Building Re-Tuning (BRT) Lesson 4: SOI Air-Handling Unit Part II

Similar documents
DUKE UNIVERSITY DESIGN & CONSTRUCTION STANDARDS

CenterPoint Energy Retro-Commissioning Program Application

BAS Chillers 8/15/2016. Achieving Energy Savings with BAS and Data Analytics Guanjing Lin Lawrence Berkeley National Laboratory August 10, 2016

BUILDING AUTOMATION YORKLAND

Driving Proactive Facility Operations with Automated HVAC Diagnostics

Saving Energy and Reducing Costs Through Better Use of Building Automation Systems

The challenge is that BAS are often very complex with 1000s of data points to review. EMS Optimization Software

SECTION GRAPHICS

Evaluation of Energy Conservation Measures by Model Simulation

Rochester Institute of Technology Control Best Practices

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

The Basics of HVAC Operation and the Role of Automation. Mr. Jay Zaino GxP Automation, LLC

How Big Data Analytics Helps Hotels Improve Maintenance and Comfort, and Save Energy

Optimizing Laboratory Controls through Fault Detection and Diagnostics Software. Laura Dyas, PE, LEED AP O+M, CEM Bryce Buchanan, PE, CCP, CEM

Building Management Systems (BMS) Back to Basics. Presented By: Andrew Smith Leader Building Technologies A.G. Coombs Advisory

Fair City Plaza. Task: Diagnose problems, recommend improvements for small municipal district cooling system

SE7600E Series Application Guide

ASHNuN. Fundamentals of HVAC Control Systems. Robert McDowell and Ross Montgomery are the authors of the

Fault Detection and Diagnostic Software

Retro-Commissioning Report

CONTENTS CONTROLLERS room controllers room units control units PRODUAL 3 CATALOGUE

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Final Thesis Presentation

HOURLY ANALYSIS PROGRAM 5.10

ENERGY AND BUILDING AUTOMATION A WHITE PAPER ON ITS POTENTIAL FOR THE CITY OF FLINT AND GENESEE COUNTY. AltEnergy Inc.

Underfloor Controllers

ExactLogic BACnet Communicating Pressure Dependent VAV Damper Control with Heat EXL01820 Sequence Datasheet

Validation and Uncertainty Characterization for Energy Simulation

WHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant

Building Tune-Up Program Application

James Donahue Control Consultants, Inc.

BCPro System Product Bulletin

Airside Economizer Comparing Different Control Strategies and Common Misconceptions

Achieving Operational Excellence

OPERATION MANUAL.

SEZ7260X5x45B Installation Guide for BACnet MS/TP Zone Controller

Building Energy Management Training Systems

Features and Benefits of XeteX Controls. Other Unit Control Functions. Energy Recovery Functions

Running Your Data Center Under Ideal Temperature Conditions

230923S01 Direct-Digital Control System for HVAC

Introduction. To use Carrier wireless sensors, you must have: A i-vu v6.5 or later system v6-00 or later drivers

Airside Economizer Comparing Different Control Strategies and Common Misconceptions

Commercial Retro-Commissioning Program Manual for 2016 SECTION 1

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

Advanced Rooftop Controller

SCHENDT ENGINEERING PRIOR EXPERIENCE

HVAC Project. Comparison of Revit MEP Automatic Duct Sizing and Equal Friction Method Manual Calculations

Carrier Hong Kong Limited. Carrier Comfort Network. - optimizes the performance of HVAC Systems & is the premier solution for Building Control

What s on the Horizon for HVAC in Title ? Mark Hydeman, PE, Principal Taylor Engineering, LLC

Committed to Energy Efficiency

Energy Engineering: Tools and Trends

WHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

What is building analytics and why should we care? Daniel Hansen Salt Lake Community College March 23, 2016

Commercial Controls. Advanced control for saving time and money

Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling

Field selectable application type and room module series, via dip-switches on controller

SMART VENTILATION MANAGEMENT: CHANGING THE WAY WE THINK ABOUT VENTILATION

Why Should We Care? Building Intelligent Solutions 2

Designing Ultra-Efficient Building Cooling Systems

BuildingSherlock: Fault Management Framework for HVAC Systems in Commercial Buildings

Building Loads and Dedicated Outdoor Air Systems

Cooling season full and part load performance evaluation of Variable Refrigerant Flow (VRF) system using an occupancy simulated research building

System Controls Suggested Specification

Viconics BACnet Zoning System Application Guide VZ7260X5x00B and VZ7656X5000B Controllers

FCU-4 FAN COIL CONTROLLER

Optimiz Chilled January 25, 2013

Title of Presentation Goes Here. Presenter Name Title, Company

Reducing Energy Consumption with

Using Loop Tuning for ASC Devices

Desigo RXA Room controllers without bus communications Range overview. CA2S3880en_ Building Technologies

Economizer Control 2-1

T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management

Tracer Controls. Tracer ZN517 Unitary Controller BAS-PRC012-EN

Control systems. Efficient room control

E e n rgy g y St S ud u y y Pr P og o r g ams December 2011

High Efficient Data Center Cooling

Viconics Zoning System Application Guide VZ7200F5x00W and VZ7656B1000W Thermostats

Tracer Controls. Tracer MP.501 Controller BAS-PRC008-EN. June 2001

Economizer Fault Detection and Diagnostics (FDD) for Built-Up Air Handlers Draft Report

ecoenergy Innovation Initiative Research and Development Component Public Report

MANUAL INSTALLATION + SERVICE. Price Intelligent Controller. PIC Series. v400 Issue Date: 12/18/ Price Industries Limited. All rights reserved.

Enterprise Building Control System: What Now? November 7, 2017

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

BACVIEW MANUAL Software Version 3.06 INSTALLATION AND OPERATION MANUAL

Control system. Type FSL-CONTROL II. Modular, stand-alone room control system, specially for decentralised ventilation systems (with bus communication

Evaluation and Modeling of Data Center Energy Efficiency Measures for an Existing Office Building

TRACE 700. Slide 1. Today, we will be talking about Airside Economizers in TRACE 700. Slide 2

Specification and Design Catalog. Waterside Economizer

O&M Roadie or Rockstar?

Building Technologies. Desigo RXC Room automation system System description. Version 5 and later

We have you walking on air

HVAC Energy Management System

SEZ7656R1045B / SEZ7656H1045B

Wireless Supervisory Controls for HVAC Energy Management

75F Smart VAV with Reheat

HVAC System Energy Savings Opportunities

Dual Duct Controller - One Air Velocity

Modernizing Control Systems for Campuses

Transcription:

Building Re-Tuning (BRT) Lesson 4: SOI Air-Handling Unit Part II

Lesson 4: Sections Review of last class (0:20) Section 1: AHU: Discharge air temperature control (0:45) Break (0:10) Section 2: AHU: Heating & cooling control (0:45) Section 3: Your final project (0:60) 2

Review of last class Minimum Outdoor Air Operation For ventilation. Even less when unoccupied. Damper fully closed during unoccupied and pre-occupancy start-up OAF (%) = ((Return-Mixed)/(Return-Outside))*100 Use to find % of outside air Air-side Economizer Operation Packaged rooftop units with economizers are often neglected, hard to access, or installed poorly. Static Pressure Control Like discharge-air temperature, discharge static should follow the real load conditions. Static Pressure Re-set - Power Laws. 3

For each SOI, we will focus on: For Each SOI Step #2: Building Walk Down: Identify common operational issues. Step #3: Data Collection: Establish baseline through trend-log data ( before BRT ). Step #4: Data Visualization & Interpretation: Create graphs & interpret data. 4

Check Your Understanding 1. What are some potential issues to identify for incorrect economizer operation? Incorrect control strategy Failed actuator What else? 2. A 20% OA damper position means 20% outdoor air. True False 3. Ideally VAV dampers should run in what range? 5

Homework: What have you found during the week? Questions on reading? AHU Discharge Air Control AHU Heating and Cooling Control Watch ECAM Webinar: Part II ECAM Basics Part III Creating & Analyzing Retuning Charts Issues with completing your Project Report? Complete the SOI Section What SOI(s) are you investigating? What observations and findings so far? 6

Section 1 Time Spent on this Section (45 Minutes) AHU: DISCHARGE AIR TEMPERATURE CONTROL 7

Air Handling Unit For the AHU SOI, we will consider: Minimum Outdoor Air Operation Air-side Economizer Operation Static Pressure Control Discharge Air Temperature Control AHU Heating + Cooling Control 8

Discharge-Air Temperature Control Discharge temperature is the single most important variable in a HVAC system. Low discharge-air temperature will cause: Overcooling Reheating in cooler zones Portable heaters in offices Drafts and cold complaints Extra load on the cooling plant Excess discharge-air pressure Excess energy in reheating the overcooled zones 9

Discharge-Air Temperature Control Step #2. Building Walk Down: Identify issues as you walk around, such as: Are people too cold (air-conditioning)? Do they have sweaters or heaters at their desks? Are air diffusers closed or covered over? Do some rooms have much higher or different loads than others in the same zone? 10

Discharge-Air Temperature Control Step #3. Data Collection: Discharge-air temperature (DAT) Discharge-air temperature set point (DATSP) Outdoor-air temperature (OAT) Zone reheat valve signal 11

Discharge-Air Temperature Control Step #4. Data Visualization & Interpretation: Trends to look for in the data: Is reset being used to control the discharge-air set point? Is the discharge-air temperature meeting the set point, or do deviations occur? Is the discharge-air temperature too cool (<55 F) or too warm (>70 F)? Does the discharge-air temperature remain relatively stable? 12

Discharge-Air Temperature Control Step #4. Data Visualization & Interpretation: Is reset being used to control the discharge-air set point? 13

Discharge-Air Temperature Control Step #4. Data Visualization & Interpretation: Are setback and resets being used? 14

Now you try: Interpret the Data CLASS ACTIVITY Step #4. Data Visualization & Interpretation: Is the discharge-air temperature meeting the set point, or do deviations occur? 15

Now you try: Interpret the Data CLASS ACTIVITY Step #4. Data Visualization & Interpretation: Is the discharge-air temperature meeting the set point, or do deviations occur? 16

Now you try: Interpret the Data CLASS ACTIVITY Step #4. Data Visualization & Interpretation: Is the discharge-air temperature too cool (<55 F) or too warm (>70 F)? 17

Now you try: Interpret the Data CLASS ACTIVITY Step #4. Data Visualization & Interpretation: Does the discharge-air temperature remain relatively stable? 18

Now you try: Interpret the Data CLASS ACTIVITY Step #4. Data Visualization & Interpretation: Is this a good or bad operation? 19

Let s Talk about Your Building! What is driving your current discharge temp set point? How is it impacting energy cost? Set it low enough to handle the peak cooling load: Summer weather peak Interior load peak Staffing peak 1% - 2% of operating hours are at peak yet most systems run 100% of the time at this set point. Reheat makes up for all areas that are too cold from a lower than needed discharge temperature. 20

Addressing Issues: Discharge-Air Temperature Discharge-air temperature can run as high as possible and still meet the cooling needs: VAV boxes can run at higher air flows Return air can be warmer and help heat building Reheats will run a lot less Staff complaints go down due to less cold drafts Building is ventilated better 21

Zones & Discharge-Air Static Pressure Dynamic Reset Does your discharge set point vary with some input signals? > 55 o F < 70 o F Set up a discharge-air set point reset schedule based on the personality of the zones it feeds. Examples: Warmest 3 zones averaged Number of reheats running Coolest perimeter zone Outdoor air temperature 22

Potential Problem Indicators Indicator Many occupant complaints. Trended data is flat or rarely varies. Trended data shows sharply falling temperatures well below set point at chiller system start, and remain well below set point. Trended data shows sharply rising temperatures well above set point at boiler/reheat system start, and remain well above set point. Potential Problem Precursor to an improperly working (or non-functioning) discharge temperature control scheme. Non-functioning discharge temperature reset control. Failed (leaking) cooling control valve. Failed (leaking) heating control valve. 23

Trends for Discharge Air Temperature Trended data for discharge temperature reset control that is properly working should show temperature set points that vary. As the building wakes up, becomes occupied, and changes in outdoor ambient temperatures and solar loading. This can vary as much as 10-15 o F over the course of the day. Does your DDC system calculate: warmest, lowest, and average zone temperatures? Does your DDC system currently reset the discharge temperature set point using either outside-air temperature or return-air temperature? 24

Break (10 Minutes) Break Time! 25

Section 2 Time Spent on this Section (45 Minutes) AHU: HEATING & COOLING CONTROL 26

AHU Heating and Cooling Control Step #2. Building Walk Down: Identify issues as you walk around, such as: Zone temperatures Thermostat settings and proximity to heat / cold Blocked registers 27

AHU Heating and Cooling Control Step #3. Data Collection: Outdoor-air temperature (OAT) Cooling-coil-valve-signal (CCV) Heating-coil-valve signal (HCV) 28

AHU Heating and Cooling Control Step #4. Data Visualization & Interpretation: Trends to look for in the data: Are outdoor-air temperature lockout set points for heating and cooling reasonable, do they overlap? Is there simultaneous heating and cooling occurring? 29

AHU Heating and Cooling Control Air handler heating vs. cooling valve positions. 100 90 80 Chilled Water vs Hot Water Valve Signals Hot Water Signal (%) 70 60 50 40 30 20 Bad Worse 10 0 0 10 20 30 40 50 60 70 80 90 100 Chilled Water Signal (%) 30

AHU Heating and Cooling Control Step #4. Data Visualization & Interpretation: Is there simultaneous heating and cooling occurring? 31

AHU Heating and Cooling Control Step #4. Data Visualization & Interpretation: Is there simultaneous heating and cooling occurring? 100 90 80 70 MAU1/HeatingValveAO MAU1/CoolingValve MAU1/OAT 100 90 80 70 Valve Position (%) 60 50 40 60 50 40 Temperature 30 30 20 20 10 10 0 0 8/15 8/16 8/17 8/18 8/19 8/20 8/21 8/22 Data/Time 32

Now you try: Interpret the Data CLASS ACTIVITY Step #4. Data Visualization & Interpretation: Is this a good or bad operation? Why? 33

Now you try: Interpret the Data CLASS ACTIVITY Step #4. Data Visualization & Interpretation: Is this a good or bad operation? Why? 34

Now you try: Interpret the Data CLASS ACTIVITY Step #4. Data Visualization & Interpretation: Is this a good or bad operation? Why? 35

Now you try: Interpret the Data CLASS ACTIVITY Step #4. Data Visualization & Interpretation: Is this a good or bad operation? Why? 36

Let s Talk about Your Building! Are the heating and cooling coils efficient? Clean? Valves not leaking through? Check (touch) coil for temperature of pipes at air-handler penetrations Should be room temperature Loops locked out at some ODA temperature preventing heating and cooling at same time. Balance point of building is critical when setting these lockouts. 37

Pump and Fan Operation Parallel in air-distribution: Know your VAV boxes! Various types of VAV boxes, e.g.: Single duct cooling only Single duct, cooling with reheat Dual duct Fan powered Fan powered 38

Variable-Speed Pumps and Fans Huge power consumption variable. Can you monitor that the speed is varying? Change it to energy units and monetize! Identify sensor that controls modulation. Common causes of failure to modulate: Three-way valves and by-pass type VAV Open by-passes (manual or pressure) 39

Section 3 Time Spent on this Section (60 Minutes) YOUR FINAL PROJECT 40

Final Project Report, page 1 BUILDING OVERVIEW Briefly describe your facility here, including: Approximate floor area (square footage) Type(s) of use Schedule of operations Mechanical systems and major equipment HANDOUT! BUILDING WALK DOWN Walk around building and note potential building issues: Zone temperatures Equipment running Scheduling during unoccupied periods Faulty equipment & components Occupant complaints 41

Final Project Report, page 1 BAS Summarize your BAS system(s): Manufacturer (Siemens, Johnson etc) Software version (Apogee, MetaSys etc) Approximate age If it includes an inter-operable protocol (BACNet, ModBus, LON) List of systems covered by the BAS 42

Final Project Report, page 2 SOI Describe here the SYSTEM-OF-INTEREST that you have selected: Relevant details about it If there is a particular reason for choosing this system, briefly describe why If you have a schematic or have drawn one, attach that to this report FUNCTIONS, BRT MEASURES TO BE INVESTIGATED Describe the specific system functions that you will collect data to investigate. Use the cookbook recipes from BRT Resources to help you with this. BRT SET-UP List the specific sensors that you need and will use for BRT of your initial SOI. Use the cookbook recipes from BRT Resources to help you with this. Indicate whether you have each of the necessary sensors available on your BAS. If you are missing certain sensors, indicate here and address in your Next Steps section. 43

Final Project Report, page 3 PROGRESS TO DATE Describe what you have done thus far to set-up and implement BRT. Include both steps taken with your BAS, as well as within your organization and with other individuals. If you have set up Trend Logs, attach sample plots and discuss any findings and patterns you have noted. PROVIDE BRIEF ANSWERS TO THE FOLLOWING: Has the Intro to BRT training made you think about your BAS system in new ways? Does BRT have promise as a procedural tool for your facility? Do you think BRT can help you identify operating patterns and improve efficiencies? 44

Final Project Report, page 4 BARRIERS ENCOUNTERED Create a numbered list of barriers encountered in setting-up and/or implementing initial BRT: Barriers can be technical or organizational Briefly describe each barrier How did you overcome the barrier? PLANNED NEXT STEPS Briefly describe the NEXT STEPS you are planning. Provide both an overall statement and a numbered list corresponding to the BARRIERS identified in the previous section. 45

46

Lesson Summary AHU: Discharge air temperature control: Discharge temperature is the single most important variable in a HVAC system. Set discharge temp set point low enough to handle the peak cooling load. Set up a discharge-air set point reset schedule based on the personality of the zones it feeds. Trended data for discharge temperature reset control that is properly working should show temperature set points that vary. AHU: Heating & cooling control Simultaneous heating and cooling. Heating and cooling coils efficient. 47

Homework READ in ES Modeling: Abstract-Exec Summary-Approach, pages iii xii On your Project Report, complete the sections: Functions, BRT Measures what functions how data acquisition has gone trial graphical plots and interpretations BRT Set-Up Progress to Date Barriers Encountered Planned Next Steps 48