SIPROTEC 5 Application Note

Similar documents
SIPROTEC 5 Application Note

SIPROTEC 5 Application Note

SIPROTEC 5 Application Note

SIPROTEC 5 Application Note

SIPROTEC 5 Application. SIP5-APN-027: Change of switching authority via function keys.

SIPROTEC 5 Application Note

SIPROTEC 5 Application Note

SIPROTEC 5 Application Note

SIPROTEC 5 Application Note

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities.

SIPROTEC 5 Application Note. Breaker-and-a-half solutions. SIP5-APN-002, Edition 2.

SIPROTEC 7SC805. Merging Unit for conventional instrument transformer. Products for digital substations.

Extension of BI/BO for busbar protection SIPROTEC 7SS85

Answers for energy. SIPROTEC 5 the new benchmark for protection, automation, and monitoring of transmission grids

Perfect protection smallest space

Go beyond... IEC Leverage the full potential with leading-edge expertise. Answers for infrastructure and cities.

Perfect protection smallest space

/ sicam SICAM CMIC The smart cube for your distribution network Answers for infrastructure and cities.

Recloser Controller for feeder protection and automation siemens.com/distribution-automation

SIPROTEC 5 V7.8 Protection, automation and monitoring for digital substations

SICAM AK 3. Flexible automation for all applications. Automation, telecontrol and communication for large data volume.

Easily configurable HMI system for power automation siemens.com/sicam

SIPROTEC 5 Protection, automation, and monitoring

Product Families and Positioning. Protection Portfolio

Change setting groups via CFC.

Products for digital substations SIPROTEC 6MU805. Merging Unit for conventional instrument transformer. Integrated PRP, HSR. siemens.

Siprotec 7ST61 / 7ST63

Voltage Control of Transformers in Parallel Operation

SICAM ertu Your Entry to Telecontrol Technology with Extended Functionality

SIPROTEC 5 Engineering Guide DIGSI 5

Always an eye to security

Substation to substation (ss2ss) GOOSE exchange for critical relay operations

SIPROTEC Overcurrent Protection 7SJ80. Motor Protection 7SK80. Preface. Content. Data in the PROFINET IO Mapping 1. Standard Mapping

SIPROTEC 5 New features of V7.5

SICAM A8000 Series. Operation, telecontrol, and automation in the smallest spaces. siemens.com/sicam-a8000

Voltage control of transformers in parallel operation.

SIPROTEC 5 Devices Protection, Automation and Monitoring

Compact Telecontrol System TM 1703 mic. SICAM 1703 flexible for all applications. Answers for energy.

DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830

RelaySimTest. Software for system-based protection testing

Secure energy supply Energy Automation for Infrastructure and Functional Buildings

Siemens AG All rights reserved.

Reliable and precise control over electrical systems and power

Automation Unit TM 1703 ACP. SICAM 1703 flexible for all applications. Answers for energy.

Protective Relays & SCADA Systems

Communication in Substations with IEC Simple Communication Test with IEC Johannes Bruss, Siemens AG, E D EA PRO LM Siemens AG 2008

SIMEAS SAFIR The network quality system

SENTRON 3VL Molded Case Circuit Breakers

Time synchronization via IEE 1588

ALPHA AS NF Universal Modular Distribution Boards

Digital Substation Unrestricted Siemens AG 2017 siemens.com/digital-substation

Applications & Tools. SINAMICS G/S: Commissioningsupport scripts for SINAMICS drives. SINAMICS commissioning auxiliary scripts

UPGRADE AND APPLICATION OF AUTOMATION SYSTEM IN T.S. 110/35/10 KV PETROVEC

5SL Miniature Circuit Breakers

09/2014 SINAMICS G/S: HMI

SIMEAS Q80 quality recorder: Voltage quality starts with measurement.

A full range of monitoring solutions for surge arresters

AUTOMATED TESTING OF BUSBAR DIFFERENTIAL PROTECTION USING A SYSTEM-BASED APPROACH. Christopher Pritchard, Florian Fink

Protection, Monitoring, and Control System for Distribution Substations ALARM HISTORY SYSTEM COMM. On-Line Documentation TRANSFORMER 12 MW

siemens.com/energy/transformers FITformer REG The adaptable distribution transformer Answers for energy.

THE INTEGRATED TESTING SOLUTION

IDS SAS. Station Automation System for Complex Applications

New Functions and Integrated Communication Capability. The new SENTRON 3VL ETUs SENTRON 3VL. Answers for industry.

HiPath Description. We are now Unify.

The innovative interface for the last few meters to the process

SICAM SICAM FCM Configurator

The complete application guide to specifying a Smart-Gear power distribution solution (PDS) E50001-F710-A123-V1-4A00. Answers for energy.

Miniature circuit breakers for all applications

Medium-Voltage Drive SINAMICS SM150. Type 6SL3845. Tests carried out on drives This documentation pertains to SM150 wassergekühlt G20 F03 F72 F79 F76

A full range of monitoring solutions for surge arresters Answers for energy.

Comprehensive Cyber Security Features in SIPROTEC & SICAM. SIPROTEC Dag 11. Mei 2017

SINAUT ST7. SINAUT ST7cc Control Center A I. Manual. Introduction to ST7cc. Installation. Preparation. Working with ST7cc Config

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Power systems 5: Protection

PROTECTION, AUTOMATION & CONTROL

Blueprint Data Center

Substation Automation Products. Line differential protection RED670 Relion 670 series

SIPROTEC 4 7SS52 Distributed Numerical Busbar and Breaker Failure Protection

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

SIMEAS SAFIR The network quality system: Know your network quality avoid faults minimize downtime

Effective commissioning of bus bar protection systems using a dynamic simulation in the field

Utility Implements Communications- Assisted Special Protection and Control Schemes for Distribution Substations

SIPROTEC. Numerical Overhead Contact Line Protection for AC Traction Power Supply 7ST6. Preface. Introduction 1. Functions 2

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Catalog Edition 6 siemens.com/protection

Digital Grid Products At a Glance Protection, Substation Automation, Power Quality

ThermoSecure medical equipment GmbH

DMM R2 PMD R2 System requirements

Setting up a secure VPN Connection between SCALANCE S and CP x43-1 Adv. Using a static IP Address. SCALANCE S, CP Advanced, CP Advanced

Power Products. Protection and Control IED Manager PCM600 Product Guide

Reyrolle Protection Devices. 7SG21 DDB20 Multi Range Digital Setting Time Delay Relay. Energy Management

Miniature Circuit Breakers for Railway Applications

Accessories / 7XV5662

Yukon Visual T&D HMI/SCADA

Lecture 5 Substation Automation Systems. Course map

Secure energy supply. Energy Automation for the Semiconductor Industry

Block for SIMOTION SCOUT for Monitoring 24V-Branches

Easy, efficient and always up to date the SIRIUS modular system

Maximize protection. Sepam series 10, 20, 40, 60, 80. Modular range of digital protection relays

SIRIUS Overload Relays. SIRIUS 3RB24 Solid-State Overload Relays with Complete Starter Functionality via IO-Link

Transcription:

www.siemens.com/protection SIPROTEC 5 Application Note SIP5-APN-010: Answers for infrastructure and cities.

SIPROTEC 5 - Application: SIP5-APN-010 SIPROTEC 5 Application Content 1 Application 3 1.1 Summary 3 1.2 The task: protection of a line feeder 3 1.3 Mapping reality in DIGSI 5 4 1.4 Selecting and creating the devices for protection 5 1.5 Which device protects what? 6 1.6 Communication 7 1.7 Setting the protection parameters 8 1.8 Routing the signals 9 1.9 Loading the parameter sets into the protection devices 10 1.10 Reuse made easy 10 1.11 Conclusion 10 SIP5-APN-010 2

1 Application 1.1 Summary DIGSI 5 is the powerful engineering tool for system and device engineering. It encompasses configuration, testing, commissioning and operation of SIPROTEC 5 protection devices. It has been tailored to your workflows and supports you with all aspects of their implementation. This description introduces you to the implementation of a typical scenario. 1.2 The task: protection of a line feeder This article highlights how you can protect a feeder of a double busbar system in few steps using a line protection device (7SL87) as main protection 1 and a distance protection device (7SA87) as main protection 2. This example demonstrates the capabilities of DIGSI 5 and therefore does not go into the details of setting the protection parameters of the two devices. Let us begin with a single-line diagram. You probably have a similar diagram as that shown in the following picture in a CAD system (at least the single-line part without the devices): Busbar 1 Busbar 2 QB1 QB2 87L 21 59 Main 1 QA 79 51BF 50/51 (N)* E1.1 E1.2 21 85 59 Main 2 QB 79 51BF 50/51 (N)* 67N *: emergency function Figure 1: a single-line diagram as displayed for instance in ELCAD 3 SIP5-APN-010

Application Legend: 87L = line differential protection 21 = distance protection 59 = overvoltage protection 67N = directional ground current protection 79 = automatic reclosing 51BF = circuit-breaker failure protection 50/51 (N) = time-overcurrent protection When designing the protection system, the modular structure of SIPROTEC 5 is used and several functions (e.g. 21, 59) are activated redundantly in both devices. 1.3 Mapping reality in DIGSI 5 First create a new project in DIGSI 5. The tree on the left side subsequently shows the structure of the project. It reflects the steps required to parameterize protection devices. In our case, we will begin by describing the primary topology of the entire system in the single-line editor. If you do not want to create the diagram manually, select one of the following options: Use a primary topology that is already available in ELCAD. Import a topology from a SCD/SSD file. Use one of the multiple single-line templates from the library for frequent application cases. In our example, select "Single-Line-Template" and drag the protection template "Doppelsammelschienen- Leitungsabzweig" from the library on the right-hand side and drop it on the drawing area. If you specify the properties of the primary elements (e.g. current transformer rated current), you save yourself much setting effort later on, as these settings can be synchronized with the connected devices. Other possible primary data include for instance the voltage level, the values of current and voltage transformers or the cable data. SIP5-APN-010 4

Figure 2: The single-line editor allows you to map your system topology 1.4 Selecting and creating the devices for protection Select "Add new device" to create a new device of the type 7SL87 with the desired functional scope (4 current inputs, 16 LEDs, small display and one Ethernet communication module). All you need for this purpose is the order number which is indicated in the order configurator for example. There you can also tailor the protection device to your own requirements. To create the device, you have to select an application template. You thus obtain a device that has the correct functional scope and is nearly ready for use. In our case, we select the application template "Freileitung mit starr geerdetem Sternpunkt" for the 7SL87. If the application template does not fully meet your requirements, you can easily customize it. Add additional functions from the library on the right-hand side by dragging & dropping. This enables you to add individual function blocks to the devices (e.g. stages), functions (detection of power swings, automatic reclosing, circuit-breaker failure protection...) or entire function groups. The application template we selected contains all functions except for the overvoltage protection which you have to drag from the library into the device for this purpose. Proceed in the same manner for the 7SA87 and create the device. 5 SIP5-APN-010

Application 1.5 Which device protects what? In the single-line editor the devices are connected to the primary system. To do so, graphically connect the current inputs and voltage inputs of the protection devices with the current transformers and voltage transformer. You also define in the graphic which circuit breaker is tripped by the protection device. The connections now enable you to transfer the topology settings you have made into the connected protection devices where you can keep them synchronous. Figure 3: Connections create a relationship between the primary topology and the device SIP5-APN-010 6

1.6 Communication SIPROTEC 5 Application The protection devices must also be capable of communicating with a substation automation system or a control center. For this purpose, we already equipped them with a communication module when creating them. In the "Hardware and protocols" editor you can add new communication modules and set their communication parameters. Figure 4: The communication parameters are set in the hardware configuration. 7 SIP5-APN-010

Application 1.7 Setting the protection parameters DIGSI 5 allows you to enter protection parameters in the parameter editor quickly and in a clearly structured way while checking their consistency. Any inconsistencies are displayed immediately. The zone settings are particularly important for the distance protection. And since you want the device to perform automatic reclosing, you have to specify them no other settings are necessary to complete the application. All other settings have already been taken over from the primary topology. The setting values, in our case e.g. the zone settings, are also displayed graphically as zone diagrams so that you can visually verify that you have entered all settings correctly. Figure 5: DIGSI 5 allows you to easily enter protection parameters showing them simultaneously in a diagram. SIP5-APN-010 8

1.8 Routing the signals SIPROTEC 5 Application In the information routing editor all information items are routed to the corresponding sources and destinations. This includes for instance alarm signals and tripping signals which must be connected to binary outputs to enable them to control the circuit breaker. Furthermore, you need the SEND signals for protection signal transmission (distance protection and ground fault protection). It also makes sense to route the selected pickup indication to LEDs. This gives you a quick overview of the incoming signals. Figure 6: Routing signals to sources and destinations 9 SIP5-APN-010

Application 1.9 Loading the parameter sets into the protection devices If all settings have been made and all signals been linked, all that remains to be done is load the parameter sets into the protection devices. You can connect the devices to the DIGSI 5 engineering computer via USB or address them via Ethernet. The latter case requires the IP addresses to be assigned to the devices. When loading via Ethernet, you can update all connected devices at once. In our case, both devices are updated and are ready for operation. 1.10 Reuse made easy If you need additional identical devices with the same functional scope, e.g. to protect additional feeders, just copy a fully configured device and insert the copy into the project. All settings or function expansions already made are thus taken over in a convenient way. The open interfaces of DIGSI 5 enable you to provide all relevant data to other systems where you can reuse them straight away. For example, it is easy to take over the communication settings, indication lists and even topology information into SICAM PAS. You can also connect your own system landscape using documented exchange formats like TEAX to optimally import the data into your systems, e.g. to archive device parameterizations, system documentation, generate or control test cases and many more applications. 1.11 Conclusion DIGSI 5 is fully tailored to your workflow and optimally supports you with all aspects of your work. The consistent reuse option is only one of countless tools that allow you to configure protection devices quickly and efficiently, to test and commission them. But support for DIGSI 5 does not stop here, because the engineering tool is designed to support your workflows in a comprehensive way. Use DIGSI 5 and see for yourself how efficient DIGSI 5 supports you with your other tasks, too, such as testing and commissioning. SIP5-APN-010 10

11 SIP5-APN-010

Fehler! Verweisquelle konnte nicht gefunden werden. Published by and copyright 2013: Siemens AG Infrastructure & Cities Sector Smart Grid Division Humboldtstr. 59 90459 Nuremberg, Germany Siemens AG Infrastructure & Cities Sector Smart Grid Division Energy Automation Humboldtstr. 59 90459 Nuremberg, Germany www.siemens.com/protection Printed on elementary chlorine-free bleached paper. All rights reserved. If not stated otherwise on the individual pages of this catalog, we reserve the right to include modifications, especially regarding the stated values, dimensions and weights. Drawings are not binding. All product designations used are trademarks or product names of Siemens AG or other suppliers. If not stated otherwise, all dimensions in this catalog are given in mm. Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract. For more information, please contact our Customer Support Center. Tel.: +49 180 524 8437 Fax: +49 180 524 24 71 (Charges depending on provider) E-mail: support.ic@siemens.com Application note: SIP5-APN-010 SIP5-APN-010 12