EOS REMSDAQ CALLISTO NX TYPE E RTU

Similar documents
EOS LUCY GEMINI 3 TYPE E RTU

ECS LUCY GEMINI 3 CONFIGURATION PROCEDURE

ECP SECONDARY SUBSTATION COMMISSIONING PROCEDURE

ECS TYPE E RTU AND ANCILLARY ITEMS INSTALLATION PROCEDURE

EOS SCHNEIDER RINGMASTER 'C' RANGE SWITCHGEAR

EDS SCADA NUMBERING SYSTEM

EOS LUCY SABRE 'A' RANGE SWITCHGEAR

ECP GPRS/3G/4G COMMS DEVICE CONFIGURATION AND COMMISSIONING PROCEDURE

EDS MW AND MVAR TRANSDUCER CONNECTION

EBB PILOT FOR THE LIVE CONNECTION OF UNMETERED EQUIPMENT TO OVERHEAD LINES

ECP NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE

EDS KV, GRID AND PRIMARY SYSTEM PROTECTION AND CONTROL SCHEMES

EDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES

Substation Workshop. 7 th February 2018

EDS LV CUSTOMER UNMETERED SUPPLIES

POWER GRID AUTOMATION. Pág.. n. RMU Automation

Specification Voltage Limiting Device

ELECTRICAL, INSTRUMENTATION & CONTROL SYSTEMS

Company Directive STANDARD TECHNIQUE: TP18A/1. Application of Connection Control Panels for Soft Intertrip and/or Voltage Constraint Schemes

TENGIZ PROJECT - FIELD SUBSTATION REPLACEMENT

MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES

Design Guidelines for SCADA & DSA

Electrical Demand Specification (Reference SOP: )

ECP REMSDAQ CALLISTO 1 CONTROL UNIT AND RTU INSTALLATION PROCEDURE

NPS/003/017 TECHNICAL SPECIFICATION FOR A GROUND MOUNTED DISTRIBUTION SWITCHGEAR REMOTE CONTROL SYSTEM.

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM

Airfield Lighting Control System

DS Agile C264. Grid Solutions. Dual-bay Modular Substation Controller. Multi-function Controller. Automation and Control. Advanced Communication

SPI PowerNet requirements for the non-contestable Interface Works at Deer Park Terminal Station

Synchronous switching of distribution sub networks

DNP Points List and Implementation

NEO 3000 Substation System THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES. Energy Sector

NEXT GENERATION NETWORK RESTORATION APPROACHES ON DISTRIBUTION FEEDERS

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers

MESP MODULAR SUBSTATION USER REQUIREMENTS

Easy Networking for Power Monitoring. network based MONITORING SOLUTIONS

Lowering Lifecycle Costs

DNP Points List and Implementation

extending the boundaries of technology evolution of proven technology FEATURES

ABB SACE A division of ABB S.p.A. L.V. Breakers Via Pescaria 5, Bergamo - Italy Phone: Fax:

Rapier GX Gas Enclosed Load Break Switch and Sectionaliser up to 38kV with automation or remote control options ENGINEERING BRILLIANT SOLUTIONS

Flexible Urban Networks Low Voltage Successful and safe installation, commissioning and operation of LV switches and circuit breakers on LV networks

PQM - Power Quality Monitoring

Blueprint Data Center

Smart Energy & Power Quality Solutions. UMG 96S Universal flush-mounting measuring instrument

EDS HV NETWORK DESIGN

DNP Points List and Implementation for Universal Controls

MNS Platform, low voltage systems Rear Access Power Motor Control Center. Alberto Carini, Global Product Manager

Distribution Network Visibility

EDS GUIDANCE FOR THE APPLICATION OF ENA ENGINEERING RECOMMENDATIONS G88 AND G81 - INSET NETWORKS (IDNOS AND OTHER LICENSED DNOS)

Automation System Solutions

SACE Emax 2 Specification guide

Title System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP)

UMG 96RM. UMG 96RM Universal measurement instrument. Areas of application

Technical Specifications. Multi Function Meter

Power System Network Simulator (PSNsim)

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

Distributed Generation Requirements Update

Protection, Monitoring, and Control System for Distribution Substations ALARM HISTORY SYSTEM COMM. On-Line Documentation TRANSFORMER 12 MW

MESP TECHNICAL SPECIFICATION FOR 22 kv METAL ENCLOSED SWITCHGEAR

U niversal Measuring Device UMG 96 S. Little Fieldbus Giant. Modbus / Profibus. Harmonics. Memory. Analogue outputs. Digital I/O

DEIF A/S. MIC Multi-instrument G. Data sheet. Features. Accuracy. Measurements. Installation. Intelligent. Display. Communication DEIF A/S

1. Project Description

PowerLogic power-monitoring units. Power Meter PM500. Technical data sheet 2006

Electrical Integration with Smart Communication

AUTOMATIC TRANSFER SWITCH CC2 & AC5 CONTROL PANELS

MultiCube. Modbus Data Tables. August Northern Design (Electronics) Ltd Bradford UK

reliable company...caterpillar

DIRIS N. Electrical network analysis system for quality control of your facilities

Network Configuration Document Selection for New Substations Framework

M-Bus Central Unit. Use

E 1. SPECOM - Network analyser. Content. E.2 Description. E.3 Specom C - Technical data. E.4 Specom M - Technical data. E.5 Data communication

VIP 40/45 VIP 400/410

REL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45

U niversal Measuring Device NEW! UMG 96 S. Little Fieldbus Giant. Modbus / Profibus. Harmonics. Memory. Analogue outputs.

Our Power & Control line of Business offers solutions that safely distribute power to your home or business. Our product range includes Low/Medium

ENGINEERING AND SERVICES FIRM THAT SPECIALIZES IN HYDROELECTRIC POWER AND CONTROL SYSTEM DESIGN, OUR TEAM OF PROFESSIONALS HAVE WORKED TOGETHER

GE Zenith ZDEC Modular Paralleling Switchgear

Mics KERYS FEATURE MAN-MACHINE INTERFACE MODULARITY / PROTECTION MEASUREMENTS / CONTROL ARCHITECTURE COMMUNICATION PRODUCT PLUS POINTS KER/GB-2004/1

Package Substation. The efficient solution for your electrical distribution network

Lecture 5 Substation Automation Systems. Course map

g Energy Multilin Recloser Controller DGCR Communications Protection Automation & Control Security & EnerVista Software Hardware Metering & Monitoring

AcuRev Multi-Circuit Power and Energy Meter. Shop for Accuenergy products online at:

Smart Grid solutions. Reliable innovation. Personal solutions. Public distribution. System LEVEL 2. Communications LEVEL 1. Network LEVEL 0 ADA SCADA

MESP TECHNICAL SPECIFICATION FOR SCADA CABLING IN SUBSTATIONS

EMDX3 Multifunction meter Cat No ModbusTable LGR EN v1.01.xls

PRODUCT BROCHURE. Cyberex Remote Power Panel (RPP) Power distribution system

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485

Peter Overgaauw Pascal Stijns 27 Oct 2016 EXPERION PKS CONTROLS ELECTRICAL SYSTEMS TOO!

EM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters

SIGMA. Advanced Generator Protection and Control. Short Form Catalogue

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

Automate and Preserve Electromechanical Relay Investment Part 3 of 3 Using the Bitronics 70 Series to Improve Remote Monitoring and Control

Smart Energy & Power Quality Solutions. UMG 505 Power analysis, LON and I/O-Vielfalt

Technical data sheet. PowerLogic power-monitoring units EM3500 series DIN Rail meter

Wise HP33 THREE PHASE HIGH PRECISION AVR SURVO-MOTOR AUTOMATIC VOLTAGE STABILIZER

ICX-CMOS-E-2006 Electrical / I&C Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS

MiCOM P111. Three phase and earth fault overcurrent relays

EARTH-FAULT AND SHORT-CIRCUIT INDICATOR TYPE EKL8001 / EKL8002 surface mounted

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

Transcription:

Document Number: EOS 05-9306 Network(s): Summary: ENGINEERING OPERATING STANDARD EOS 05-9306 REMSDAQ CALLISTO NX TYPE E RTU EPN, LPN, SPN This standard details the application, installation and operation of the Remsdaq Callisto NX Type E RTU. Author: James Ford Approver: Paul Williams Date: 19/07/2017 This document forms part of the Company s Integrated Business System and its requirements are mandatory throughout UK Power Networks. Departure from these requirements may only be taken with the written approval of the Director of Asset Management. If you have any queries about this document please contact the author or owner of the current issue. Applicable To UK Power Networks External Asset Management G81 Website Capital Programme UK Power Networks Services Connections Contractors Health & Safety ICPs/IDNOs Legal Meter Operators Network Operations Procurement Strategy & Regulation Technical Training THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE

Revision Record Version 1.0 Review Date 19/07/2022 Date 07/06/2017 Author James Ford New document detailing the features of the Remsdaq Callisto NX Type E RTU Version Date Review Date Author UK Power Networks 2017 All rights reserved 2 of 13

Contents 1 Introduction... 4 2 Scope... 4 3 Glossary and Abbreviations... 4 4 Description... 6 4.1 Remsdaq Callisto NX Type E RTU Overview... 6 4.2 Remsdaq Callisto NX Type E RTU... 6 5 Operation... 7 5.1 Local Controls and Indications... 7 5.2 Local Operations from the Control Unit... 7 6 Telecontrol... 8 6.1 Power-On Controls... 8 6.2 Power-On Indications and Alarms... 8 7 Asset Register Data... 12 8 Manufacturer s Documentation... 12 9 Installation and Commissioning... 12 10 Inspection and Maintenance... 12 11 References... 12 11.1 UK Power Networks Standards... 12 11.2 National and International Standards... 13 12 Dependent Documents... 13 Figures Figure 1 Remsdaq Callisto NX RTU Layout... 7 Tables Table 1 Power-On controls... 8 Table 2 Power-On Digital Indications and Alarms... 8 Table 3 Power-On Analogue Indications... 10 Table 4 Remsdaq Callisto NX Ellipse Data... 12 UK Power Networks 2017 All rights reserved 3 of 13

1 Introduction This standard details the application, installation and operation of the Remsdaq Callisto NX range of remote terminal units (RTU). The following is included in this document: General description; Local operation; Power-On telecontrol facilities; Asset Register details; Installation and commissioning; Inspection and maintenance; Documentation. Type E RTUs are used to provide control and monitoring for ground mounted secondary switchgear. 2 Scope This standard applies to the following: Remsdaq Callisto NX (Type E) RTU used with the new UKPN design secondary switchgear on the EPN, LPN and SPN secondary distribution networks (11kV). 3 Glossary and Abbreviations Term ACB CB CT DNP3 DSL EFPI FPI GPRS/3G/4G HMI I/O IP LV PAKNET PLTU Power-On RJ45 Definition Air Circuit Breaker Circuit Breaker Current Transformer SCADA Protocol Digital Subscriber Line (broadband comms over copper cables). ADSL circuits are rented and SHDSL are UK Power Networks owned Earth Fault passage Indicator Fault Passage Indicator Communications networks provided by Vodafone and O2 Human/Machine Interface Input/Output, analogue, digital and control data Internet Protocol Low Voltage Data comms service provided by Vodafone Parasitic Load Tripping Unit Network management system used in UK Power Networks Standard communications plug/socket interface UK Power Networks 2017 All rights reserved 4 of 13

RMU RTU SIM SCADA THD TX UK Power Networks Ring main Unit Remote Terminal Unit Subscriber Identity Module. Identity card used to provide access to GPRS/3G/4G networks Supervisory Control and Data Acquisition Total Harmonic Distortion Transformer UK Power Networks (Operations) Ltd consists of three electricity distribution networks: Eastern Power Networks plc (EPN). London Power Network plc (LPN). South Eastern Power Networks plc (SPN). UK Power Networks 2017 All rights reserved 5 of 13

4 Description 4.1 Remsdaq Callisto NX Type E RTU Overview The Remsdaq Callisto NX Type E RTU/Controller includes the following features: Remote control of up to four switches or circuit-breakers; Integral FPI/EFPI functionality; Integral PLTU functionality; Mains powered with battery back-up; Battery test/monitoring functionality; Self monitoring; IP Communications (including GPRS/3G/4G, xdsl, Satellite and Fibre); PAKNET Communications; DNP3 protocol; Control/monitoring of all UK Power Network spec RMUs and ACBs; A, V, kw kva kvar monitoring of the TX LV (depending on the capabilities of the power meter installed); Current monitoring of the RMU Tee CB (depending on the capabilities of the protection relay/transducer installed); Current monitoring of the RMU ring switches via the FPI CTs and RTU/RMU Umbilical cables; Remote configuration capability; Additional hardwired I/O not included in the Type E RTU design can be connected using the Auxiliary I/O box. 4.2 Remsdaq Callisto NX Type E RTU The Remsdaq Callisto NX provides the control and monitoring functionality for: UKPN Spec RMUs. LPN ACBs. 11kV/LV Transformer LV way. The Remsdaq Callisto NX RTU utilises modern IP communications and can operate with any compliant IP communications systems, such as GPRS/3G, DSL etc, and will also operate using the PAKNET system. The main details of the Remsdaq Callisto NX Type E RTU are shown in Figure 1. UK Power Networks 2017 All rights reserved 6 of 13

Figure 1 Remsdaq Callisto NX RTU Layout The RTU can be mounted to the wall of a GRP or brick substation, or can be mounted using a floor standing frame in an open substation. 5 Operation 5.1 Local Controls and Indications Local controls and indications are facilitated by the use of the touch screen HMI mounted inside the RTU cabinet, see Figure 1. 5.2 Local Operations from the Control Unit The touch screen HMI (see Figure 1) is configured to initiate or display any function the RTU is capable of, such as: Local/remote selection. Switch or circuit-breaker open/close. Dummy circuit-breaker open/close. Check analogue values. Check alarm/indication states. UK Power Networks 2017 All rights reserved 7 of 13

6 Telecontrol Full telecontrol facilities including remote control, indications and alarms are available from Power-On and described in this section. 6.1 Power-On Controls The available telecontrol operations are given in Table 1. Table 1 Power-On controls Description Switch/CB Open/Close (up to 4) Dummy Circuit-breaker Open/Close Start/Stop battery test Reset FPI PLTU 1 Logic Enable/Disable Comments 6.2 Power-On Indications and Alarms The available telecontrol indications and alarms are shown in Table 2 and Table 3. All plant failure alarms should be reported for investigation and remedial action in a timely manner to avoid failure of the equipment. Table 2 Power-On Digital Indications and Alarms Description Switch/CB Open/Closed (up to 4) Dummy Circuit-breaker Open/Closed LV1 loss of voltage LV2 loss of voltage Power Meter 1 Comms failed Power Meter 2 Comms failed Mains Fail RTU Imminent Shutdown RTU charger failure Battery test Battery failure Common RTU/plant fault Watchdog restart RTU has been reset RTU Cabinet Door open Flood Alarm Comments The RTU will shutdown in one hour to preserve battery. RTU battery test result RTU battery voltage below threshold RTU has been restarted due to an internal watchdog. Connected via additional I/O box UK Power Networks 2017 All rights reserved 8 of 13

Description Intruder Alarm LV1 loss of voltage Switch on local control PLTU Logic Disabled PLTU Logic Operated PLTU Logic Failed to Operate PLTU Switch 1/2 Voltage Mismatch Switch 1 Phase Fault Switch 1 Earth Fault Switch 2 Phase Fault Switch 2 Earth Fault Switch 3 Phase Fault Switch 3 Earth Fault Switch 4 Phase Fault Switch 4 Earth Fault Switch 1 FPI Switch 2 FPI Switch 3 FPI Switch 4 FPI Switch 1 Actuator Disabled Switch 2 Actuator Disabled Switch 3 Actuator Disabled Switch 4 Actuator Disabled TLF / Protection operated Low Gas Switch 1 L1 HV voltage lost Switch 1 L2 HV voltage lost Switch 1 L3 HV voltage lost Switch 2 L1 HV voltage lost Switch 2 L2 HV voltage lost Switch 2 L3 HV voltage lost RTU has power cycled router Modbus device 3 comms failed Modbus device 4 comms failed Power Meter 1 Comms failed Power Meter 2 Comms failed Comments Connected via additional I/O box UK Power Networks 2017 All rights reserved 9 of 13

Description LV2 loss of voltage Modbus device 3 comms failed Modbus device 4 comms failed Power Meter 1 Comms failed Power Meter 2 Comms failed LV2 loss of voltage Comments Table 3 Power-On Analogue Indications Description Switch 1 L1 HV Current Switch 1 L2 HV Current Switch 1 L3 HV Current Switch 2 L1 HV Current Switch 2 L2 HV Current Switch 2 L3 HV Current Switch 3 L1 HV Current (via RTU input) Switch 3 L2 HV Current (via RTU input) Switch 3 L3 HV Current (via RTU input) Switch 4 L1 HV Current (via RTU input) Switch 4 L2 HV Current (via RTU input) Switch 4 L3 HV Current (via RTU input) LV1 Real Power (kw) LV1 Apparent Power (kva) LV1 Reactive Power (kvar) LV1 Power Factor LV1 L1 (red) Phase Voltage LV1 L1 (red) Phase Current LV1 L1 (red) Phase Voltage THD (%) LV1 L1 (red) Phase Current THD (%) LV1 L1 (red) Phase Real Power (kw) LV1 L2 (yellow) Phase Voltage LV1 L2 (yellow) Phase Current LV1 L2 (yellow) Phase Voltage THD (%) LV1 L2 (yellow) Phase Real Power (kw) LV1 L3 (blue) Phase Voltage Comments Spare for future I/O Spare for future I/O Spare for future I/O Spare for future I/O Spare for future I/O Spare for future I/O UK Power Networks 2017 All rights reserved 10 of 13

Description LV1 L3 (blue) Phase Current LV1 L3 (blue) Phase Voltage THD (%) LV1 L3 (blue) Phase Current THD (%) LV1 L3 (blue) Phase Real Power (kw) LV1 Neutral Current LV2 Real Power (kw) LV2 Apparent Power (kva) LV2 Reactive Power (kvar) LV2 Power Factor LV2 L1 (red) Phase Voltage LV2 L1 (red) Phase Current LV2 L1 (red) Phase Voltage THD (%) LV2 L1 (red) Phase Current THD (%) LV2 L1 (red) Phase Real Power (kw) LV2 L2 (yellow) Phase Voltage LV2 L2 (yellow) Phase Current LV2 L2 (yellow) Phase Voltage THD (%) LV2 L2 (yellow) Phase Current THD (%) LV2 L2 (yellow) Phase Real Power (kw) LV2 L3 (blue) Phase Voltage LV2 L3 (blue) Phase Current LV2 L3 (blue) Phase Voltage THD (%) LV2 L3 (blue) Phase Current THD (%) LV2 L3 (blue) Phase Real Power (kw) LV2 Neutral Current Air Temperature Transformer 1 Temperature Transformer 2 Temperature RTU Battery Voltage RTU Battery Current Switch 3 L1 HV Current (via modbus) Switch 3 L2 HV Current (via modbus) Switch 3 L3 HV Current (via modbus) Switch 4 L1 HV Current (via modbus) Switch 4 L2 HV Current (via modbus) Switch 4 L3 HV Current (via modbus) Comments Connected via additional I/O box Connected via additional I/O box Connected via comms bus Connected via comms bus Connected via comms bus Connected via comms bus Connected via comms bus Connected via comms bus UK Power Networks 2017 All rights reserved 11 of 13

7 Asset Register Data The Remsdaq Callisto NX RTU is recorded in the Asset Register as a control unit (class CU). Table 4 outlines the asset data that should be recorded. Table 4 Remsdaq Callisto NX Ellipse Data ATTRIBUTE NAME ATTRIBUTE DESC NPL VALUE TABLE TYPE ART REF BATTERYTYPE Control Unit Battery Type 2-NPL24-12I $BTY NC BATYEARMANUF Battery Year Of Manufacture $YYN NC RTUNAME RTU Name (LPN) NC SOFTCONFIG RTU Software/Config Version $SOF NC BATTERYCOOL Battery Cooler Fitted N NC MDL Manufacturers Type/Model Callisto NX C MFR Manufacturers Name REM $MFR C YEARMANUF Year Manufactured (E=Estimate) 0000 $YMN C SERIALNO Serial Number C 8 Manufacturer s Documentation The manufacturer s user manual is available in the Alfresco Library. Alfresco > Reference Library > Manufacturers > Remsdaq. 9 Installation and Commissioning The installation and commissioning details are given in the commissioning document (see section 11). 10 Inspection and Maintenance The Remsdaq Callisto NX is nominally maintenance free. The battery is designed for a life of 8 years and should be replaced after this time. All Remsdaq Callisto NX RTUs will have a maintenance schedule task (MST) setup in the Asset Register for the battery replacement in accordance with the Inspection and Maintenance Frequency Schedule (see section 13). Additionally, the battery is also monitored via telecontrol. If a battery failure alarm is received in Power-On the battery should be replaced immediately. 11 References 11.1 UK Power Networks Standards EDS 05-9003 UK Power Networks RTU Specification EAS 05-9016 Remsdaq Callisto NX EMS 10-0002 Inspection and Maintenance Frequency Schedule ECP 11-0536 Remsdaq Callisto NX RTU Commissioning Procedure and Test Forms UK Power Networks 2017 All rights reserved 12 of 13

11.2 National and International Standards The Distribution Code (http://www.dcode.org.uk/) The Electricity Safety, Quality and Continuity Regulations (ESQC) 2002 as amended (2006) BS 7671:2008 incorporating Amendment No 1: 2011 Requirements for Electrical Installations (IEE Wiring Regulations Seventeenth Edition) 12 Dependent Documents The documents below are dependent on the content of this document and may be affected by any changes. EAS 05-9016 EBP 03-0102 ECP 11-0501 ECP 11-0601 ECS 05-9540 ECS 05-9542 Remsdaq Callisto NX HV Switchgear Remote Control Changes Secondary Ground Mount Substation Commissioning Procedures GPRS/3G/4G Comms Device Commissioning Procedure Type E RTU and Ancillary Items Installation Procedure Remsdaq Callisto NX Configuration Procedure UK Power Networks 2017 All rights reserved 13 of 13