FX-485PC-IF RS485 Interface Unit Hardware Manual

Similar documents
USER'S GUIDE FX-485ADP COMMUNICATION ADAPTER FX0N-485ADP COMMUNICATION ADAPTER

FX2N-4AD-PT SPECIAL FUNCTION BLOCK

FX1N-4EX-BD Input Expansion Board

FX1N-2EYT-BD Output Expansion Board

USER S MANUAL. FX2N-64DNET DeviceNet Interface Block

INTRODUCTION FX2N-1HC SPECIAL FUNCTION BLOCK USER S GUIDE

FX2NC-ENET-ADP Ethernet adapter USER'S MANUAL

VB -1HC SPECIAL FUNCTION BLOCK USER'S GUIDE

FX1N JAPANESE SPECIFICATION UNITS

FX-1HC SPECIAL FUNCTION BLOCK USER'S GUIDE

FX2N-232IF RS232C INTERFACE BLOCK

USER S MANUAL. FX2N-32ASI-M AS-interface Master Block

HARDWARE MANUAL GRAPHIC FX-50DU-TK(S)-C UNITS

1) Indicates that the identified danger WILL cause physical and property damage.

USER S MANUAL. FX2N-32DP-IF Profibus-DP Interface Unit

MODEL: R2K-1 SEN TRONIC AG. R2K Series

OPERATION NANUAL E-20TP TEACHING PANEL

EX-RC1 Remote I/O Adapter

Manual name Manual No. Description. When installed to a PLC 2 (0.07) (1.57) (0.35) (1.03) (0.86) 28 (1.1) (0.55) 2.6(0.1) (1.25) 8 (0.31) 8 (0.

AD-8923-BCD. Remote Controller (BCD) INSTRUCTION MANUAL 1WMPD

Manual Fiber Optic Interfaces

Manual Industry Interfaces

FX2N-232IF RS232C INTERFACE BLOCK

MODEL: R1M-D1. PC Recorders R1M Series. SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.)

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

TABLE OF CONTENTS. Communication Functions

EX-RC1 Remote I/O Adapter

MODEL: R1M-A1. PC Recorders R1M Series. SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.)

Package Contents. GP3000H Direct-connect Cable Installation Guide. Safety Precautions. About the Manual

IO-PT4. Component identification. User safety and equipment protection guidelines. Unitronics Industrial Automation Systems 1

EX-RC1 Remote I/O Adapter

Appearance Size (mm) Power supply voltage Model (W H D) 100 to 240 VAC K3SC to 240 VAC

Select a Data Communication Interface

MODEL: R1M-P4. PC Recorders R1M Series. SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.)

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

Industriefunkuhren. Technical Manual. Signal Converter. for DIN Rail Mounting Series 4800xx-yy ENGLISH

This guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens).

1) Indicates that the identified danger WILL cause physical and property damage.

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B.

Guidelines for the Safety of the User and Protection of the F940WGOT Series.

Package Contents. GP3000H Direct-connect Cable Installation Guide. Safety Precautions. About the Manual

W&T. Universal Fiber Optic Interface Converter W&T. Manual. Universal FO Interface Converter. Model Release 1.0. Subject to error and alteration

F1000 User's Manual. (Version: V1.01)

Unitronics Devices and RS485 Table Of Contents

IO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs

Communication Controller CC-Link/CPL Converter CMC10A

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)

Guidelines for the Safety of the User and Protection of the F94*GOT-*WD-E

About the Manual. ST-3300 Series Installation Guide. Package Contents

About the Manual. ST-3400 Series Installation Guide. Package Contents

1. Safety Precautions (Read these precautions before use.)

USER'S MANUAL - MODBUS Serial Communication Edition FX3U SERIES PROGRAMMABLE CONTROLLERS

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

R1M-GH BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL PC RECORDER MODEL. (thermocouple or DC input, 16 points)

MODEL: R1M-GH. PC Recorders R1M Series

IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs

8 Channel USB to RS485/422 Converter USB-402 User s Manual Ver. 1.0 HuMANDATA LTD.

This document hosted by: Extension Load Cell Cable (OP-02)

VIGOR PROGRAMMABLE LOGICAL CONTROLLERS VIGOR ELECTRIC CORP.

USER S MANUAL. FX2N-5A Special function block

R1M-GH BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL PC RECORDER MODEL. (thermocouple or DC input, 16 points)

V E1B Snap-in I/O Module

This guide provides basic information for Unitronics controllers V C30B and V T40B.

Operating Manual UMB ISO Converter ISOCON Order Number: 8160.UISO

V E1B Snap-in I/O Module

Hardware Manual RM CANview

MODEL: GR8-EM. Communication Adaptor GR8 Series

Vision OPLC. General Description. Standard Kit Contents. Installation Guide Vision120. This guide provides basic information for Unitronics Vision120.

W&T Manual Interface modules W&T

Safety Relay Unit (I/O Unit Type)

SCB-C08 USB to RS232/422/485 Converter

V E2B Snap-in I/O Module

EasySync Ltd. ES-R-2x01-M RS232 to RS422 / RS485 Converter. User Guide. Document Reference No.: ES_ Version draft Issue Date:

Installation Guide V1210-T20BJ This guide provides basic information for Unitronics controllers V1210-T20BJ.

Media Converters. Media Converters. Product Selection Guides

Table 8 shows the pin configuration and function of a standard computer-to-printer parallel cable. Table 8 Parallel Cable Pin Configuration

OHIO SEMITRONICS, INC. AC MULTIFUNCTION PROGRAMMABLE TRANSDUCERS & -1000L

USER S MANUAL Enhanced Communication Function

Four opto-isolated signal channels: SD, RD, RTS, and CTS. Electrical compatibility with RS-485. A 5V DC/DC converter for power isolation

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B.

USB to RS232 Converter USB-013 (Rev3) User s Manual Ver. 1.2 HuMANDATA LTD.

Product Manual. USB to Optical Adapter Industrial Isolated RS- 232/422/485. Coolgear, Inc. Version 2.1 December 2018 Model Number: USB-COMi-Si-M

IST ULTRASTAB Power Supply for high precision transducers

Bluetooth to RS-232&RS422/485. EX-9132B/BI Bluetooth Adapter Operation Manual

RS485 MODBUS Module 6RO

User safety and equipment protection guidelines

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY

Appendix G. CJ1W-CIF11 RS-422A Converter

FP-1000PW. Thermal Printer User s Manual. Fujitsu Isotec Limited. KA02066-Y Standard Model Built-in Power Supply Model FP-1000

PSM-ME-RS232/TTY-P Interface converter for RS-232 to TTY transmission systems

MILLENIUM MASI INSTALLATION MANUAL NTR 748 / E. Simple Automation Control Module (MAS)

Appendix 3 Using NS-AL002 Converters

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual

RTU560 Remote Terminal Unit Connections and Settings

IST ULTRASTAB Power Supply for IT/ITN ULTRASTAB transducers

Connection Guide (RS-232C)

Series LC6D/LC6C. LJ1 LG1 LC1 LX LC6D/LC6C Switches LC6C LC6D. Series LX Dedicated Stepper Motor Driver and Positioning Driver

Installation and commissioning guide SmartLink Host Communication Module (HCM-GPU)

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01

Transcription:

JY992D81801B Date: 2015 April FX- RS485 Interface Unit Hardware Manual This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX- RS485 Interface Unit. It should be read and understood before attempting to install or use the unit. Further information can be found in the FX Communication User s manual. If in doubt at any stage during the installation of the FX- Interface Unit always consult a professional electrical engineer who is qualified and trained to the local and national standards. 1. Introduction The interface unit FX- (hereinafter referred to as ) can exchange signal of RS232C and RS485 (RS422) for computer link. 1.1 External Dimensions FX,FX0N,FX2N,FX2NC,A series programmable controller(s) *1 *1 Each programmable controller requires necessary adaptor or unit for suporting computer link. For system configuration of computer link, refer to FX communication user s manual. For A series, refer to A series manual. Dimensions: mm (inches) Weight: Approx. 0.3kg (0.66lbs) Accessories: Terminating resistor (330Ω 2, 110Ω 1) a) b) c) d) e) f) POW ER RS-232C SD FX- 5 V DC 80 (3.15") RS-422/485 100 (3.94") 30 h) g) (1.18") a) RS232C connector: Used for connection between and computer. b) LED: Lit when the programmable controller sends data to the computer. c) SD LED: Lit when the programmable controller receives data from the computer. d) POWER LED: Lit when 5V is supplied to the power feed jack f). e) Power supply cable grip: Safety grip to prevent disconnection of 5 V power supply. f) Power feed jack: Jack for connecting power supply unit. For using a plug with specifications, refer to section 3.2. g) Terminal cover mounting screws (M3 (0.12")) h) Terminal for RS422/485: Used in connection and programmable controller(s). Terminal This terminal is used when the programmable controller receives data from the computer. This terminal is used when the programmable controller sends data to the computer. Signal ground

1.2 RS232C Connector Pin Layout (D-SUB 25 Pin) 25 24 23 22 21 20 19 18 17 16 15 14 1 2 3 4 5 6 7 8 9 10 11 13 12 2. Wiring 2.1 Connecting to a (RS232C) RS (RTS) and CS (CTS), DR(DSR) and ER (DTR) signals are not used, but are connected inside the, connect wiring depending on the need of the computer. 2.2 Connecting to a Programmable Controller(s) (RS485/RS422) 2.2.1 Selection of Wiring Pin No. Signal Name 1 NC No connection 2 SD (TXD) Send data ( RS232C device(computer)) 3 (RXD) Receive data (RS232C device(computer) ) 4 RS (RTS) No used (These pins are connected inside. In some cases computer 5 CS (CTS) 6 DR (DSR) No used (This pin is connected to ER (DTR) inside. In some cases computer 7 Signal ground 8 to 19 NC No connection 20 ER (DTR) No used (This pin is connected to DR (DSR) inside. In some cases computer 21 to 25 NC No connection Caution for wiring The terminal screws for the terminal block of the RS485 are M3 screws and therefore the crimp style terminal (see drawing) suitable for use with these screws should be fitted to the cable for wiring. For M3 (0.12") For M3 (0.12") Dimensions: mm (inches) 6.2 mm (0.24" ) 6.2 mm (0.24") The terminal tightening torque is 0.5 to 0.8 Nm (5 to 8 kgf.cm), and tighten securely to avoid malfunction. Signal Name Pin No. SD (TXD) 2 (RXD) 3 RS (RTS) 4 CS (CTS) 5 DR (DSR) 6 7 ER (DTR) 20 Wiring of RS485 is one-pair wiring or two-pair wiring. The wiring method is decided according to the usage. Please select the wiring method from the table below. For message wait and on-demand function, please see FX Communication User s Manual. Using Link Signal Name SD (TXD) (RXD) RS (RTS) CS (CTS) DR (DSR) ER (DTR) One-pair wiring (Refer to section2.2.3) Two-pair wiring (Refer to section2.2.2) If is necessary to set the message wait to 70ms If is not necessary to set the message wait to 70ms * 1 Use on-demand function... Recommendation,... OK,... Can not use *1 When using with this wiring method remember to take account for/or ignore the echo of the commands sent from computer.

2.2.2 Two-pair Wiring controllers ' computer link unit A B *1 R is the terminating resistor. Connect the terminating resistor (330Ω) between terminals and, and terminals and. The shield of the shielded twisted-pair cable must be connected to ground (100Ω ). When using parallel link, ground both side. When using no protocol or dedicated protocol, ground one side. Connect terminal to each terminal of the programmable controller main body grounded with resistance of 100Ω. 2.2.3 One-pair Wiring controllers computer link unit *1 R is the terminating resistor. Connect the terminating resistor (110Ω) between terminals and. The shield of the shielded twisted-pair cable must be connected to ground (100Ω ). Connect terminal to each terminal of the programmable controller main body grounded with resistance of 100Ω. 3. Specifications 3.1 General Specifications General specifications other than the those-mentioned below are the same as for the FX or FX2N series programmable controller. Dielectric withstand voltage Insulation Resistance 500 V AC > 1 min, tested between terminals in batch and case 5 MΩ > 500 V DC, tested between terminals in batch and case

3.2 Power Supply Specifications Power source 5 V DC ± 5% Current consumption Max. 260 ma Use a plug with specifications as shown right. 3.3 Performance Specifications 9.5 (0.37") φ5.5(0.22") φ2.1(0.08") Dimensions: mm (inches) Transmission standard RS485/422 RS232C Communication method transmission RS232C distance RS485/422 Supported baud rate Isolation Conforming to RS232C Conforming to RS485 and RS232C Full-duplex communication Max. 15 m Max. 500 m 300 to 19,200 bps Photo coupler isolation and transformer isolation (between programmable controller and communication signal) 4. Diagnostics For diagnostics of computer link, please see FX Communication User s Manual. 4.1 POWER LED Check LED Status Lit Otherwise Power source is OK. Check power supply unit and connection. 4.2 SD LED and LED Check Check the status of the SD LED and the LED. Location LED Status Check Point SD LED is lit Wiring between computer and is OK. Sending data form computer to programmable controller(s). Sending data form programmable controller to computer. SD LED is not lit LED is lit LED is not lit Check wiring between computer and. Check that data has been sent from computer. Wiring between programmable controller and is OK. Check wiring between programmable controller and. Check setting of programmable controller(s) for computer link. Guidelines for the safety of the user and protection of the FX- RS485 Interface Unit This manual has been written to be used by trained and competent personnel. This is defined by the European directives for machinery, low voltage and EMC. If in doubt at any stage during the installation of the FX- always consult a professional electrical engineer who is qualified and trained to the local and national standards. If in doubt about the operation or use of the FX- please consult the nearest Mitsubishi Electric distributor. Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment. All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples. Owing to the very great variety in possible application of this equipment, you must satisfy yourself as to its suitability for your specific application. HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN Specifications are subject to change without notice

FX- RS485 Interface Unit Hardware Manual This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX- RS485 Interface Unit. It should be read and understood before attempting to install or use the unit. Further information can be found in the FX Communication User s manual. If in doubt at any stage during the installation of the FX- Interface Unit always consult a professional electrical engineer who is qualified and trained to the local and national standards. 1. Introduction The interface unit FX- (hereinafter referred to as ) can exchange signal of RS232C and RS485 (RS422) for computer link. 1.1 External Dimensions FX,FX0N,FX2N,FX2NC,A series programmable controller(s) *1 *1 Each programmable controller requires necessary adaptor or unit for suporting computer link. For system configuration of computer link, refer to FX communication user s manual. For A series, refer to A series manual. Dimensions: mm (inches) Weight: Approx. 0.3kg (0.66lbs) Accessories: Terminating resistor (330Ω 2, 110Ω 1) a) b) c) d) e) f) RS-232C POW ER SD FX- RS-422/485 100 (3.94") 30 h) g) (1.18") a) RS232C connector: Used for connection between and computer. b) LED: Lit when the programmable controller sends data to the computer. c) SD LED: Lit when the programmable controller receives data from the computer. d) POWER LED: Lit when 5V is supplied to the power feed jack f). e) Power supply cable grip: Safety grip to prevent disconnection of 5 V power supply. f) Power feed jack: Jack for connecting power supply unit. For using a plug with specifications, refer to section 3.2. g) Terminal cover mounting screws (M3 (0.12")) h) Terminal for RS422/485: Used in connection and programmable controller(s). Terminal 5 V DC This terminal is used when the programmable controller receives data from the computer. This terminal is used when the programmable controller sends data to the computer. Signal ground 80 (3.15") JY992D81801B Date: 2015 April 1.2 RS232C Connector Pin Layout (D-SUB 25 Pin) 25 24 23 22 21 20 19 18 17 16 15 14 1 2 3 4 5 6 7 8 9 10 11 13 12 2. Wiring 2.1 Connecting to a (RS232C) RS (RTS) and CS (CTS), DR(DSR) and ER (DTR) signals are not used, but are connected inside the, connect wiring depending on the need of the computer. 2.2 Connecting to a Programmable Controller(s) (RS485/RS422) 2.2.1 Selection of Wiring Pin No. Signal Name 1 NC No connection 2 SD (TXD) Send data ( RS232C device(computer)) 3 (RXD) Receive data (RS232C device(computer) ) 4 RS (RTS) No used (These pins are connected inside. In some cases computer 5 CS (CTS) 6 DR (DSR) No used (This pin is connected to ER (DTR) inside. In some cases computer 7 Signal ground 8 to 19 NC No connection 20 ER (DTR) No used (This pin is connected to DR (DSR) inside. In some cases computer 21 to 25 NC No connection Caution for wiring The terminal screws for the terminal block of the RS485 are M3 screws and therefore the crimp style terminal (see drawing) suitable for use with these screws should be fitted to the cable for wiring. For M3 (0.12") For M3 (0.12") Dimensions: mm (inches) 6.2 mm (0.24" ) 6.2 mm (0.24") The terminal tightening torque is 0.5 to 0.8 Nm (5 to 8 kgf.cm), and tighten securely to avoid malfunction. Signal Name Pin No. SD (TXD) 2 (RXD) 3 RS (RTS) 4 CS (CTS) 5 DR (DSR) 6 7 ER (DTR) 20 Wiring of RS485 is one-pair wiring or two-pair wiring. The wiring method is decided according to the usage. Please select the wiring method from the table below. For message wait and on-demand function, please see FX Communication User s Manual. Using Link Signal Name SD (TXD) (RXD) RS (RTS) CS (CTS) DR (DSR) ER (DTR) One-pair wiring (Refer to section2.2.3) Two-pair wiring (Refer to section2.2.2) If is necessary to set the message wait to 70ms If is not necessary to set the message wait to 70ms * 1 Use on-demand function... Recommendation,... OK,... Can not use *1 When using with this wiring method remember to take account for/or ignore the echo of the commands sent from computer.

2.2.2 Two-pair Wiring controllers ' computer link unit 3.2 Power Supply Specifications Power source 5 V DC ± 5% Current consumption Max. 260 ma *1 R is the terminating resistor. Connect the terminating resistor (330Ω) between terminals and, and terminals and. The shield of the shielded twisted-pair cable must be connected to ground (100Ω ). When using parallel link, ground both side. When using no protocol or dedicated protocol, ground one side. Connect terminal to each terminal of the programmable controller main body grounded with resistance of 100Ω. 2.2.3 One-pair Wiring A B controllers computer link unit Use a plug with specifications as shown right. 3.3 Performance Specifications Transmission standard RS485/422 RS232C Communication method transmission RS232C distance RS485/422 Supported baud rate Isolation 4. Diagnostics For diagnostics of computer link, please see FX Communication User s Manual. 4.1 POWER LED Check 9.5 (0.37") Conforming to RS232C Conforming to RS485 and RS232C Full-duplex communication Max. 15 m Max. 500 m 300 to 19,200 bps Photo coupler isolation and transformer isolation (between programmable controller and communication signal) φ5.5(0.22") φ2.1(0.08") Dimensions: mm (inches) LED Status Lit Power source is OK. Otherwise Check power supply unit and connection. 4.2 SD LED and LED Check Check the status of the SD LED and the LED. Location LED Status Check Point SD LED is lit Wiring between computer and is OK. Sending data form computer to programmable controller(s). Sending data form programmable controller to computer. SD LED is not lit LED is lit LED is not lit Check wiring between computer and. Check that data has been sent from computer. Wiring between programmable controller and is OK. Check wiring between programmable controller and. Check setting of programmable controller(s) for computer link. *1 R is the terminating resistor. Connect the terminating resistor (110Ω) between terminals and. The shield of the shielded twisted-pair cable must be connected to ground (100Ω ). Connect terminal to each terminal of the programmable controller main body grounded with resistance of 100Ω. 3. Specifications 3.1 General Specifications General specifications other than the those-mentioned below are the same as for the FX or FX2N series programmable controller. Dielectric withstand voltage Insulation Resistance 500 V AC > 1 min, tested between terminals in batch and case 5 MΩ > 500 V DC, tested between terminals in batch and case Guidelines for the safety of the user and protection of the FX- RS485 Interface Unit This manual has been written to be used by trained and competent personnel. This is defined by the European directives for machinery, low voltage and EMC. If in doubt at any stage during the installation of the FX- always consult a professional electrical engineer who is qualified and trained to the local and national standards. If in doubt about the operation or use of the FX- please consult the nearest Mitsubishi Electric distributor. Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment. All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples. Owing to the very great variety in possible application of this equipment, you must satisfy yourself as to its suitability for your specific application. HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN Specifications are subject to change without notice