HI HIPS Logic Solver (2oo3)

Similar documents
Safe & available...vigilant!

SVI II ESD. SIL3 Partial Stroke Test Device October 2007 BW5000-ESD. The only SIL3 Smart ESD device that is live during and after a shutdown.

CO General Specifications GS48D62Z00-00E-N GENERAL. ProSafe-COM extended communication system

Digital Output Module 8-Channel Version for Zone 1 Series 9475/

PRM Integration Guide with. MTL 4840 Series HART Multiplexer

II ESD. SIL3 Partial Stroke Test Device. The only SIL3 Smart ESD device that is live during and after a shutdown.

DeltaV SIS TM. Logic Solver. DeltaV SIS Logic Solver. Introduction. DeltaV SIS Product Data Sheet. World s first smart SIS Logic Solver

Tank terminal demonstrates the electrically operated solution for Emergency Shutdown Valves

Scanner 2000 Steam Mass Flow Transmitter

Digital Output Module 8-Channel Version for Zone 2 Series 9475/

IQ Pro SIL option TÜV Certified for use in SIL 2 & 3 applications

INTRINSICALLY SAFE INSTRUMENTATION FOR HAZARDOUS AREAS

Description. Monitoring functions Evaluation of brush length monitoring, digital, non-floating A00

Safety Instrumented Systems: Can They Be Integrated But Separate?

Chassis Power Supplies

GE Power Management. MMII Intelligent MCC Controller

Safety Control Relay Product Catalog

Fault Tolerant Protection System (Safety PLC with Integrated Overspeed Protection)

Removal of Hardware ESD, Independent of Safety Logic Solver

Polymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3

IQ SIL Option. IQ actuators for use in applications up to SIL 3. sira CERTIFICATION

T500 DUALTACH. JAQUET T500 DualTach. 2 channel measurement & monitoring instrument 2 CHANNEL TACHOMETER I N C H A R G E O F S P E E D.

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, MN USA

Loop-powered Transmitter for Thermocouple Type K (NiCr-Ni)

Safety manual. This safety manual is valid for the following product versions: Version No. V1R0

The TVC Positioner is designed to provide precise position control of rotary or linear hydraulic or pneumatic actuated valve systems.

Control unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V

AI-917-A0. Analogue Input Module (4x 0-20 ma)

Backplane. System integration. Backplane

SIL 2/3 Relays for all applications, with or without Line & Load Diagnostics. Product presentation

Multiphase Flowmeter FlowSys TopFlow Multiphase Meter Operations Manual

TURCK Process Automation IS Interface Technology. Interface Modules. IM Series Cabinet

The new reference class F870S

Hazardous Area Protection

SMARTSCAN INFORMATION

Control unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~

General. Remote I/O A4/1.

2oo4D: A New Design Concept for Next-Generation Safety Instrumented Systems 07/2000

Digital Output Module 4-Channel Version for Zone 1 Series 9475/

Operating Instructions. Intrinsically Safe Isolation Relay for Switches Model: REL manual_rel-6_0505

Intrinsically Safe Barriers

ED17: Architectures for Process Safety Applications

Sigma XT Ancillary Board (K588)

ICS Regent. Monitored Digital Input Modules 24 VDC (T3411) PD-6031

Skilmatic SI3-3 Electric Fail-Safe Actuators

ALTERNATING RELAYS & CONTROLLERS ARM Series

Proline Prowirl 72, 73

MACX MCR-EX-SD LP(-SP)

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

USER MANUAL. Valve System Test Centre 1/26

IQM & IQML RANGE CONTROL AND MONITORING FACILITIES. Publication E420E issue 7/02

ELECTRONIC AND CONTROL PROCESS DEVICES. reliability. professionalism. Company Profile.

Failure Modes, Effects and Diagnostic Analysis

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25H, STT25S, STT25M, STT25D EN0I-6031 March 2010

PF 3100 BMS CARD PRO.FIRE

T4HD: Installation Supplement R8.1.13

Applying branch circuit breakers and supplementary protectors in North America

High-precision valve control using intelligent positioners. sipart

Datasheet - AZM300Z-ST-1P2P-A

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS

SYSTEM COMPONENTS SYSTEM COMPONENTS MODULES

MTL830 SERIES. Cuts installation and cable costs for all IS hazardous-area circuits

Digital Positioner 8049

CONTROL PANEL WIRING SPECIFICATIONS

technical datasheet technical datasheet MTL660 Displays Loop-powered indicators for hazardous areas

SafeC S to MSR127 Conversion

Twickenham. Scientific Instruments. The Transfer Control Module (TCM) Instruction manual, release 1.1

Engineering Guideline. pac-carriers Type for Honeywell system Experion Series C I/O

Terminal Block Catalog Numbers 1719-TB6, 1719-TB6S, 1719-TB8, 1719-TB8S, 1719-TB8Sx2, 1719-TB8x2

Digital Output Module 4-Channel Version for Zone 1 Series 9475/

Operating instructions. Standstill monitor A / / 2011

Safety Barriers. CEAG safety barriers can be used for all kinds of instrumentation applications.

APPLICATION GUIDE. Interface Modules IM Series.

Operating Instructions

RT4F-120V/20A-WAC RECTIFIER

HART Temperature Transmitter for up to SIL 2 applications

Installation & Operation and Maintenance

D Issue D Original. Instruction Manual. Micro Tool Interface

ProductDiscontinued. Rosemount TankRadar Rex. Safety Manual For Use In Safety Instrumented Systems. Safety Manual EN, Edition 1 June 2007

DeltaV Safety Instrumented System (SIS) with Electronic Marshalling

MicroNet TMR Control System

SX90 Process Controller

MEASURING AND MONITORING RELAYS

HR1S-AC Safety Relay Modules

Combinable for All Applications

Intelligent Valve Controller NDX. Safety Manual

Inductive sensor Dual sensors with extended temperature range NI4-DSU35TC-2Y1X2/S97

Mobrey Hydratect 2462

Digital Output Module 8-Channel Version for Zone 2 Series 9475/

FUNCTIONAL SAFETY CERTIFICATE

Eagle Logic Solver (ELS) SPECIFICATION DATA SIL-2 Rated Fire & Gas System

Point Level Transmitters. Pointek CLS200 (Standard) Functional Safety Manual 02/2015. Milltronics

Product Specifications

Dräger Polytron 8200 Stationary gas detector (CatEx)

Safety instructions Overvoltage protection B81-35

Applying branch circuit breakers and supplementary protectors in North America

MTL8000-2/x Series Modular I/O

Inductive sensor For rotary actuators NI4-DSU35TC-2Y1X2

Solutions for Oil and Gas

INTRINSICALLY SAFE Ex ia PSU TYPE AC36W

Transcription:

General Specifications GS48C00Z00-00E-N HI-100-00 HIPS Logic Solver (2oo3) INTRODUCTION HIPS is the abbreviation for High Integrity Protection System. A HIPS is a specific application of a Safety Instrumented System (SIS) designed in accordance with the worldwide agreed and accepted IEC 61508 and IEC 61511 safety standards and consisting at least of the following three (3) main parts: 1. Sensors (Pressure Transmitters) 2. Logic solver 3. Final elements HIPS functionality is to protect fully autonomously any downstream installation(s) against excess pressure by closing the source of the overpressure. Normally this is done by timely closing one or more dedicated safety shutdown valves preventing further pressurization of the downstream installation. A HIPS is defined by the IEC as a complete loop consisting of sensors (pressure transmitters) logic solver and final elements (shutdown valves), as per the picture below, which should be classified at a certain Safety Integrity Level (SIL). Communication to PAS HIPS LOGIC SOLVER PTs 2oo3 Manifold Flow direction Figure 1 HIPS sketch Pipeline HIPS valve 1 HIPS valve 2 Yokogawa Europe Solutions B.V. PO Box 163, 3800 AD, Amersfoort, The Netherlands Tel: (31) 88-464 1000 Fax: (31) 88-464 1111 GS48C00Z00-00E-N Copyright 2011 3rd Edition February 2013

HI-100-00 2 of 10 Logic Solver This document describes the design for a HIPS logic solver using Yokogawa s ProSafe-SLS system which is a standalone, hardwired, solid state safety system from a simple design and built with robust, oversized components. The ProSafe-SLS system has proven itself in the field for more than 40 years. The main design criteria that are embedded in this HIPS logic solver are: 1. High integrity. 2. High availability, low demand for maintenance 3. Totally independent of any other system. 4. Robust design. 5. As simple as possible. HIPS Design Considerations The following design criteria are taken into consideration designing the Yokogawa HIPS logic solver: 1. All safety I/O loops are powered by the HIPS logic solver. 2. All safety I/O loops are configured for use with Eexd certified field equipment. 3. The 3 pressure transmitter input loops are configured in a 2oo3 configuration. 4. All safety functions are based on the DTS (de-energise to safe) principle. 5. The logic solver is implemented with the inherently failsafe Yokogawa ProSafe-SLS system (using the CTL (Core Transistor Logic) technique) certified by TÜV for applications up to and including SIL 4 according IEC 61508. 6. All digital functions are inherent fail-safe (SIL 4). 7. Supply feeders and AC/DC-converters are installed in a redundant configuration to reduce spurious trips. 8. The solenoid valves per HIPS shutdown valve are configured in a 1oo2 configuration. 9. The HIPS shutdown valves are configured in a 1oo2 configuration. HIPS Philosophy The principle aims and objectives of the HIPS are: 1. The protection of personnel. 2. The protection of plant and equipment. 3. The minimisation of pollution to the environment. The main objective of the HIPS system is to provide reliable means for safely isolating and shutting down the installation downstream of the HIPS valves and to initiate the appropriate alarms when process pressure exceeds the high pressure setpoint. Therefore the HIPS will: 1. Sense automatically an abnormal operation or equipment/process condition. 2. React automatically to this condition by shutting down and/or isolating the downstream installation, preventing any consequential effects of the abnormal condition. 3. Provide system status information for the operator and/or other personnel as appropriate.

HI-100-00 3 of 10 Basic Principle The Yokogawa 2oo3 HIPS logic solver (HIPS using 2 out of 3 voting), which is available with different options, is based on one (1) single system design allowing optimal production and test results as well as using the most efficient way of logic design, control panel lay out, power supply and mechanical construction. Redundant power supply converters are implemented to reduce spurious trips. This configuration is a worldwide standard and will benefit the engineering effort for customers and subcontractors. The design principle is based on a system with fixed I/O and functionality to meet all basic needs for HIPS logic solvers. The logic and the HIPS control panel are built into one (1) fixed rack which is mounted on the backplane of the cabinet. All field I/O is connected to terminals. The cable entry (power supply, communication and field cables) is at the bottom. The I/O signals will be made available to the ProSafe- COM which is the communication module that deals with the communication between the ProSafe-SLS and the external world. It has two serial, 2-wire RS-485 communication links which can be connected in dual configuration to one external device or as two (2) separate links to separate external devices. This HIPS functionality is fixed and dedicated to be used in predefined process setup with a Manifold, three Pressure transmitters, HIPS Logic solver, HIPS valves, PAS (see Figure 3) and a HIPS control panel (see Figure 4). The HIPS offers the following functionality: 1. The Manifold is equipped with three transmitters and an interlocking system providing functionality that allows only one transmitter to be tested (isolated from the process) at any one time. If the interlocking system is operated and one transmitter is in test mode (isolated from the process), this will be automatically detected by the logic solver. The trip signal from the transmitter in test mode will be disabled from the trip logic, hence the logic solver will change the trip logic from 2oo3 voting to 1oo2 voting on the two transmitters remaining. 2. The Yokogawa HIPS logic solver is equipped with a Proof Test Configuration (PTC). This PTC allows for proof testing the logic solver including the valves when testing only one transmitter. This facility can only be selected by operating a dedicated key-operated switch located on the local control panel in combination with the manifold test mode. When PTC is selected the Yokogawa HIPS automatically changes the trip logic from 2oo3 voting to 1oo3 voting. The transmitter selected for test via the interlocking manifold can now be used to trip the HIPS. The Transmitter High level trip will trip the logic and close the ESDV 1 / 2 HIPS valves. This test will be used to prove: a. Individual transmitter trip settings tripping the HIPS logic solver. b. Adequate closing time of each of the ESDV 1/2 HIPS valves. 3. The Yokogawa HIPS is provided with a dedicated SOV Test facility. This facility allows for proof testing that individual solenoid valves will trip the relevant HIPS valve. This facility can only be operated by using two dedicated key-operated switches located on the HIPS control panel. By operating the first switch ( SOV x-1 where x is 1 or 2 ) the solenoids for each HIPS valve will be tripped. By operating the second ( SOV x-2 ) switch the solenoids for each HIPS valve will be tripped. The consequence of each operation should be of course the closing of the appropriate HIPS valve. 4. The HIPS can be reset by means of: a. Operating the logic reset on the HIPS control panel (reset logic and the HIPS valves). b. Operating individual local HIPS valve reset facilities when option is enabled. c. Operating the PAS HIPS reset and individual HIPS valve reset when this option is enabled. 5. The Process Automation System (PAS) can read dedicated HIPS information like HIPS I/O and alarms via the serial link(s) to the ProSafe-COM and, if the option is enabled, send HIPS reset, individual HIPS valve reset and close commands for the HIPS valves.

HI-100-00 4 of 10 Figure 2 HIPS functionality overview Figure 3 HIPS Logic solver (2oo3)

HI-100-00 5 of 10 Figure 4 HIPS logic solver control panel The HIPS control panel is included in the logic solver rack which is located inside the cabinet. The indications on this panel are based on the all dark principle, meaning that under normal operational conditions all indications are off. The panel provides the following functionality: -Input indications: PT tripped (3 off, red), PT in test mode (3 off, yellow) PT deviation (1 off, red). -Control indication: Proof Test Configuration (PTC) active (1 off, yellow). -Output indications: Trip to ESD (1off, red), SOV tripped (4 off, red), HIPS valve closed (2 off, red). -Control equipment: Proof Test Switch (1 off, key-operated), Solenoid Test (2 off, key-operated). -Control equipment: HIPS reset (1 off, pushbutton), Lamptest (1 off, pushbutton). The HIPS drawings are a uniform set of ACAD drawings that use internal tagnames like PT1, PT2, SOV 1, SOV 2, etc. Client tagnames will be shown at the relevant places like the control panel. The coupling between client tagnames and Yokogawa internal tagnames can be contained in the I/O-list. A HIPS system fault is indicated on the HIPS front door and is available as volt-free contact for a hardwired alarm to an external device. The alarms initiating this system alarm are individually available to the ProSafe-COM for serial alarming to external devices.

HI-100-00 6 of 10 Yokogawa 2oo3 HIPS Configuration The Yokogawa HIPS logic solver is one single rack that is mounted on the panel mounting plate. The logic solver power supply and I/O is connected via a robust connector. Figure 5 Mounting plate HIPS logic solver

HI-100-00 7 of 10 HIPS Scope The 2oo3 voting HIPS application contains all the basic safety functions necessary to protect the downstream installation against damage as a result of high pressure. On top of this, options have been developed to meet customer s demands on issues not related to the primary safety function. The options chosen will be described in the quotation and are the basis for the table of compliance. If the customer insists on the fulfilment of other requirements that are not foreseen in this solution, Yokogawa will quote a client specific solution. In the quotation phase, options will be chosen that are best fitting the customer s requirements and this will be reflected in the table of compliance. The basic safety functions are pre-described in a Functional design specification (FDS) and Safety Validation Plan (SVP).

HI-100-00 8 of 10 Included in the standard delivery: Nr Item Description 1 Enclosure Rittal TS8 type cabinet, RAL7035, dimensions 800mmx800mm*2100mm (w*h*d) including 100mm plinth, front access door, mounting plate, auxiliary socket and panel lighting. 2 Redundant AC/DC converters. (85 230Vac / 24Vdc / 10A) 3 Failsafe equipment & design. 4 Pressure transmitter inputs. 5 Pressure transmitter test & maintenance Inputs. 6 HIPS Valve Open/Closed inputs. To reduce spurious trips 2 AC/DC converters are implemented in a redundant (2oo2) configuration. Each converter is well capable of supplying power to the complete HIPS under full load conditions. The logic solver is implemented using ProSafe-SLS, the inherent failsafe hardwired Yokogawa safety system. Each of the three (3) PT s is connected to a separate, failsafe analogue input module (0-20mA) providing a logic signal tripping on an adjustable high pressure setpoint, input linefault (3.6 ma<input>21 ma) and deviation alarming functionality is provided. Each PT has one (1) digital input reading the (ASTAVA Manifold) PT block valve status. When the block valve is closed (for maintenance or test) the PT trip signal will be inhibited to the 2oo3 voting logic and change this logic automatically into 1oo2 voting logic. Open/Close signals are available to ProSafe-COM (modbus). Additionally the closed signals are indicated on the control panel as well and will illuminate when HIPS valves are closed. 7 2oo3 voting. The 2oo3 voting logic will initiate a trip when any two out of three pressure transmitter inputs are generating a trip. 8 1oo2 voting. If one pressure transmitter input is in trip condition the logic automatically changes to 1oo2 voting logic. 9 Proof Test Configuration (1oo3 Voting). 10 SOV Output Test Configuration. 11 Individual solenoid outputs (20W) A key-interlocked Proof Test Switch on the control panel is used to switch the logic solver into a 1oo3 voting configuration. This is required to test the complete HIPS (pipe-to-pipe) at certain time intervals in order to keep the HIPS at the required SIL level. Two (2) key-interlocked SOV Test switches on the control panel are used to prove that each HIPS shutdown valve closes on only one solenoid valve trip. There is one (1) switch ( SOV x-1 ) to test the First solenoid valves on both HIPS valves and one (1) switch ( SOV x-2 ) for the Second solenoids both HIPS valves. Each of the four (4) solenoids is connected to an individual fused failsafe output circuit with a maximum power consumption of 20W at 24Vdc. 12 Control panel. Embedded in the logic solver rack and providing functionality as follows: -Input indications: PT tripped (3), PT in test mode (3) PT deviation (1). -Controls indication: Proof test active (1). -Output indications: Trip to ESD (1), SOV tripped (4), HIPS valve closed (2). -Control equipment: Proof Test (1), Solenoid Test (2). (key-operated switches). -Control equipment: HIPS reset (1), Lamptest (1). (pushbuttons). 13 Documentation Functional Design Specification Safety Validation Plan Detailed design documents: Functional logic diagrams, Loop diagrams Hardware documents: Mechanical and Electrical drawings Operating and maintenance instructions Safety Certification

HI-100-00 9 of 10 Ordering Ordering code for the standard 2oo3 HIPS consists of a basic code (HIPS2oo3) and if necessary followed by some features and if required followed by option codes as indicated in the table below. CODE Item Description HIPS2oo3 Standard HIPS Yokogawa standard 2oo3 HIPS solution In the standard delivery the following FEATURES are implemented but disabled. When ordering a HIPS logic solver please specify the appropriate code if the project requires these features to be enabled. CODE Item Additional Features -TTV Trip on Transmitter Deviation This feature enables the logic solver to trip on a deviation alarm; i.e. a deviation above a preset value (in %) between the PT s will cause the HIPS to trip. (Note that if this choice is not enabled the deviation indication on the control panel and deviation alarming to the ProSafe-COM will still be operational). -SLC Serial Link Commands This feature enables serial link commands from an external device for the operation of: HIPS reset, ESDV1 close, ESDV 2 close. -IVRC Individual HIPS Valve Reset Commands This feature enables individual HIPS valve reset command from the field. (i.e. from the HIPS valve control boxes). NOTE: If the features SLC and IVRC are both ENABLED it will also be possible to reset the HIPS valves individually from an external device. Additionally the HIPS valves can be individually closed from this device as well. Additionally the following OPTIONS are available: CODE Item Option Option description /MP24 Main Power supply - Main power supply to the HIPS is 24VDC. 24VDC /CS400 Cabinet Size Depth 400cm - Cabinet size: 800*400*1600mm (w*d*h). (front door access) /FP Control Panel on front - HIPS Control Panel is located in the cabinet front door. door. /SP Field I/O- Surge - Field I/O protected on by surge protectors. Protection /IS Intrinsically Safe field - Field inputs connected via intrinsic safe isolators. input /HQ2 HIPS Quantity 2 Two (2) HIPS logic solvers per cabinet. /SL4 SIL Level 4 4 HIPS logic solver is a SIL 4 classified system. /CD Customer Documentation - Special customer required documents can be provided. When option SP is chosen field I/O will be protected by MTL surge protectors: For inputs type:sd32x. For outputs type:sd150x. When option IS is chosen field inputs will be connected via MTL intrinsic safe isolators: For analogue inputs type: MTL-5541. For digital inputs type: MTL-5517. Example of overall ordering code: HIPS2oo3-TTV-SLC/MP24/IS (2 Features specified, 2 options added)

HI-100-00 10 of 10 Special Versions If required all kind of HIPS (tailor-made) systems can be built using other or the same building blocks as used for this Yokogawa 2oo3 HIPS. This allows a sophisticated custom-made alignment with customer s wishes but needs more design and test effort. Yokogawa will always strive for the optimal solution. Example of special version: - 3 or 4 HIPS in one cabinet - HIPS logic solver rack to be combined within subcontracting cabinet or console - ATEX (Atmosphères Explosives) zone specific cabinet - Earthquake proof cabinet - Cabinet size custom-made - Cabinet Color - Etc.