SYSTIMAX GigaSPEED Xpress Solution Design Guidelines

Similar documents
InstaPATCH Cu Cabling Solutions for Data Centers

The six major components of a structured wiring system are:

Telecommunications Structured Cabling Systems

Bonding and grounding NETCONNECT copper cabling systems

f) Telecommunications Equipment Rooms

Fiber Backbone Cabling in Buildings

Siemon PON Fiber Cabling Solutions

Communications. UNM IT/Telecommunications Guide Specification Communications

Industry Standards in ICT Enabled Projects Reading and Applying the "Fine Print"

SPECIFICATION STANDARD COPPER RISER AND INTRABUILDING CABLING

COMMON WORK RESULTS FOR COMMUNICATIONS

SECTION COMMON WORK RESULTS FOR COMMUNICATIONS

Implementation considerations for cabling supporting remote powering

Los Angeles Community College District Design Standards

Government of Prince Edward Island Structured Cabling Standards August 24, 2009

Anixter Standards Reference Guide

A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

E. Numbering and Labeling Pathway components. In general, pathway components are not labeled.

NGEAB-T Use Cases. Berlin, Germany February Chris DiMinico MC Communications/Panduit

ANSI/TIA/EIA-568-B Cabling Standard NOTE

Qualified Partner Programme QPP. Installation Practice Felice Guarna Wetzikon, July 2001

Universal connectivity grid design guide

SYSTIMAX Solutions. GigaSPEED Xpress. Solution Guide.

With the publication. Make the right connection: Bonding a shielded system. installation

ANSI/TIA/EIA-568-B Cabling Standard

Tarleton State University. Specifications

Copper Cabling Standards

Fiber backbone cabling in buildings

CommScope and Cisco - The ideal connectivity system for multilayer directors

Office of the Chief Information Officer Technical Note: IT-960-TN14 Effective: 05/25/2006 Last Revised: 02/17/2012 Issuing Office: OCIO

Cabling a Data Center to TIA-942 Standard

Computer Network Design Guide Existing Systems 1 / 6

Introduction to Key Principles of Telecommunications Cabling

Standards Update. Mylaraiah J N, RCDD Member, BICSI India Steering Committee

Data Center Design and the ANSI/TIA-942 Standard

Anticipating Cat 8 Agenda. Cat 8 Overview Cat 8 Customer Design Considerations Testing Procedures and Standards

ANSI/TIA/EIA-568-B Cabling Standard

ANSI/BICSI , Information Transport Systems Design Standard for K-12 Educational Institutions

Application Note. Data Center Standards and Layouts

Classroom WiFi Network Infrastructure Plan

SYSTIMAX 360 Product Guide

STANDARDS REFERENCE GUIDE ANIXTER anixter.com. Products. Technology. Services. Delivered Globally.

Cable Sharing: An ANSI & ISO Recognized Solution for High Density, Low-Speed Applications. Robert Y. Faber Jr., RCDD/NTS.

The University of Texas at Austin July 30, 2014 SECTION COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS

Laying the groundwork for a new level of Power over Ethernet

TIA/EIA 568A Sub-system HORIZONTAL CABLING

Copper Riser And Intrabuilding Cabling

Structured Cabling Guidelines For The State Of Oregon

COMPUTER NETWORK WIRING SYSTEMS FOR PLCs

REFERENCE T3 R3 T2 R1 T1 R2 T4 R4 WHT GRN T2 R2 T3 R1 T1 R3 T4 R4 WHT

FTTE Revisited for New Technologies

The SYSTIMAX GigaSPEED X10D solution. The infrastructure modern enterprises and data centers depend on

NZQA registered unit standard version 2 Page 1 of 7. Demonstrate basic knowledge of electronic security data protocols and cabling

History of Standards

Structured Cabling Guidelines

SYSTIMAX SCS Power Sum Solution

Atras Network Communications

AMP ACT 1 INSTALLING PREMISES CABLING SYSTEM. Welcome!!! Instructor : Nicholas Yeo

Certification for 10G copper cabling

Structured Cabling Supplement

Laying the groundwork for a new level of Power over Ethernet

ANSI/TIA-568-C Cat 6A Field Test Specifications

The advantages of the 6-connector channel

The Riser as a Contract Document. Peter Sharp, RCDD

Cat.8 Shielded Field Termination Plug Description

Network Construction Guide Specification Telecommunications Infrastructure Standards V 2.6

Wirewerks Datacenters Becoming More Common in Our Workplace, Next Step Solution

SYSTIMAX Rack and Cabinet Solution

Power Over Ethernet with Panduit Copper Cabling. How To Create More Meaningful Connections With The Highest Performing Infrastructure

ANSI/TIA-568-C Cat 6 Field Test Specifications

1 of 5 12/31/2008 8:41 AM

IBDN 110 Cross-Connect System

Target Interface / Construction Compliance Inspection Checklist

SPECIFICATION STANDARD

Optical Fiber Premises Standards News & Trends

Cat.8 Shielded Keystone Jack Description

Communication

Appendix D. EMC Installation Guidelines. Safety Considerations. Ferrite Absorbers and P-Clips. General Product Philosophy

Family of Cords SYSTIMAX. Structured Cabling Systems. Quality Stranded and Solid Cords That Connect Data and Voice Circuits

Copper Cabling from 10G to 400G, and back down to 10Mbps, but on 1 pair only

Optimization and Speed: Two Critical Standards Enabling Next Generation Networks. Stephanie Montgomery, TIA Brett Lane, Panduit

PANGEN INDUSTRIAL AUTOMATION SYSTEM WARRANTY

Field-testing procedure of. LANmark-6 10G. Cabling System. Technical Paper Nexans Cabling Solutions June Revision 1.4

Peter Sharp RCDD IBI Group

STRUCTURED CABLING GUIDELINES. for PALM BEACH STATE COLLEGE

The SYSTIMAX GigaSPEED X10D solution. The infrastructure modern enterprises and data centers depend on

CERTIFICATION PLUS SM

Passive Infrastructure Technical Specification. Version 1 / March 14

SYSTIMAX 360 PATCHMAX Modular Panel Instructions

Master Format Division 27 - Communications

Fiber Design for 1 Gigabit and 10 Gigabit Campus Backbone Applications

Enterprise Network Test Strategies for Network Availability and Performance. A Sitaramaiah Director Fluke Networks India

or go home GO SMALL SEPTEMBER 2015 FOR PROFESSIONALS MANAGING THE CABLE AND WIRELESS SYSTEMS THAT ENABLE CRITICAL COMMUNICATIONS STANDARDS

DATA CENTER CABLING DESIGN FUNDAMENTALS

Cabling to support ac and beyond. Nate Herring Sr. Product Manager Hubbell Premise Wiring

v2.5 was updated May 10, v2.6 is an updated copy from March 1, 2017.

Element Z General Design Requirements Owner Standards and Other Requirements

Ethernet and PoE Operation Over Single Pair Twisted-Pair Copper Cabling (SPE) Chris DiMinico AEM Technical Sales Test and Measurement

SYSTIMAX GS3 and 1100GS6 Evolve Modular Panel Instructions

DESIGN & SPECIFICATION GUIDE

Transcription:

Design Guidelines Issue 2 August 2010

Contents 1.0 Overview 3 2.0 Power Separation 4 3.0 Bonding and Grounding 4 4.0 Administration and Labeling 5 5.0 General Cable Guidelines 5 6.0 Bundling and Alien Crosstalk 6 7.0 Fill Guidelines 7 8.0 Faceplate, Boxes and the GigaSPEED Xpress Cables 7 9.0 GigaSPEED Xpress Cable Installation Alongside Other Cabling 8 10.0 Cable/Cord Distance 8 11.0 Work Area Channel Models 9 12.0 Data Center Computer Rooms 13 13.0 Data Center Channel Models 14 2

1.0 Overview The SYSTIMAX GigaSPEED Xpress Solution is a 500MHz UTP copper Solution guaranteed to support IEEE 10GBASE-T for up to 60 meters with unparalleled design freedom and space savings making it ideal for Data Center applications. Some highlights of the GigaSPEED Xpress Solution include: Supports 10GBASE-T operation for up to 60 meters and 4 connections with no mitigation required for alien crosstalk suppression Guaranteed performance up to 500MHz Exceeds IEEE 802.3an Link Segment Specifications (Section 55.7), TIA TSB155 and ISO TR24750 Category 6 UTP size profile No 15 meter rule or minimum length requirement on cables and cords The flexibility of channel configurations comparable to the SYSTIMAX GigaSPEED XL Solution Excellent fit for Data Center environment The GigaSPEED Xpress Solution includes the following components: 88 Series Cables (1088B/2088B/3088B) GSXP Patch Cords MGS500 Information Outlets 1100GS5 Panels PATCHMAX GS5 Panels VisiPatch 360 system M2000, M2100, M3000 and M3600 Modular Patch Panels Additional information for design purposes can be found in the following documents: SYSTIMAX Performance Specification IEEE 802.3an 10GBASE-T standard Telecommunications cabling and associated standards published by organizations such as the American National Standards Institute /Telecommunications Industry Association/Electronic Industries Association (ANSI/TIA/EIA; e.g., EIA-568-B.1, 569-B, ANSI/TIA/-942, TSB-155), International Standardization Organization /International Electrotechnical Commission (ISO/IEC; e.g., ISO/IEC IS 11801, TR24750), and Comite Europeen de Normalisation Electrotechnique (CENELEC; e.g., EN 50173 and EN 50174 series). National and local codes such as the National Electrical Code (NEC), or equivalent documents. BICSI Telecommunications Distribution Methods Manual This set of guidelines supports copper cabling solutions that conform to existing architectures, The SYSTIMAX 20-year Extended Product Warranty and Application Assurance program provides coverage to cabling installations that conform to this guide and the SYSTIMAX Performance Specifications. These guidelines also include: The standards defined architecture for the horizontal channel and permanent link Design options for SYSTIMAX components used within the channel Information on software tools for cable design and administration 3

2.0 Power Separation Refer to the SYSTIMAX PowerSUM, GigaSPEED XL and GigaSPEED X10D Cabling Design Guidelines for power separation guidelines. ANSI/TIA/EIA-942 has Data Center guidelines that should also be followed. Always check with applicable codes and standards, and consult with authorities having jurisdiction before submitting final designs. Applicable local or national safety regulations take precedence whenever their required separation distances are larger or other requirements conflict with those specified in this document. For example: In the UK, BS 6701 and BS 7671 In the USA, NEC In Europe, EN 50174-2 3.0 Bonding and Grounding Always check with applicable codes and standards, and consult with authorities having jurisdiction before submitting final designs. Applicable local or national safety regulations take precedence whenever their requirements conflict with those specified in this document. The proper bonding and grounding of the telecommunications cabling, pathways, equipment, and connecting hardware is critical to achieve optimal cabling performance, reduce electromagnetic interference (EMI), protect equipment, and maintain safety for building occupants and maintenance personnel. Refer to the ANSI-J-STD-607-A-2002 and ISO/IEC 60364 for accepted industry practices. Requirements for grounding and bonding include: A ground reference for telecommunications and equipment within the telecommunications entrance facility (EF), telecommunications rooms (TR), and equipment rooms (ER), and at all equipment locations and racks within a Computer Room. Bonding and connecting cable pathways, cabling, and connecting hardware at the TRs, ERs, and EF. Ground and bond backbone cables at both ends. The telecommunications grounding and bonding infrastructure also has interconnectivity to other building grounding systems (e.g., electrical, water piping, lightning protection) and is also bonded to the metal framework of a building. The primary components of a telecommunications grounding and bonding infrastructure include: Telecommunications Main Grounding Busbar (TMGB) located at the telecommunications EF and connected to the electrical EF or building grounding electrode system. Telecommunications Bonding Backbone (TBB) ties TMGB to TGBs (typically No. 6 AWG). Telecommunications Grounding Busbar (TGB) located in the TRs and EFs and is also connected to the metal framework of a building. Grounding Equalizers (GE) tie multiple TBBs together. 4

4.0 Administration and Labeling Cabling administration and labeling is an important cabling element that allows for easy maintenance and management of the telecommunications cabling system. Use the labeling inserts supplied with the SYSTIMAX connecting hardware and faceplates to properly label the cabling components. Additionally CommScope offers a labeling tool located on the BusinessPartner and Consultant sites for use with both commercially available and proprietary card stock. Color-coded labels for termination fields should be implemented as follows: If a cabling element contains mixed categories of cabling, such as the horizontal, they should be identified by enhanced color-coding (i.e., white stripes on blue label to differentiate higher performance cabling) or suitable markings. Cables, as a minimum requirement, should also be identified at both ends with labels suitable for wrapping. The labels should be made of a durable material, such as vinyl, use a white printing surface, and wrap around the cable so that a clear label end self-laminates the printed area. Refer to the ANSI/TIA-606-A Administration Standard for the Telecommunications Infrastructure of Commercial Buildings for proper administration and labeling practices. 5.0 General Cable Guidelines Follow local regulations and applicable codes of the authority having jurisdiction. Refer to TIA-568-C for generic planning and installation practices. All cables and components should be visually inspected for proper installation. Avoid water, high humidity, chemicals, and cold temperature bending of cables. The use of cable lubricant is not allowed. Operation temperature range for SYSTIMAX copper cable is -4 F to 140 F (-20 C to 60 C). Installation temperature range for SYSTIMAX copper cable is 32ºF to 140ºF (0ºC to 60ºC). At the extreme temperatures care must be exercised to prevent excessive kinking or increases in pulling tension. If the cable has been stored below 32ºF (0ºC) for more than 8 hours, the cable must be conditioned at room temperature, 59ºF to 86ºF (15ºC to 30ºC) for at least 4 hours before installation. 5

TABLE 1: CABLE WEIGHTS (IN LB/KFT AND KG/KM) Cable Type 1088B 2088B 3088B Weight 28.5/42.4 37.5/55.8 28.7/42.7 Telecommunications cables should be installed with proper pathway support. They: Must not be placed directly on fluorescent light fixtures Must not be supported by electrical conduits Must not be supported by gas or water pipes. Must not be supported by ceiling grid system 6.0 Bundling and Alien Crosstalk A primary feature of the GigaSPEED Xpress Solution cabling is its Alien Crosstalk performance in support of the 10GBASE-T standard. This performance is achieved even under the worst case condition of all cables routed together in the most tightly packed form. This is usually referred to as a combed and laced cable bundle where all cables maintain their position within a bundle and the bundle is tie wrapped at regular intervals. The GigaSPEED Xpress Solution supports: Tie wrapping up to 5 times per meter (once every 8 inches). Tie wraps must not distort cable jacket. Cable Tray vertical depths up to 23 cm (9 inches) using hardware with sweeping edges and well controlled entry. Check with raceway manufacturer for tray support and design and limitations. Note that current standards call for 15 cm (6 inches) maximum. GSXP cords may also be bundled by combing to eliminate crossovers and tie wrapping. Bundling is typical for long equipment cords. Cross-connect cords and Work Area cords are generally not combed and tied. These cord applications are usually randomly placed or routed separately. 6

7.0 Fill Guidelines The GigaSPEED Xpress Solution cable diameter is slightly larger than the other category 6 (GigaSPEED XL) cables. At 6.2 mm (0.245 inches), the fill guidelines are as follows: 2.3 cables per cm 2 (14 cables per in 2 ) in small tight packed spaces if the layout is done as follows - cables are laid in place without tying in smaller bundles - crossovers are not made in the raceway - crossovers are not made where cables enter or exit the raceway - entries and exits are wide enough to sweep cables out from the raceway 1.6 cables per cm 2 (10 cables per in 2 ) in trays or other open raceways if cables have crossovers in the raceway and where individual cables randomly enter or exit the raceway. Note that density will be lowered further if tied bundles have crossovers in the raceway and randomly enter or exit the raceway, or if entry or exit openings are constrictive. Note that raceway manufacturers guidelines on fill and weight may be more restrictive. Standards generally call for 40% fill limits. The following table is a guide for different conduit sizes. Note that this can be increased where conduit is used for short sleeves and when careful feed and pulling is exercised. TABLE 2: NOMINAL CONDUIT FILL Conduit Size 3/4 1 1.25 2 3 4 Number of cables 3 6 10 26 59 106 Use the online Pathways Estimator for more specific fill calculations. 8.0 Faceplate, Boxes and the GigaSPEED Xpress Cables The single gang six-plex faceplates (M16L, M16LE, M13FP, M26FP, M26C) can be utilized to load with MGS500 information outlets for the GigaSPEED Xpress Solution. If loaded with outlets of other cabling types, the MGS500 must be grouped together either from the top or from the bottom. 7

9.0 GigaSPEED Xpress Cable Installation Alongside Other Cabling When installing GigaSPEED Xpress cable with other cable types (including PowerSUM, GigaSPEED XL7, XL8 and X10D), ensure that cable types are laid, routed, and/or bundled in separate groups. Spacing from PowerSUM, GigaSPEED XL7, XL8 and X10D is not required, but GigaSPEED Xpress cable bundles that include other cable types are not allowed. Each cable type must be routed together. Cable trays and baskets with different bundles can be used as long as cable types are not mixed, and the GigaSPEED Xpress cables are bundled together. When alternating pulls between different cable types, allocate tray positions for each so that different types will not end up bundled together. When connector types other than MGS500 are installed in the same 6 port M2000/M2100, 8 port M3000, or 12-port M3600 panels, keep the MGS500s grouped together. 10.0 Cable/Cord Distance The GigaSPEED Xpress Solution supports 10GBASE-T operation over channel length up to 60 meters. This design and installation guidelines call for no more than 50 meters of 1088B/2088B/3088B cable and 10 meters of GSXP cord/cordage length. However, site guidelines may alter this, provided the site guidelines are effectively documented and followed. Often, additional cordage length is called for, with a corresponding decrease in cable distance. There are several motivations for such a tradeoff. Cordage to a Consolidation Point is a coordinated design replacement for cable. Additional length of Work Area Cords for Multi- User Telecom Outlet Assemblies requires the same coordination. Data Center Cords might need additional cord length to span large Equipment Distribution Areas. These changes are coordinated so that strict attenuation limits are preserved. The following formula and table, adopted from The TIA-568-C series standards may be used to determine alternate maximum cordage lengths useable with reduced cable length. These may be applied to any of the configurations outlined within this document. Total Cord Length in Meters = (62 Horizontal) / 1.2 Horizontal Length in Meters 62 1.2 (Total Cord Length) TABLE 3: ALTERNATE MAXIMUM LENGTHS FOR CABLE AND AGE Maximum Length of Horizontal Cable 50 m (164 ft) 45 m (148 ft) 40 m (131 ft) 35 m (115 ft) 30 m (98 ft) Maximum Combined Length of all cordage and cords 10 m (33 ft) 14 m (46 ft) 18 m (59 ft) 23 m (75 ft) 27 m (89 ft) 8

11.0 Work Area Channel Models The following illustrations of the various channels identify connections from the central equipment (data hub, BAS controller, etc.) to the work area equipment (workstations, servers, etc.). They show the ANSI/TIA/EIA-568-B Commercial Building Telecommunications Cabling Standard and ISO/IEC IS 11801 Information Technology- Generic Cabling for Customer Premises defined configurations containing up to four connections. The connections on the end equipment are not counted. A connection is where two cabling segments come together. Two Connection Model The most basic channel model has only 2 connections and is typically referred to and tested (without the cords) as a permanent link. The horizontal with the cords may also be tested as a channel. Figure 1. Two Connection Model, Interconnection to Telecommunications Outlet CABLE WORK AREA INTERCONNECTION TELECOM OUTLET HUB CABLE WORKSTATION TELECOM OUTLET WORK AREA 9

Three Connection Model A third connection can support two different channel models, a cross-connection or a consolidation point. At large sites or sites with a high density of work stations or where space constraints might otherwise dictate, the telecommunication room can be configured with a cross-connection. The cross-connection is a solution that separates equipment administration from cabling administration, and provides maximum flexibility and protection for horizontal cabling. This configuration is tested with the cords as a channel. Figure 2. Three Connection Model: Cross-connection to Telecommunications Outlet CABLE WORK AREA CROSS-CONNECT AND TELECOM OUTLET HUB CROSS-CONNECT CABLE WORKSTATION WORK AREA Where open office spaces may have a high turnover or where installation may be staged, the horizontal cable can be terminated at a consolation point. This is often done for supporting modular office designs, allowing easy cabling changes from the consolidation point to the telecommunication outlet that follow changes made to the open office space. This configuration is typically called a permanent link. It may be tested without the cords as a permanent link, or with the cords as a channel. 10

Figure 3. Three Connection Model: Interconnection to a Consolidation Point CABLE CP WORK AREA INTERCONNECTION CONSOLIDATION POINT TELECOM OUTLET HUB CABLE CONSOLIDATION POINT WORKSTATION CP WORK AREA 11

Four Connection Model At large open office sites where administration flexibility calls for it, four connections are often used in channels. This configuration offers flexibility and protection at both ends of the horizontal cabling, providing the advantages of cross-connection in the telecommunications room and the flexibility of the consolidation point for modular office design. This configuration is typically referred to and tested (with the cords) as a channel. Figure 4. Four Connection Model: Cross-connection with a Consolidation Point CABLE CP WORK AREA CROSS-CONNECT AND CONSOLIDATION POINT TELECOM OUTLET HUB CROSS-CONNECT CABLE CROSS-CONNECT WORKSTATION CONSOLIDATION POINT CP WORK AREA 12

12.0 Data Center Computer Rooms Data center cabling is an excellent application for the GigaSPEED Xpress Solution, allowing data center operations upgrades when 10GBASE-T equipment becomes available. The following pages show configurations for supporting ANSI/TIA/EIA-942 Telecommunications Infrastructure Standard for Data Centers). The standardized channel configurations were developed based on those in the ANSI/TIA/EIA-568-B Commercial Building Telecommunications Cabling Standard because data centers utilize much of the same LAN equipment that was designed for these channels. However, data center equipment has become specialized and is typically deployed in high density. The cabling design must be tightly coordinated with other system designs, such as the electrical and HVAC. Security and operations also become significant design factors. Consult ANSI/TIA/EIA-942 for additional information and details. Figure 5. Data Center Computer Room Cabling Architecture OFFICE & MANAGEMENT CABLING (BACKBONE AND CABLING PER TIA/EIA 568) ENTRANCE FACILITY COMPUTER ROOM MAIN CROSSCONNECT CORE SWITCHES BACKBONE CABLING CROSSCONNECT CROSSCONNECT LAN, SAN & BACKEND SWITCHES CABLING EQUIP DIST AREAS EQUIP DIST AREAS EQUIP DIST AREAS EQUIP DIST AREAS 13

13.0 Data Center Channel Models The following illustrations identify various channels between different areas within a data center's computer room. These standards-defined configurations contain up to four connections. A connection is where two cabling segments come together, while the connections on the end equipment are not counted in the models. Two Connection Model The most basic channel model has only 2 connections and is typically referred to and tested (without the cords) as a permanent link. The horizontal with the cords may also be tested as a channel. Figure 6. Two Connection Model, Interconnection to Interconnection OR BACKBONE CABLE INTERCONNECTION INTERCONNECTION SWITCH TO SERVER SWITCH SERVER CABLE BACKBONE CORE SWITCH TO SERVER SWITCH C-SWITCH S-SWITCH CABLE 14

Three Connection Model A third connection can support two different channel models, a cross-connection or a consolidation point. At large sites or sites with a high density of switching equipment or where space constraints might otherwise dictate, the horizontal distribution area can be configured with a cross-connection. This configuration is typically referred to and tested (with the cords) as a channel. This configuration can also be applied to backbone cabling with a main crossconnect. Figure 7. Three Connection Model, Cross-connection to Interconnection CABLE CROSS-CONNECT AND INTERCONNECT DISTRIBUTION AREA DISTRIBUTION AREA CABLE CROSS-CONNECT 15

Where a site administrator may need flexibility or where installation may be staged, the horizontal cable can be terminated at a consolation point. It might be used for example to terminate a horizontal bundle at the middle of a row of equipment, and allow the site administrator to apportion horizontal cables between sections of the row as needed. This configuration is typically called a Permanent Link. It may be tested without the cords as a permanent link, or with the cords as a channel. Figure 8. Three Connection Model, Interconnection with a Consolidation Point CABLE CP INTERCONNECTION CONSOLIDATION POINT INTERCONNECT DISTRIBUTION AREA CABLE CONSOLIDATION POINT CP 16

Four Connection Model At large data centers the cabling administration is typically consolidated at cross-connects, and four connections would be used in channels. These configurations are typically referred to and tested (with the cords) as a channel. There are two configurations, a cross-connection with a consolidation point and a double cross-connect. The consolidation point configuration (Figure 9) allows for two levels of administration to the server equipment as in Figure 8 on the previous page, but also provides a cross-connect for the switching equipment. The consolidation point may be useful for flexibility allocating horizontal capacity to many small customers that must be independently maintained. Figure 9. Four Connection Model, Cross-Connection to Consolidation Point CABLE CROSS-CONNECT AND CP SWITCH DISTRIBUTION AREA CABLE CONSOLIDATION POINT CROSS-CONNECT DISTRIBUTION AREA CROSS-CONNECT CP SERVER The dual cross-connect configuration is a classic backbone configuration. It provides uniform administration and is suited for large corporate data centers. This configuration is also applicable to backbone cabling from the main distribution area. 17

Figure 10. Four Connection Model, Cross-Connect to Cross-Connect CABLE CROSS-CONNECT AND CP SWITCH DISTRIBUTION AREA CABLE CONSOLIDATION POINT CROSS-CONNECT DISTRIBUTION AREA CROSS-CONNECT CP SERVER 18

The installation of SYSTIMAX GigaSPEED Xpress is similar to SYSTIMAX GigaSPEED X10D and the installation information in SYSTIMAX GigaSPEED X10D Solution Design and Installation Guidelines should be followed. Note that 2088B cable and Xpress cordage does not utilize the separator tapes. You may also find the following documents useful for installing and handling the GigaSPEED Xpress cables, cords, and apparatus: SYSTIMAX GigaSPEED X10D Solution Design and Installation Guideline for UTP SYSTIMAX 1100 GS5-Type Modular Panel Installation Instructions SYSTIMAX M2000 Modular Patch Panel SYSTIMAX M2100 Modular Patch Panel SYSTIMAX M3000 Modular Patch Panel SYSTIMAX M3600 Modular Patch Panel Installation Instructions SYSTIMAX PATCHMAX GS5 Modular Panel Installation Instructions SYSTIMAX VP360-2U-RMBKT Kit for Rack Mounting VisiPatch 360 Panel System Installation Instructions SYSTIMAX VisiPatch 360 Wall Mounted Panel System Installation Instructions RFE (Raised Floor Enclosure) 19

2010 CommScope, Inc. All rights reserved. Visit our Web site at or contact your local CommScope representative or BusinessPartner for more information. All trademarks identified by or are registered trademarks or trademarks, respectively, of CommScope. This document is for planning purposes only and is not intended to modify or supplement any specifications or warranties relating to SYSTIMAX products or services. 09/10 MI-B-6