PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B

Similar documents
PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B

PSR-SCP- 24DC/SSM/2X1 PSR-SPP- 24DC/SSM/2X1

PSR UC/ESAM4/3X1/1X2/B

PSR DC/ESP4/2X1/1X2

SAFETY RELAY YRB-4EML-31S MAIN FEATURES

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

PSR-PC20. SIL coupling relay. Data sheet. 1 Description

Safety Switching Devices SNO 4003K. Basic device for Emergency-Stop and Safety Gate Applications PI E

ILBIB24DO16-DSUB. Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors

ETD-BL-1T-230(-PT) Multifunctional time relay with various functions and adjustable times. Data sheet. 1 Description

EMD-FL-C-10. Electronic monitoring relay for overcurrent and undercurrent monitoring of direct and alternating current in single-phase networks

PSR-PS21. SIL coupling relay. Data sheet. 1 Description

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

Safety module - PSR-SCP- 24DC/TS/S

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description

ETD-BL-1T-OFF-CC- 10S

PHOENIX CONTACT Features

PI-EX-ME-2NAM/COC-24VDC

MINI MCR-SL-PT100-UI(-SP)(-NC)

PHOENIX CONTACT - 05/2007

MINI MCR-SL-CVS NC

PLC-R 21HC. PLC INTERFACE With SPDT Relay, High-Current Version. INTERFACE Data Sheet _03_en. Description

PI-EX-ME-2NAM/COC-120VAC

PHOENIX CONTACT - 12/2007

MINI MCR-SL-UI-2I(-SP)(-NC)

MINI MCR-SL-UI-REL(-SP)

MINI-PS AC/10-15DC/8

MINI MCR-SL-PT100-UI-200

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

MINI MCR-SL-RPS-I-I. Repeater power supply, active. Data sheet. 1 Description

IB IL 24/48 DOR 2/W-XC-PAC

MINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description

SECTION 16 LED DIAGNOSTIC FEATURES: EXPANSION UNITS: SCR-31P-i. SCR-73-i. SEU-31-i. SCR-31-42TD-i. SEU-31TD-i

BNS SERIES - COMPATIBLE SERIES AES SAFETY CONTROLLERS SELECTION CHART AVAILABLE STANDARD MODELS

PHOENIX CONTACT - 01/2007

PHOENIX CONTACT - 07/2006

Safety relay emergency stop/protective door, 24VDC/AC, 4 enabling paths

Original operating instructions Safety relay with relay outputs G1501S / / 2016

PLC-RSC- 24UC/21. Extract from the online catalog. Order No.:

MINI MCR-SL-PT100-UI. Active resistance thermometer measuring transducer. Data sheet. 1 Description

PHOENIX CONTACT - 10/2009

EMD-SL-LL-230. Electronic monitoring relay for level monitoring of conductive liquids. INTERFACE Data sheet _en_04. 1 Description.

MACX MCR-EX-SD LP(-SP)

INTERFACE. User Manual

QUINT-PS-3x AC/24DC/10

Safety relay emergency stop/protective door, 24V-230VDC/AC, 3 enabling paths

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

ELR H3-IES-PT- 24DC/500AC-...

MINI MCR-SL-UI-2I-NC. Extract from the online catalog. Order No.:

Safety relay emergency stop/protective door, 24VDC/AC, 3 enabling paths

AS-i Safety Relay Output Module with Diagnostic Slave, 1 EDM, 1 x 2 channel Safe Input

Positive-guided relay outputs: 4 safety contacts (N/O), instantaneous

Operating instructions. Switching amplifier DN0210 DN / / 2015

PLC-RSC- 24DC/21 Order No.:

onlinecomponents.com

Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016

PLC-RSC- 24DC/21. Extract from the online catalog. Order No.:

MACX MCR-EX-SL-NAM-R(-SP)

MACX MCR-EX-SL-NAM-2RO(-SP)

Contact protection relay

Operating instructions. Speed monitor D / / 2014

Positive-guided relay outputs: 4 safety contacts (N/O), instantaneous

PSI-MODEM-SHDSL/PB. Broadband PROFIBUS extender, SHDSL PROFIBUS leased line modem. Data sheet _en_03. 1 Description. 1.

MINI-DC-UPS/12DC/4. Extract from the online catalog. Order No.:

PHOENIX CONTACT - 11/2007. This data sheet is only valid in association with the IB IL SYS PRO UM E user manual.

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Technical data. Housing Polyamide housing PA 66, self-extinguishing V0 acc. to UL 94. Supply Rated supply voltage (U n

E-STOP relay, safety gate monitor

QUINT-BUFFER/24DC/24DC/40

Faults on the system Proximity switch connection technology:

Safety relay emergency stop/protective door, 230VAC, 3 enabling paths

ISOMETER isoev425 with coupling device AGH420

DEK-REL- 5/I/1. Extract from the online catalog. Order No.:

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

Extract from the online catalog

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5

TRIO-DIODE/12-24DC/2X10/1X20

PSI-MODEM-SHDSL/SERIAL

E-STOP relays, safety gate monitors

Redundancy Module QUINT-DIODE/40

This data sheet is only valid in association with the IL SYS INST UM E user manual.

Phone: Fax: Web: -

PLC-RSC- 24DC/ Extract from the online catalog. Order No.:

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

ASI QUINT /2.4 EFD

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

E-STOP relays, safety gate monitors

VAL-CP-1S-175. Extract from the online catalog. Order No.:

Safe monitoring relays

E-STOP relay, safety gate monitor

VAL-CP-3S-350. Extract from the online catalog. Order No.:

Safety relays PNOZsigma

Technical data. Safety parameters: see page 333. DC maximum residual ripple: 10% Supply voltage tolerance: DC consumption: Control circuit

ITEM ESM-BA301

QUINT-PS/ 1AC/24DC/ 5

PHOENIX CONTACT - 01/2008

IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description

Transcription:

PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B Safety Relay for Emergency Stop and Safety Door Circuits INTERFACE Data Sheet 102858_02_en PHOENIX CONTACT - 12/2006 Description The PSR-...- 24DC/SDC4/2X1/B safety relay can be used in safety circuits according to DIN EN 60204-1/VDE 0113-1 and EN 954-1. Control is implemented via single or two-channel switches with N/O/N/C or N/C/N/C contacts (mechanical or electronic) or via light grids. The device has an interface for the T-BUS DIN rail connector. This interface can be used for single-channel control and monitoring of extension units. For this function, a T-BUS connector with switchable contacts is required. Depending on the external wiring, the maximum safety category that can be achieved is safety category 2 or 4. The device has two enable current paths and a 24 V alarm output (N/O contact function) with stop category 0 according to EN 60204-1/VDE 0113-1. Observe the safety instructions on page 4. Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com. A conversion table is available on the Internet at http://www.download.phoenixcontact.com/general/7000_en_00.pdf. This data sheet is valid for all products listed on the following page:

Ordering Data Safety Relays Description Type Order No. Pcs./Pkt. Safety relay for emergency stop and safety door circuits, with screw connection Safety relay for emergency stop and safety door circuits, with spring-cage connection Technical Data PSR-SCP- 24DC/SDC4/2X1/B 2981486 1 PSR-SPP- 24DC/SDC4/2X1/B 2981499 1 Accessories Description Type Order No. Pcs./Pkt. DIN rail connector, yellow, for PSR applications PSR-TBUS 2890425 50 Dummy plug PSR-TBUS-TP 2981716 50 Documentation Description Type Order No. Pcs./Pkt. Application manual for PSR safety relays UM EN SAFETY RELAY APPLICATION 2888712 1 Input Data Nominal input voltage U N Permissible range Typical current consumption at U N Typical response time Monitored/manual start Automatic start Typical release time Simultaneity between channel 1 and channel 2 when using the restart inhibit in the event of a mains failure Status indicators Alarm Output Y30 Switching voltage Limiting continuous current 24 V DC 0.85-1.1 x U N 70 ma 20 ms 150 ms 10 ms 3 seconds, approximately Green LED 24 V DC 100 ma Output Data Contact type 2 enable current paths Contact material Silver tin oxide (AgSnO 2 ) Maximum switching voltage 250 V AC/DC Minimum switching voltage 15 V AC/DC Limiting continuous current (N/O contact) 6 A Maximum inrush current (N/O contact) 6 A Minimum switching current 25 ma Maximum shutdown power Ohmic load τ = 0 ms 24 V DC 48 V DC 110 V DC 220 V DC 250 V AC 144 W 288 W 77 W 88 W 1500 VA Minimum switching power 0.4 W Mechanical service life 10 7 cycles, approximately Inductive load τ = 40 ms 48 W 40 W 35 W 33 W 102858en_02_ PHOENIX CONTACT 2

Output Data (Continued) Switching capacity according to DIN EN 60947-5-1/VDE 0660-200 Cycles DC13 AC15 360/h: 24 V: 6 A 230 V: 5 A Short-circuit protection of the output circuits, external 3600/h: 24 V: 3 A 230 V: 3 A NEOZED 10 A gl/gg General Data Permissible ambient operating temperature -20 C to +55 C Nominal operating mode 100% operating factor Degree of protection according to VDE 0470-1 Housing IP20 Connection terminal blocks IP20 Installation location IP54, minimum Mounting position Any Air and creepage distances between circuits Basic insulation According to DIN EN 50178:1998-04 1 Impulse voltage withstand level 4 kv 1 Pollution degree 2 Surge voltage category III Dimensions (W x H x D) PSR-SCP- 24DC/SDC4/2X1/B 22.5 mm x 99 mm x 114.5 mm PSR-SPP- 24DC/SDC4/2X1/B 22.5 mm x 112 mm x 114.5 mm Conductor cross section PSR-SCP- 24DC/SDC4/2X1/B 0.2 mm 2... 2.5 mm 2 PSR-SPP- 24DC/SDC4/2X1/B 0.2 mm 2... 1.5 mm 2 Housing material Polyamide PA, not reinforced 1 Safe isolation, reinforced insulation, and 6 kv between the input circuit/n/c contacts and the enable contact current paths. Tests/Approvals BG/GS UL applied for 102858en_02_ PHOENIX CONTACT 3

Safety Instructions During operation, parts of electrical switching devices carry hazardous voltages. Before working on the device, disconnect the power. Please observe the safety regulations of electrical engineering and industrial safety and liability associations. Disregarding these safety regulations may result in death, serious personal injury or damage to equipment. Startup, assembly, modifications, and upgrades may only be carried out by a skilled electrical engineer. For emergency stop applications, the machine must be prevented from restarting automatically by a higher-level control system. Protective covers must not be removed when operating electrical switching devices. In the event of an error, replace the device immediately. Repairs, especially if the housing must be opened, may only be carried out by the manufacturer or authorized persons. Otherwise the warranty is invalidated. When operating relay modules the operator must meet the requirements for noise emission for electrical and electronic equipment (EN 61000-6-4) on the contact side and, if required, take appropriate measures. 102858en_02_ PHOENIX CONTACT 4

24 24 PSR-...- 24DC/SDC4/2X1/B Structure 7 8 5 6 5 6 7 8 4 2 S34 S33 S35 13 14 23 Y1 IN 1 IN 2 K1 K2 S11 S10 S12S13 Power A1 Y30 S22 A2 9 4 3 S34 S33 S35 13 14 IN 1 IN 2 K1 K2 A1 Y30 S22 A2 S11 S10 S12S13 Power S11 S10 S12 S13 A1 Y30 S22 A2 9 23 Y1 S34 S33 S35 Y1 S34 S33 S35 Y1 APPROVAL APPROVAL 13 14 23 24 13 14 23 24 23 24 Order No.: 29 81 49 9 Serial No. Order No.: 29 81 48 6 Serial No. PSR-SPP- 24DC/SDC4/2X1/B PSR-SCP- 24DC/SDC4/2X1/B 1 PSR-SCP- 24DC/SDC4/2X1/B 1 PSR-SPP- 24DC/SDC4/2X1/B Figure 1 Structure 1 Metal lock for mounting on the DIN rail 2 Plug-in COMBICON screw terminal blocks 3 Plug-in COMBICON spring-cage terminal blocks 4 13-14, 23-24: Enable current paths 5 S33, S34, S35: Start circuit (activating circuit) 6 Y1: Activating circuit 7 A1, A2: Supply voltage connection 8 Y30: 24 V alarm output 9 S10, S11, S12, S13: Input circuits Block Diagram A1 T-BUS A2 T-BUS S11 24VDC POWER 24VDC T-BUS Y1 LOGIC Y30 RESET & FEEDBACK T-BUS S12 IN1 K1 K2 IN2 S33 S34 S35 S10 S13 S22 14 13 24 23 +24V T-BUS K1/K2 Figure 2 Block diagram 102858en_02_ PHOENIX CONTACT 5

Function When the operating voltage (24 V DC) is applied at A1 and A2, the "Power" LED lights up. Depending on the two N/C contacts connected, e.g., for the emergency stop button, the positive potential is at S11 and the negative potential at A2. There must be a flow of current via contacts S33 and S34 (activating circuit) in order to activate the module. Contacts S33, Y1, and S35 must be jumpered for automatic activation. In this state, relays K1 and K2 are excited. If one of the emergency stop N/C contacts opens, the relays drop and cannot be switched on again. They can only be switched back on when both N/C contacts are open. In the event of a cross circuit between terminal blocks S11 and A2, this is detected and the relays drop. Operation without cross-circuit detection is also possible. For additional connection examples, see page 7. Connection Notes For PSR applications, only yellow PSR-TBUS connectors (Order No. 2890425) may be used. Connection with another T-BUS is not permitted. Devices may only be mounted on/removed from the T-BUS when the power is switched off. A T-BUS unit can contain a basic device (PSR-...-SDC...) and a maximum of 10 extension units (PSR-UR...). Extension units must be mounted to the right of the basic device. The feedback circuit must be closed at the last extension unit (on the right) by a cable jumper or by the PSR-TBUS-TP dummy plug (Order No. 2981716). The voltage supply can be provided at any PSR device or using a system power supply via the T-BUS. When using T-BUS DIN rail connectors, connect together the required number of T-BUS connectors and push them onto the DIN rail. When attaching the safety relay to the DIN rail, ensure that it is aligned correctly with the T-BUS connector (see Figure 3). ) PSR-TBUS D * + 3 Figure 3 Using the T-BUS DIN rail connector 102858en_02_ PHOENIX CONTACT 6

S34 S33 S35 Y1 24 24 PSR-...- 24DC/SDC4/2X1/B In order to comply with UL approval, use copper cables that are designed for operating temperatures > 75 C. For reliable and safe-to-touch contacts, strip the cable ends as follows: 7mm 14 3 S35 Y1 23 8mm 14 3 S35 23 Y1 S34 S33 S35 Y1 13 14 13 14 23 24 23 24 23 24 Figure 4 PSR-SCP- 24DC/SDC4/2X1/B Figure 5 PSR-SPP- 24DC/SDC4/2X1/B Connection Examples Circuits +24VDC -K2 A1 Y1 S33 S34 S35 Y30 A2 S22 S10 S11 S12 S13 0V EMERGENCY STOP 102858B001 Figure 6 Two-channel emergency stop circuit (2 N/C contacts) with cross-circuit detection Manual activation (monitored reset button at S33-S34) Automatic activation (jumper at Y1-S33-S35) Suitable up to safety category 4 102858en_02_ PHOENIX CONTACT 7

+24VDC -K2 A1 Y1 S33 S34 S35 Y30 A2 S22 S10 S11 S12 S13 EMERGENCY STOP 0V 102858B002 Figure 7 Two-channel emergency stop circuit without cross-circuit detection Manual activation (monitored reset button at S33-S34) Automatic activation (jumper at Y1-S33-S35) Suitable up to safety category 3 102858en_02_ PHOENIX CONTACT 8

+24VDC -K2 A1 Y1 S33 S34 S35 Y30 A2 S22 S10 S11 S12 S13 Safety door 0V 102858B003 Figure 8 Two-channel safety door monitoring without cross-circuit detection, one N/C contact and one N/O contact Manual activation (monitored reset button at S33-S34) Automatic activation (jumper at Y1-S33-S35) Suitable up to safety category 2 102858en_02_ PHOENIX CONTACT 9

+24VDC -K2 A1 Y1 S33 S34 S35 Y30 A2 S22 S10 S11 S12 S13 Magnetic switch 0V 102858A006 Figure 9 Monitoring with encoded magnetic switch without cross-circuit detection, with closed safety door Manual activation (monitored reset button at S33-S34) Automatic activation (jumper at Y1-S33-S35) Suitable up to safety category 3 * * Due to the high level of protection from errors and manipulation offered by magnetic switches, unlike monitoring using safety doors with position switches, only one switch is required for safety category 3 according to EN 954-1. 102858en_02_ PHOENIX CONTACT 10

S1 S2 S3 S10 S11 S12 S13 102858A007 Figure 10 Connection for safety category 3 according to EN 954-1: Example with three magnetic switches with 2-pos. control switch (N/C contact and N/O contact), with open safety door Comparison of Safety Categories According to EN 954-1 and Product Standard EN 60947-5-3 The machine manufacturer must carry out a risk analysis according to the Machinery Directive. The assignment of safety categories according to EN 954-1 for proximity switches is somewhat difficult because it is not fully congruent with product standard EN 60947-5-3. The proximity switches (magnetic switches) are classified as PDFs (Proximity Devices with Defined Behavior under Fault Conditions): Class PDF-D PDF-T PDF-S PDF-M Description Reliability due to special design Test capability Single-fault tolerance Self monitoring Categories acc. to EN 954-1 B PDF classes acc. to EN 60947-5-3 D 1 T 2 S 3 M 4 102858en_02_ PHOENIX CONTACT 11

+24VDC K3 -K2 K4 L A1 Y1 S33 S34 S35 Y30 A2 S22 S10 S11 S12 S13 EMERGENCY STOP K4 K3 0V N 102858B004 Figure 11 Single-channel emergency stop circuit with monitored contact extension Manual activation (monitored reset button at S33-S34) Automatic activation (jumper at Y1-S33-S35) Suitable up to safety category 2 102858en_02_ PHOENIX CONTACT 12

+24VDC -K2 A1 Y1 S33 S34 S35 Y30 A2 S22 S10 S11 S12 S13 OSSD1 OSSD2 Light grid 0V 102858B005 Figure 12 Two-channel light grid monitoring with cross-circuit detection Manual activation (monitored reset button at S33-S35) Automatic activation (jumper at Y1-S33-S35) Suitable up to safety category 4 102858en_02_ PHOENIX CONTACT 13

Start and Feedback Circuits S33 Y1 S34 S35 Figure 13 Monitored reset K3 ext. K4 ext. S33 Y1 S34 S35 T-BUS Figure 14 Automatic activation with monitored contact extension (K3 ext., K4 ext.) via T-BUS DIN rail connector K3 ext. K4 ext. Figure 15 S33 Y1 S34 S35 T-BUS Monitored reset with monitored contact extension (K3 ext., K4 ext.) via T-BUS DIN rail connector K3 ext. K4 ext. S33 Y1 S34 S35 Figure 16 Automatic activation with monitored contact extension (K3 ext., K4 ext.) K3 ext. K4 ext. E-S 2 E-S 1 S33 Y1 S34 S35 S11 Figure 17 Monitored reset with monitored contact extension (K3 ext., K4 ext.) Figure 18 S33 Y1 S34 S35 Automatic activation with restart inhibit in the event of mains failure (E-S1, E-S2) Not fault-proof E-S 1 K3 ext. K4 ext. E-S 2 S33 Y1 S34 S35 S11 Figure 19 Automatic activation Figure 20 S33 Y1 S34 S35 Automatic activation with restart inhibit in the event of mains failure (E-S1, E-S2) with monitored contact extension (K3 ext., K4 ext.) Not fault-proof 102858en_02_ PHOENIX CONTACT 14

Emergency Stop Circuits E-S 1 E-S 2 E-S 1 S11 Figure 21 S12 S13 S10 A2 S22 S11 Two-channel with cross-circuit detection, two N/C contacts Figure 22 S12 S13 S10 A2 S22 Single-channel E-S 1 E-S 2 +24V Output 1 2 S11 S12 S13 S10 A2 S22 S11 S12 S13 S10 A2 S22 Figure 23 Two-channel without cross-circuit detection, two N/C contacts Figure 24 Semiconductor outputs E-S 1 E-S 2 S11 Figure 25 S12 S13 S10 A2 S22 Two-channel without cross-circuit detection, one N/C contact and one N/O contact PHOENIX CONTACT 12/2006 102858_02_en PHOENIX CONTACT GmbH & Co. KG 32823 Blomberg Germany 15 Phone: +49-(0) 5235-3-00 Fax: +49-(0) 5235-3-4 12 00 www.phoenixcontact.com