series from The Wiremold Company

Siemon PON Fiber Cabling Solutions

Bonding and grounding NETCONNECT copper cabling systems

Structured Cabling Supplement

Newark, Delaware Architectural Engineering Senior Thesis Portfolio

FLORIDA A&M UNIVERSITY S

The Riser as a Contract Document. Peter Sharp, RCDD

BACKBONE CABLING. Structured Cabling Systems. Entrance Closet. Telco Closet. Intermediate Cross Connect. Telco Closet. Main Cross Connect.

Information Transport Systems and Spaces

Technology Infrastructure: Category 6A & SM Fiber to the Desktop Cabling Standards. Revision 6 2/1/2018

9/27/04 cci Cablecom Inc. 1

PRAIRIE-HILLS ELEMENTARY SCHOOL DISTRICT 144, 470 APPLICATION INTERNAL CONNECTIONS CABLING RFP (TOTAL OF 1500 CAT6 DROPS)

Element Z General Design Requirements Owner Standards and Other Requirements

REQUEST FOR PROPOSAL:

CCNA 1: Networking Basics v3.0 Cisco Networking Academy Program

Structured Cabling Guidelines For PALM BEACH STATE COLLEGE

ARIADROP: Fiber to the MDU (FTTM)

The following pages contain a guide for the installation

Section COMMUNICATION EQUIPMENT ROOM FITTINGS. Section Communications Cable Management and Ladder Rack

Cabling a Data Center to TIA-942 Standard

MCIWEST G6 TELECOMMUNICATION REQUIREMENTS SECTION (ISP)

The 5400 Series Raceway from The Wiremold


Passive Infrastructure Technical Specification. Version 1 / March 14

Qualified Partner Programme QPP. Installation Practice Felice Guarna Wetzikon, July 2001

CableSmart Series Nonmetallic Raceway

Cabinet Location Plan FIG.01. Cabinet Symbol Key. Air Handler. Air Handler SAN disk storage. SAN disk storage. option B. Not To Scale.

Transcription:

Tarleton State University Campus Communication Infrastructure Specifications Cabling Standards Summary This document identifies Tarleton State University communication infrastructure standards. The communication infrastructure supports the campus voice, data and cable television communication network. Prior to any cable being pulled at or for Tarleton, Information Technology Services is required to obtain approval from the Director of Risk Management to certify the cable route is asbestos free. Any Contractor doing business on Tarleton s behalf is required to comply with these specifications. Any deviation from these specifications requires written authorization from the Tarleton ITS Project Manager. Contractor shall purchase and install components for a structured cable system utilizing a Belden/ Ortronics integrity solution. Ortronics provides Tarleton with a 15-year system and applications warranty on all parts and labor. Warranty commences at the time of completion. Contractor Technicians must Belden/Ortronics integrity certified installers and are authorized to provide cable warranty certifications. Quality Assurance

Tarleton uses and installs materials and equipment in compliance with the latest applicable standards from ANSI, FCC, ASTM, TIA/EIA, IEEE, NEC, NFPA, NEMA, REA and UL includes but not limited to. 1. ANSI/TIA/EIA-568-C.0 and C1 Standards, Commercial Building Wiring Standard 2. ANSI/TIA/EIA-569-A Standard, Commercial Building Standard for Telecommunications Pathways and Spaces. 3. ANSI/TIA/EIA-570 Standard, Residential and Light Commercial Building Wiring Standard. 4. ANSI/TIA/EIA-606 Administration Standard for the Telecommunications Infrastructure of Commercial Buildings 5. ANSI/TIA/EIA-607 Commercial Building Grounding and Bonding Requirements for Telecommunications 6. Institute of Electrical and Electronic Engineers (IEEE) Standards 7. Underwriters Laboratories (UL) i. UL 467 Grounding and Bonding Equipment 8. National Electrical Code (NEC) (Latest revision and pertinent addendums) 9. National Fire Protection Association (NFPA) Publications (Latest revision and pertinent addendums) Cable Plant Requirements Information outlets for data and voice communication shall be fed using the horizontal cable system. The horizontal system consists of plenum rate 4-pair Unshielded Twisted Pair (UTP) Belden cable (CAT 6). Information outlets will accommodate future installation of telephone, computers, and modems. A. Horizontal Wiring System (voice & data) 1. Tarleton Cable pulls are no longer than 270 feet. Longer pulls must be preapproved by Tarleton Telecom prior to installation. 2. CAT 6 is cable is orange for data and white for voice. It is used for all new construction or if specifically requested. 3. EIA-568B termination sequence is always used. 4. A 36 service loop is provided in the ceiling above each jack location for all copper cables. These service loops shall be neatly dressed and properly supported. 5. Voice cable is terminated on a Cat6 Patch Panels in the closet and RJ45 flush mount jacks at work station. 6. Data cable is terminated in 19 equipment rack mounted Ortronics patch panels in the closet and RJ45 flush mount jacks at the work station. 7. Caddy J hooks are installed to support all horizontal cables. J hooks are to be installed no more than five (5) feet on center and are installed using only Caddy approved installation methods and materials. 8. All conduct, sleeves or any other penetrations are properly fire-stopped.

9. Grounding and bonding consists of a minimum number 6 AWG copper wire fed from an approved building ground and bonded to an approved electrical earth ground. 10. All conduits for data and voice workstations will be stubbed out the nearest cable tray. 11. Contractor must provide a current and complete Project of Requirements, floor plans with voice and data locations including room numbers and any additional drawings or information required to successfully take eventual ownership and to maintain telecom infrastructure in new building. 12. Contractor must provide documentation detailing labeled workstations with corresponding room numbers. B. Equipment Room Contractor must use the appropriate Industry codes and standards. Contractor must submit a proposed layout to Tarleton Telecom for approval prior to 100% design completion. C. Intrabuiliding Fiber Optic Cable Contractor is responsible for installing, terminating, labeling and testing any required intrabuilding fiber. Contractor must submit a proposed cable route to Tarleton Telecom for approval prior to 100% design completion. D. Intrabuilding Copper Cable Contractor is responsible for installing, terminating, labeling and testing any required intrabuilding fiber. Contractor must submit a proposed cable route to Tarleton Telecom for approval prior to 100% design completion. Testing A. Each data run is tested to compliance with ANSI/TIA/EIA standards, including but not limited to, continuity, length, anomalies, and attenuation. B. Records are submitted for all test results. C. Fiber terminations are outsourced but require bi-directional OTDR testing, including launch and landing reel as well both wavelengths for each type of fiber specified. D. All Ethernet cabling must be tested as a channel test with the patch cords provided by the contractor. These patch cords must be left in place at the patch panel and workstation after testing. Identification, Labeling and Documentation A. Contractor shall labels all terminal blocks, patch panels, cabling pairs, wiring pairs, and both ends of each cable between the work station outlet and the closet. B. Contractor shall uses a mechanically generated white label with black lettering to label both the outlet face plates and patch panel.

C. Tarleton's labeling scheme is customized. Work Station Label: Closet #-Patch Panel #- Patch Panel port# MDF and IDF Patch Panel Label will be the Work Station room #. Approved Equipment List Fiber: Corning Inside Fiber-XXX-E88-33131-D3 Outdoor Fiber-XXX-EUC-T4101D20 Rack Mount Fiber Cabinet (item CORNING CABLE SYSTEMS CCH-0#U) Wall Mount Fiber Cabinet (WCH-#P) Fiber pigtail cassettes CCH-CS##-A9-P00RE (single jacket, single armor, OS2) Fiber is to be fusion spliced to a manufactured fiber jumper instead of terminations being made. LC connectors Fiber cassettes for Cable TV CCH-CS06-6C-P00RE 6f SM APC Pigtailed Cassette Copper: Essex PE-89 -The voice cables will be jumped with a 25 pair cables from the Circa to an Ortronics patch panel. -The horizontal voice will be terminated on an Ortronics patch panel. -Building Entrance- Circa 1880ECA1-100G for 100 pair backbone cable The voice cables will be jumped with a 25 pair cables from the Circa to an Ortronics patch panel part #. OR-PHD-66U48 The horizontal voice will be terminated on an Ortronics patch panel. Voice& Data Workstation Wiring: Belden/Ortronics (EIA-TIA 568B) Cable: Belden Cat6 (item # 2413), Data - Orange Hardware, general- Ortronics Faceplates (item # OR-40300158 Blanks (item# OR-40300164) Hardware, Cat 6 - Ortronics Single Data or Voice Jack (item # OR-S21600) Double Data or Voice Jack (item # OR-S22600) 6 ft. Patch Cord (item # OR-MC606, orange) 15 ft. Patch Cord (item # OR-MC615, orange) Patch Panel (item # OR-PHD-66U48) Note: The contractor will provide 2 patch cords per phone and data drop. The split will be 15 ft. (50), and 6 ft. (50%)

The contractor will provide 1 LC-LC 3 meter fiber jumper per fiber termination Equipment Racks Chatsworth Products, Inc. 15212-703, Rack 13902-703, 6 Wire Manager 13930-702, Horizontal Wire Manager Chatsworth Cable Runway will need to be provided through each MDF and IDF Cable tray must be installed throughout the cable path. Cope Cat-Tray Wire Mesh Cable Tray System cope_cattray_0501s m[1].pdf All walls must be covered with plywood and painted with fire resistant paint or a fire retardant plywood can be used. Separate cooling system must be installed for each telecom room. 1-20 amp circuit with quad plate with 5-20R plug and 1-30 amp circuit with L5-30R plug. These are to be mounted to the top of 7ft cable rack. Grounding of all racks and provide a Ground bus bar per closet. Closet will need to be wired for card access. Refer to one card specs.