1 Engineering Specification Electrical Networks L1-CHE-SPE-152 Specification Voltage Limiting Device Version: 1 Issued: 20 th April 2018 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering, Electrical PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION

2 Approval Amendment Record Approval Date Version Description 20/04/ Initial Release PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 2 of 16

3 Table of Contents 1. Purpose Scope Background Abbreviations Definitions References & Legislations General Rail Industry Standards/Documents Australian and International Standards/Documents Engineering Quality and Management Compliance with Standards General Equipment Requirements Application General Functional Requirements Communication Requirements Protection Requirements Additional Requirements Main Components References Testing Type Test Test Certificates Documentation and Support Contract Documentation Design Documentation Delivery Documentation Design Drawings Technical Maintenance Plan Maintenance Manual Installation Instruction Manual Operating Instructions Manual Tools & Equipment PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 3 of 16

4 Documentation Requirements Drawing Format Appendix A Technical Data Schedule Form PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 4 of 16

5 1. Purpose This document is the technical specification for the Voltage Limiting Device (VLD) for use in the MTM 1,500V DC traction system. 2. Scope The specification covers the functionality, technical requirements and communication interface requirements of the Voltage Limiting Device. This specification is to be read in conjunction with the scope of works document for each site which details the quantities and site specific requirements. 3. Background The VLD is intended to be used to protect against dangerous touch voltages between earthed structures such as station platforms and the traction return circuit due to operating currents as well as short circuit currents to fulfil the requirement of EN Abbreviations AC CB DC HV HVAC HVDC MTM RTU SCADA VLD VRIOGS Alternating Current Circuit Breaker Direct Current High Voltage High Voltage Alternating Current High Voltage Direct Current Metro Trains Melbourne Pty. Ltd. Remote Terminal Unit (of the SCADA system) Supervisory Control And Data Acquisition system Voltage Limiting Device Victorian Rail Industry Operators Group Standard 5. Definitions Shall Should Is used as the descriptive word to express a requirement that is mandatory to achieve conformance to the standard. Is used as the descriptive word to express a requirement that is recommended in order to achieve compliance to the standard. Should can also be used if a requirement is a design goal but not a mandatory requirement. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 5 of 16

6 6. References & Legislations 6.1 General The Voltage Limiting Device shall be designed and constructed in accordance with all relevant MTM Standards and Australian, Rail Industry and International Standards. The Voltage Limiting Device shall comply with all applicable legislative and regulatory requirements. Any non-compliance shall be detailed, with a determination by MTM Chief Engineer of its acceptance or otherwise. 6.2 Rail Industry Standards/Documents Document Number IPGOR -01 The Orange Book Title PTC Train Infrastructure Electrical Safety Rules (High Voltage Rules The Victorian Traction Industry Electrical Safety Rules 6.3 Australian and International Standards/Documents Document Number EN EN EN EN EN EN IEC EN AS2067 Title Railway applications. Electromagnetic compatibility. Emission and immunity of fixed power supply installations and apparatus Railway applications. Fixed installations. Electrical safety, earthing and the return circuit. Protective provisions against electric shock Railway applications. Fixed installations. Electrical safety, earthing and the return circuit. Provisions against the effects of stray currents caused by D.C. traction systems Railway applications. Fixed installations. Electrical safety, earthing and the return circuit. Provisions against the effects of stray currents caused by D.C. traction systems Railway Applications - Fixed Installations - D.C. Surge Arresters And Voltage Limiting Devices - Part 2: Voltage Limiting Devices Railway application. Fixed installations. D.C. surge arresters and voltage limiting devices. Application Guide Fixed installations - DC switchgear - Part 6: DC switchgear assemblies Railway applications. Fixed installations. D.C. switchgear. D.C. switchgear assemblies Substations and high voltage installations exceeding 1kV AC 2008 PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 6 of 16

7 AS/NZS 3000 Wiring Rules 2007 AS High-voltage switchgear and control gear N/A Electricity Safety (Installations) Regulations 2009 N/A Building Code of Australia IEC Communication Networks and Systems in Substations N/A Victorian Service and Installation Rules 7. Engineering Quality and Management 7.1. Compliance with Standards All design, equipment and items covered in this document shall comply with all the relevant Australian Standards, or where these do not exist the relevant IEC or EN Standards. 8. General Equipment Requirements The Voltage Limiting Device shall detect any rise in potential of the connected metallic structures and prevent the potential from reaching unsafe levels by shorting the connected metallic structures reliably to the track negative Application The VLD shall be a recoverable device which is compliant with Class 4.1 and Class 4.2 in accordance with EN The VLD shall be able to operate as Type 1 (VLD-F) and Type 2 (VLD-O) in accordance with EN The operating profile of the Voltage Limiting Device shall comply with the Effective touch voltage limits defined in section of EN (refer section 9) General Functional Requirements The Voltage Limiting Device shall comply as a minimum to the specifications given in Table 1 below: PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 7 of 16

8 Table 1 Minimum Requirements Voltage Limiting Device Parameter Requirements Reference Standard EN /2 EN /3 Voltage Level Nominal Voltage 1500VDC Lighting and Power Supply 230VAC Rated insulation voltage 3,600VDC Rated short-duration power frequency voltage 15kV (50Hz 1min) Basic Insulation Level 40kV Rated Current Nominal Current 1200A Short Time Withstand Current 100kA (100ms) Instantaneous Triggering Voltage Yes 400VDC (Desirable) 300VDC (Acceptable) Auto Reset for Voltages below Instantaneous Triggering Voltage Yes Settable Latched Operation Yes Above Instantaneous Triggering Voltage Bypass Facility Yes Surge Protection Yes Redundant Monitoring Circuit Yes Redundant Tripping Circuit Yes Local Control Yes - toggle switch PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 8 of 16

9 Parameter Requirements Remote Control Yes, floating contacts marshalled to SEL 2505 I/O module. Communication Protocol DNP 3.0 Enclosure IP rating IP65 Application Outdoor Settable Tripping Voltage Yes (Annex F.3 of EN ) Type Tested to IEC / EN Yes 8.3. Communication Requirements Indications, Alarms and Control of the Voltage Limiting Device shall be marshalled to a suitable I/O module such as SEL 2505 or similar. The Voltage Limiting Device shall as a minimum have the following indications/control: - Open indication - Closed indication - Blocked indication - Fault Alarm(s), Open Control - Close Control & Block Command. The VLD shall be capable of DNP 3.0 protocol. Communications requirements shall be confirmed and approved by MTM prior to construction Protection Requirements The device shall comply with the requirements of Annex F.3 of EN and shall be capable of programmable setting for voltage pick up characteristic. The Voltage Limiting Device shall be capable of Instantaneous Triggering Voltage of 400V which shall be settable. The device shall be capable of auto-reset for voltages less than the Instantaneous Triggering Voltage. Operation above the Instantaneous Triggering Voltage shall be latched and require a local reset (and the option for remote reset). As a minimum the device shall have the protection functions detailed in Table 2 below: PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 9 of 16

10 Table 2 VLD Protection Functions Protection Protection Function Description Typical Function Type name Values Thyristor (Solid state switch) Voltage threshold N/A If the voltage exceeds the configured value, thyristor is triggered. 400V (300V acceptable) Contactor switch Static voltage threshold Voltage Threshold 1 Voltage Threshold 2 If the voltage exceeds a set value and remains there longer than the set time delay, a tripping is initiated. 50V 400V Dynamic voltage threshold Voltage Limiting Depending on the voltage level, this function automatically calculates the maximum permissible time, according to EN standard. Current threshold Current threshold 1 Current threshold 2 If the current exceeds a set value after expiry of a set time delay, a trip is initiated A Maximum automatic reopening Reopening counter To prevent the possibility of a succession of reclosures in case of closing followed by an automatic reopening 1 6 times 8.5. Additional Requirements The device shall comply with Section 5.4 Minimum requirements of EN The VLD shall become conductive in a time not greater than the permissible values in accordance with EN and EN The VLD shall not open if the current through it exceeds its breaking capacity The VLD shall open at an adjustable time after it has closed unless the breaking capacity is exceeded. If the VLD re-opens automatically and then re-triggers, after a set number of operations in a given time interval, It shall be prevented from re-opening and a warning or an alarm shall be signalled. The VLD shall close the contactor in the event of the panel door being opened. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 10 of 16

11 8.6. Main Components Following are the main components of the Voltage Limiting Device: Earthing Contactor Thyristor Control board Display/HMI Current measuring unit Voltage measuring unit Panel Heating and Lighting 9. References Table 2: Maximum permissible effective touch voltages U te, max in DC traction systems as a function of time duration as per EN Time Duration, t (s) Permissible Voltage, U te, max (V) Long-term Short-term > < PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 11 of 16

12 10. Testing Type and routine tests shall be performed on the Voltage Limiting Device in accordance with IEC 62590, section Type Test Type test certificates shall be provided from a design which is representative of the Voltage Limiting Device to be supplied. All type tests listed in Table 6 of IEC shall be completed Test Certificates The results of all tests shall be recorded on test certificates. The test certificates shall clearly show the performance of the equipment and shall be accompanied by tables showing the actually measured values and all calculations. The test certificates shall be forwarded to MTM and the results approved by MTM prior to delivery. 11. Documentation and Support Contract Documentation One set of PDF copies of the drawings and documentation should be provided for review and approval by MTM approximately 4 weeks after the contract award date. No manufacture shall commence until the drawings have been approved. An allowance of ten working days should be made by the supplier for the review of submitted drawings Design Documentation A hard copy and a soft copy of the following documentation shall be provided to MTM for every design of Voltage Limiting Device produced at the conclusion of design, and prior to delivery of the assembly: Technical Maintenance Plan Maintenance Manual Installation Instruction Manual Operating Instruction Manual Storage, handling, loading and off-loading instructions Approved drawings Whenever a design change is made, new copies of the updated design documentation shall be provided to MTM. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 12 of 16

13 11.3. Delivery Documentation Each delivery shall include a hard copy of the following documents: Technical Maintenance Plan Maintenance Manual Installation Instruction Manual Operating Instruction Manual Storage, handling, loading and off-loading instructions Test Certificates Approved drawings In addition, a soft copy of the test certificates shall be forwarded to MTM Design Drawings The drawings described in the table below shall be provided to MTM at the nominated design stages for review, and at the completion of design. Drawing Concept / Tender Preliminary Design Detailed Design Physical layout and arrangement of the overall assembly including dimensions and terminals. Physical arrangement of all components of the assembly. Installation details for the Voltage Limiting Device including mounting requirements. Physical layout and arrangement of all cable connections. Power circuit diagram and control circuit diagram All other drawings required for Installation, Testing, Commissioning, Operation and Maintenance Technical Maintenance Plan A Technical Maintenance Plan which establishes the maintenance policy for the assembly recommended by the supplier shall be provided. This shall detail the preventative servicing schedules and maintenance intervals for all components of the assembly. The servicing schedules shall reference appropriate detailed instructions in the maintenance manual. The Technical Maintenance Plan shall contain a list of any spare parts, suppliers, indicative pricing, lead times and recommended spares holdings. The Technical Maintenance Plan shall detail safe disposal procedures applicable for when the assembly is no longer serviceable (recycling, hazardous waste etc.). PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 13 of 16

14 11.6. Maintenance Manual A Maintenance Manual shall be provided which shall detail: The theory of operation of the equipment. All servicing activities. Overhaul instructions. The changing of components for repairs. Fault-finding procedures. The spares support schedule detailing price, supplier and procurement lead-times. The maintenance manual shall also include a complete set of as-built drawings and a comprehensive parts list for the assembly Installation Instruction Manual An Installation Instruction Manual shall be provided The instructions shall enable the transformer to be properly installed, tested and commissioned. This shall include all necessary drawings Operating Instructions Manual An Operating Instruction Manual shall be provided which shall clearly describe the required procedures for physically operating all of the components of the Transformer. The operating procedures shall be consistent with MTM s requirements Tools & Equipment Any special tools or other equipment necessary to operate or maintain the Voltage Limiting Device shall be provided with each assembly. Any special lifting and installation equipment shall be supplied with the Voltage Limiting Device Documentation Requirements All documentation shall be provided in English. Every page of the documentation shall be clearly identified in relation to the document to which it belongs and the version of that document. All pages of multi-page documents shall be uniquely numbered. It shall be possible to readily determine if all pages of a document are present. Manuals shall be A4 size and shall be bound in durable covers or in 4-D ring binders. Electronic copies of the Maintenance Manual, Installation Instructions Manual and Operating Instructions shall be provided in both PDF and Microsoft Word formats. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 14 of 16

15 Drawing Format All drawings shall comply with PTV Infrastructure Drafting Standard and shall be submitted for MTM approval prior to manufacturing. Drawings shall be provided in Microstation format and PDF. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 15 of 16

16 12. Appendix A Technical Data Schedule Form The Tenderer shall supply the following information and guaranteed performance. Compliance Does the Voltage Limiting Device fully comply with this Specification? YES / NO Is the Voltage Limiting Device type 1 VLD-F as defined in EN YES / NO Is a type test certificate attached? YES / NO Assembly a. Maximum system voltage (V DC) b. Nominal Current (A) d. Overall dimensions of enclosure: Height (mm) Width (mm) Depth (mm) e. Weight, fully equipped (kg) f. Clearance above cubicle for air ventilation (mm) g. Rated one-minute insulation voltage (V rms) h. Rated Impulse Insulation voltage (V p) i. Rated short-circuit capability (ka) j. Rated short-circuit capability duration (ms) Voltage Limiting Device Protection a. Does it comply with the requirements of Annex F.3 of EN YES / NO b. Is the VLD capable of programmable setting for voltage pick up characteristic as per EN YES / NO c. Does the VLD have an Instantaneous Triggering Voltage YES / NO d. Is auto-reset available below the Instantaneous Triggering Voltage YES / NO e. Does the VLD latch above the Instantaneous Triggering Voltage YES / NO Communication a. Has the VLD been optioned with DNP 3.0 protocol YES / NO PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 16 of 16

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V Version: 1 Issued: March 2014 Owner: Electrical Networks Asset

More information

Remotely Operable 1500V DC Disconnector & Short-Circuit Switch Assembly

Remotely Operable 1500V DC Disconnector & Short-Circuit Switch Assembly Specification Electrical Networks L1-CHE-SPE-128 Remotely Operable 1500V DC Disconnector & Short-Circuit Switch Assembly Version: 1 Issued: February 2016 Owner: Head of Engineering - Electrical Approved

More information

MESP MODULAR SUBSTATION USER REQUIREMENTS

MESP MODULAR SUBSTATION USER REQUIREMENTS Engineering Specification Electrical Networks MODULAR SUBSTATION USER Version: 2 Issued: November 2015 Owner: Head of Engineering/Electrical Approved By: Head of Engineering/Electrical PRINTOUT MAY NOT

More information

MESP TECHNICAL SPECIFICATION FOR 22 kv METAL ENCLOSED SWITCHGEAR

MESP TECHNICAL SPECIFICATION FOR 22 kv METAL ENCLOSED SWITCHGEAR Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR 22 kv Version: 2 Issued: 19 th December 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical

More information

MESP TECHNICAL SPECIFICATION FOR SCADA CABLING IN SUBSTATIONS

MESP TECHNICAL SPECIFICATION FOR SCADA CABLING IN SUBSTATIONS Engineering Specification Electrical Networks MESP 081000-01 TECHNICAL SPECIFICATION FOR SCADA CABLING IN Version: 1 Issued: March 2014 Owner: Electrical Networks Asset Manager Approved By: George Marulli

More information

TECHNICAL SPECIFICATION FOR A 1500V DC SWITCHGEAR ASSEMBLY

TECHNICAL SPECIFICATION FOR A 1500V DC SWITCHGEAR ASSEMBLY Engineering Specification Electrical TECHNICAL SPECIFICATION FOR A 1500V DC SWITCHGEAR ASSEMBLY Version: 2 Issued: October 2017 Owner: Chief Engineer Approved By: Phil Ellingworth Chief Engineer PRINTOUT

More information

MTM DESIGN PRACTICE NOTE 110V AC SURGE PROTECTION IN SIGNAL EQUIPMENT ROOMS AND TRACKSIDE ZONE BOXES

MTM DESIGN PRACTICE NOTE 110V AC SURGE PROTECTION IN SIGNAL EQUIPMENT ROOMS AND TRACKSIDE ZONE BOXES SURGE PROTECTION IN SIGNAL Approval Amendment Record Approval Date Version Description 11/05/2016 1 Initial Issue under MTM PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION

More information

////// SUBSTATIONS. Voltage Limiting Device. VGuard

////// SUBSTATIONS. Voltage Limiting Device. VGuard ////// SUBSTTIONS Voltage Limiting Device GENERL INFORMTION During normal operation of railway system, dangerous voltage can occur across accessible points of the return circuit and earth due to the voltage

More information

Title Substations - Base Safety & Operating Standards. Reference Number POP 07 - (RIC Standard: EP SP)

Title Substations - Base Safety & Operating Standards. Reference Number POP 07 - (RIC Standard: EP SP) Discipline Engineering Standard - NSW Category Electrical Title Reference Number POP 07 - (RIC Standard: EP 99 00 00 04 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

Type MVTT 14 and MVTT 15: Static Digital Time delay relays Type MVTT 4 and MVTT 5: Static Digital Time delay relays Features 000/ setting range Time settings easily selected by means of thumbwheel switches Provide time delayed pick-up, or drop-off Compact construction

More information

DESIGN PRACTICE NOTE NEGATIVE BUSBAR SHUNTS

DESIGN PRACTICE NOTE NEGATIVE BUSBAR SHUNTS Approval Amendment Record Approval Date Version Description 27/05/2013 1 Initial issue under MTM. PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 6 Table of Contents

More information

////// SUBSTATIONS SCMS. Stray Current Monitoring System

////// SUBSTATIONS SCMS. Stray Current Monitoring System ////// SUBSTATIONS SCMS Stray Current Monitoring System GENERAL INFORMATION The operation of DC traction systems requires suitable measures to prevent corrosion caused by stray currents on railway and

More information

Application Switchgear for industrial and advanced commercial applications. U e V AC 240/ (per pole) I cs 7,5 ka

Application Switchgear for industrial and advanced commercial applications. U e V AC 240/ (per pole) I cs 7,5 ka DATASHEET - FAZ-C16/1 Miniature circuit breaker (MCB), 16A, 1p, C-Char, AC Part no. FAZ-C16/1 Catalog No. 278561 Eaton Catalog No. FAZ-C16/1 EL-Nummer 0001695154 (Norway) Similar to illustration Delivery

More information

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE IMPORTANT! Please read all the information on this sheet. SAVE THESE INSTRUCTIONS! NOTICE BEFORE USING READ INSTRUCTIONS COMPLETELY. TO BE INSTALLED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL

More information

DC Substations / Supply Program

DC Substations / Supply Program DC Substations / Supply Program Sécheron offers an extensive range of products for DC electrification of public transport This document is intended to give a brief idea of our services, cubicles and systems

More information

QUINT-PS/ 1AC/24DC/ 5

QUINT-PS/ 1AC/24DC/ 5 Extract from the online catalog QUINT-PS/ 1AC/24DC/ 5 Order No.: 2866750 DIN rail power supply unit 24 V DC/5 A, primary switched-mode, 1- phase. The SFB technology (Selective Fuse Breaking Technology)

More information

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 REDUNDANCY MODULE TSP-REM360 AND TSP-REM600 Operating Instructions Seite 1 Dimensions drawings: TSP-REM360 Weight: 0.882lb Gewicht: 0.40kg Seite 2 Dimensions drawings: TSP-REM600 Bottom view Top view Side

More information

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1 INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1 TOSHIBA Corporation 2004 All Rights Reserved. ( Ver. 1.6 ) Safety Precautions Before using this product, please read this chapter carefully. This

More information

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station SPI PowerNet Reference: ZD23 Version: 1.1 Issue date: 15 May 2014 Contents 1 Scope... 3 2 Deer Park Terminal

More information

MTM Standards Induction for the Signal Design Roles

MTM Standards Induction for the Signal Design Roles MTM Standards Induction for the Signal Design Roles Version 1, 2018 Applicant Name: RSW number It is a requirement of the MTM Signals, CS&C, and Project Competency Management system for all RSW to be familiar

More information

Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units. Reference Number SPS 30 - (RIC Standard: SC SP)

Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units. Reference Number SPS 30 - (RIC Standard: SC SP) Discipline Engineering Standard - NSW Category Signalling Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units Reference Number SPS 30 - (RIC Standard: SC 09 10 07 00 SP)

More information

COMMUNICATION LINKS FOR SIGNALLING

COMMUNICATION LINKS FOR SIGNALLING Engineering Standard - Design Signalling & Operational Control Systems COMMUNICATION LINKS FOR SIGNALLING Version: 2 Issued: April 2016 PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST

More information

XPSMCMDI Input expansion module with screw term

XPSMCMDI Input expansion module with screw term Characteristics 16 Input expansion module with screw term Main Range of product Product or component type Device short name Electrical connection [Us] rated supply voltage Number of inputs Number of outputs

More information

ATS22D75S6 soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)/500V(45kW)

ATS22D75S6 soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)/500V(45kW) Characteristics soft starter-ats22-control 220V-power 230V(18.5kW)/400...440V(37kW)/500V(45kW) Price* : 683.00 GBP Main Range of product Altistart 22 Product or component type Product destination Product

More information

Application Switchgear for industrial and advanced commercial applications. U e V AC 240/ (per pole)

Application Switchgear for industrial and advanced commercial applications. U e V AC 240/ (per pole) DATASHEET - FAZ-C10/2 Miniature circuit breaker (MCB), 10A, 2p, C-Char, AC Similar to illustration Part no. FAZ-C10/2 Catalog No. 278756 Eaton Catalog No. FAZ-C10/2 EL-Nummer 1695166 (Norway) Delivery

More information

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.: Extract from the online catalog QUINT-PS/1AC/24DC/10 Order No.: 2866763 DIN rail power supply unit 24 V DC/10 A, primary-switched mode, 1- phase. The SFB technology (Selective Fusebreaking Technology)

More information

QUINT-PS/ 1AC/24DC/20/CO

QUINT-PS/ 1AC/24DC/20/CO Extract from the online catalog QUINT-PS/ 1AC/24DC/20/CO Order No.: 2320898 DIN rail power supply unit 24 V DC/20 A/CO, dip-coated circuit board, primary-switched, 1-phase. For the first time, SFB (selective

More information

PanelView Plus/VersaView CE Terminals and Display Modules

PanelView Plus/VersaView CE Terminals and Display Modules Installation Instructions PanelView Plus/VersaView CE Terminals and Display Modules (Catalog Numbers 2711P-xxxxxx, 6182H-xxxxxx) English Inside: Overview...2 For More Information...2 Modular Components...3

More information

ATS22D17Q soft starter-ats22-control 220V-power 230V(4kW)/ V(7.5kW)

ATS22D17Q soft starter-ats22-control 220V-power 230V(4kW)/ V(7.5kW) Characteristics soft starter-ats22-control 220V-power 230V(4kW)/400...440V(7.5kW) Main Range of product Altistart 22 Product or component type Product destination Product specific application Component

More information

Switching module for AC V and up to three load stages, with manual switching

Switching module for AC V and up to three load stages, with manual switching 8 149 PTM13-M3 DESIGO I/O modules Switching module for AC 24 250 V and up to three load stages, with manual switching PTM13-M3 Signal converter for connection to P-bus, with three interlocked on/off control

More information

MTM Standards Induction for the Signal Maintain Roles

MTM Standards Induction for the Signal Maintain Roles MTM Standards Induction for the Signal Maintain Roles Version 1, 2018 Applicant Name: RSW number It is a requirement of the MTM Signals, CS&C, and Project Competency Management system for all RSW to be

More information

ABL8WPS24400 regulated SMPS - 3-phase V - 24 V - 40 A

ABL8WPS24400 regulated SMPS - 3-phase V - 24 V - 40 A Characteristics regulated SMPS - 3-phase - 380..500 V - 24 V - 40 A Main Range of product Product or component type Power supply type Input voltage Output voltage Rated power in W Jan 11, 2018 Phaseo Power

More information

ATS22D62Q soft starter-ats22-control 220V-power 230V(15kW)/ V(30kW)

ATS22D62Q soft starter-ats22-control 220V-power 230V(15kW)/ V(30kW) Characteristics soft starter-ats22-control 220V-power 230V(15kW)/400...440V(30kW) Main Range of product Altistart 22 Product or component type Product destination Product specific application Component

More information

Title System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP)

Title System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP) Discipline Engineering Standard - NSW Category Electrical Title s Reference Number PCP 07 - (RIC Standard: EP 99 00 00 02 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical Issued for Review Section 26 28 16.01 Air Circuit Breakers Page 1 of 7 PART 1 GENERAL 1.1 GENERAL.1 This specification serves to define requirements for a replacement of low voltage circuit breaker of

More information

11 kv Indoor Switchgear - SCADA Controlled

11 kv Indoor Switchgear - SCADA Controlled Specification 11 kv Indoor Switchgear - SCADA Controlled Important Warning This document is one of a set of standards developed solely and specifically for use on the rail network owned or managed by the

More information

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC/ DC - solid state output Main Range of product Product or component type Discrete output type Width Component name Time delay type Time

More information

Company Directive ENGINEERING SPECIFICATION EE SPEC: 136

Company Directive ENGINEERING SPECIFICATION EE SPEC: 136 Company Directive ENGINEERING SPECIFICATION EE SPEC: 136 Ancillary Electrical Equipment for Use in Conjunction with Switchgear and Protection/Control Panels NOTE: The current version of this document is

More information

GB/T / IEC :2006

GB/T / IEC :2006 Translated English of Chinese Standard: GB/T14048.2-2008 www.chinesestandard.net Sales@ChineseStandard.net GB NATIONAL STANDARD OF THE PEOPLE S REPUBLIC OF CHINA ICS 29.120.40 K 31 GB/T 14048.2-2008 /

More information

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output Characteristics off-delay timing relay - control - 1 s..100 h - 24..240 V - solid state output Main Range of product Product or component type Discrete output type Width Component name Time delay type

More information

ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)

ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW) Product data sheet Characteristics ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/400...440V(37kW) Complementary Assembly style Function available Power supply voltage limits Main Range of

More information

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O Characteristics star-delta timing relay - 230VAC/440VAC - 1 C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts type

More information

ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/ V(7.5kW)

ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/ V(7.5kW) Product datasheet Characteristics ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/400...440V(7.5kW) Complementary Assembly style Function available Supply voltage limits Main Range of product

More information

QUIZ-MTM Standards Induction for the Signal Design Roles

QUIZ-MTM Standards Induction for the Signal Design Roles QUIZ-MTM Standards Induction for the Signal Design Roles Version 1.1, 2018 Applicant Name: RSW number It is a requirement of the MTM Signals, CS&C, and Project Competency Management system for all RSW

More information

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064 Monitoring technique VARIMETER Voltage relay MK 9064N, MH 9064 0269462 Your Advantages Preventive maintenance For better productivity Quicker fault locating Precise and reliable Min-, Max. value or window

More information

Safety Standards. Model Number:

Safety Standards. Model Number: 040APS Highlights & Features Compliant to IEC 60601-1 3rd edition IT and medical safety approvals Low earth leakage Current (

More information

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases Characteristics three-phase control relay 183 528Vac, 2 C/O Main Range of product Product or component type Relay type Network number of phases Relay name Relay monitored parameters Time delay type Switching

More information

1. Project Description

1. Project Description Page No: 1 of 16 1. Project Description 1.1 Introduction This document outlines protection, monitoring and control requirements for the shared network assets associated with establishment of Tarrone Terminal

More information

ABL8RPS24100 regulated SMPS - 1 or 2-phase V - 24 V - 10 A

ABL8RPS24100 regulated SMPS - 1 or 2-phase V - 24 V - 10 A Characteristics regulated SMPS - 1 or 2-phase - 100..500 V - 24 V - 10 A Main Range of product Product or component type Power supply type Input voltage Output voltage Rated power in W Jun 27, 2018 Phaseo

More information

Powerterm L144R Transformer/Rectifier Model C2260C four channel 12V/1.5A Transformer/Rectifier Module with Remote Control

Powerterm L144R Transformer/Rectifier Model C2260C four channel 12V/1.5A Transformer/Rectifier Module with Remote Control Unprecedented control of individual zones using this four zone TR module. DATASHEET Ideal for concrete beams and piers Avoids the need for paralleling of zones across different sections. Communication

More information

QUINT-PS AC/24DC/10

QUINT-PS AC/24DC/10 Extract from the online catalog QUINT-PS-100-240AC/24DC/10 Order No.: 2938604 DIN rail power supply unit 24 V DC/10 A, primary switched-mode, 1- phase Commercial data EAN 4017918890537 Pack 1 Pcs. Customs

More information

Electrical Demand Specification (Reference SOP: )

Electrical Demand Specification (Reference SOP: ) Project: Equipment Description: Location: Equipment No.: Project No: Protocol No.: Content Index 1. GENERAL...3 Design Standards...3 1.1. Standards...3 2. DESIGN...3 2.1. Safety...3 2.2. Circuit protection...3

More information

TRIO-PS/1AC/24DC/20. Extract from the online catalog. Order No.:

TRIO-PS/1AC/24DC/20. Extract from the online catalog. Order No.: Extract from the online catalog TRIO-PS/1AC/24DC/20 Order No.: 2866381 DIN rail power supply unit, primary-switched mode, 1-phase, output: 24 V DC / 20 A Commercial data EAN 4046356046664 Pack 1 pcs. Customs

More information

QUINT-PS/24DC/48DC/ 5

QUINT-PS/24DC/48DC/ 5 Extract from the online catalog QUINT-PS/24DC/48DC/ 5 Order No.: 2320128 QUINT DC/DC converter, primary-switched, input: 24 V DC, output: 48 V DC/5 A Commercial data GTIN (EAN) sales group Pack Catalog

More information

RT4B-110V/12A RECTIFIER

RT4B-110V/12A RECTIFIER The RT4B-110V/12A is a switched mode rectifier (SMR) module designed to provide up to 12A of output current into a 110V nominal system. It can be used with or without a cooling fan. With a fan it runs

More information

Safety Standards. Model Number:

Safety Standards. Model Number: PMC Highlights & Features Universal AC input range from 85Vac to 264Vac without power de-rating High operating ambient temperature, > 60 o C de-rating power High MTBF > 700,000 hrs. as per Telcordia SR-332

More information

CONTROL PANEL WIRING SPECIFICATIONS

CONTROL PANEL WIRING SPECIFICATIONS CONTROL PANEL WIRING ISSUE STATUS FIRST REV DESCRIPTION DATE 001 1 ST ISSUE 22/04/2014 002 1 ST AMMENDMENT 10/03/2017 003 2 ND AMMENDMENT 08/09/2017 THIS DOCUMENT IS DESIGNED TO COVER ALL APPLICATIONS,

More information

PMT. Model Number: CC Code PM 24V 200W 1 A Panel Mount Product Type T Enclosed L L Frame*

PMT. Model Number: CC Code PM 24V 200W 1 A Panel Mount Product Type T Enclosed L L Frame* PMT Highlights & Features AC input voltage selectable by switch Full Aluminium casing for light weight and corrosion resistant handling Convection cooling Cold start -20 C at 100% load (200W) Low leakage

More information

Application Switchgear for industrial and advanced commercial applications. U e V AC 277/480 Y V DC 60

Application Switchgear for industrial and advanced commercial applications. U e V AC 277/480 Y V DC 60 DATASHEET - FAZ-C5/2-RT Miniature circuit breaker (MCB), 5A, 2p, C-Char, AC Part no. FAZ-C5/2-RT Catalog No. 102203 Eaton Catalog No. FAZ-C5/2-RT EL-Nummer 1691799 (Norway) Similar to illustration Delivery

More information

ABL8RPS24030 regulated SMPS - 1 or 2-phase V - 24 V - 3 A

ABL8RPS24030 regulated SMPS - 1 or 2-phase V - 24 V - 3 A Characteristics regulated SMPS - 1 or 2-phase - 100..500 V - 24 V - 3 A Product availability : Stock - Normally stocked in distribution facility Price* : 270.00 USD Main Range of product Product or component

More information

Motor-protective circuit-breaker, 3p, Ir=16-25A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A

Motor-protective circuit-breaker, 3p, Ir=16-25A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A DATASHEET - PKZM4-25 Delivery program Motor-protective circuit-breaker, 3p, Ir=16-25A, screw connection Part no. PKZM4-25 Catalog No. 222352 Eaton Catalog No. XTPR025DC1NL EL-Nummer 0004355158 (Norway)

More information

Chrome DIN Rail Power Supply 5V 7.5W 1 Phase (Class II & NEC Class 2) / DRC-5V10W1AZ

Chrome DIN Rail Power Supply 5V 7.5W 1 Phase (Class II & NEC Class 2) / DRC-5V10W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range

More information

CENTERLINE 2500 Motor Control Centers

CENTERLINE 2500 Motor Control Centers CENTERLINE 2500 Motor Control Centers High Performance Motor Control Centers and Switch Gear Meeting IEC 61439-2 Product Description Allen-Bradley CENTERLINE 2500 motor control centers (MCCs) are designed

More information

2T105. Multi Range Digital Setting Time Delay Relay. Features. Application. Operation

2T105. Multi Range Digital Setting Time Delay Relay. Features. Application. Operation 2T15 Multi Range Digital Setting Time Delay Relay Technical Bulletin Features Four time ranges -.99s, -9.9s, -99s, -99s High accuracy & repeatability timing compensated for output relay delay Time settings

More information

ABL8WPS24200 regulated SMPS - 3-phase V AC - 24 V - 20 A

ABL8WPS24200 regulated SMPS - 3-phase V AC - 24 V - 20 A Characteristics regulated SMPS - 3-phase - 380..500 V AC - 24 V - 20 A Product availability : Stock - Normally stocked in distribution facility Price* : 735.00 USD Main Range of product Product or component

More information

XPSMCMMX inputs 2 output pairs expansion module with screw term

XPSMCMMX inputs 2 output pairs expansion module with screw term Characteristics 8 inputs 2 output pairs expansion module with screw term Main Range of product Product or component type Device short name Electrical connection [Us] rated supply voltage Number of inputs

More information

QUIZ-MTM Standards Induction for the Signal Maintain Roles Version 1.1, 2018

QUIZ-MTM Standards Induction for the Signal Maintain Roles Version 1.1, 2018 QUIZ-MTM Standards Induction for the Signal Maintain Roles Version 1.1, 2018 Applicant Name: RSW number It is a requirement of the MTM Signals, CS&C, and Project Competency Management system for all RSW

More information

LL1x150-CR-DA. 150 W Dimmable DALI-2 LED driver. 150 W V 0 / Hz. Functional Description. Mains Characteristics

LL1x150-CR-DA. 150 W Dimmable DALI-2 LED driver. 150 W V 0 / Hz. Functional Description. Mains Characteristics 150 W Dimmable DALI-2 LED driver DALI-2 certified LED driver, 1-100 % dimming range Filtered hybrid dimming technology Very high efficiency up to 96 % Low ripple and flicker (according to IEEE 1789) Suitable

More information

Withstands max. 320 VAC (max. 1 hour) *) Low frequency, LED load: Cree XP-G L LEDs. 350 ma 600 ma Fixed output 850 ma P Rated

Withstands max. 320 VAC (max. 1 hour) *) Low frequency, LED load: Cree XP-G L LEDs. 350 ma 600 ma Fixed output 850 ma P Rated 35 W SELV Constant current LED driver Product code: 5732 35 W 220 240 V 0/ 50 60 Hz SELV output protection for safety and flexibility in luminaires Very low current ripple, complying with IEEE 1789 standard

More information

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter Installation, Operation & Maintenance Sheet Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter > Contents 1 Contents 1 Contents...2 2 General Information...2 2.1 Manufacturer...2

More information

CAPABILITY STATEMENT. A full list of our services.

CAPABILITY STATEMENT. A full list of our services. CAPABILITY STATEMENT A full list of our services. About Us MVLV Power Solutions Pty Ltd is a privately owned Western Australian based company, specialising in the Design and Manufacture of Electrical Switchboards

More information

02/11/2015

02/11/2015 DIN Rail Mount 22.5 mm ETM2 Part number 84874023 Version ETM : Controls temperature of machines using built-in PTC probes Line break or probe short-circuit detection Version ETM2 / ETM22 : Fault latching

More information

XPSMCMDO Digital output pairs expansion modules with screw term

XPSMCMDO Digital output pairs expansion modules with screw term Characteristics 2 Digital output pairs expansion modules with screw term Main Range of product Product or component type Device short name Electrical connection [Us] rated supply voltage Number of inputs

More information

Safety Standards. Model Number: Unit Weight:

Safety Standards. Model Number: Unit Weight: MEA-250A24C Highlights & Features Meet Efficiency Level VI Safety Approvals to IEC 60601-1 3.1 Ed. & IEC 60950-1 Compliant with IEC 60601-1-2 3 th and 4 th Ed. Requirements IP22 ingress protection rating

More information

Zelio Control-modular measurement and control relays 1

Zelio Control-modular measurement and control relays 1 Presentation, description 1 106439 RM35 TM111MW Presentation Motor temperature measurement and 50MW and RM35 TM250MW monitor the following, on 3-phase supplies: correct sequencing of phases L1, L2 and

More information

CUS150M1 Instruction Manual

CUS150M1 Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Be sure to read this instruction manual thoroughly before using this product. Pay attention to all cautions and warnings before using this product. Incorrect usage could

More information

Rhino Redundancy Module PSM24-REM360S. Operating Instructions

Rhino Redundancy Module PSM24-REM360S. Operating Instructions Rhino Redundancy Module PSM4-REM360S Operating Instructions RHINO REDUNDANCY MODULE PSM4-REM360S Description With this module and two power supplies of the PSM series (78, 90, 56, 80 and 360 watt models),

More information

ATS22C11S6U soft starter-ats22-control110vpower208v(30hp)/230v(40hp)/460v(75hp)/575v(100h

ATS22C11S6U soft starter-ats22-control110vpower208v(30hp)/230v(40hp)/460v(75hp)/575v(100h Characteristics soft starter-ats22-control110vpower208v(30hp)/230v(40hp)/460v(75hp)/575v(100h Complementary Assembly style Function available Power supply voltage limits Main Range of product Altistart

More information

Technical Data. Circuit Protection - Surge Protection Devices. Ver 1.0 CUSPD1110. Brief product description:

Technical Data. Circuit Protection - Surge Protection Devices. Ver 1.0 CUSPD1110. Brief product description: Technical Data Circuit Protection - Surge Protection Devices Ver 1.0 CUSPD1110 Brief product description: Surge Protection Device (SPD) protect against lightning surges and man made surges such as motors,

More information

PMT. Model Number: Model Number Input Voltage Range Output Voltage Output Current PMT-5V350W1A (Selectable by Switch)

PMT. Model Number: Model Number Input Voltage Range Output Voltage Output Current PMT-5V350W1A (Selectable by Switch) PMT Highlights & Features AC input range selectable by switch Full Aluminium casing for light weight and corrosion resistant handling Built-in automatic fan speed control circuit Wide operating temperature

More information

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output Characteristics on-delay timing relay - 1 s..100 h - 24..240 V AC/DC - solid state output Complementary Control type Voltage range Main Range of product Product or component type Discrete output type Width

More information

PMT. Safety Standards. Model Number:

PMT. Safety Standards. Model Number: PMT Highlights & Features AC input range selectable by switch Full aluminium casing for light weight and corrosion resistant handling Built-in automatic fan speed control circuit MTBF > 700,000 hrs. as

More information

RM35JA32MR Current control relay 0.15A 15A, 2 C/O

RM35JA32MR Current control relay 0.15A 15A, 2 C/O Characteristics Current control relay 0.15A 15A, 2 C/O Main Range of product Product or component type Relay type Relay name Relay monitored parameters Time delay type Switching capacity in VA Measurement

More information

For Sales and Support call KMParts.com (866)

For Sales and Support call KMParts.com (866) Overcurrentswitch,5A,1p,B-Char,AC Partno. FAZ-B5/1 Articleno. 278528 CatalogNo. FAZ-B5/1 Similar to illustration Deliveryprogram Basic function Miniature circuit breakers Number of poles 1 pole Tripping

More information

SECTION APPENDIX B SFC DOCUMENT SUBMITTAL SCHEDULE

SECTION APPENDIX B SFC DOCUMENT SUBMITTAL SCHEDULE SECTION 16262 - APPENDIX B SFC DOCUMENT SUBMITTAL SCHEDULE PART 1 - GENERAL 1.01 RELATED SECTIONS A. Section 01300 Submittals B. Section 16262 Static Frequency Converter C. Section 16262A Appendix A SFC

More information

LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual

LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp Single phase two wire DIN rail energy meter (One module) 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic

More information

Model Number: Model Number Input Voltage Range Output Voltage Output Current PMC-24V100W1AX Vac ( Vdc) 24Vdc 4.17A

Model Number: Model Number Input Voltage Range Output Voltage Output Current PMC-24V100W1AX Vac ( Vdc) 24Vdc 4.17A PMC Highlights & Features Universal AC input range from 85Vac to 264Vac without power de-rating Full Aluminum casing for light weight and corrosion resistant handling High MTBF > 700,000 hrs. as per Telcordia

More information

An Urgent Bulletin from CSA Group

An Urgent Bulletin from CSA Group An Urgent Bulletin from CSA Group Photovoltaic Equipment No. 5 Date: September 21, 2015 See Attachment 1 for Effective Dates. See Attachment 1 for Application Due Dates Announcing: Publication of List

More information

INSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F

INSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F PSD1000 - PSD1000F INSTRUCTION MANUAL Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD1000 - Universal AC Input Switching Power Supply 24 Vdc Output ISM0089-4

More information

060AAS19 B MDS. MDS Medical AC-DC Adapter 19Volt, 60Watt / MDS-060AAS19 B. Highlights & Features. Safety Standards. Model Number: General Description

060AAS19 B MDS. MDS Medical AC-DC Adapter 19Volt, 60Watt / MDS-060AAS19 B. Highlights & Features. Safety Standards. Model Number: General Description 060AAS19 B Highlights & Features Safety Approvals to IEC 60601-1 3rd ed. & IEC 60950-1 Risk management report available Low touch current (

More information

////// SUBSTATIONS. DC Switchgear Range. Type MBS (IEEE/ANSI standards)

////// SUBSTATIONS. DC Switchgear Range. Type MBS (IEEE/ANSI standards) ////// SUBSTATIONS DC Switchgear Range Type MBS (IEEE/ANSI standards) GENERAL INFORMATION With a complete range of equipment and a leading expertise in DC traction power substations, Sécheron SA is a world

More information

Chrome DIN Rail Power Supply 12V 9.96W 1 Phase (Class II & NEC Class 2) / DRC-12V10W1A

Chrome DIN Rail Power Supply 12V 9.96W 1 Phase (Class II & NEC Class 2) / DRC-12V10W1A Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range

More information

040APS12 B MDS. MDS Medical AC-DC Open Frame 12Volt, 40Watt / MDS-040APS12 B ``` Highlights & Features. Safety Standards.

040APS12 B MDS. MDS Medical AC-DC Open Frame 12Volt, 40Watt / MDS-040APS12 B ``` Highlights & Features. Safety Standards. 040APS12 B Highlights & Features Safety Approvals to IEC 60601-1 3rd ed. & IEC 60950-1 Risk management report available Low touch current (

More information

Application Instantaneous release response current 5-10 x In. Switching capacity Switching Capacity 15 ka (IEC/EN ) U e V AC 230/400

Application Instantaneous release response current 5-10 x In. Switching capacity Switching Capacity 15 ka (IEC/EN ) U e V AC 230/400 Overcurrentswitch,10A,3p,C-Char,AC Partno. FAZ-C10/3 Articleno. 278869 CatalogNo. FAZ-C10/3 Similar to illustration Deliveryprogramme Product range FAZ Application Instantaneous release response current

More information

ATS22C17Q. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

ATS22C17Q. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection Product datasheet Characteristics ATS22C17Q Complementary Assembly style Function available Supply voltage limits Main Range of product Altistart 22 Product or component type Product destination Product

More information

Residual Current Devices. Residual Current Devices FRCmM-NA according to UL1053 & IEC/EN 61008

Residual Current Devices. Residual Current Devices FRCmM-NA according to UL1053 & IEC/EN 61008 Residual Current Devices FRCmM-NA according to UL1053 & IEC/EN 61008 Wide range of compact types of RCDs serving as fault-current and additional protection according to UL1053 & IEC/EN 61008 standards,

More information

PMT. Model Number: CC Code PM 24V 150W 1 A Panel Mount Product Type T Enclosed L L Frame*

PMT. Model Number: CC Code PM 24V 150W 1 A Panel Mount Product Type T Enclosed L L Frame* PMT Highlights & Features Conforms to harmonic current IEC/EN 61000-3-2, Class A Selectable AC Switch (90-132Vac, 180-264Vac) High MTBF > 700,000 hrs. as per Telcordia SR-332 Versatile configuration options

More information

ABL8RPS24100 regulated SMPS - 1 or 2-phase V - 24 V - 10 A

ABL8RPS24100 regulated SMPS - 1 or 2-phase V - 24 V - 10 A Product datasheet Characteristics ABL8RPS24100 regulated SMPS - 1 or 2-phase - 100..500 V - 24 V - 10 A Complementary Input voltage limits Network frequency Inrush current Cos phi Main Range of product

More information

LC35SE-CC LOOP

LC35SE-CC LOOP 35 W SELV Constant current LED driver Product code: 5748 35 W 220 240 V 0/ 50 60 Hz SELV output protection for safety and flexibility in luminaires Very low current ripple, complying with IEEE 1789 standard

More information

LC51SE-CC LOOP

LC51SE-CC LOOP 51 W SELV Constant current LED driver Product code: 5740 51 W 220 240 V 0/ 50 60 Hz SELV output protection for safety and flexibility in luminaires Very low current ripple, complying with IEEE 1789 standard

More information