Dual Digital Module Technical Guide

Similar documents
COND. A ENABLE RELAY CONTACT COOLA ENABLE 24 VAC. RATING IS 1 AMP COND. B ENABLE COOL B ENABLE.

USB-Link 2 Technical Guide

USB-Link 2 Technical Guide. USB-Link 2 Code: SS0073 Version 4.11 and up

UPDATING CONTROLLERS USING PRISM 2 Updating the VCB-X / VCC-X Controller

UPDATING CONTROLLERS USING PRISM 2 Updating the VCC-X Controller

Modular Service Tool SD Quick Start Guide

GPC-XP Controller Technical Guide

Factory Packaged Controls. MODGAS-X Controller Field Technical Guide

Modular System Manager SD Quick Start Guide

VAV/Zone Controller Actuator Package Technical Guide

FACTORY CONTROLS SYSTEM. VAV/CAV Controller Technical Guide

VAVBOX Controller Technical Guide

FACTORY CONTROLS SYSTEM. MUA II Controller Technical Guide

VCM-X E-BUS Component & System Wiring Technical Guide

Starzone 4000 Master Control Panel Figure 2.1 Master Control Panel

Product Manual SZ2141

ETM-2050/ETM-2051 Service Manual

System Manager TS II Technical Guide. Requires System Manager TS II Code: SS9003 Version 1.0 and up DDC Controller Code: SS9001 Version 1.

M1000 INTELLIGENT ZONE CONTROL SYSTEM

GPC Plus Controller. General Information & Application Guide

Microprocessor based Temperature / CO2 Controller c/w 365 Day Time Switch & Modbus Communication.

IP Module Technical Guide

IP Module Technical Guide

Rev Cutler-Hammer Smart Breaker Panel Control Manual

Measure & Control Temperature & CO2 levels with analog & digital I/O

FX 2 Instruction Manual

LTEC Heat Pump DDC Controller

Rev MultiFlex I/O Board Installation and Operation Manual

Rev MultiFlex PAK Compressor/ Condenser Control Board User s Guide

WSHP-IOP-2 May Installation, Operation, and Programming. Tracer ZN510 Controller

Product Manual SZ2144

IP Module Technical Guide

Prodigy Control System Premium Rooftop Unit Control

FX-2 Control Board ASY-360-XXX Setup and Configuration Guide

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

BACnet MS/TP Interface User s Guide

FCU-4 FAN COIL CONTROLLER

IP Module Technical Guide

Introduction. What is the RTU Open controller?

USB-Link 2 Technical Guide

CommLink 5 Technical Guide

FCU-4 FAN COIL CONTROLLER

Fast Route to Reliable Energy Savings ZIP Economizer

TEMPERATURE CONTROLLER 2 HEAT/ 2 COOL with Digital Room Temperature Display. Made in Australia 100% Australian Owned Company

VAV Modular Assembly (VMA) 1410/1420

CDD4 Duct Carbon Dioxide Transmitter

ESC 201. Installation and Operating Instructions Manual. SG Jan 2015

MicroTech II Vertical Self-contained Systems Unit Controller

CommLink 5 Technical Guide

HLS34 Modbus FCU/VAV Controllers installation instructions

rcc.1081 Installation Instructions

TPE 1464 Series Pressure Transducer

MicroTech Unit Ventilator Controller

PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION!

Installing VO2 Analog Output Boards

Economizer Controller Installation Guide

Temperature controller Ducted systems

LTEC Unit Ventilator DDC Controller

BA/BS4S Temperature Sensor Installation & Operating Instructions

ECON-ZIP-BASE. ZIP Economizer Base Unit. Wiring Diagram USA CANADA LATIN AMERICA / CARIBBEAN

INSTALLATION INSTRUCTIONS MBPEFY Series Mixing Box for Mitsubishi PEFY Series Units. Before Starting Installation Warning. Installation Instructions

IP Module Technical Guide

FRICK QUANTUM HD UNITY SYSTEM CONTROLLER

DUKE UNIVERSITY DESIGN & CONSTRUCTION STANDARDS

Description. descriptors, makes set-up and monitoring very user friendly.

AE R6 July 2018 Electronic Unit Controller

SEZ7656R1045B / SEZ7656H1045B

Table of Contents. RTU Open Controller

Andover ContinuumTM Infinet II

Rev CH Breaker Gateway Installation and Operation Manual

Millennium Simplicity Elite Parameter Points and Quirks

Application Engineering B U L L E T I N. AE R1 November Intelligent Store Discus V1.0 Operators Manual

Andover ContinuumTM Infinet II

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

KWIC (Kysor-Warren Interface Control) Installation and Operations Manual

SE7600E Series Application Guide

USB-Link Technical Guide

L Connection Network Control System For Energence Rooftop Units

CommandCenter Operator Panel

UNIT CONTROLLER 7 (UC7) Operation & Installation. Hydronic Units

Quick Start Guide DDC (2014/02) Subject to change without prior notice Quick Start Guide

H7625A, H7635A Humidity/Temperature Sensors

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification

CDD4 Series Room CO2 Transmitter Installation Instructions

Andover ContinuumTM Infinet II

Andover ContinuumTM. b3850 Series Terminal Controllers

SE7600E Series Application Guide

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS

Product Catalog. Tracer Controls Tracer ZN517 Unitary Control BAS-PRC012-EN. August 2010

Installation and Operation. Tracer MP501 Controller CNT-SVX08B-EN

PT-Link II N2-4 Technical Guide

QUICK START GUIDE M2000 SERIES rue Charles, Suite 100, Mirabel, QC, J7J 1X9

Pump Data Sheet - Patterson HVAC Pumps Company: Intermountain Hydron Name: Cache County Mountain Crest Date: 09/24/2018

Zone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions

Specification and Design Catalog. Waterside Economizer

DLA. DMX512 Analyzer. DLA Users Manual SV2_00 B.lwp copyright ELM Video Technology, Inc.

CDD Carbon Dioxide Transmitter

H7625B; H7635B,C; H7655B Duct-Mount and Outdoor-Mount Humidity/Temperature Sensors

Tracer Controls. Tracer ZN517 Unitary Controller BAS-PRC012-EN

Transcription:

Factory Packaged Controls Coil Products Dual Digital Module

Table of Contents OVERVIEW... 3 INSTALLATION AND WIRING... 4 Environmental Requirements...4 Mounting...4 Power Supply and Communications...4 Important Wiring Considerations...5 VCM-X Modular E-BUS Controller to Dual Digital Module Wiring...6 START-UP AND COMMISSIONING... 8 General...8 Unit Confi gurations...8 SEQUENCE OF OPERATION... 9 Off Mode...9 Cooling Mode...9 Dehumidifi cation Mode...9 Heat Pump Heating Mode (Air to Air)...9 Defrost Mode...9 Staging Delays...9 TROUBLESHOOTING... 10 Using LEDs to Verify Operation...10 LED Diagnostics...12 Other Checks...12 APPENDIX... 14 VCM-X Controller to Dual Digital Module Wiring...14 PART NUMBER CROSS REFERENCE TABLE PART DESCRIPTION ORION AAON COIL VCM-X Dual Digital Module OE370-23-DD-C 30311 VCM-X Controller OE332-23-VCMX-MOD-C 30553 VCM-X Modular E-BUS Controller OE332-23E-VCMX-C TBA VCM-X E-BUS Distribution Module OE365-23-EBD-C 30312 VCM-X Expansion Module OE333-23-EM 30308 VCM-X 12 Relay Expansion Module OE358-23-12R 30309 www.aaon.com WattMaster Controls Inc. 8500 NW River Park Drive Parkville, MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 FAX: (816) 505-1101 E-mail: mail@wattmaster.com Visit our web site at www.orioncontrols.com Copyright January 2017 WattMaster Controls, Inc. WattMaster Form : AA-DDM-TGD-01G AAON is a registered trademark of AAON, Inc., Tulsa, OK. Neither WattMaster Controls, Inc. nor AAON assumes any responsibility for errors or omissions in this document. This document is subject to change without notice.

Module Overview Overview The Dual Digital Module (OE370-23-DD-C) is a device that enables and modulates two digital compressors on HVAC Units controlled by the VCM-X Modular Controller (OE332-23-VCMX-MOD-C) or VCM-X Modular E-BUS Controller (OE332-23E-VCMX-MOD-C). The Dual Digital Module will control the digital compressors to satisfy the cooling, dehumidification, and heat pump requirements of the VCM-X Modular series controller. If the Dual Digital Module is in the Cooling Mode or Heat Pump Heating Mode, it will modulate the compressors to maintain the appropriate Supply Air Temperature Setpoint. If the module is in the Dehumidification Mode, it will modulate compressors to maintain the Coil Suction Temperature Setpoint. If the module is in the Heat Pump Heating Mode, the module can also monitor a signal for a Defrost Cycle from the VCM- X Modular series controller if a Two Condenser Head Pressure Module (OE370-23-HP2C) is also installed. The Dual Digital Module must be used in conjunction with the VCM- X Modular Controller. The Dual Digital Module is connected to the VCM-X Modular Controller using the E-BUS Distribution Module (OE365-23-EBD). The Dual Digital Module can also be directly connected to the the VCM-X Modular E-BUS Controller. Either connection allows the Dual Digital Module to receive setpoints and monitor the Supply Air Temperature from the VCM-X Modular series controller. The Dual Digital Module requires a 24 VAC power connection with an appropriate VA rating. NOTE: Software versions 1.04 or above allow two modules per HVAC unit. If using two modules, set addresses accordingly set 1st to address 1 and 2nd to address 2. Refer to wiring diagrams for address settings. NOTE: The Dual Digital Module contains no user-serviceable parts. Contact qualified technical personnel if your module is not operating correctly. Figure 1: Dual Digital Module 3

Installation and Wiring Environmental Requirements The Dual Digital Module needs to be installed in an environment which can maintain a temperature range between -30 F and 150 F and not exceed 90% RH levels (Non-Condensing). Mounting The Dual Digital Module is housed in a plastic enclosure. It is designed to be mounted by using the 3 mounting holes in the enclosure base. It is important to mount the module in a location that is free from extreme high or low temperatures, moisture, dust, and dirt. Be careful not to damage the electronic components when mounting the module. See Figure 2 for Module dimensions (in inches). Power Supply and Communications The Dual Digital Module is connected to the E-BUS Distribution Module with a modular HSSC cable to provide communications from the VCM-X Modular Controller. The E-BUS Distribution Module uses WattMaster Control s standard I 2 C modular cable to connect with the VCM-X Modular Controller, VCM-X Expansion Module, or 12-Relay Expansion Module. The Dual Digital Module can also be directly connected to the VCM-X Modular E-BUS Controller, bypassing the use of the E-BUS Distribution Module. The Dual Digital Module requires a 24 VAC power connection with an appropriate VA rating. WARNING: Observe polarity! All boards must be wired -to- and 24 VAC-to-VAC. Failure to observe polarity could result in damage to the boards. Figure 2: Dual Digital Module Dimensions 4

Installation and Wiring Important Wiring Considerations Please carefully read and apply the following information when wiring the Dual Digital Module: 1. The 1 to 5 VDC signals for the Copeland Compressor Speed need to use 18-gauge shielded twisted pair cable, and the Drain wire must be the signal. 2. All 24 VAC wiring must be connected so that all ground wires remain common. Failure to follow this procedure can result in damage to the module and connected devices. 3. All wiring is to be in accordance with local and national electrical codes and specifications. 4. Be sure that all wiring connections are properly inserted and tightened into the terminal blocks. Do not allow wire strands to stick out and touch adjoining terminals. This could potentially cause a short circuit. 5. Be sure all modular wiring harness connectors are seated firmly in their respective modular connectors on the circuit board. NOTE: The Compressor Relays on the Dual Digital Module are used rather than the relay outputs on the VCM-X Modular series controller. WARNING: Be sure all controllers and modules are powered down before connecting or disconnecting HSSC cables. OE370-23-DD-C Dual Digital Module NOTE: ALL RELAY OUTPUTS ARE NORMALLY OPEN AND RATED FOR 24 VAC POWER ONLY - 1 AMP MAXIMUM LOAD SIG 1 SIG 3 Set dipswitches to OFF if using only one module. Software versions 1.04 or above allow two modules per HVAC unit. If using two modules, set the addresses consecutively. SIG 1 SIG 2 SIG 3 SIG 4 BIN 1 BIN 2 COM ADDRESS SIG 1 SIG 2 SIG 3 SIG 4 BIN 1 BIN 2 COM Connect To E-BUS Distribution Module or VCM-X Modular E-BUS Controller PWR HSSC Cable www.orioncontrols.com OE370-23-FD FULL DIGITAL COMPRESSOR MODULE E-BUS Connector COMPRESSOR #1 NOT USED COPELAND CNTRLR P6 COPELAND CNTRLR P5 COMPRESSOR #2 NOT USED COPELAND CNTRLR P6 COPELAND CNTRLR P5 NOT USED NOT USED NOT USED WattMaster Label #LB102056 E-BUS Connector RELAY CONTACT RATING IS 1 AMP MAX @ 24 VAC COMP. #1 ENABLE R1 COMP. #2 ENABLE R2 NOT USED R3 NOT USED R4 RELAY COMMON RC COMP. #1 CNTRLR C2 COMP. #2 CNTRLR C2 COMP. #1 & #2 CNTRLR C1 AO1 AO2 +24 VAC HSSC Cable 24 VAC R1 R2 R3 R4 Rc ANALOG AO1 AO2 PWM1- PWM1+ PWM2- PWM2+ RELAYS OPTIONS ALARM STAT COMM R1 R2 R3 R4 COMM AO1 AO2 This Dip Switch Is Not Used For This Application 24 VAC Transformer 3 VA Minimum COMPRESSOR A1 ENABLE COMPRESSOR A2 ENABLE COMPRESSOR B1 ENABLE COMPRESSOR B2 ENABLE P5 P6 C1 C2 SHLD P4 EXC P3 OUT COM P2 P1 Copeland Digital Compressor Controller A1 P5 P6 SHLD EXC P4 P3 C1 C2 OUT COM P2 P1 Copeland Digital Compressor Controller B1 Line Voltage Connect To Other WattMaster-Approved E-BUS Expansion Module(s) HVAC UNIT CONNECTIONS RD WH BK RD WH BK OE275-01 Suction Pressure Transducer OE275-01 Suction Pressure Transducer WARNING!! Observe Polarity! All boards must be wired with -to- and 24 VAC-to-24 VAC. Failure to observe polarity could result in damage to the boards. Figure 3: Dual Digital E-BUS Connection Wiring 5

E-BUS Controller to Dual Digital Module Wiring VCM-X Modular E-BUS Controller to Dual Digital Module Wiring The Dual Digital Module directly connects to the VCM-X Modular E- BUS Controller using a modular HSSC cable. The Dual Digital Module requires a 24 VAC power connection with an appropriate VA rating. See Figure 4 below for wiring. Any E-BUS Module can be connected to the E-BUS Controller s E-BUS port or can be daisy-chained together using HSSC cables. NOTE: Contact Factory for the correct HSSC cable length for your application. Cables are available in ½ and 3 meter lengths and 100 and 150 foot lengths. OE370-23-DD-C Dual Digital Module SIG 1 SIG 2 R1 R2 R3 R4 Rc SIG 3 SIG 4 BIN 1 BIN 2 RELAYS ANALOG AO1 AO2 PWM1- PWM1+ PWM2- PWM2+ COM Set address switches to OFF if using only one module. Software versions 1.04 or above allow two modules per HVAC unit. If using two modules, set the 1st to address 1 and the 2nd to address 2. PWR ADDRESS 24 VAC OPTIONS ALARM STAT COMM WARNING!! Observe Polarity! All boards must be wired with -to- and 24 VACto-24 VAC. Failure to observe polarity could result in damage to the boards. Line Voltage 24 VAC Transformer 3 VA Minimum Connect To Other WattMaster-Approved E-BUS Expansion Module(s) HSSC Cable HSSC Cable Connect To VCM-X E-BUS Controller Figure 4: VCM-X Modular E-BUS Controller to Dual Digital Module Wiring Diagram 6

AI1 SET AI2 SET AI3 SET AI4 SET AI5 SET AI7 SET 2 2 Dual Digital Module E-BUS Controller to Dual Digital Module Wiring WARNING: Be sure all controllers and modules are powered down before connecting or disconnecting HSSC cables. For Stand Alone Applications, Connect To System Manager. For Network Applications Connect To Next Controller And/Or MiniLink PD On Local Loop. Local Loop RS-485 9600 Baud OE332-23E-VCMX-MOD-C VCM-X Modular E-BUS Controller Note: All Relay Outputs Are Normally Open And Rated For 24 VAC Power Only. 1 Amp Maximum Load. All Comm Loop Wiring Is Straight Thru T to T, R to R & SHLD to SHLD RS-485 COMMUNICATION LOOP. WIRE R TO R, T TO T SHLD TO SHLD www.aaon.com RELAY CONTACT RATING IS 1 AMP MAX @ 24 VAC RELAY COMMON FAN RELAY 2 RELAY 3 RELAY 4 R - 24VAC G - Fan ON/OFF Only RELAY 5 HSSC Cable Connect To VCM-X E-BUS Port See Individual Component Wiring Diagrams For Detailed Wiring Of Analog Inputs And www.orioncontrols.com VCM-X MODULAR E-BUS CONTROLLER AAON No.: Orion No.:OE332-23E-VCMX-MOD-C AI1 = SPC (SPACE TEMPERATURE SENSOR) AI2 = SAT (SUPPLY AIR TEMPERATURE SENSOR) AI3 = RAT (RETURN AIR TEMPERATURE SENSOR) AI4 = OAT (OUTDOOR AIR TEMPERATURE SENSOR) AI5 = SUCTION PRESSURE SENSOR (FROM EXP. MODULE) AI7 = SPACE TEMPERATURE SENSOR SLIDE ADJUST OR VOLTAGE RESET SOURCE A01 = ECONOMIZER (2-10 VDC OUTPUT) A02 = SUPPLY FAN VFD (0-10 VDC OUTPUT) E-BUS CONNECTOR ANALOG INPUT JUMPER LED BLINK CODES SETTINGS THERM LED NAME STATUS1 STATUS2 4-20mA AI1 0-10V NORMAL OPERATION 0 1 0-5V SAT FAIL 1 2 THERM OAT FAIL 2 2 4-20mA AI2 0-10V SPC FAIL 3 2 0-5V MODULE ALARM 4 2 THERM MECH COOL FAIL 1 3 4-20mA AI3 0-10V MECH HEAT FAIL 2 3 0-5V FAN PROOF FAIL 3 3 THERM DIRTY FILTER 4 3 4-20mA AI4 0-10V EMERGENCY SHUTDOWN 5 3 0-5V LOW SAT 1 4 THERM HIGH SAT 2 4 AI5 4-20mA CONT. TEMP COOL FAIL 3 4 0-10V 0-5V CONT. TEMP HEAT FAIL 4 4 Relay Output Contacts R2 Through R5 May Be User-Configured For The Following: 1 - Heating Stages 2 - Cooling Stages 3 - Warm-up Mode Command (VAV Boxes) 4 - Reversing Valve (Air To Air Heat Pumps) 5 - Reheat Control (Dehumidification) 6 - Exhaust Fan Interlock 7 - Preheater For Low Ambient Protection 8 - Alarm 9 - Override 10 - Occupied 11 - OA Damper 12 - Heat Wheel 13 - Emergency Heat Note: 1.) When Using the HP2C Module, All Compressors Will Be Wired From the Protection Module, Not the VCM-X Controller. Note: A Total Of 20 Relays Are Available By Adding Relay Expansion Modules. All Expansion Module Relay Outputs Are User Configurable As Listed Above. THERM PUSH BUTTON OVR 1 5 4-20mA AI7 ZONE OVR 2 5 0-10V 0-5V OUTPUT FORCE ACTIVE 0 6 ANALOG INPUT JUMPER SETTINGS 24 VAC POWER ONLY MUST BE SET AS SHOWN FOR WARNING! POLARITY MUST BE OBSERVED PROPER OPERATION OR THE CONTROLLER WILL BE DAMAGED STATIC WattMaster Label #LB102073-01-A PRESSURE Rev.: 1A IC EXPANSION IC DIGITAL SENSOR Line Voltage 24VAC Size Transformer For Correct Total Load. VCM-X Controller = 8 VA Jumpers Splice If Required OE271 Static Pressure Transducer Connect To Digital Room Sensor And/Or Digital CO2 Sensor Connect To Expansion Module(s) (When Used) Warning: 24 VAC Must Be Connected So That All Ground Wires Remain Common. Failure To Do So Will Result In Damage To The Controllers. Connect FRP Tubing To High Pressure Port (Bottom Tube) and Route To Static Pressure Pickup Probe Located In Unit Discharge. Leave Port Marked Lo Open To Atmosphere Figure 4, cont.: VCM-X E-BUS Controller to Dual Digital Module Wiring Diagram 7

Start Up and Commissioning General In order to have a trouble free start-up, it is important to follow a few simple procedures. Before applying power for the first time, it is very important to run through a few simple checks. One of the most important checks to make before powering up the system for the first time is to make sure that the VCM-X Modular or VCM-X Modular E-BUS Controller is configured properly for your application. Refer to the VCM-X Controller or VCM-X Modular E-BUS Controller for more information. A handheld Modular Service Tool, Modular System Manager, or System Manager Touch Screen connected to the VCM-X Modular or VCM-X Modular E-BUS Controller will allow you to configure your application. Refer to the VCM-X Operator s Interfaces or System Manager TS for more information. Check all wiring leads at the terminal block for tightness. Be sure that wire strands do not stick out and touch adjacent terminals. Confirm that all sensors required for your system are mounted in the appropriate location and wired into the correct terminals. WARNING: Observe polarity! All boards must be wired -to- and 24 VAC-to-VAC. Failure to observe polarity could result in damage to the boards. UNIT CONFIGURATIONS CIRCUIT A CIRCUIT B PERMUTATION Comp A1 Comp A2 Comp B1 Comp B2 HARDWARE VCM-X WSHP CONFIGURATION Relay 1 Relay 2 Relay 3 Relay 4 1 Fixed N/A Fixed N/A 2 Digital N/A Fixed N/A 3 Digital N/A Digital N/A 4 Fixed Fixed Fixed Fixed 5 Digital Fixed Fixed Fixed 6 Digital Fixed Digital Fixed Use VCM-X Modular Series Controller Only Use VCM-X Modular Series Controller Only Use VCM-X Modular Series Controller and Dual Digital Module Use VCM-X Modular Series Controller Only Use VCM-X Modular Series Controller Only Use VCM-X Modular Series Controller and Dual Digital Module 2 Compressors 2 Compressors Digital Compressor 2 Compressors Dual Digital 4 Compressors 4 Compressors Digital Compressor 4 Compressors Dual Digital Table 1: Unit Configurations Chart 8

Sequence of Operation NOTE: See Unit Configurations Chart on page 10 for more information about compressor staging. Off Mode The Dual Digital Module will be in the Off Mode when no signal is being received from the VCM-X Modular series controller to run the compressors. Cooling Mode When a Cool Signal is received, the Dual Digital Module will go into Cooling Mode. At this point, Compressor A1 will energize and modulate as necessary to maintain the Supply Air Temperature at the Active Supply Air Setpoint that is broadcast from the VCM-X Modular series controller. When Compressor A1 reaches 100%, a stage up timer is started. If Compressor A1 stays at 100% for the stage up timer, Compressor B1 will energize and both compressors will go to 50% and begin to modulate together. If there are additional fixed compressor stages and modulating Compressors A1 and B1 have modulated together up to 100%, then after a stage up delay, fixed Compressor A2 will stage on while A1/B1 go to 50% and begin to modulate from there. If A1/B1 again modulate up to 100%, then after a stage up delay, fixed compressor B2 will stage on while A1/B1 go to 50% and begin to modulate from there. Staging down will happen in the reverse order as just described if the Supply Air Temperature falls below the Supply Air Temperature Setpoint by the Cooling Stage Window value and the stage down timer has elapsed. After the fixed compressors have staged off, or if there are no fixed compressors, then the staging down of the digital compressors A1 and B1 will continue as follows. If Compressors A1/B1 modulate together down to 30% and the stage down timer elapses, Compressor B1 will deactivate and Compressors A1 will go to 60%. Compressors A1 will stage down if it is at 0% for the duration of the stage down timer. Heat Pump Heating Mode (Air to Air) Heating Mode works the same as Cooling Mode except the Reversing Valve is switched and the sequence is opposite. Compressors modulate up when below the Heating Supply Air Setpoint and modulate down when above the setpoint. Dehumidification Mode In Dehumidification Mode, the compressor(s) will modulate to maintain the Suction Pressure Temperature Setpoint broadcast from the VCM-X Modular series controller. If there are two compressors, Compressor A1 will modulate up to 100% before Compressor B1 can be energized. If Compressor B1 is energized, Compressor A1 will be locked at 100%. If there are additional fixed compressor stages and Compressor B1 has modulated up to 100%, then after a stage up delay, fixed Compressor A2 will stage on while B1 will again go to 50% and begin to modulate from there. If B1 again modulates up to 100%, then after a stage up delay, fixed compressor B2 will stage on while B1 will again go to 50% and begin to modulate from there. Stage down will again be the reverse as just described with Compressor A1 being the last compressor to stage off. Defrost Mode In Defrost Mode, if only Circuit A is energized, it will go to 100% and the reversing valve will deactivate. If both Circuit A & Circuit B are energized, they will both go to 100% and the reversing valve will be deactivated. The duration for Defrost Mode is determined by the VCM-X Modular series controller. NOTE: Defrost Mode is only available if a Two Condenser Head Pressure Module is installed. Staging Delays Staging Delays minimum run times and minimum off times are sent from the VCM-X Modular series controller. 9

Troubleshooting Using LEDs to Verify Operation The Dual Digital Module is equipped with LEDs that can be used to verify operation and perform troubleshooting. There are LEDs for communication, operation modes, and diagnostic codes. The module has seven LEDs one used for power, one used for operation status, one used for alarms, and four used for the compressor relays. See Figure 5 for the LED locations. The LEDs associated with these inputs and outputs allow you to see what is active without using a voltmeter. The LEDs and their uses are as follows: Status LEDs COMM - The COMM LED lights up to indicate Communications between the module and the VCM-X Modular series controller. If Communications are established, the COMM LED will blink. STAT - This is the status blink code LED. It will light up and every 10 seconds will blink the status mode that the module is currently operating under. See Table 3 for Status Blink Code code descriptions. The blink code descriptions are also located on the module s front cover. No. of Blinks Status 1 Off Mode 2 Cool Mode 3 Heat Mode 4 Dehumidify Mode 5 Defrost Mode Table 3: STAT LED Blink Codes ALARM - This is the diagnostic blink code LED. It will light up and blink out diagnostic codes. See Table 2 for Diagnostic Blink Code descriptions. The blink code descriptions are also located on the module s front cover. No. of Blinks Status 0 No Problems 1 Low Suction Pressure Compressor A1 3 Low Suction Pressure Compressor B1 5 Pressure Sensor A1 Not Detected 7 Pressure Sensor B1 Not Detected 9 No Communication Table 2: ALARM LED Blink Codes 10

Troubleshooting Compressor LEDs R1 - This LED will light up when Compressor A1 is enabled and will stay lit as long as Compressor A1 is active. R2 - This LED will light up when Compressor A2 is enabled and will stay lit as long as Compressor A2 is active. R3 - This LED will light up when Compressor B1 is enabled and will stay lit as long as Compressor B1 is active. R4 - This LED will light up when Compressor B2 is enabled and will stay lit as long as Compressor B2 is active. Figure 5: LED Locations 11

Troubleshooting LED Diagnostics PWR LED: When the Dual Digital Module is powered up, the PWR LED (located below the address switches) should light up and stay on continuously. If it does not light up, check to be sure that the power wiring is connected to the board, the connections are tight, and the VCM-X Modular series controller is powered. If after making all these checks, the PWR LED does not light up, the module is probably defective. Other Checks NOTE: The Dual Digital Module contains no user-serviceable parts. Contact qualified technical personnel if your module is not operating correctly. COMM LED: The COMM LED lights up to indicate Communications between the module and the VCM-X Modular series controller. If the COMM LED does not blink, then communications have not been established. Check the connection between the VCM-X Modular Controller, the VCM-X Modular E-BUS Controller, the E-BUS Distribution Module, and the Dual Digital Module. STAT LED: As previously described, this LED will blink out the operation mode that the Dual Digital Module is operating under. When the board is first powered up, the STAT LED will do the following: Light up Blink out status code every ten seconds to indicate controller status ALARM LED: As previously described, this LED will blink on and off to indicate alarms and diagnostics. 12

Troubleshooting OE275-01 Suction Pressure Transducer Testing for R410A Refrigerant The Evaporator Coil Temperature is calculated by converting the Suction Pressure to Temperature. The Suction Pressure is obtained by using the OE275-01 Suction Pressure Transducer, which is connected into the Suction Line of the Compressor. Use the voltage column to check the Suction Pressure Transducer while connected to the Dual Digital Module. Read voltage with a meter set on DC volts. If the temperature/voltage or pressure/voltage readings do not align closely with the chart, your Suction Pressure Transducer is probably defective and will need to be replaced. See the OE275-01 Suction Pressure Transducer, Pressure, Temperature, and Voltage Chart for R410A Refrigerant testing (Table 4). The chart shows a temperature range from 20 F to 80 F. For troubleshooting purposes, the DC Voltage readings are also listed with their corresponding temperatures and pressures. OE275-01 Suction Pressure Transducer Coil Pressure Temperature Voltage Chart for R410A Refrigerant Temperature F Pressure PSI Signal DC Volts Temperature F Pressure PSI Signal DC Volts 21.19 80.94 1.8 59.03 168.10 3.2 24.49 87.16 1.9 61.17 174.32 3.3 27.80 93.39 2.0 63.19 180.55 3.4 30.99 99.62 2.1 65.21 186.78 3.5 33.89 105.84 2.2 67.23 193.00 3.6 36.80 112.07 2.3 69.24 199.23 3.7 39.71 118.29 2.4 71.15 205.46 3.8 42.30 124.52 2.5 72.95 211.68 3.9 44.85 130.75 2.6 74.76 217.91 4.0 47.39 136.97 2.7 76.57 224.14 4.1 49.94 143.2 2.8 78.37 230.36 4.2 52.23 149.42 2.9 80.18 236.59 4.3 54.50 155.65 3.0 56.76 161.88 3.1 Table 4: Coil Pressure/Voltage/Temp for OE275-01 Suction Pressure Transducers - R410A Refrigerant 13

AI1 SET AI2 SET AI3 SET AI4 SET AI5 SET AI7 SET AI1 SET AI2 SET AI3 SET AI4 SET AI5 SET AI7 SET Dual Digital Module Appendix VCM-X Modular Controller to Dual Digital Module Wiring When using the VCM-X Modular Controller, the E-BUS Distribution Module is required to connect to the Dual Digital Module. The Dual Digital Module connects to the E-BUS Distribution Module using a modular HSSC cable. The Dual Digital Module requires a 24 VAC power connection with an appropriate VA rating. The E-BUS Distribution Module connects to the VCM-X Modular Controller, VCM-X Expansion Module, or 12 Relay Expansion Module using the I 2 C port. See Figure 6 below for wiring. Any E-BUS module can be connected to each of the four E-BUS Distribution Module s output ports or can be daisy-chained together using HSSC cables. If using a spliced terminal connection for longer runs, one module can be connected to the E-BUS Distribution Module and any additional modules would be daisy-chained to the first module. For more information, refer to the E-BUS Distribution Module. For Stand Alone Applications, Connect To System Manager. For Network Applications Connect To Next Controller And/Or MiniLink PD On Local Loop. Local Loop RS-485 9600 Baud All Comm Loop Wiring Is Straight Thru T to T, R to R & SHLD to SHLD OE332-23-VCMX-MOD-C VCM-X Modular Controller Note: All Relay Outputs Are Normally Open And Rated For 24 VAC Power Only. 1 Amp Maximum Load. R - 24VAC G - Fan ON/OFF Only See Individual Component Wiring Diagrams For Detailed Wiring Of Analog Inputs And Outputs AI1 AI2 AI3 AI4 AI5 AI7 Relay Output Contacts R2 Through R5 May Be User-Configured For The Following: 1 - Heating Stages 2 - See Note 1 Below 3 - Warm-up Mode Command (VAV Boxes) 4 - Reversing Valve (Air To Air Heat Pumps) 5 - Reheat Control (Dehumidification) 6 - Exhaust Fan Interlock 7 - Preheater For Low Ambient Protection 8 - Alarm 9 - Override 10 - Occupied 11 - OA Damper 12 - Heat Wheel 13 - Emergency Heat Note: 1.) When Using the HP2C Module, All Compressors Will Be Wired From the Protection Module, Not the VCM-X Controller. 2.) A Total Of 20 Relays Are Available By Adding Relay Expansion Modules. All Expansion Module Relay Outputs Are User- Configurable As Listed Above. 24 VAC Line Voltage 24VAC Size Transformer For Correct Total Load. VCM-X Controller = 8 VA Connect To E-BUS Distribution Module Jumpers Splice If Required Connect To Digital Room Sensor And/Or Digital CO2 Sensor Line Voltage OE271 Static Pressure Transducer Connect FRP Tubing To High Pressure Port (Bottom Tube) and Route To Static Pressure Pickup Probe Located In Unit Discharge. Leave Port Marked Lo Open To Atmosphere Connect To E-BUS Distribution Module or Expansion Module(s) (When Used) Warning: 24 VAC Must Be Connected So That All Ground Wires Remain Common. Failure To Do So Will Result In Damage To The Controllers. Figure 6: VCM-X Modular Controller Connection to Dual Digital Module 14

485 DRV PWR ALARM STAT COMM Dual Digital Module Appendix NOTE: Contact Factory for the correct HSSC cable length for your application. Cables are available in ½ and 3 meter lengths and 100 and 150 foot lengths. WARNING: Be sure all controllers and modules are powered down before connecting or disconnecting HSSC cables. OE365-23-EBD E-BUS Distribution Module OE370-23-DD-C Dual Digital Module YS102308 REV 1 I2C TO COMM DIST. BOARD OUTPUT +COMM SHLD -COMM +VDC INPUT +COMM SHLD -COMM SIG 1 SIG 2 SIG 3 SIG 4 BIN 1 BIN 2 R1 R2 R3 R4 Rc RELAYS ANALOG AO1 AO2 PWM1- PWM1+ PWM2- PWM2+ COM PWR 24VAC WARNING!! Observe Polarity! All boards must be wired with -to- and 24 VACto-24 VAC. Failure to observe polarity could result in damage to the boards. Modular Cable Connect To VCM-X Modular Controller Set address switches to OFF if using only one module. Software versions 1.04 or above allow two modules per HVAC unit. If using two modules, set the 1st to address 1 and the 2nd to address 2. ADDRESS HSSC Cable Connect To E-BUS Distribution Module 24 VAC HSSC Cable Connect To Other WattMaster-Approved E-BUS Expansion Module(s) OPTIONS 24 VAC Transformer 3 VA Minimum WARNING!! Observe Polarity! All boards must be wired with -to- and 24 VAC-to-24 VAC. Failure to observe polarity could result in damage to the boards. Line Voltage Figure 6: VCM-X Modular Controller Connection to Dual Digital Module 15

www.aaon.com AAON Coil Products 203 Gum Springs Road Longview, TX 75602-1721 Ph: (903) 236-4403 Fax: (903) 236-4463 WattMaster Manual Form No: AA-DDM-TGD-01G