2T105. Multi Range Digital Setting Time Delay Relay. Features. Application. Operation

Similar documents
2C138. Sensitive Earth Fault Relay. Features. Application. Operation

Reyrolle Protection Devices. 7SG21 DDB20 Multi Range Digital Setting Time Delay Relay. Energy Management

2H34. Definite Time Frequency Relay with ROCOF. Features. Operation. Application

2V67-S Four Stage Over / Under Voltage Relay

2V67 Four Stage Over / Under Voltage Relay

2V67-S Four Stage Over / Under Voltage Relay

USB Driver Installation Guide

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

2C138 User Guide. Sensitive Earth Fault Relay. Advanced Protection Devices. relay monitoring systems pty ltd. User Guide.

ABM Status Input Active Burden Module

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

Reyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy

6R MATRIX Pre-Defined. Modular Relays. rms. Auxiliary, Trip & Supervision Relays

Reyrolle Protection Devices. 7SG118 Argus 8 Voltage & Frequency Relay. Answers for energy

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

RE11RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

02/11/2015

AUGUST 2001 APPLICATION AND COMMISSIONING MANUAL MIT161 RELAY EASUN REYROLLE LIMITED

02/11/2015

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

08/07/2015

RE Product data sheet Characteristics. time delay relay for star-delta starter ms - 230/380 V AC - 1 contact. Main.

RE Product data sheet Characteristics. universal plug-in timing relay - flashing s..60 mn V AC - 2 OC. Main.

RM4TR31 three-phase network control relay RM4-T - range V

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

relay monitoring systems pty ltd Advanced Protection Devices

RM4JA01F current measurement relay RM4-J - range ma V AC

02/11/2015

7SG26 Tau Autoreclose and synchronization Answers for energy

XU1-DC DC voltage relay. (June 1998) Manual XU1-DC (Revision New)

Residual overvoltage relay

RM4JA32MW current measurement relay RM4-J - range A V AC DC

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O

REYROLLE. 2C73 User Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd. User Guide.

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

RE22R2CMR Off-delay Timing Relay s 300h V AC/DC - 2C/O

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

RM35TF. Main. Product or component type. Product specific application. Relay monitored parameters 250 V AC 5 A AC

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

XU1-E Earth fault voltage relay. (August 1996) Manual XU1-E (Revision New)

Multifunctional time delay relay MFT U31S, MFT U41SE

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O

Model Number Structure

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

RMS Product Presentation

Feeder protection relay SPAA 121 C. Product Guide

RM4JA31M current measurement relay RM4-J - range ma V AC

Earth-fault Relay SPAJ 110 C. Product Guide

RE8TA31BU industrial timing relay s - type A - 24 V AC/DC, V AC - 1 C/O

C-Bus Network Bridge 5500NB. Series. Installation Instructions REGISTERED DESIGN REGISTERED PATENT

Voltage Dip-Proofing Inverter

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA 250 V AC

02/11/2015

RM4TA32 three-phase network control relay RM4-T - range V

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

RM35UB3. Product data sheet Characteristics. voltage control relay RM35-U - range V AC. Main. Complementary

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

RM35TF V AC

RTU511. Binary Output 23BO62. Characteristics. Application. Data Sheet Binary Output 23BO62. The binary output is made via relay contacts.

Protection Relays PHASE & RESIDUAL OVERCURRENT

NPW800R RETROFITTING. Power and Volatge Protection Relay

Zelio Control-modular measurement and control relays 1

RM17UB3. Product data sheet Characteristics. voltage control relay RM17-U - range V AC. Main. Complementary

RE22R1AMR On-delay Timing Relay s 300h V AC/DC - 1C/O

QUINT-PS/ 1AC/24DC/20/CO

NewCode. Comprehensive Motor Protection and Control Relay. Relay Field Input and Output LEDs. LED Fault Indicators

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC

RM4UA33M voltage measurement relay RM4-U - range V V AC

RE22R2QGMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O

Feeder protection relay SPAA 341 C. Product Guide

MiCOM P111. Three phase and earth fault overcurrent relays

QUINT-PS/ 1AC/24DC/ 5

300 WATT, PFC, OPEN FRAME POWER SUPPLIES TABLE 1. OUTPUT RATINGS AND SPECIFICATIONS, RMW 300W SERIES

RM4LA32M liquid level control relay RM4-L V AC

Voltage Dip-Proofing Inverter

Specification Voltage Limiting Device

Content. Time delay relays mounting position. Multifunctional time delay relay Clock-pulse generator time delay relay... 3.

RM17UAS. Product datasheet Characteristics. voltage control relay RM17-U - range V DC. Main. Complementary. Price* : 70.

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

RE8YG31BUTQ industrial timing relay s - type Qc - 24 V AC/DC, V AC - 1C/O

RM35JA32MR Current control relay 0.15A 15A, 2 C/O

DIAC/DIFC/DSFC. Single Phase Digital O/C. Single phase or ground overcurrent protection for industrial and utility power systems.

Electronic timer CT-ARE OFF-delayed without auxiliary voltage, 1 c/o (SPDT) contact

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA

PROGRAMMABLE MULTI-RANGE REPEAT CYCLE & DELAYED INTERVAL

Synchro-check relay. Application

Voltage Sag Simulator

Millenium 3. General Characteristics. General environment characteristics for CB, CD, XD, XR and XE product types

RE8YG31BUTQ industrial timing relay s - type Qc - 24 V AC/DC, V AC - 1C/O

TM221M16R controller M IO relay

Transcription:

2T15 Multi Range Digital Setting Time Delay Relay Technical Bulletin Features Four time ranges -.99s, -9.9s, -99s, -99s High accuracy & repeatability timing compensated for output relay delay Time settings easily selected by digital thumb wheel switches Selectable delay operate or delay release Optional reset functions Instantaneous (Fast), definite time, count down 4 C/O output contacts Wide auxiliary supply range with fail alarm contact Timing in progress LED Non-volatile trip indication Multi voltage timer initiate input Multi voltage flag reset input Size 2M draw out case Application The 2T15 time delay relay is particularly suitable for use in protection & control schemes where precision time delays are required. CB FAIL A typical use is for providing a definite time delay in circuit breaker failure protection. For example: The transformer multi-trip relays energize the 2T15 timer & if the circuit breaker (CB) fails to clear the fault within the pre-set (.6s) the timer times out & operates a multi-trip relay. This in turn trips all CB s on the section of the busbar connected to the CB, which has failed to trip. INDUCTION DISC RESET EMULATION Replacement of induction disc timing elements with solid-state relays can result in a loss of grading & reduced functionality due to the different reset characteristics. For example, the inherent slow reset time of induction disc relays provide an advantage in sensitive overcurrent schemes where pecking faults could go undetected due to the timer being instantaneously reset each time the current momentarily falls bellow the start setting. The 2T15 may be specified with a number of reset functions to avoid this problem & to suit specific protection applications. Operation 2T15 depicted in a 2M28 case. Made in Australia A crystal oscillator & embedded micro controller based timing circuit are employed to provide accurate timing & flexible functionality. When a control signal is applied to the timer initiate input, a counter begins counting down from the thumb wheel switch setting. When the zero is detected, the output relay contacts & flag operate. Three time ranges are selected via a front panel switch. An internal configuration switch can be used to select a x1 range multiplier to provide up to 99s of precision time delay. Two timing modes are available: Time delay ON mode (Relay starts timing after the initiate control signal is applied & output contact picks up after the pre-set time delay has elapsed) or; Time delay OFF mode (Relay output contact picks up instantaneously when the initiate control signal is applied, starts timing after the initiate control signal is removed & drops out after the pre-set time delay has elapsed). An amber LED on the front panel indicates when the relay has been initiated & flashes during timing. The 2T15 timer may be specified with a number of different reset functions to provide instantaneous reset, definite time reset or induction dist reset emulation. These functions are specified at time of order. A switchmode power supply provides a very wide auxiliary operating range. A relay fail alarm is provided in the form of a C/O contact which is picked up when the auxiliary supply rail & CPU watchdog status is healthy. Due to RMS continuous product improvement policy this information is subject to change without notice. 2T15/Iss K/12/1/9-1/5

Timing Functions TIMING FUNCTION / INITIATE SIGNAL INPUT (Status input ) For accurate timing functions the 2T15 detects application or removal of an external voltage control signal. This mode is set using internal configuration switch 2 (Refer order code details). Refer to Table 2 for timing initiate & times. DELAY OPERATE TIMING FUNCTION This timing mode is selected using internal configuration switch 3. The relay is permanently connected to the auxiliary supply & is initiated by the application of a control signal. Application of the initiate signal starts the pre set timing cycle. During timing the front panel initiate LED will flash & then go on solid once the thumbwheel time setting has elapsed, this sets the output relay & visual indicator. The initiate LED is extinguished & the output contacts reset when the initiate signal is removed. After system reset the visual indicator may be reset locally using the front panel push button or remotely via the flag reset input. To achieve a simple but less accurate delay ON function, the initiate signal may be connected directly to the auxiliary supply. Timing will then commence when power is applied to the relay while removal of power will reset the time delay & output relay. This mode is only suitable for longer time delay settings as the switch mode power supply takes 1 5ms (Depending on Vx), to start which adds to the inherent time delay. Flag reset Flag Initiate Contacts Delay Operate (ON) 2ms min reset pulse t Set AC t Set DC Removal of the initiate signal during timing will reset the time delay (Refer timing reset options). After time out the contacts are reset to the condition upon removal of the initiate signal. The flag can be reset provided the timer initiate signal is removed. t DELAY RELEASE TIMING FUNCTION This timing mode is selected using internal configuration switch 3. The relay is permanently connected to the auxiliary supply. Application of the initiate control signal, causes the output relay to set instantaneously (Rset). It will remain in this state until the control signal is removed; this starts the timing cycle & resets the output relay when the preset time delay is reached. Flag reset Flag Initiate Contacts Delay Release (OFF) r Set 2ms min reset pulse t Set Re-application of the initiate signal during timing will reset the time delay (Refer timing reset options). After time out the contacts are reset to the condition. The flag can be reset at any time, except during timing. TIMING RESET OPTIONS Instantaneous If reset before the preset time delay is reached the timing element will reset () as per Table 2. Definite Time Reset (Treset) If reset before the preset time delay is reached the delay timer will pause until the reset time has elapsed before resetting. If the timer is re-initiated before the reset time has elapsed, the delay timer will restart the timing sequence from the paused timing point. Count Down Reset If reset before the preset time delay is reached, the timer will count down toward reset. If the timer is re-initiated before reset is reached the timer will start counting back up towards the time delay pre set. t RESET FUNCTION DIAGRAM Due to RMS continuous product improvement policy this information is subject to change without notice. 2T15/Iss K/12/1/9-2/5

Technical Data AUXILIARY SUPPLY 4-3V DC & 4-275V AC or 2-7V DC switchmode supply. BURDEN (11V DC nominal supply) Less than 2 watts during idle & timing. Less than 4 watts when output relays are energized. RELAY FAIL ALARM A C/O alarm contact is maintained in the energized state when all of the following conditions are met: The auxiliary supply is applied The internal 24V DC rail is within acceptable limits The CPU hardware watchdog maintains a pulsing output A CPU software watchdog records suspect events to an assert register & if necessary performs a soft restart. TIME SETTING RANGES The 2T15 relay allows for precision time settings of between zero (Minimum operate time) & 99 seconds. This is achieved by the use of two decimal thumb wheel switches & a range multiplication switch on the front panel. A 1x setting multiplier is activated when configuration switch 5 is set to OFF to extend timer range 3 up to 99s. Range Selector Setting Achievable Time Setting Range Resolution of Time Setting Range 1 Zero to.99 Sec.1 Sec Range 2 Zero to 9.9 Sec.1 Sec Range 3 Zero to 99 Sec 1 Sec Range setting x1 Zero to 99 Sec 1 Sec Table 1 TIME DELAY SETTING CHANGES The time delay & function settings should only be changed when the timing initiate LED is extinguished. Time delay settings are read at the beginning of each timing sequence. TIMER INITIATE STATUS INPUT DELAY AC Rejection Filter Initiate input Minimum ON OFF DC AC <16ms <4ms <4ms <16ms N/A MINIMUM OUTPUT CONTACT OPERATE TIME 2T15 time delay setting <23ms <33ms Table 2 Minimum Time delay The minimum output contact operate time is equal to the timer initiate status input delays in Table 2 6ms. Time delay settings to this figure will result in a relay contact operate time equal to the minimum. TIMING ACCURACY Maximum timing error as a % of setting uncertainty in ms. AC Rejection Filter Initiate input ON OFF DC -.19%.2ms AC N/A -.19% 1ms Table 3 CONFIGURATION SWITCHES Configuration switches are accessible to the user & can be set by withdrawing the relay module & following the instructions on the side plate label. A bank of 5 switches are provided as depicted below & are read each time the 2T15 is powered up: Configuration Switches 1 2 3 4 5 STATUS INPUT OPERATING VOLTAGE (AC rejection filter) The operating range of the status inputs are set using internal configuration switch 1. This setting may be pre defined when ordering. 18-3V DC Set Configuration Switch to ON In this mode the universal status input will reject AC signals that may be induced on the control wiring. Suitable for high security applications where a DC battery supply is available. 18-3V DC & 18 275V AC Set Configuration Switch to OFF In this mode the universal status input is designed to operate on both AC & DC input voltages. Suitable for applications where an AC auxiliary voltage is available such as transformer or generator control panels. STATUS INPUT MINIMUM OPERATING CURRENT 1mA for 1ms then reducing to1.5ma after 4ms. While the function of the configuration switches may vary for special custom models, the standard functions & default settings are described in the Ordering Information section. FRONT PANEL INDICATORS Four LED indicators are provided on the front panel: Power On solid when auxiliary supply healthy Green Timing Flashing during timing Amber Trip On solid when output relay operated Red Range x1 On when the x1 time range selected Green The trip LED status is stored in non volatile memory & will be restored when the 2T15 is powered up after loss of the auxiliary supply. The preserved trip LED state is reset using the front panel flag reset button or status input. A hand & remote reset magnetic disc flag (permanent memory) indicator may be specified as an option. Note that an auxiliary supply is required to reset the flag circuits. TRANSIENT OVERVOLTAGE IEC6255-5 CLASS III Between all terminals & earth 5kV 1.2/5us.5J Between independent circuits without damage or flashover 5kV 1.2/5us.5J INSULATION COORDINATION Between all terminals & earth Between independent circuits Across normally open contacts AUXILIARY SUPPLY Allowable breaks / dips in supply Collapse to zero from nominal voltage HIGH FREQUENCY DISTURBANCE 2.5kV 1MHz common mode 1.kV 1MHz differential mode ELECTROSTATIC DISCHARGE 6kV contact discharge FAST TRANSIENT 4kV, 5/5ns, 1KHz repetitive TEMPERATURE RANGE Operating: Storage: HUMIDITY 4 o C & 95% RH non condensing IEC6255-5 CLASS III 2.kV RMS for 1 minute 2.kV RMS for 1 minute 1.kV RMS for 1 minute 2ms IEC6255-11 IEC6255-22-1 CLASS III 3% variation IEC6255-22-2 CLASS III 5% variation IEC6255-22-4 3% variation IEC68-2-1/2-1 to 55 o C -25 to 75 o C IEC68-2-78 Due to RMS continuous product improvement policy this information is subject to change without notice. 2T15/Iss K/12/1/9-3/5

Wiring Diagram OUTPUT RELAY CONTACT CONFIGURATION 4 C/O contacts OUTPUT CONTACT DWELL TIME Once operated all time delayed output contacts have a minimum dwell time of 1ms. OUTPUT CONTACT RATINGS IEC6255--2 Carry continuously 5A AC or DC Make & carry.5s 2A AC or DC L/R 4ms & V 3V.2s 3A AC or DC Break capacity AC resistive AC inductive 1,25VA 25VA @ PF.4 I 5A & V 3V DC resistive 75W DC inductive 3W @ L/R 4ms 5W @ L/R 1ms Minimum number of operations 1 6 at maximum load Minimum recommended load.5w limit 1mA / 5V Vx 1 3 25 23 27 Fail Healthy Alarm common Timer initiate SI1 5 7 11 13 15 Output 1 17 Remote flag reset SI2 9 1 19 21 Output 2 12 14 16 Output 3 18 2 22 Output 4 2 2T15 wiring diagram - Relay shown in de-energised condition Indicative position Size 2M28-S draw out case Drawing units: mm 14 1 2 Suits flush panel mounting & 4U high 19 inch rack frame 27 28 Front view 15 Side view Terminal layout Panel cut out 2 holes of 3.7 Due to RMS continuous product improvement policy this information is subject to change without notice. 2T15/Iss K/12/1/9-4/5

Ordering Information CASE Size 2M28-S draw out case 28 M4 screw terminals Flush panel mount or 4U high 1/8 width 19 inch rack mount ACCESSORIES SUPPLIED WITH EACH RELAY 1 x M4 self threading mounting screw kit P/N 29-46-151 1 x M4 terminal screw kit P/N 29-47-153 1 x Product Test Manual ORDER CODE The order code determines the production build in the factory & cannot be changed in the field. Generate the required order code as follows: e.g. 2T15-BAA General Type 2T15 - Order Code 1 2 3 1 AUXILIARY SUPPLY RANGE A B 2-7V DC 4-275V AC & 4-3V DC 2 TIMING RESET FUNCTION A B C Instantaneous reset Definite time reset Treset s Specify a Treset delay in the range.1 to 255s in.1s steps Count down reset 3 TRIP FLAG A Red LED non volatile trip indication (Standard) B Magnetic disc trip flag CONFIGURATION CODE (Optional specification) The configuration code can be set in the field by withdrawing the relay module & following the instructions on the side plate label. The configuration code may be specified at time of order so that the relay will be shipped from the factory pre-set to meet customer requirements. e.g. CONFIG-111 If a configuration code is not specified the factory default will be set as indicated below. i.e. CONFIG-11111 Specify factory Configuration CONFIG - Configuration Switches 1 2 3 4 5 1 STATUS INPUT OPERATION 1 ON DC operation only - AC rejection ON (Default) OFF AC / DC operation - AC rejection OFF 2 TIMER INITIATE INPUT 1 ON Apply volts to initiate (Default) OFF Remove volts to initiate 3 TIME DELAY FUNCTION 1 ON Time delay OPERATE (Default) OFF Time delay RELEASE 4 OUTPUT RELAY FUNCTION 1 ON All outputs contacts are time delayed (Default) OFF Output contact 4 will operate instantaneously irrespective of the front panel time delay settings. 5 TIME RANGE MULTIPLIER 1 ON Selected time range x1 (Default) OFF Selected time range x1 Due to RMS continuous product improvement policy this information is subject to change without notice. 2T15/Iss K/12/1/9-5/5

Australian Content Unless otherwise stated the product(s) quoted are manufactured by RMS at our production facility in Melbourne Australia. Approximately 6% of our sales volume is derived from equipment manufactured in house with a local content close to 9%. Imported components such as semi-conductors are sourced from local suppliers & preference is given for reasonable stock holding to support our build requirements. Quality Assurance RMS holds NCSI (NATA Certification Services International), registration number 6869 for the certification of a quality assurance system to AS/NZS ISO91-28. Quality plans for all products involve 1% inspection and testing carried out before despatch. Further details on specific test plans, quality policy & procedures may be found in section A4 of the RMS product catalogue. Product Packaging Protection relays are supplied in secure individual packing cardboard boxes with moulded styrene inserts suitable for recycling. Each product & packing box is labeled with the product part number, customer name & order details. Design References The products & components produced by RMS are based on many years of field experience since Relays Pty Ltd was formed in 1955. A large population of equipment is in service throughout Australia, New Zealand, South Africa & South East Asia attesting to this fact. Specific product & customer reference sites may be provided on application. Product Warranty All utility grade protection & auxiliary relay products, unless otherwise stated, are warranted for a period of 24 months from shipment for materials & labour on a return to factory basis. Repair of products damaged through poor application or circumstances outside the product ratings will be carried out at the customer s expense. Standard Conditions of Sale Unless otherwise agreed RMS Standard Terms & Conditions (QF 97) shall apply to all sales. These are available on request or from our web site. Relay Monitoring Systems Pty Ltd 6 Anzed Court, Mulgrave, Victoria 317, AUSTRALIA Tel: 61 3 8544 12 Fax: 61 3 8544 121 Email: rms@rmspl.com.au Web: www.rmspl.com.au 21 Relay Monitoring Systems Pty Ltd Due to RMS continuous product improvement policy this information is subject to change without notice.