VAVBOX Controller Technical Guide

Similar documents
VAV/Zone Controller Actuator Package Technical Guide

FACTORY CONTROLS SYSTEM. MUA II Controller Technical Guide

Dual Digital Module Technical Guide

FACTORY CONTROLS SYSTEM. VAV/CAV Controller Technical Guide

COND. A ENABLE RELAY CONTACT COOLA ENABLE 24 VAC. RATING IS 1 AMP COND. B ENABLE COOL B ENABLE.

USB-Link 2 Technical Guide

GPC Plus Controller. General Information & Application Guide

Starzone 4000 Master Control Panel Figure 2.1 Master Control Panel

GPC-XP Controller Technical Guide

USB-Link 2 Technical Guide. USB-Link 2 Code: SS0073 Version 4.11 and up

Modular System Manager SD Quick Start Guide

UPDATING CONTROLLERS USING PRISM 2 Updating the VCB-X / VCC-X Controller

Modular Service Tool SD Quick Start Guide

MG VAV Controller

UPDATING CONTROLLERS USING PRISM 2 Updating the VCC-X Controller

WOODINVILLE, WA SUPERSTEP 2100 SERIES SEQUENCING PROPORTIONAL LOAD CONTROLLERS INSTALLATION & OPERATING MANUAL. Models: SLC2102-SLC2112

CDD4 Duct Carbon Dioxide Transmitter

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

TOXALERT MODEL AIR 2000

Installation and Operation Instructions I/CO 2, I/CO 2 -VDC, I/CO 2 -T

Installation and Operation. Tracer MP501 Controller CNT-SVX08B-EN

DUKE UNIVERSITY DESIGN & CONSTRUCTION STANDARDS

ETM-2050/ETM-2051 Service Manual

BA/BS4S Temperature Sensor Installation & Operating Instructions

USB-Link 2 Technical Guide

Millennium Simplicity Elite Parameter Points and Quirks

FCU-4 FAN COIL CONTROLLER

Andover Continuum Infinet II i2865/866 VAV Controllers with Built-in Actuator

TEC Terminal Box (VAV) Controller

Factory Packaged Controls. MODGAS-X Controller Field Technical Guide

M1000 INTELLIGENT ZONE CONTROL SYSTEM

WCC III Training Guide

MANUAL INSTALLATION + SERVICE. Price Intelligent Controller. PIC Series. v400 Issue Date: 12/18/ Price Industries Limited. All rights reserved.

USB-Link Technical Guide

Product Manual SZ2141

CDD Carbon Dioxide Transmitter

Andover ContinuumTM. b3850 Series Terminal Controllers

Actuating Terminal Equipment Controller (ATEC) VAV with Reheat - Cooling and Heating, Application Application Note

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

Andover ContinuumTM b3865/866 VAV Controllers with Built-in Actuator

Installation and Operation Instructions

WSHP-IOP-2 May Installation, Operation, and Programming. Tracer ZN510 Controller

Andover ContinuumTM Infinet II

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

Description. descriptors, makes set-up and monitoring very user friendly.

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

ExactLogic BACnet Communicating Pressure Dependent VAV Damper Control with Heat EXL01820 Sequence Datasheet

VAV Modular Assembly (VMA) 1410/1420

TEC Unit Conditioner Controller

IP Module Technical Guide

IP Module Technical Guide

Andover ContinuumTM Infinet II

Custom Controller Installation Instructions

Siemens BACnet Programmable TEC Constant Volume

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

MicroTech II Vertical Self-contained Systems Unit Controller

BAC-9000 Series VAV Controller Installation Guide

Instruction Manual CTC-1

IP Module Technical Guide

FCU-MULTI Modbus Fan Coil Unit Controller

IP Module Technical Guide

Andover ContinuumTM Infinet II

SEZ7260X5x45B Installation Guide for BACnet MS/TP Zone Controller

FOCUS GUIDE VAV ZONE CONTROLLER. Configuration Guide for ProLon Focus Software

Table of Contents 1. Overview Installation...6

Rev Cutler-Hammer Smart Breaker Panel Control Manual

FCU-4 FAN COIL CONTROLLER

Installation Guide. Carbon Dioxide (CO 2. ) Detectors. General Information. Mounting WARNING CAUTION. SAE-1011/1012 Space Mount SAE-1011/1012/1062

75F Smart VAV with Reheat

Field selectable application type and room module series, via dip-switches on controller

USB-Link 2 Technical Guide. USB-Link 2 Code: SS0073 Version 4.11 and up

LTEC Heat Pump DDC Controller

System Manager TS II Technical Guide. Requires System Manager TS II Code: SS9003 Version 1.0 and up DDC Controller Code: SS9001 Version 1.

Actuating Terminal Equipment Controller (ATEC) VAV with Reheat. Start-up Procedures Building Technologies Restricted

Installation and Operation Guide. BAC-5841/5842 UFAD and BAC / VAV Advanced Application Controllers, 8 x 8

Lab and Central Plant Controller

BACVIEW MANUAL Software Version 3.06 INSTALLATION AND OPERATION MANUAL

CDD4 Series Room CO2 Transmitter Installation Instructions

PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION!

MicroTech 2000 Water Source Heat Pump Unit Controller

Tracer Controls. Tracer ZN517 Unitary Controller BAS-PRC012-EN

VCM-X E-BUS Component & System Wiring Technical Guide

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

Installation & Operation Guide

BACnet Terminal Box (VAV) Controller

BACnet. b3810 Series Local Controllers

Temperature controller Ducted systems

Series 3000V Input/Output Board

ECONOMIZERS. Z1ECON30B-1 ECONOMIZER (Cat No. 10Z29) INSTALLATION INSTRUCTIONS FOR ECONOMIZERS USED WITH ZC,ZG,ZH UNITS CAUTION WARNING

LTEC Unit Ventilator DDC Controller

FXVMA Variable Air Volume (VAV) Box Controller

Product Catalog. Tracer Controls Tracer ZN517 Unitary Control BAS-PRC012-EN. August 2010

Torque Series LCD Remote Panel Installation/Operation Manual Model: TQ-DSP-12/24

ASI Systems ML5740A Series

ASI Systems ML5720A Series

Product Manual SZ2144

ExactLogic BACnet Communicating Zone Damper EXL01710 Sequence Datasheet

BACnet. b3867 Terminal Controllers

NEUROLOGIC RESEARCH CORPORATION MODEL 2500

System Controls Suggested Specification

Transcription:

www.wattmaster.com Technical Guide

Table Of Contents Controller Overview... 3 Features... 3 Controller Inputs and Outputs... 5 General... 5 Analog Inputs:... 5 Other Controller Connections... 5 Optional - Expansion Board Outputs... 5 Controller Installation & Wiring... 6 Important Wiring Considerations... 6 General... 7 Controller Mounting... 7 Transformer Sizing & Wiring... 7 Expansion Board Installation & Wiring... 8 Wiring Considerations... 8 Start-up & Commissioning... 0 General... 0 Controller Addressing... 0 Power Wiring... Initialization... Programming The Controller... Sequence Of Operations... 3 Initialization... 3 VAVBO Configuration & Setup... 3 Scheduling... 4 Modes Of Operation... 4 Damper Positions... 5 Occupied Mode Sequences... 5 Unoccupied Mode Sequences... 6 Damper Control... 8 Tenant Override Logs... 9 Alarm Detection And Reporting... 9 Internal Trend Logging... 9 Force Modes or Overrides... 0 Troubleshooting... Using LED s To Verify Operation... Other Checks... WattMaster Controls Inc. 8500 NW River Park Drive Parkville, MO 645 Toll Free Phone: 866-98-00 PH: (86) 505-00 FA: (86) 505-0 E-mail: mail@wattmaster.com Visit our web site at www.wattmaster.com Form: WM-VAVBO-TGD-0C Copyright 006 WattMaster Controls, Inc. WattMaster Controls, Inc. assumes no responsibility for errors, or omissions. This document is subject to change without notice.

D5 AU +VS AU AU TMP V3 FLOW D5 R3 T'STAT 4VAC D7 RN R6 D4 R5 C9 R P.U. R3 R4 C0 LD3 U9 ADDRESS ADD RAM 4 8 6 3 TOKEN NET C7 C4 D3 U3 EPROM C3 V R5 R6 R7 R R R3 R4 C 6L8 C Controller Overview Features This manual applies to the VAVBO controller that is included in the following WattMaster products: MG74-VAV MG744-VAV MG74-03-VAV MG744-03-VAV Pressure Dependent VAVBO Kit For Terminal Units w/o Fan Electric or Hot Water Pressure Independent VAVBO Kit For Terminal Units w/o Fan Electric or Hot Water Pressure Dependent VAVBO Kit For Terminal Units or Fan Terminal Units With Electric or Hot Water Pressure Independent VAVBO Kit For Terminal Units or Fan Terminal Units With Electric or Hot Water The is used for controlling airflow and operation of VAV terminal units. It is a programmable digital controller, which allows for program setpoints to be stored in non-volatile memory. The controller is connected to a room sensor which monitors space temperature allowing the VAVBO controller to modulate a damper in response to space temperature, duct temperature and airflow requirements in the controlled space. Technical Guide The VAVBO controller is provided with two relays for tri-state control of the damper actuator. All outputs and the relay common are electrically isolated from all other circuitry on the board. All relay outputs are supplied with transient suppression devices across each set of contacts to reduce EMI and arcing. The relay output contacts are rated for pilot duty control of a maximum of Amps @ 4 VAC or 4 VDC. The actuator connects via a modular cable to the board and provides the VAVBO controller with feedback monitoring for precise positioning of the actuator. OE3 Output Expansion Board The OE3, 3 Relay with Analog Output Expansion board is used in conjunction with the board to allow for control of VAV terminal units, including series and parallel fan terminal units with up to stages of electric heat or modulating hot water heat. The OE3, 3 Relay with Analog Output Expansion board provides 3 relay outputs for pilot duty switching control, and Analog output for control of a 0-0 V modulating hot water valve. The OE3 Output Expansion board connects to the VAVBO controller board by means of a modular cable provided with the expansion board. Power is supplied to the board by means of this modular cable. Screw terminals are provided for connection of field wiring to the relay and analog outputs. The relay outputs are N.O. contacts with one common terminal. All outputs and the relay common are electrically isolated from all other circuitry on the board. All relay outputs are supplied with transient suppression devices across each set of contacts to reduce EMI and arcing. The relay output contacts are rated for pilot duty control of a maximum of Amps @ 4 VAC or 4 VDC. The analog output provides a 0 0 VDC modulating signal output into a K ohm minimum load. The VAVBO controller has three integral modular jacks for connection to the actuator, airflow sensor (for pressure independent applications), and relay or analog expansion boards, via modular cables. The controller has an on-board dip switch provided for board addressing. 7.00" 4.00 EPANSION C6 Q Q3 R5 SW U0 7576 POWER R L VR 784 U7 R7 R6 R35 YS056 REV 3 SCAN REC ACTUATOR Q U C C C5 PJ R8 C3 C4 PJ V R9 D K D K R00 R0 R C5 R3 R R34 C9 C8 C0 R9 R0 C U5 EWDOG U6 R4 LD LD C6 U8 C3 C4 VREF ADJ U C5 R7 R8 COMM C8 U4 U PAL R8 Figure : Dimensions 3

R8 R34 U8 U PAL R7 C9 C3 C8 C4 Q VREF ADJ C0 U C R8 C R9 R0 C U C5 C5 U5 EWDOG EPANSION PJ C3 R8 U6 C6 SW U0 7576 COMM R00 C5 R3 ACTUATOR PJ V C4 R4 LD LD R9 C6 R35 R0 R R L K D Q R5 D Q3 U7 K Technical Guide Controller Overview Figure : OE3 Output Expansion Boards Air Flow Sensor Modular Connector Typical Pin Indicator RAM Chip EPROM Chip PAL Chip FLOW RN C8 U4 C4 U3 C3 C Auxiliary Wiring Terminals Room Sensor Wiring Terminals D5 AU +VS AU AU D5 R3 T'STAT TMP C9 R P.U. R3 R4 U9 RAM 80C55 EPROM R R R3 6L8 C Snap Track For Controller Mounting Address Switch (SetBetween&58) Communication Wiring Terminals Communications Driver Chip Power LED T SHLD R YS056 REV 3 V3 D7 R6 D4 R5 C0 LD3 POWER R ADDRESS ADD 4 8 6 3 SCAN REC TOKEN NET R5 R6 R7 R4 Expansion Board Modular Connector Damper Actuator Modular Connector 4 VAC Power Terminals 4VAC VR 784 R7 R6 D3 C7 V Damper Actuator Positioning Relay Open Damper Actuator Positioning Relay Close Figure 3: Component Locations REC LED SCAN LED 4

Controller Inputs and Outputs General The following inputs and outputs are available on the VAVBO controller and the OE3 Output Expansion Board that can be added by connecting it to the main controller board expansion port. For component locations of the inputs on the see Figure 3. For wiring of inputs and outputs see Figure 4 thru 9. Analog Inputs: Input #: Space Temperature Sensor The Room Sensor that reads space temperature is attached the TMP and terminals. If the Room Sensor with slide adjust option is used a third wire connects to terminal AU. Input #: Airflow Sensor If the is to be configured for pressure independent operation, you need to install the OE74 Airflow Sensor and connect the modular plug from the pressure sensor to this input. The pressure signal from the Airflow Sensor is used for CFM (airflow) calculations. If an OE74 Airflow Sensor is attached to this input, the VAVBO controller will automatically detect this and switch to pressure independent operation. If the sensor is not attached or becomes defective, the controller automatically reverts to pressure dependent operation. Input #3: Supply Air Temperature Sensor The optional Supply Air Temperature Sensor is connected to terminals AU and when it is used. If it is to be used as a Supply Air Sensor, it should be mounted in the supply duct close to the terminal unit where the VAVBO controller is installed. This sensor can be used for monitoring purposes or in place of the Supply Air Temperature Broadcast from the WMVAV Controller. Note: All temperature sensors must be Thermistor Type III. Other Controller Connections Expansion Board Modular Connector This modular connector is used to connect the optional OE3 Output Expansion Board to the VAVBO controller. These boards are only required when electric or hot water heating and/or fan terminal control is required. The expansion boards are not required for cooling only terminal units. Actuator Modular Connector This modular connector is used to connect a modular cable from the VAVBO controller to a tri-state actuator. Optional - OE3 Expansion Board As previously stated when control of a fan or if heating is required the OE3 Output Expansion board must be used. Relay Output # - Fan Enable The first expansion relay on the Output Expansion boards is used for enabling the fan for Series or Parallel Fan Terminal Units. Relay Output # - Stage ing If you have at least one stage of auxiliary heating, this is the relay used to energize the st stage of terminal unit heating. This heating stage can either be used with electric heat or On/Off hot water valve control. Relay Output #3 - Stage ing If you have two stages of auxiliary heating, this relay controls the nd stage of electric heat. For 3 stage heating, this relay output would be energized for both the nd and 3rd stage of heat. See the following section for more information regarding 3 stage heating applications. 3 Stage ing Applications If three stages of electric heat are configured, relays # and #3 will stage in a staggered sequence. This allows you to achieve 3 stages of heating using only relays # and #3. Each of the 3 heating elements should be sized for /3 of the total KW output required. Both the nd and 3rd stage heating contactors (C & C3) must be connected to Relay Output #3. See Table for relay sequencing information. Stage No. Relay Output # Relay Output #3 # ON (C) OFF (C & C3) # OFF (C) ON (C & C3) #3 ON (C) ON (C & C3) Table : Relay Sequencing For 3 Stage ing 4 VDC Power Terminals (+V & ) These terminals can supply 4 Volts DC for a 4 VDC hot water valve actuator if desired. This output is rated at Watts maximum load. Analog Output If you are using hot water or steam heating via a modulating steam or hot water valve, this output can supply a 0-0 Volts DC signal for proportional control of the valve. 5

R8 R34 U8 U PAL R7 C9 C3 C8 Q VREF C4 ADJ C0 U C R8 C R9 R0 C U C5 C5 U5 EWDOG PJ EPANSION U6 R8 C3 C6 SW U0 7576 COMM C5 R00 ACTUATOR PJ V C4 R3 R4 LD LD R9 C6 R35 R0 R R L K D Q R5 K D Q3 Technical Guide Controller Inputs and Outputs Airflow Probe & Sensor (For Pressure Independent Applications Only) Airflow Notes:.) All wiring to be in accordance with local and national electrical codes and specifications..) A Duct Supply Air Temperature Sensor is not required when the VAVBO Controller is connected to an WMVAV Unit Controller board. A global Supply Air temperature is broadcast by the WMVAV Unit Controller. The Supply Air Temperature Sensor is required if the is required to operate as a Stand Alone controller. The Duct Sensor can also be placed on the discharge side of the VAVBO duct and used as a Discharge Temperature Sensor to monitor VAVBO discharge air temperature if desired. This is normally used only if the VAV Terminal unit has heating capabilties. Zone Actuator Lo Duct Supply Or Discharge Temperature Sensor (See Note ) Hi Locate In Supply Or Discharge Duct Near Zone Damper AU AU FLOW RN D5 AU +VS C8 AU AU C9 U9 R D5 P.U. C4 U4 RAM 80C55 C3 C U3 6L8 R R EPROM R3 C 0 R3 R3 Room Sensor TMP T'STAT TMP R4 R4 Connection To AU Terminal Is Only Required When Sensor Is Specified With Slide Adjust Option OVR W A R M E R C O O L E R TMP AU T SHLD R D7 R5 ADDRESS ADD C0 4 8 6 3 LD3 TOKEN NET R6 D4 POWER R R5 R6 R7 Connect To Next VAVBO Controller Or WMVAV Controller On Local Communications Loop 4VAC YS056 REV 3 V3 4VAC VR 784 SCAN REC R6 R7 D3 C7 U7 V Line Voltage To Optional Relay Expansion Board 4 VAC Transformer Size For 6 VA Maximum Load Figure 4: Wiring Controller Installation & Wiring General Correct wiring of the VAVBO controller is the most important factor in the overall success of the controller installation process. The VAVBO controller wiring has been simplified by the use of modular connectors and prefabricated modular cables. Controller Mounting If the Round Zone Dampers were purchased from WattMaster, the controller and actuator are factory mounted and wired in the damper control enclosure. If your VAVBO controllers are pressure independent, an airflow probe and pressure sensor will also be factory mounted and wired. Most terminal unit manufacturers will offer the option of factory mounting the WattMaster controls in their terminal units for an additional charge. An installation worksheet and instructions are available for the WattMaster VAVBO controller package which can be shipped with the VAVBO control(s) to the terminal unit manufacturer to simplify third party factory mounting and wiring of the controller. When the VAVBO controller is to be field mounted, it is important to mount the controller in a location that is free from extreme high or low temperatures, moisture, dust and dirt. The VAVBO controller board must be mounted within 0 of the damper actuator in order for the actuator cable to extend between the controller and the actuator. 6 Be careful not to damage the electronic components when mounting the controller. Remove the controller from its snap track mount. Mark the control enclosure base using the snap track as a template. Drill pilot holes in the enclosure base and secure the snap track to it using sheet metal screws. Do not allow metal shavings to fall onto the circuit board. Reattach the controller to the snap track. Mount the damper actuator to the damper shaft following the instructions supplied with the damper actuator. Important Wiring Considerations Please carefully read and apply the following information when wiring the WMVAV controller. See Figure 4 for VAVBO controller wiring diagram.. Size and wire the transformer per the instructions. Failure to size the transformer and/or wire the transformer correctly may cause the VAVBO controllers to not operate erratically or not at all. See Figure 5 for wiring and transformer sizing information.. If a Duct Sensor is to be connected, the minimum wire size used should be 4 gauge. 3. Do not pry on the connectors when connecting or disconnecting the modular cables. Be sure to push in on the connector release clip and then pull straight up.

4VAC Power - Transformer & Wire Sizing Considerations For s Some installers like to use one large 4VAC transformer to power several devices. This is allowable as long as polarity is maintained to each device on the transformer circuit. Warning: If polarity is not maintained, severe damage to the devices may result. WattMaster Controls recommends using a separate transformer for each device in order to eliminate the potential for damaging controllers due to incorrect polarity. Using separate transformers also allows redundancy in case of a transformer failure. Instead of having 8 controllers inoperative because of a malfunctioning transformer you have only controller off line. If the installer does decide to use a large transformer to supply power to several devices, the following transformer and wire sizing information is presented to help the installer correctly supply 4VAC power to the devices. Following is a typical example to help the installer to correctly evaluate transformer and wiring designs. Each requires 6 VA @ 4VAC power. In the examples below we have a total of 0 VAV Controllers. 0 s @ 6VA each... 0 x 6VA =60VA. The above calculation determines that our transformer will need to be sized for a minimum of 60VA if we are to use one transformer to power all the controllers. We will use a 75 VA transformer, as this is a readily available size that meets our VA load requirements. Next we must determine the maximum length of run allowable for the wire gauge we wish to use in the installation. Each wire gauge below has a voltage drop per foot value we use to calculate total voltage drop. 8ga wire...0.00054 = voltage drop per length of wire 6ga wire...0.00034 = voltage drop per length of wire 4ga wire...0.000 = voltage drop per length of wire For our example we will use 8 gauge wire. WattMaster recommends 8 gauge as a minimum wire size for all power wiring. Next use the voltage drop per foot value for 8 gauge wire from the list above and multiply by the total VA load of the 0 controllers to be installed. 0.00054 (Voltage drop per foot for 8 gauge wire) x 60VA controller load = 0.034 Volts/Ft. WattMaster VAVBO controllers will operate efficiently with a voltage drop no greater than Volts. Divide the total allowable voltage drop of Volts by the number you arrived at above and you have the maximum number of feet you can run the 8 gauge wire with an 75 VA transformer with no more thanavoltdropatthefarthest controller from the transformer.. (Volts total allowable voltage drop) = 6.73 feet 0.034 (Voltage drop per ft. @ 60VA load) Parallel circuiting of the wiring instead of wiring all 0 controllers in series allows for longer wire runs to be used with the same size wire (as shown in our examples below). It is often necessary for the installer to calculate and weigh the cost and installation advantages and disadvantages of wire size, transformer size, multiple transformers, circuiting, etc., when laying out an installation. No matter what layout scheme is decided upon, it is mandatory that the farthest controller on the circuit is supplied with a minimum of Volts and that the polarity is maintained to all controllers connected to the transformer. B C F E D C A B 0 / 4VAC B 0 / 4VAC Distance A to B cannot exceed 6.73 Ft. A Figure 5: WMVAV Controller Transformer Sizing A 0 / 4VAC Distance from A to B cannot exceed 3.46 Ft. Distance from A to C cannot exceed 3.46 Ft. Distance from A to B cannot exceed 30.40 Ft. Distance from A to C cannot exceed 308.64 Ft. Distance from A to D cannot exceed 308.64 Ft. Distance from A to E cannot exceed 308.64 Ft. Distance from A to F cannot exceed 308.64 Ft. Transformer Sizing & Wiring Each VAVBO controller requires 6 VA minimum at 4 VAC in order to function properly. Wiring and transformer information shown above is provided to help correctly size and layout wiring schemes for the VAVBO controllers. As stated above, all wiring should be 8 Ga. minimum. Long runs may require heavier gauge wire to keep the voltage drop within the volt maximum range. Please follow these guidelines. Warning: If polarity between controllers is not maintained, severe damage to the controllers may result. WattMaster recommends using a separate transformer for each controller in order to eliminate the potential for damaging controllers due to incorrect polarity. 7

Expansion Board Installation & Wiring Figure 6: Expansion Board Wiring For Two Position Hot Water Applications Wiring Considerations Expansion boards are used to supply extra relays and/or analog outputs to control fan and heating functions for the VAVBO controller. When Round VAVBO Dampers or Rectangular Kits are ordered from WattMaster, the OE3 Expansion board is shipped loose for field mounting by others. Mounting of the OE3 Expansion Board is identical to the previously described mounting for the VAVBO controller. Mount the Expansion board near the VAVBO controller using the sheet metal screws provided. Be sure the mounting location is close enough so that the supplied modular cable will reach from the VAVBO controller to the Expansion board. Warning: The 3 relay outputs available on the OE3 Output Expansion board are each rated for Amps @ 4 VAC. If your device load exceeds these limits, a pilot duty relay (by others) must be used in the circuit. The wiring consideration information previously outlined for the VAVBO controller should be followed when wiring the OE3 Expansion Boards. 8

Expansion Board Installation & Wiring Technical Guide WattMaster Part #OE3 Relay Expansion Board w/ Modular Cable Supplied by WattMaster Mounted by Others Connect To Using Modular Cable Supplied By WattMaster WattMaster Part # BK000047 Snaptrack Supplied by WattMaster Mounted by Others. Remove Control Board from Snaptrack & Mount Snaptrack on Box R3 R R6 R5 R R4 PJ R7 Q3 Q Q R0 R9 R8 C D RLY RLY RLY 3 D4 D3 D C6 C3 U LM358 C C4 VR R I O K C5 R 784CT VR RAOUT BD. YS074 REV. 3 V4 K K3 Q4 M V3 V V R3 R4 COM 3 +V ANALOG V5 OUT + TB TB TB3 SERIAL # 4VAC COM 4 VAC Transformer Supplied & Wired by Others. Size For Required Contactor(s) Load. st Stage Contactor C nd Stage Contactor C 3rd Stage Contactor C3 Note: 3 Stage ing is Attained by Sizing All 3 ing Elements For Equal KW Output. Each Element Should be Sized for /3 of the Total KW Output Required. To Achieve 3 Stage ing the System would be Configured to Energize Contactor C for First Stage. For nd Stage the System Would be Configured to Deenergize Contactor C and Energize Contactor C & C3. For 3rd Stage the System Would be Configured to Leave Contactor C & C3 Energized and also Energize Contactor C. 4 VAC Contactor(s) Supplied & Installed By Others. Amp Max. Load Each. Typical Wiring for Single Duct Terminal with Electric WattMaster Part #OE3 Relay Expansion Board w/ Modular Cable Supplied by WattMaster Mounted by Others Connect To Using Modular Cable Supplied By WattMaster R R R3 R4 R5 R6 R7 Q3 Q Q R8 R9 R0 PJ C6 C3 D D D3 D4 RLY RLY RLY 3 C U LM358 VR R K C5 R RAOUT BD. YS074 REV. 3 V4 K K3 Q4 V3 V V R3 R4 COM 3 +V ANALOG V5 OUT + TB TB TB3 4VAC COM Fan Relay R 4 VAC Fan Relay Supplied & Installed By Others. Amp Max. Load. 4 VAC Transformer Supplied & Wired by Others. Size For Required Fan Relay Load. WattMaster Part # BK000047 Snaptrack Supplied by WattMaster Mounted by Others. Remove Control Board from Snaptrack & Mount Snaptrack on Box C C4 I O 784CT VR M SERIAL # Typical Wiring for Fan Terminal Unit with Cooling Only WattMaster Part #OE3 Relay Expansion Board w/ Modular Cable Supplied by WattMaster Mounted & Wired by Others Connect To Using Modular Cable Supplied By WattMaster WattMaster Part # BK000047 Snaptrack Supplied by WattMaster Mounted by Others. Remove Control Board from Snaptrack & Mount Snaptrack on Box R3 R R6 R5 R R4 PJ R7 Q3 Q Q R0 R9 R8 C D RLY RLY RLY 3 D4 D3 D C6 C3 U LM358 C C4 VR R I O K C5 R 784CT VR RAOUT BD. YS074 REV. 3 V4 K K3 Q4 M V3 V V R3 R4 COM 3 +V ANALOG V5 OUT + TB TB TB3 SERIAL # 4VAC COM Fan Relay R st Stage Contactor C nd Stage Contactor C 3rd Stage Contactor C3 Note: 3 Stage ing is Attained by Sizing All 3 ing Elements For Equal KW Output. Each Element Should be Sized for /3 of the Total KW Output Required. To Achieve 3 Stage ing the System would be Configured to Energize Contactor C for First Stage. For nd Stage the System Would be Configured to De-energize Contactor C and Energize Contactor C & C3. For 3rd Stage the System Would be Configured to Leave Contactor C & C3 Energized and also Energize Contactor C. 4 VAC Transformer Supplied & Wired by Others. Size For Required Fan Relay & Contactor(s) Load. 4 VAC Fan Relay & Contactor(s) Supplied & Installed By Others. Amp Max. Load Each. Typical Wiring for Fan Terminal Unit with Electric Figure 7: Expansion Board Wiring For Electric Applications 9

Figure 8: Expansion Board Wiring For Modulating Hot Water Applications Start-up & Commissioning General In order to have a trouble free start-up it is important to follow a few simple procedures. Before applying power for the first time it is very important to correctly address the controller and run through a few simple checks. Controller Addressing All VAVBO controllers are equipped with address switches. If the VAVBO controller is to operate as a Stand Alone controller (not connected to any other HVAC unit or VAVBO controllers) the controller address switch should be set for address. When the VAVBO controller is to be connected to other controllers on a communication loop, each VAVBO controllers address switch must be set with a unique address between and 58. When programming the VAVBO controller and asked to enter the Unit ID you would first enter the MiniLink loop address for the loop the controller is connected to and then enter the VAVBO controllers address. See Figure 0 for a diagram depicting address switch settings. 0

R8 R34 U8 U PAL R7 C9 C3 C8 C4 Q VREF ADJ C0 U C R8 C R9 R0 C U C5 C5 U5 EWDOG PJ EPANSION U6 R8 C3 C6 SW U0 7576 COMM C4 C5 PJ R00 ACTUATOR R3 V R4 LD LD R9 C6 R35 R0 R R L K D Q VR R5 784 D Q3 U7 K R6 R7 Start-up & Commissioning Technical Guide SW ADD 4 8 6 3 TOKEN NET Board FLOW D5 AU +VS AU AU C4 C3 C C8 U4 U3 RN 6L8 C9 U9 R R RAM EPROM R3 NET 4 8 6 3 TOKEN Address Switch Shown Is Set For Address 9 ADD Controller Address Switch The Address For Each Controller Must Be Between And 58 And Be Unique To The Other Controllers On The Local Loop NET 4 8 6 3 TOKEN ADD Address Switch Shown Is Set For Address 3 TMP T SHLD R D5 R3 T'STAT D7 R6 D4 R5 R P.U. R3 R4 C0 LD3 POWER R ADDRESS ADD 4 8 6 3 TOKEN NET 80C55 R4 R5 R6 R7 C YS056 REV 3 V3 SCAN REC 4VAC C7 D3 V Figure 9: Address Switch Setting For detailed information regarding communication wiring and connection for Interconnected and Networked systems, please see the Watt- Master WMVAV System Installation & Troubleshooting Guide. Power Wiring One of the most important checks to make before powering up the system for the first time, is to confirm proper voltage and transformer sizing for the VAVBO boards that are connected to it. Each VAVBO controller requires 6 VA of power delivered to it at 4 VAC. See page 7 of this manual for complete wiring and transformer sizing information for the VAVBO controller. Check all connections to be sure they are tight with no loose wire starnds hanging loose. Confirm that all sensors required for your system are mounted in the appropriate location and wired correctly to the VAVBO controller. Check the actuator cable and be sure it is plugged in and secured to the modular connector on the actuator and the VAVBO controller board modular connector. Be sure any expansion boards connected to the VAVBO controller are also correctly wired per the expansion board wiring instructions on pages 8 through 0 of this manual. After all the above wiring checks are complete, apply power to the first VAVBO on the loop, that is connected to the WMVAV controller. Initialization Upon applying power to the VAVBO controller the following should occur: On system power-up, the SCAN LED is extinguished for a few seconds and then the controller flashes its address switch setting. If the address switch were set to 7, you would see 7 flashes. After the address is finished, the LED will extinguish for another 5 seconds. At the conclusion of this 5-second delay, the LED will begin a continuous flashing while the Damper Feedback limits are calibrated. If the Damper is driving open, the LED will blink slowly. If the Damper is driving closed, the LED will blink fast. When the calibration is completed, the normal diagnostic flashes will commence. These diagnostic flashes are described later in this document. In addition, during the first few seconds of powerup, all default setpoints are initialized and all outputs are turned off. a 30 second start-up delay to protect the fan and other components from short cycling during intermittent power conditions. If all inputs are operating correctly it will blink once every ten seconds.

Programming The Controller The next step is programming the controller for your specific requirements. In order to configure and program the VAVBO controller you must have a central operators interface or a personal computer with the Prism computer front end software installed. Two different operators interfaces are available for programming of the VAVBO controller. You may use either the Modular Service Tool or the Modular System Manager to access the status and setpoints of any VAVBO controller or WMVAV controller on the systems communications loop. See the Operators Interface Technical Guide for VAVBO controller programming information. If you are going to use a personal computer and the Prism computer front end software, please see the WattMaster Prism Computer Front End Operations Manual. No matter which operators interface you use, it is recommended that you proceed with the programming and setup of the controller in the order that follows:. Configure The Controller For Your Application. Program The Controller s. 3. Review Controller Status Screens To Verify System Operation And Correct Controller Configuration Mode Selection UP STATUS PREV NET System Manager SETPOINTS ESC DOWN CLEAR UP STATUS SCHEDULES ENTER 3 SETPOINTS OVERRIDES ALARMS CONFIGURATION BALANCE - TEST ON 3 4 7 DEC 5 8 0 6 9 - MINUS 4 7 DEC 5 8 0 6 9 - MINUS PREV ESC DOWN ENTER CLEAR NET SCHEDULES OVERRIDES ALARMS Figure 0: Operators Interfaces

Sequence Of Operations Initialization On system power-up, the SCAN LED is extinguished for a few seconds and then the controller flashes its address switch setting. If the address switch were set to 7, you would see 7 flashes. After the address is finished, the LED will extinguish for another 5 seconds. At the conclusion of this 5 second delay, the LED will begin a continuous flashing while the Damper Feedback limits are calibrated. If the Damper is driving open, the LED will blink slowly. If the Damper is driving closed, the LED will blink fast. When the calibration is completed, the normal diagnostic flashes will commence. These diagnostic flashes are described later in this document. VAVBO Configuration & Setup There are a few configuration selections available to the user, which can be used to tailor the software operation to match the mechanical equipment this controller is installed on. These are programmed using either the Modular System Manager, Modular Service Tool or a personal computer with Prism computer front end software installed. See the Operator Interfaces Technical Guide or the Prism Computer Front End Software manual for specific programming information. General Several options are available to configure the VAVBO controller for the appropriate equipment it is installed on. All of these options can be set from the Configuration menu with the exception of AHU Call which is set from the s menu. Again, please refer to the Operators Interface Technical Guide or the Prism Computer Front End Software manual for detailed programming information. Box Control Method Set this configuration item for the type of box the VAVBO controller is used on. The options available are: 0 = Cooling Only Box (With Reheat if Required) = ing/cooling Changeover Box = Series Fan Powered Box With Reheat 3 = Parallel Fan Powered Box With Reheat Damper Operating Mode This allows the user to set the direction of rotation the damper moves when driving towards its full open position. The options available are: 0 = Direct Acting (Clockwise To Open Damper) = Reverse Acting (Counterclockwise To Open Damper) Pressure Independent Boxes - Airflow @ W.C. If this is a pressure independent box, this option allows you to calibrate the box CFM correctly using the box manufacturers K factor. Enter the correct K (CFM) factor for the inlet diameter of the box you are configuring. Expansion Relays - Steps of Reheat If the box has reheat supplied by an electric coil, this option must be set for the number of electric heating stages on the box. If the box has hot water heat with a position hot water valve, set the number of stages to. For hot water heat with a proportional hot water valve this must be set for 0. Options available are: 0 = No Staging = Stage of Reheat = Stages of Reheat 3 = 3 Stages of Reheat Proportional ing Signal If the box has hot water reheat using a proportional hot water valve, set this option to match the voltage signal required by the hot water valve you are using. Options available are: 0 = 0-0 VDC Voltage Signal = -0 VDC Voltage Signal Allow Box With AHU If the box you are using has reheat, configuring this setting to =Yes will allow the box heat to operate at the same time as the HVAC unit heat. Options available are: 0 = No = Yes Main Fan Status If the VAVBO controller is installed on a non-fan powered box that has reheat set this option to Yes in order to enable box reheat only when the HVAC unit fan is running. A full description of how this setting affects the various box types in the occupied and unoccupied modes is contained under the Mode Sequence heading that follows later in this manual. Options available are: 0 = No can operate without fan = Yes cannot operate without fan Push Button Override Group ID# During Unoccupied Mode, all VAVBO controllers with a corresponding Group ID# will resume Occupied operation whenever any of the VAVBO controllers with the same Group ID # has it s push-button depressed to initiate an override condition. This allows you to group zones in various areas of the building. For example, individual tenants with several offices could restore occupied mode for just their zones and not affect other zones in the building. If you don t want a specific zone to be a part of any group, enter a 0 for its Group ID #. Dump Zone If this VAVBO controller is to be used as a Dump Zone set this configuration to =Yes. The dump zone is a controller without an actuator that is used to control a duct heater or auxiliary heat. Options available are: 0 = No = Yes AHU Call This setting is located under the s menu on screen #3. This is used only for the unoccupied mode. This temperature setpoint is used to allow auxiliary heat such as baseboard heaters to be energized in an attempt to satisfy the heating demand prior to initiating the HVAC unit Supply Air ing mode. 3

Sequence Of Operations During unoccupied mode when the temperature in the space drops below the AHU Call setpoint the VAVBO controller sends a signal to the WMVAV controller to initiate the HVAC unit Supply Air ing Mode. This setpoint temperature can be set higher or lower than the Space ing setpoint. Scheduling Occupied/Unoccupied Mode The monitors the communications loop for its Occupied and Unoccupied mode of operation command. Either the WMVAV Controller or a special Optimal Start Scheduling device can transmit the Occupied command to the. This requires the s to all be connected to the system communication loop through their RS-485 connector and to be properly addressed for the command to be received. Push-button Override Operation During unoccupied hours, the user can force the and WMVAV Controller back to occupied operation by pressing the override button for a period of time less than 3 seconds. This initiates the override or resets the override timer back to zero during unoccupied hours of operation. During Override operations, the user can cancel the override by pressing the override button for a period of time between 3 seconds and 0 seconds. This restores the normal unoccupied operation. On larger installations with several terminal units, the s can be configured into groups so that an override generated by one can cause several other controllers to follow along and return to occupied mode for the programmed duration. Other s not in the same group will simply maintain an unoccupied damper or airflow setting as set by the user. Push-button overrides are broadcast continuously by the initiating until the controller itself times out or the override is cancelled by the user. This broadcast forces the air handler to start its main fan and provide cooling or heating, if so configured. It will remain on until the override broadcast has not been detected for at least consecutive minutes. Modes Of Operation General There are 7 possible modes of operation for the HVAC Unit and the VAVBO controller. These modes are determined by the supply air and/or space demand conditions. They are: Supply Air Vent Mode (Based on HVAC Unit SAT) Space Vent Mode (Based on Space Temp.) Space Cooling Mode (Based on Space Temp.) Supply Air ing Mode (Based on HVAC Unit SAT) Space ing Mode (Based on Space Temp.) Off Mode (Not displayed. See definition below) The process of determining each mode is discussed below, but the actual operation of each mode is explained in the section that follows. Definitions Of Modes VAVBO Control Schemes On all fan-powered and non-fan-powered terminal units, supply air modes and space demands are calculated the same. If the supply air rises ºF above the cooling setpoint, the supply air mode is heating. To cancel the supply air heating mode, the supply air temperature must fall below the cooling setpoint. If the supply air falls ºF below the heating setpoint, the supply air mode is cooling. To cancel the supply air cooling mode, the supply air temperature must rise above the heating setpoint. If the supply air is between the heating and cooling setpoints, it is considered vent mode. Supply Air Vent Mode This mode occurs when the Supply Air Temperature is between the heating and cooling setpoints. Space Vent Mode This mode occurs when the Space Temperature is between 0.5 F below the Cooling and 0.5 F above the ing. Supply Air Cooling Mode This mode occurs when the Supply Air Temperature falls to.0 F below the Space ing. Space Cooling Mode This mode occurs when the Space Temperature rises to 0.5 F below the Space Cooling. Supply Air ing Mode This mode occurs when the Supply Air Temperature rises to.0 F above the Space Cooling. Space ing Mode This mode occurs when the Space Temperature falls to 0.5 F above the Space ing. Off Mode During unoccupied mode, the mode is considered OFF if the space temperature does not generate a heating mode or cooling mode based on the unoccupied heating & cooling setpoints. Supply Air Cooling Mode (Based on HVAC Unit SAT) 4

Damper Positions The actual values for the minimum damper positions that are described in the following paragraphs can be user configured by changing the values in setpoint screens 5, 6 and 7 for the VAVBO controller. These minimums are expressed in damper open percentages for pressure dependent terminal units or in CFM for pressure independent terminal units. Cooling Minimum When the HVAC unit is in the Supply Air Cooling mode but the space does not require cooling, the VAVBO damper will go to the Cooling Minimum position. ing Minimum When the HVAC unit is in the Supply Air ing mode but the space does not require ing, the VAVBO damper will go to the ing Minimum position. Vent Minimum This is the position the VAVBO damper will move to when the HVAC unit is in the Supply Air Vent mode. Nite/Reheat Minimum This setpoint has two different functions depending on whether the HVAC unit is in Occupied or Unoccupied mode. Occupied Mode If the VAVBO controller is used on a non-fan-powered terminal unit that has reheat, the VAVBO damper will move to the Nite/Reheat position whenever a Space ing demand occurs and the HVAC unit is in Supply Air Cooling or Vent modes. When the HVAC unit is in Supply Air ing mode the VAVBO damper will modulate as required to maintain the Space ing setpoint. Unoccupied Mode When using non-fan powered terminal units, the VAVBO damper will position itself in the Nite/Reheat minimum position. In order for fan powered terminal units to position the damper to the Nite/Reheat minimum position, the check for main fan status must be selected and the HVAC unit fan must be operating. Occupied Mode Sequences Space Vent Mode This mode only applies to the Occupied Mode of operation. If the equipment is in the Unoccupied Mode, then a lack of heating or cooling demand would generate the Off Mode. If the HVAC unit is in Supply Air Vent Mode, the user can adjust the damper position on pressure dependent terminal units and the airflow on pressure independent terminal units to provide a fixed amount of ventilation air into the space when there are no heating or cooling demands. During this time, the damper does not modulate on pressure dependent terminal units. On pressure independent terminal units, it only modulates to the extent required to maintain the vent minimum airflow setting. If the detects that the HVAC unit is in Supply Air ing mode, indicating that the air handler has activated its heat, the heating airflow minimum will be substituted for the vent minimum position. If the detects that the HVAC unit is in Supply Air Cooling mode, indicating that the air handler has activated its cooling, the cooling airflow minimum will be substituted for the vent minimum position.. Space Cooling Mode Occupied Space Cooling mode is initiated by the temperature in the space rising to within 0.5 ºF of the Occupied Cooling. If the HVAC unit is in the Supply Air ing and another VAVBO controller has a cooling demand, the damper/airflow for the VAVBO controller requiring cooling will position itself to provide the heating minimum setpoint amount of air into the space. No modulation open will occur because the space does not want the warm air currently being supplied by the air handler. When the HVAC unit is in the Supply Air Cooling mode, the damper is normally held at the minimum cooling position until the space temperature begins to rise above the cooling setpoint. As the space temperature rises to within 0.5 ºF of the Occupied Cooling, the damper/ airflow calculation causes the air valve to open proportionally until the maximum setpoint is achieved at 3.5 ºF above the setpoint. This is a 4 ºF proportional window starting 0.5 ºF below the cooling setpoint to 3.5 ºF above the cooling setpoint. The damper/airflow is never allowed to modulate outside the user adjusted minimum setpoint and the maximum setpoint. The maximum damper/airflow setpoint applies to heating and cooling modes of operation only. All of the modes have their own individual minimum setting. Series Flow Fan Terminals If the has been configured as a Series Fan Powered terminal unit, the series fan relay will activate and run the series box fan continuously anytime the HVAC unit fan is running. In all cases, before the series box fan can be activated, the air damper is driven fully closed and held that way for 30 seconds to make sure the series box fan hasn t inadvertently started to spin backwards. Once the series box fan starts, it waits an additional 0 seconds to allow the fan to spin up before it starts to open the damper and introduce airflow from the HVAC unit fan. Parallel Flow Fan Terminals During normal cooling or vent mode and adequate air supply, the parallel fan will be off. During the occupied cooling mode the fan will only activate if the damper/airflow is below a user defined low limit setting. This causes it to be used as a make-up air source. When the damper/ airflow rises 5% above the low limit setpoint, the fan will be deactivated 5

Sequence Of Operations Space ing Mode Occupied Space ing mode is initiated by the temperature in the space falling to within 0.5 ºF of the Occupied ing. If the HVAC unit is in the Supply Air Cooling mode and another VAVBO controller has a heating demand, the damper/airflow for the VAVBO controller requiring heating will position itself to provide the Cooling Minimum amount of air into the space. No modulation open will occur because the space does not want the cold air currently being supplied by the air handler. When the HVAC unit is in the Occupied Supply Air ing mode, the damper will be held at the ing Minimum position until the space temperature falls to within 0.5 ºF of the Occupied ing. As the space temperature falls below the heating setpoint, the damper/ airflow calculation causes the air valve to open proportionally until the maximum setpoint is achieved at 3.5 ºF below the setpoint. This is a 4 ºF proportional window starting 0.5 ºF above the heating setpoint to 3.5 ºF below the heating setpoint. Two different configurations are available for the Occupied Space ing mode. If the box is configured to allow reheat during Supply Air ing mode, the reheat relays can be activated even when the HVAC unit is in the Supply Air ing mode. If the box is configured not to allow reheat when the HVAC unit is in Supply Air ing mode, the box heat relays will be de-energized when the HVAC unit is in Supply Air ing mode. In either configuration, when the HVAC unit is in the Supply Air ing mode, the damper will modulate open proportionally to the space demand. The proportional window for the space temperature is 0.5 ºF above to 3.5 ºF below the heating setpoint. This allows the space to take advantage of the warm supply air in the duct. See Table : Relay Staging - Occupied Mode for a complete layout of the various fan and heat relay staging points. Series Flow Fan Terminals If the has been configured as a Series Fan Powered terminal unit, the series fan relay will activate and run the series box fan continuously anytime the HVAC unit fan is running. Relays Stage On At +0.5 ºF Above Box At Box -.0 ºF Below Box -.0 ºF Below Box Relays Stage Off At +.0 ºF Above Box +.0 ºF Above Box At Box -.0 ºF Below Box Box Fan Relay & Reheat Relay Staging Occupied Mode Series Fan ON With HVAC Fan Series Fan OFF With HVAC Fan Parallel Fan Parallel Fan Stage Stage Stage Stage Table : Relay Staging - Occupied Mode Stage 3 Stage 3 In all cases, before the series box fan can be activated, the air damper is driven fully closed and held that way for 30 seconds to make sure the series box fan hasn t inadvertently started to spin backwards. Once the series box fan starts, it waits an additional 0 seconds to allow the fan to spin up before it starts to open the damper and introduce airflow from the HVAC unit fan. Parallel Flow Fan Terminals On parallel fan powered terminal units, the fan will run whenever Space ing mode is active. At all other times, the fan will only activate if the damper/airflow is below a user defined low limit setting. This causes it to be used as a make-up air source. When the damper/airflow rises 5% above the low limit setpoint, the fan will be deactivated if there are no heating stages active, and no space demand exists. The check for main fan status setting has no effect on the Parallel Fan box when in the occupied mode. The Parallel Fan will only be energized when in the Space ing mode. Unoccupied Mode Sequences Space Vent Mode This mode only applies to the Occupied Mode of operation. If the equipment is in the Unoccupied Mode, then a lack of heating or cooling demand would generate the Off Mode. Off Mode This mode only applies to the Unoccupied Mode of operation. If the equipment is in the Unoccupied Mode, then a lack of heating or cooling demand would generate this mode. The VAVBO controller will put the damper into the Night/Reheat minimum position if check main fan status has been selected. If check main fan status has not been selected the damper will be in the fully closed position. Space Cooling Mode During unoccupied mode the HVAC unit is normally off. Unoccupied Space Cooling mode is initiated by the temperature in the space rising to within 0.5 ºF of the Unoccupied Cooling. 6

If the HVAC unit is in the Unoccupied Supply Air ing mode because one or more of the VAVBO controllers has a heating demand, and another VAVBO controller has a cooling demand, the damper/ airflow for the VAVBO controller requiring cooling will position itself to provide the heating minimum setpoint amount of air into the space. No modulation open will occur because the space does not want the warm air currently being supplied by the air handler. When the HVAC unit is in the Unoccupied Supply Air Cooling mode, the damper will be held at the Night/Reheat minimum position until the space temperature begins to rise above the cooling setpoint. As the space temperature rises to within 0.5 ºF of the Unoccupied Cooling, the damper/airflow calculation causes the air valve to open proportionally until the maximum setpoint is achieved at 3.5 ºF above the setpoint. This is a 4 ºF proportional window starting 0.5 ºF below the cooling setpoint to 3.5 ºF above the cooling setpoint. The damper/airflow is never allowed to modulate outside the user adjusted minimum setpoint and the maximum setpoint. The maximum damper/airflow setpoint applies to heating and cooling modes of operation only. All of the modes have their own individual minimum setting. Series Flow Fan Terminals If the has been configured as a Series Fan Powered terminal unit and check for main status has been selected, the series fan relay will activate and run the series box fan continuously anytime the HVAC unit fan is running. The damper will be held at the Nite/ Reheat minimum until the space temperature begins to rise above the cooling setpoint. If check for main fan status has not been selected, the series fan relay will activate and run the series box fan when in the Space Cooling mode. The damper will be in the fully closed position until the space temperature begins to rise above the cooling setpoint. In all cases, before the series box fan can be activated, the air damper is driven fully closed and held that way for 30 seconds to make sure the series box fan hasn t inadvertently started to spin backwards. Once the series box fan starts, it waits an additional 0 seconds to allow the fan to spin up before it starts to open the damper and introduce airflow from the HVAC unit fan. Parallel Flow Fan Terminals In the Unoccupied Cooling mode the parallel fan will be off whether check for main fan status has been selected or not. If check for main fan status has been selected the damper will be held at the Nite/Reheat minimum until the space temperature begins to rise above the cooling setpoint. If check for main fan status has not been selected the damper will be held in the fully closed position until the space temperature begins to rise above the cooling setpoint. Space ing Mode During unoccupied mode the HVAC unit is normally off. Unoccupied Space ing mode is initiated by the temperature in the space falling to within 0.5 ºF of the Unoccupied Space ing. If the HVAC unit is in the Unoccupied Supply Air Cooling mode because one or more of the VAVBO controllers has a cooling demand, and another VAVBO controller has a heating demand, the damper/ airflow for the VAVBO controller requiring heating will position itself to provide the Night/Reheat setpoint amount of air into the space. No modulation open will occur because the space does not want the cold air currently being supplied by the air handler. When the HVAC unit is in the Unoccupied Supply Air ing mode, the damper will be held at the Night/Reheat minimum position until the space temperature begins to fall below the Unoccupied ing. As the space temperature falls to 0.5 ºF below the Unoccupied ing, the damper/airflow calculation causes the air valve to open proportionally until the maximum setpoint is achieved at 3.5 ºF below the setpoint. This is a 4 ºF proportional window starting 0.5 ºF above the heating setpoint to 3.5 ºF below the heating setpoint. As with the Occupied Mode of operation, two different configurations are available for the Unoccupied Space ing mode. If the box is configured to allow reheat during Supply Air ing mode, the reheat relays can be activated even when the HVAC unit is in the Supply Air ing mode. If the box is configured not to allow reheat when the HVAC unit is in Supply Air ing mode, the box heat relays will be de-energized when the HVAC unit is in Supply Air ing mode. In either configuration, when the HVAC unit is in the Supply Air ing mode, the damper will modulate open proportionally to the space demand. The proportional window for the space temperature is 0.5 ºF above to 3.5 ºF below the heating setpoint. This allows the space to take advantage of the warm supply air in the duct. If check for main fan status is not selected and the VAVBO terminal unit has auxiliary heat (baseboard heat etc.) that does not require the HVAC unit fan to operate, reheat can be used without the HVAC unit fan operating. If check for main fan status is selected, the reheat will only operate when the HVAC unit fan is operating. The can activate auxiliary heating relays if the relay expansion board has been connected and the correct number of heating stages (, or 3) has been configured. During demands for heat, the first stage will activate whenever the space temperature drops below the heating setpoint. The second stage will activate if the space temperature falls.0 ºF below the heating setpoint. The third stage will activate if the space temperature falls.0 ºF below the heating setpoint. There is a two-minute delay between staging. This prevents stages from activating at the same time. Once a heating stage has been activated, it must remain on for at least one minute. Once it has been deactivated, it must remain off for at least two minutes. The third stage relay will deactivate when the space temperature rises to within.0 ºF of the heating setpoint. The second stage relay will deactivate when the space temperature rises to the heating setpoint. The first stage relay will deactivate when the space temperature rises above the heating setpoint by.0 ºF. See Table 3: Relay Staging - Unoccupied Mode for a complete layout of the various fan & heat relay staging points. Series Flow Fan Terminals If the has been configured as a Series Fan Powered terminal unit, the series fan will run continuously when the VAVBO controller is in the Space ing mode no matter whether check for main fan status has been selected or not. If the HVAC unit is in Supply Air ing mode the damper will modulate to maintain the Space ing. Any series fan terminal unit that has check for main fan status selected will also operate its series box fan anytime the HVAC unit controller is broadcasting that the HVAC unit fan is operating, regardless of whether it is calling for heat or not. The damper will be held at the closed position until the main fan status broadcast is received. Once the broadcast 7