ABM Status Input Active Burden Module

Similar documents
2T105. Multi Range Digital Setting Time Delay Relay. Features. Application. Operation

2C138. Sensitive Earth Fault Relay. Features. Application. Operation

2V67 Four Stage Over / Under Voltage Relay

2H34. Definite Time Frequency Relay with ROCOF. Features. Operation. Application

2V67-S Four Stage Over / Under Voltage Relay

2V67-S Four Stage Over / Under Voltage Relay

USB Driver Installation Guide

Reyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

Reyrolle Protection Devices. 7SG118 Argus 8 Voltage & Frequency Relay. Answers for energy

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

6R MATRIX Pre-Defined. Modular Relays. rms. Auxiliary, Trip & Supervision Relays

RE22R2QGMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O

RE22R2CMR Off-delay Timing Relay s 300h V AC/DC - 2C/O

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O

RE22R2KMR Off-delay Timing Relay s 10min V AC/DC - 2C/O

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O

2C138 User Guide. Sensitive Earth Fault Relay. Advanced Protection Devices. relay monitoring systems pty ltd. User Guide.

RE22R2QTMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

RTU500 series Data Sheet Power Supply CP-E 24/2.5

RE22R1AMR On-delay Timing Relay s 300h V AC/DC - 1C/O

02/11/2015

Contact protection relay

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

Features. Applications and Benefits TRC ELECTRONICS, INC

Section 4 Ground-Fault Protection Devices

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC

Test Report S

Specification Voltage Limiting Device

ENGINEERING SPECIFICATION SHEET SPEC. Revision History

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

Electronic timer CT-SDD.22 Star-delta change-over with 2 n/o contacts

Redundancy unit CP-A RU

Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact

RE Product data sheet Characteristics. time delay relay for star-delta starter ms - 230/380 V AC - 1 contact. Main.

ELV12 Series. Instruction Manual

Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact

Relion 611 series. 611 series Type Test Certificate

Electronic timer CT-ARE OFF-delayed without auxiliary voltage, 1 c/o (SPDT) contact

Electronic timer CT-APS.21 OFF-delayed with 2 c/o (SPDT) contacts

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

RE11RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

Voltage monitoring relays CM-ESS.1 For single-phase AC/DC voltages

08/07/2015

Residual overvoltage relay

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

Gelo LED Driver 100W, Single output, Constant Voltage RGLD100-24

Relays & Sockets. RSC Series. RSC Series Solid State Relays. Part Number Selection Specifications

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

TM3SAF. Main. Device short name

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases

02/11/2015

RM4TR31 three-phase network control relay RM4-T - range V

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

FL MC 2000E (SM40) LC

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

Power supply CP-C 24/5.0

Earth-fault Relay SPAJ 110 C. Product Guide

RM22LA32MR Level control relay RM22-L V AC/DC - 2 C/O

ABL8BBU24200 battery control module V DC - 24 V - 20 A - for regulated SMPS

RM35JA32MR Current control relay 0.15A 15A, 2 C/O

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

VEO. V2UF230V10 Art.Nr.: TECHNICAL DATA

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

Circuit Breaker Sentinel (CBS) for SF 6. power circuit breakers

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC

This annex is valid from: to Replaces annex dated: Location(s) where activities are performed under accreditation

TM3SAK. Main. Device short name

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

ENGINEERING SPECIFICATION SHEET. Table of Contents 1 SCOPE ELECTRICAL SPECIFICATION...5

Switching relay CT-IRE with 1 c/o (SPDT) contact

TM3SAC5RG SAFETY MODULE FOR PLC TM2xx, 1 FUNCTION, CAT3, SPRING TERMINALS

ABL8BBU24400 battery control module V DC - 24 V - 40 A - for regulated SMPS

Electronic timer CT-AHD.22

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

Power supply CP-E 48/1.25 Primary switch mode power supply

RM4JA31M current measurement relay RM4-J - range ma V AC

Universal Power Supplies

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

16-Channel Digital Input Termination Card 24Vdc

RM35UB3. Product data sheet Characteristics. voltage control relay RM35-U - range V AC. Main. Complementary

Electronic timer CT-SDS.23 Star-delta change-over with 2 n/o contacts

Electronic timer CT-ERD.12

MINI-PS AC/10-15DC/8

RM35TF V AC

RE8TA31BU industrial timing relay s - type A - 24 V AC/DC, V AC - 1 C/O

Voltage Current Front-mounting bracket

RE9RA21MW7 off-delay timing relay s V AC -

RE Product data sheet Characteristics. universal plug-in timing relay - flashing s..60 mn V AC - 2 OC. Main.

RM4TA32 three-phase network control relay RM4-T - range V

SPM Series Plug-in Surge Protection

Transcription:

Technical Bulletin ABM Status Input Active Burden Module Features Improve security of sensitive, high speed digital status inputs Provides capacitor discharge protection for solid state status inputs to ENA TS 48-4 Transient noise withstand to IEC60255 standards Compact and easy to fit and retrofit Instantaneous burden turn-on with ~50ms fixed dwell time Wide voltage operating range Thermal cut out protection Operation check LED Status input pick-up LED M4 screw terminals or optional flying leads ABMZ version with minimum voltage pick-up threshold ABM Active Burden Modules ( Screw terminal and Flying lead versions depicted) Application The ABM Active Burden Module is designed for application with solid state status inputs wherever high security signaling is required. The ABM is intended to be used with digital relays and related products such as RTU s as an aid to improve electrical transient and noise immunity. In particular, for added immunity against infrequent and irregular transients such as represented by the capacitor discharge test as defined in standard ENA TS 48-4. In normal operation, the ABM imposes a short term increased burden to the operate signal which is then removed after ~50 ms. It is essential that devices that the ABM module is intended to be used with are specifically designed and purpose built for power industry and substation applications and already incorporate industry standard filtering, input loading and threshold setting capabilities. The ABMZ version is a special version that provides a minimum voltage pick-up threshold. Screw terminals and Flying lead type versions are available. Description Made in Australia Binary status inputs are employed extensively in power protection and control schemes for signaling a range of system events. For example: Direct trip to input commands e.g. Buchholz; Global enable or disable function; Blocking specific protection elements; Initiate timing or logical functions; Change protection setting groups; Maintaining status of secondary equipment circuits such as CB open / close; Reset of flag indicators. The reliability of these inputs is critical to avoid false operation due to voltage fluctuations under transient conditions. The interface between different devices has historically been achieved using hard wired I/O logic with simple electro-mechanical relays employed to provide the electrical isolation and noise immunity. With the integration of protection, control and metering functions the number of status inputs required has dramatically increased and as a consequence modern protection relays commonly employ electronic status inputs based on an optically isolated insulation barrier. While this approach can provide a wide operating voltage range and fast operation, a lower DC burden is required to minimize the heat dissipated within the protection relay case. Status input pick-up currents in the low ma range are common and as a consequence their stability and immunity to noise transients may be compromised. Disturbance immunity difficulties become more apparent where control signal wiring extends outside into the switchyard or when interfacing modern equipment with traditional electro-mechanical I/O. Due to RMS continuous product improvement policy this information is subject to change without notice. ABM/Issue I/25/01/2011-1/9

Operation OPERATING VOLTAGE Nominal operate voltage: Order code C: 48 / 54 V DC Order code D: 110 / 125 V DC Order code F: 220 / 250 V DC Operating range (ABM): 50-125% of nominal operate voltage BURDEN The ABM module presents a dynamic load, or burden, to voltage driven operate signals. Operate burden: 100W < BURDEN < 150W The high operate burden is maintained for ~50ms to help ensure operation of any cascade devices or relays. After the expiration of this short delay the ABM will self economize to reduce the burden and associated self heating that would otherwise occur. Operated burden: The ABM element self economizes after ~50ms. 48 / 54V DC <0.5 W 110 / 125V DC <1.1 W 220 / 250V DC <2.3 W Maximum repetition rate: 0.5 Hz: High - Low - High burden THERMAL PROTECTION A one shot fuse is integrated in the ABM and will operate in the event the economizing circuit fails to deactivate. This safety feature will only operate in abnormal circumstances to avoid overheating and possible loss of the status input function. Once the thermal fuse has operated the ABM shunt load will remain open circuit and the relay status input will continue to operate but without the active burden function. Operation of the one shot fuse is determined by lack of operation of the LED flash when the status input is activated by a legitimate operate signal. Should this occur the ABM should be replaced. FRONT PANEL LAYOUT (-) BLACK ABM P/U (+) RED ABM Made in Australia Figure 1 Figure 2 Flying lead version 1 2 3 4 ABM P/U Screw terminal version ABM & ABMZ FUNCTIONALITY The ABM is designed to present a shunt resistance across each status input to be protected. This ensures that a higher level of current must be delivered by the source to achieve the required pick-up voltage threshold. In order to achieve the necessary immunity from transient noise and to meet the capacitor discharge test, the operating burden of the ABM is >100W. When the ABM detects a differential voltage, a fast acting solid state switch is activated to shunt the input current through a wire wound power resistor s encapsulated in heat conductive potting compound. In the event that the pick-up voltage is transient and unable to provide adequate sustained power, the energy from the transient is dissipated as heat within the ABM. Legitimate pick-up signals that are capable of driving the high burden state are unaffected and immediately operate the digital status inputs. The ABM automatically economizes after ~50 ms to avoid thermal overload and prolonged burden on the DC supply. A one shot thermal fuse is incorporated within the ABM as protection against possible exposure to extreme conditions that may cause it to fail to auto-economize. Even with the ABM in this blown condition, the status input will continue to operate but without the high burden and noise protection functionality. The ABM is fitted with a red LED which flashes once each time the status input is picked up to indicate correct function of the ABM. An additional green LED is provided to indicate the presence of a continuous status input. This is a useful feature during commissioning checks and routine maintenance inspections. ABMZ VERSION MINIMUM VOLTAGE THRESHOLD ABMZ versions provide the same Active Burden functionality as the standard ABM devices. They also incorporate circuitry to provide a minimum voltage pick-up threshold. This feature is designed to be employed in applications where very sensitive input devices are being employed in a system susceptible to continuous background voltage coupling causing possible false activations. The output signal of the ABMZ is not energized unless the input voltage exceeds the specified threshold voltage as nominated by the ordering code. The ABMZ version employs a solid state switch to connect the output terminals to the operate input voltage once the minimum voltage threshold level has been exceeded. It does not provide isolation between input and output. Voltage threshold tolerances: + 10% The ABMZ version is only available in the Screw terminal housing. Note: The ABMZ output is designed for driving status inputs of digital relays with purely resistive loads. The ABMZ output has a maximum continuous rating of 15mA and is short circuit rated for a maximum of 1 minute. Due to RMS continuous product improvement policy this information is subject to change without notice. ABM/Issue I/25/01/2011-2/9

Capacitor Discharge CAPACITOR DISCHARGE TEST ENA TS 48-4 for classes ESI 1 and ESI 2 The ABM module is specifically designed to absorb electrical energy associated with transient impulses that may be coupled onto digital input lines from electrical switching events and other such sources of disturbance. The industry standard test for high energy, non repetitive transients of this form is the capacitor discharge test as defined in ENA TS 48-4 for class ESI 1 and ESI 2 relays. The standard describes the high energy impulse used for testing utilizing a 10 µf capacitor charged to 120% of the nominal operate voltage and applied differentially directly to the input circuit of the protection or control relay. As unprotected solid state status inputs may typically require only a few ma to pick-up, the minimum operate voltage must be set high and the time delay >>20ms to pass the capacitor discharge test. Such voltage levels and time delays are usually not acceptable in the design and grading of protection and control schemes. Figures 3 to 5 depict the time required to dissipate the capacitive discharge voltage applied during the capacitor discharge test for 5mA and 10mA status input operating currents. The green curve represents the enhanced capacitor discharge performance provided by the ABM. e.g. The ABM module is capable of absorbing and dissipating the total energy delivered by the capacitor discharge test for a 125V DC nominal system in less than 5 ms. A minimum voltage pick up threshold and time delay should be selected to ensure that the intersection point of these parameters is above the green ABM curve. The dotted red line on figures 3 to 5 represent a 50% voltage threshold level for the status input. This level is often used as the minimum voltage pick-up to ensure the status input will not operate under a battery earth fault condition. Where status inputs do not have a fixed or configurable minimum voltage pick-up threshold the ABMZ version may be used to provide this. With digital input filtering typically set to 10-15ms to provide AC immunity of input signals, the ABM module is able to contain the capacitor discharge impulse within the sample filtering time thus eliminating any false or mal op readings being raised by the digital relay. 125% Capacitor Discharge Test 48 V ABM V IN 100% 75% 50% 5 ma Input 20 ma Input 25% RMS ABM 0% ms 0 2 4 6 8 10 12 14 16 18 20 Figure 3: Voltage versus time delay curve for the 48V ABM 125% V IN 100% 75% 50% 25% Capacitor Discharge Test 125 V ABM 5 ma Input 20 ma Input RMS ABM 0% ms 0 2 4 6 8 10 12 14 16 18 20 Figure 4: Voltage versus time delay curve for the 125V ABM 125% V IN 100% 75% 50% Capacitor Discharge Test 250 V ABM 5 ma Input 20 ma Input RMS ABM 25% 0% ms 0 2 4 6 8 10 12 14 16 18 20 Figure 5: Voltage versus time delay curve for the 250V ABM Due to RMS continuous product improvement policy this information is subject to change without notice. ABM/Issue I/25/01/2011-3/9

Noise Immunity SURGE IMMUNITY IEC 60255-22-5 Inputs to digital relays can be exposed to transients such as can be coupled into wiring systems from switching and the operation of large contactors and external environmental events such as lightening. The standard test for immunity to such disturbances is IEC 60255-22-5 Electrical disturbance tests Surge immunity test This test consists of applying a number of high voltage, high energy impulses differentially across the relay inputs. Both Positive and Negative pulses are applied. HIGH FREQUENCY DISTURBANCE IEC 60255-22-1 Digital relay inputs can be exposed to repetitive damped oscillatory waves such as those originating from closing or opening circuit breakers or disconnectors in high voltage substations or power plants. The standard test for confirming immunity to such disturbances is IEC 60255-22-1 Electrical disturbance tests 1 MHz burst immunity test The Differential mode test consists of a 1 kv peak, 1MHz decaying envelope, repeated at a rate of 400 bursts per second for 2 seconds applied across the relay inputs both in the non energized state and the operated/energized state. Figure 6: IEC 60255-22-5 Severe Environments 1kV differential mode The ABM helps protect digital relay inputs from such surges by limiting the peak voltage level, clamping the major negative voltage excursions, minimizing the total transient time and by absorbing the total energy of the disturbance. Peak Voltage containment Approximately +/- 1.5x rated voltage Transient pulse time Less than 25µs Energy absorbed 100% Figure 7: IEC 60255-22-1 HFD Differential 1kV, 1 MHz bursts The ABM helps protect digital relay inputs from such high frequency disturbances by limiting the peak voltage level, clamping the major negative voltage excursions, and minimizing the total transient time. Peak Voltage containment Approximately +/- 1.5x rated voltage Burst containment time Less than 25µs Energy absorbed 100% COMMON MODE DISTURBANCES The ABM does not require a ground connection and does not have provision for one. Common mode tests are therefore not applicable to the module and it does not compromise common mode ratings of equipment to which it is attached. Due to RMS continuous product improvement policy this information is subject to change without notice. ABM/Issue I/25/01/2011-4/9

Performance Standards Table 1 summarizes the operating parameters and standards that the ABM complies with: Operating Voltage Range ENA TS 48-4 Class ESI 2 Complies The ABM is rated for continuous operation at the maximum voltages for their class as specified in ENA TS 48-4 Operating Burden ENA TS 48-4 Class ESI 2 Complies Non Operate Energizing Current ENA TS 48-4 Class ESI 2 N/A Drop Out Voltage ENA TS 48-4 Class ESI 2 N/A Insulation Coordination Dielectric withstand IEC 60255-5 Complies Note 2 Insulation Coordination Impulse Voltage IEC 60255-5 Complies Note 2 Insulation Coordination Insulation Resistance IEC 60255-5 Complies The ABM module is potted in a specifically designed insulated housing to allow it to come into direct contact with other system wiring. Insulation: 2.5kV RMS for 1 minute Thermal withstand IEC 60255-1: 2009 Complies 1 s short term thermal withstand. The ABM module is potted in a specifically designed insulated housing to allow it to come into direct contact with other system wiring. Furthermore, in the event of exposure to sustained and excessive overvoltages, the ABM is provided with an internal, non resettable fuse to eliminate any over temperature condition that could impact other wiring. Capacitor Discharge ENA TS 48-4 Class ESI 2 Pass High Frequency Disturbance IEC 60255-22-1 Class III Pass Fast Transient IEC 60255-22-4 Class IV Pass Surge Immunity IEC 60255-22-5 Class IV Pass Vibration Shock Bump Seismic Radiated EMI IEC 60255-21-1 class I IEC 60255-21-2 class I IEC 60255-21-2 class I IEC 60255-21-3 class I IEC 60255-22-3 Class III Conducted EMI IEC 60255-22-6 Electrostatic Discharge IEC 60255-22-2 class III Magnetic Field IEC 61000-4-8 level 5, Class 5 Complies Temperature IEC 60068-2-1, IEC 60068-2-2 Complies Operation Storage -10 C to +55 C -20 C to +70 C Humidity 40 o C and 95% relative humidity IEC 60068-2-3 Complies IP Rating IEC 60529 Complies The RMS ABM provides a protection rating of minimum IP50 Table 1 N/A: Note 1: Note 2: Not Applicable The ABM is a single circuit device with no ground connection Tests conducted with ABM sitting directly on copper ground plane Due to RMS continuous product improvement policy this information is subject to change without notice. ABM/Issue I/25/01/2011-5/9

ENA TS 48-4 Reference Table 2 provides a guide for the requirements specified in the ENA TS 48-4 standard for classes ESI 1 and ESI 2 relays. ENA TS 48-4 standard for classes ESI 1 and ESI 2 relays DC System Nominal Voltage 48 110 220 Ŧ Relay Rated Voltage 48 125 250 Nominal Working Voltage 54 125 250 Operative Voltage range 29-60 66-143 150-300 Energizing Current Current (ma) at or below which relay shall not operate: For ESI 1 Relays 10 25 25 For ESI 2 Relays 20 50 50 Capacitance discharge test For ESI 1 Relays Not Required Not Required Not Required For ESI 2 Relays 10 µf 60 V 10 µf 150 V 10 µf 300 V Thermal Withstand Voltage at 40 o C Ambient 60 143 300 Maximum Percentage AC ripple permitted on DC supply + 12% of rated Voltage + 12% of rated Voltage + 12% of rated Voltage Table 2 Ŧ Values for 220V Nominal System Voltages not specified in ENA TS48-4. Extrapolated values adopted by RMS for these higher voltages. Due to RMS continuous product improvement policy this information is subject to change without notice. ABM/Issue I/25/01/2011-6/9

Application OPERATIONAL CHECKS Operation of the ABM and ABMZ modules can be checked while in circuit during commissioning or as part of a normal ongoing maintenance program. To check the module: 1. From no energisation, apply an operate signal of rated voltage. 2. The RED LED will flash briefly (less than one second) showing that the active burden load is functioning correctly. ABM APPLICATION Flying lead version wiring ~250mm insulated flying leads with 1.5 sq. mm conductors are suitable for termination direct to the rear of protection and control equipment. The ABM must be wired in accordance with the polarized and color codes leads: RED lead is positive (+) BLACK lead is negative (-) 3. The GREEN LED should remain illuminated for as long as the driving voltage is present. (And so long as it is greater than the threshold level in the case of an ABMZ) Note: Extreme care should be exercised if testing beyond this standard operational test for immunity to high voltage or high energy disturbances such as the Capacitor discharge test or HFD. Many of these tests impose high voltages above those of the system rating. Ensure that any connected status inputs on digital relays are capable of tolerating these conditions. Screw terminal version wiring Figure 8: ABM Flying lead version wiring diagram Screw terminals are provided at the front top and bottom of the DIN rail mount housing. These are designed to accept heavy duty M4 ring lug terminals. The ABM must be wired in accordance with the following wiring diagrams: Figure 9: ABM Screw terminal version wiring diagram ABMZ MINIMUM VOLTAGE THRESHOLD APPLICATION Screw terminal wiring Screw terminals are provided at the front top and bottom of the DIN rail mount housing. These are designed to accept heavy duty M4 ring lug terminals. The ABMZ must be wired in accordance with the following wiring diagram: Figure 10: ABMZ Minimum voltage pick-up option wiring Due to RMS continuous product improvement policy this information is subject to change without notice. ABM/Issue I/25/01/2011-7/9

Mounting FLYING LEAD VERSION The Flying lead version is sealed with thermally conductive potting compound and two flying leads with 0.75 sq. mm multistrand conductors are employed for termination on site. SCREW TERMINAL VERSION The DIN rail version is built in a compact enclosure sealed with thermally conductive potting compound and four M4 screw terminals are employed for termination on site. Mounting Figure 11: ABM Flying lead version DIN rail mounting of multiple DIN rail modules allows for a compact installation close to the protection relay status inputs. The DIN rail clip may be removed if required and the module secured using a number of methods: self adhesive tape; cable ties; left free to hang from the flying leads. Dimensions Mounting Figure 13: Screw terminal version DIN rail mounting of multiple DIN rail modules allows for a compact installation close to the protection relay status inputs. Wiring should be kept as short as practical to minimize the circuit resistance. Dimensions Figure 14: ABM Screw terminal version dimensional details Figure 12: ABM Flying lead version dimensional details Figure 15: Array of 7x ABM Screw terminal version modules Due to RMS continuous product improvement policy this information is subject to change without notice. ABM/Issue I/25/01/2011-8/9

Ordering Information ABM ACTIVE BURDEN MODULE Generate the required ordering code as follows: e.g. ABM-D-2 Order Code General Type 1 2 ABM - - ABMZ ACTIVE BURDEN MODULE & MINIMUM VOLTAGE THRESHOLD Generate the required ordering code as follows: e.g. ABMZ-D-80V Order Code General Type 1 2 ABMZ - - 1 NOMINAL AUXILIARY VOLTAGE C D F 48 / 54V DC 110 / 125V DC 220 / 250V DC 2 TERMINATION STYLE 1 Flying leads as per figures 11 and 12 2 Screw terminals as per figures 13 to 15 1 NOMINAL AUXILIARY VOLTAGE C 48 / 54V DC D 110 / 125V DC F 220 / 250V DC 2 INPUT THRESHOLD VOLTAGE 30V 30V DC 80V 80V DC 150V 150V DC Note: The ABMZ is only available in the Screw terminal version. ABM / ABMZ Application Warranty The ABM is intended to be used in conjunction with digital relays specifically designed for power industry applications as an aid to improving the robustness of inputs to intermittent electrical transients and impulse noise. It is not a general panacea for making general purpose devices or inputs work in all possible power utility applications. The ABM is a unipolar device and must be connected correctly in DC circuits only. Voltage rating selection for the ABM must be appropriate to the application. The ABM unit will not tolerate sustained excessive, over voltage transients with high energy content. The ABM can be degraded and damaged by such conditions and is designed to ultimately fuse internally in such situations to prevent the possibility of catastrophic failure that may otherwise impact surrounding wiring. The ABM modules are not warranted for such applications or against such failure modes. Due to RMS continuous product improvement policy this information is subject to change without notice. ABM/Issue I/25/01/2011-9/9

Australian Content Unless otherwise stated the product(s) quoted are manufactured by RMS at our production facility in Melbourne Australia. Approximately 60% of our sales volume is derived from equipment manufactured in house with a local content close to 80%. Imported components such as semi-conductors are sourced from local suppliers & preference is given for reasonable stock holding to support our build requirements. Quality Assurance RMS holds NCSI (NATA Certification Services International), registration number 6869 for the certification of a quality assurance system to AS/NZS ISO9001-2008. Quality plans for all products involve 100% inspection and testing carried out before despatch. Further details on specific test plans, quality policy & procedures may be found in section A4 of the RMS product catalogue. Product Packaging Protection relays are supplied in secure individual packing cardboard boxes with moulded styrene inserts suitable for recycling. Each product & packing box is labeled with the product part number, customer name & order details. Design References The products & components produced by RMS are based on many years of field experience since Relays Pty Ltd was formed in 1955. A large population of equipment is in service throughout Australia, New Zealand, South Africa & South East Asia attesting to this fact. Specific product & customer reference sites may be provided on application. Product Warranty All utility grade protection & auxiliary relay products, unless otherwise stated, are warranted for a period of 24 months from shipment for materials & labour on a return to factory basis. Repair of products damaged through poor application or circumstances outside the product ratings will be carried out at the customer s expense. Standard Conditions of Sale Unless otherwise agreed RMS Standard Terms & Conditions (QF 907) shall apply to all sales. These are available on request or from our web site. Relay Monitoring Systems Pty Ltd 6 Anzed Court, Mulgrave, Victoria 3170, AUSTRALIA Tel: +61 3 8544 1200 Fax: +61 3 8544 1201 Email: rms@rmspl.com.au Web: www.rmspl.com.au 2011 Relay Monitoring Systems Pty Ltd Due to RMS continuous product improvement policy this information is subject to change without notice.