1
Rittal Cooling Solutions Presented by Adam Tropp 2
Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 3
Cooling strategies. Aisle containment. An economical solution to improve the performance of any cooling system. Benefits Increased airstream management Supply air and return air do not mix Uniform distribution of cold air Higher delta T for increased efficiency Modular, scalable, and retrofittable Can be used with perimeter-based cooling Can be used with row-based cooling 4
Cooling strategies. Aisle containment. An economical solution to improve the performance of any cooling system. When to use aisle containment Issues with bypass air Issues with hot air recirculation Issues with hot spots Issues with uneven cold air distribution Issues with maximum cooling capacity * Image from 42U.com 5
Cooling strategies. Aisle containment. Hot and cold air distribution with and without containment. 6
Cooling strategies. Aisle containment. An economical solution to improve the performance of any cooling system. Why aisle containment works Prevents hot and cold air from mixing Higher supply air temperatures Increased energy savings! Increased economizer hours Increased energy savings! Increased cooling efficiency Increased energy savings! 7
Cooling strategies. Aisle containment. An economical solution to improve the performance of any cooling system. Cold aisle containment benefits Precise, targeted cooling Consistent air temperature Eliminates hot spots No raised floor required Minimal infrastructure requirements Creates easy retrofit installations Using only doors shows increased efficiency Prevents end of row recirculation 8
Cooling strategies. Aisle containment. An economical solution to improve the performance of any cooling system. Hot aisle containment benefits Work environment is flooded with cold air Hot air can be ducted back to CRAC Increased efficiency Consistent air temperature Eliminates hot spots * Image from 42U.com 9
Cooling strategies. Aisle containment. * Image from EDS Plano TX * Image from CoreSite Los Angeles CA 10
Cooling strategies. Aisle containment. * Images from State Department Richmond VA 11
Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 12
Cooling strategies. Chimney solution. Deployment Requirements Return vents for equipment not equipped with chimneys Return extensions for CRAC units Chimney installed on rack Drop ceiling installed in data center Benefits Increased airflow efficiency Minimal hot/cold air intermixing Increased cooling capacity Hot aisle containment 13
Cooling strategies. Chimney solution. 14
Cooling strategies. Chimney solution. 15
Agenda Cooling Strategies Aisle Containment Chimney Solution Airstream Management Rittal Liquid Cooling Packages Data Monitoring 16
Cooling strategies. Airstream management. Rack-Level Air Containment Benefits Increased airflow efficiency Minimal hot/cold air intermixing Can be set into traditional raised floor Passive components No energy consumption Reduce point of failure Can accommodate blade chassis Cold aisle containment 17
Cooling strategies. Airstream management. 18
Cooling strategies. Airstream management. 19
Agenda Cooling Strategies Rittal Liquid Cooling Packages LCP Extend & LCP Passive CW LCP+ General Features LCP+ Cooling Applications Data Monitoring 20
Rittal Liquid Cooling Packages. LCP Passive CW Rear Door LCP Inline EC Open Loop LCP Hybrid EC LCP+ EC Hybrid Closed Loop 0 Tons 2.8 4.3 5.7 7.1 8.5 10.0 Tons 0 kw 10 15 20 25 30 35 kw 21
Rittal Liquid Cooling Packages. LCP Passive CW. Features Passive rear doors are designed to be installed as a replacement rear door for the racks on which they are installed A passive rear door simply has the fan system removed from the equation, allowing the server fans to do the necessary work of moving the air through the heat exchanger Maximum energy efficiency as there is no electrical power consumption Uses chilled water as the rejection medium HxWxD: 80x24x6 in. (2000x600x170 mm) 20 kw cooling capacity * Image from Sun Microsystems 22
Agenda Cooling Strategies Rittal Liquid Cooling Packages LCP Extend & LCP Passive CW LCP+ Cooling LCP+ General Features Applications Data Monitoring 23
Rittal Liquid Cooling Packages. LCP+ Cooling. Open Loop (Inline) Open front Open return More units are required to achieve N+1 Hybrid System Open front Closed return Better redundancy can be accomplished at row and room level Closed Loop Closed front Closed return Ultra high density Door release option must be used 24
Rittal Liquid Cooling Packages. LCP+ General Features. Features System Capacity: 30 kw Typical High efficiency heat exchanger developed to operate with 59 F chilled water Microprocessor controller LCD touch screen 2-way modulating valve 6 EC fans, N+1 design, hot-swappable Can be monitored remotely via web browser or SNMP via TCP/IP HxWxD: 80x12x48 in. (2000x300x1200 mm) 42 in. (1050 mm) depth also available Available in sand texture black or IBM white 25
Rittal Liquid Cooling Packages. 26
Rittal Liquid Cooling Packages. LCP+ General Features. Heat Exchanger 9.5 deep x 12.5 wide x 70 tall 27
Rittal Liquid Cooling Packages. LCP+ General Features. Electrical Design Wide input voltage range 208V, 230V, 400V EC fan technology 1 year ago: step motor technology Rated current: 6.5A 1 year ago: 11.5A Power rating: 1050W 1 year ago: 2650W 5 pole terminal block Fuses are easy accessible by opening the rear door Every unit comes high voltage tested EMC tested configuration 28
Rittal Liquid Cooling Packages. LCP+ General Features. 29
Rittal Liquid Cooling Packages. LCP+ General Features. Features Summary Auto-Temperature-Control: Cold air inlet temperature automatically controlled via integrated controller board Monitoring: Integrated controller with Rittal Basic CMC Intelligent sensor network: Fault tolerant sensors for water inlet/outlet temperatures, air inlet/outlet temperatures, water flow rates, leakage, etc. Fault tolerant controller boards and systems: In the case of electronic failures the valves will open and the fans will provide maximum airflow Alarm / events / sensor logging Three fan controller boards + one water controller board (individually fused) 30
Agenda Cooling Strategies Rittal Liquid Cooling Packages and their Energy Efficiency LCP Extend & LCP Passive CW LCP+ Cooling LCP+ General Features Applications Data Monitoring 31
Rittal Liquid Cooling Packages. Applications. Low Density (<5 kw) Application Networking switches, half-equipped server racks Products Fans Baffles Aisle Containment Mid Density (5-10 kw) Application Server and small blade servers Products LCP Inline LCP Hybrid Aisle Containment Chimney High Density (10+ kw) Application Blade servers and fully equipped server racks Products LCP Inline LCP Hybrid LCP+ Closed Loop Aisle Containment 32
Customers Using the LCP Family. 33
Agenda Cooling Strategies Rittal Liquid Cooling Packages Data Monitoring CMC III RiZone 34
Data monitoring. CMC III. CMC 3rd generation, the monitoring system for IT, building services, and industry. Monitors and measures up to 32 sensors. Enclosure and room temperature Humidity Vandalism Air flow Differential pressure Current, voltage, frequency, and energy Cooling units 35
Data monitoring. CMC III. CMC 3rd generation, the monitoring system for IT, building services, and industry. Control system for: Handles / Doors Fans Sockets Control system with: 8 digital inputs 4 relay outputs 2 energy outputs 36
Data monitoring. RiZone. RiZone is Rittal software for the monitoring and management of the IT infrastructure in data centers Power supply and reliability Cooling output and distribution Rack status Data center security (access, temperature, etc.) Efficiency and energy consumption Optimization Efficiency 37
Data monitoring. RiZone. RiZone Functions How efficient is the data center? How efficient is the UPS? How efficient is the chiller? How efficient is the cooling chain? How efficient is the power chain? What is the actual monthly / yearly power consumption? RiZone Benefits Higher visibility of systems inside the data center Historical data trending Making the data center more reliable and efficient 38
Data monitoring. RiZone. Definition of PUE/DCiE DCiE = Data Center Infrastructure Efficiency DCiE = IT Load (Server-Load) Entire Electrical Load of Data Center PUE = Power Utilization Effectiveness Entire Electrical Load of Data Center PUE = IT Load (Server-Load) PUE and Total Power Consumption are the basis for Data Center optimization. 39
Data monitoring. RiZone. Server, Infrastructure, And Total Power Consumption PUE CO 2 -Emission Power Costs 40
Any Questions? Thank you for attending and listening. 41