Network Integration Engine (NIEx9) for Third-Party Integrations Catalog Page

Similar documents
NAE. Metasys. BAS network automation Supervisory controllers. Network Automation Engine

NIEx9. Metasys. BAS network automation Supervisory controllers. Network Integration Engine

Features Communication Using Commonly Accepted IT Standards, Including Web Services, at the Automation and Enterprise Level Web-Based User Interface

Network Automation Engine Catalog Page MS-NAE35xx-x, MS-NAE45xx-x, MS-NAE55xx-x, NAE Software Release 8.1 Issued February 2017

Network Automation Engine Catalog Page MS-NAE35xx-x, MS-NAE45xx-x, MS-NAE55xx-x, MS-NAE551S-2, NAE Software Release 9.0 Issued August 2017

Network Integration Engine (NIEx9) for Third-Party Integrations Product Bulletin

Network Control Engine Catalog Page

NIE59 Network Integration Engine Figure 1: NIE59 Network Integration Engine

Application and Data Server (ADS) Lite-A System Catalog Page

Network Integration Engine Product Bulletin

Network Integration Engine

Network Automation Engine

NIE39/NIE49 Installation Instructions MS-NIE39xx-2, MS-NIE49xx-2

FX-PCX Expansion Input/Output Modules Catalog Page Code No. LIT Issued April 17, 2015

Network Control Engine

NxE85 Commissioning Guide

Metasys N1 Network Integration

Input/Output Module (IOM) Series Catalog Page

Input/Output Module (IOM) Series Controllers Catalog Page Code No. LIT Issued June 2018

PEAK TM. PEAK TM controllers. Mid-Market BAS Smart equipment controllers. HVAC/R controllers

NAE55/NIE55 Installation Instructions MS-NAE55xx-3, MS-NIE55xx-3, MS-NAE5510-2U

Field Equipment Controller (FEC) Series Catalog Page Code No. LIT Issued June 2018

Advanced Application Field Equipment Controller (FAC) Catalog Page

FX-DIS1710 Local Controller Display Installation Instructions Part No , Rev. B Issued April 2016

Application. NAE55 Installation Instructions * S* Installation. Parts included. Materials and special tools needed

LCS85 Product Bulletin

Input/Output Module (IOM) Series Controllers Catalog Page Code No. LIT Issued December 2017

FX Input/Output (I/O) Modules XM07 and XM14

LCS85 Turnkey User's Guide Part No , Rev. F Software Release 6.1 Issued June 17, 2013 Supersedes January 30, 2011

FX-PCA Advanced Application Programmable Controller Catalog Page

Smart Equipment Controls (SEC)

NAE55/NIE55 Installation Instructions MS-NAE55xx-3, MS-NIE55xx-3

FEC - FAC. Metasys controllers. Complex BAS Programmable controllers. Catalog Page. Field Equipment Controllers

Metasys For Validated Environments, Extended Architecture Catalog Page

Medium User Interface (MUI) Version 3

Onboard Inputs and Outputs. Remote User Interface. Integral LCD User Interface

FXVMA Variable Air Volume (VAV) Box Controller

LN Series Remote Input/Output (I/O) Modules

Metasys System Configuration Tool (SCT)

Metasys for Validated Environments, Extended Architecture Catalog Page

FX06 Field Controller

PEAK TM. SMART Equipment Controllers. Product bulletin

TC-9102 Terminal Controller

NCE25 Installation Instructions MS-NCE25xx-x

VMA Programmable VAV Box Controllers Catalog Page Code No. LIT Issued February 2018

TALON Network Manager- 2 & 6 Express

LX Series Remote Input/Output (I/O) Controller

Web server. Simplified.

TC Modular Series for BACnet Networks

Application and Data Server (ADS) Lite-E Catalog Page

FX40 Supervisory Controller

VMA Programmable VAV Box Controllers Catalog Page

Web server. Simplified.

N2 Dialer Module. Features and Benefits

Comprehensive User/Group Security Restrict or allow access to myriad of points based on individual or group credentials

Verasys System Product Bulletin

Supervisory Controllers

FX14 Field Controller

FX-DIS Local Controller Display Technical Bulletin

Product Description. FX22, FX62, and FX70 Supervisory Controllers

TC Compact Series for BACnet Networks

Clarity 3 GCE-8000 EMBEDDED IOT CONTROLLER PRODUCT DATA SHEET

BCPro System Product Bulletin

EC-BOS-8 Multi-protocol Web Building Controller

Overview. Applications. Features

PXC Modular Series. Features. Description. Technical Specification Sheet Document No Rev. 1.1, May 2007

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

EC-BOS-8 Multi-protocol Web Building Controller

TC Compact Series Unitary Equipment Controller

DX-9100 Digital Controller, Version 2

Metasys System Software Purchase Options Product Bulletin

Andover ContinuumTM. b3850 Series Terminal Controllers

LX Series Free Programmable LX-PRG6x0-11 Controllers and LX Series Input/Output (I/O) Extension Modules

PXC Modular Series. Features. Description. Technical Specification Sheet Document No July 24, 2012

FX-BTCVT Bluetooth Commissioning Converter Installation Instructions

controller data sheet JACE 8000 PRODUCT DEFINITION HARDWARE SPECIFICATIONS

[SmartX Controller ] Introduction. Features. SmartStruxure solution

Industrial PC - VL BPC

Pro. LCN1840/05 Wireless gateway. Specification sheet. Connected lighting. Find out more about Interact

The Simply Smart Way to Optimize Building Control and Performance

TC Compact Series for BACnet Networks

DKG-210 UNIVERSAL INTERNET GATEWAY UNIT

Field selectable application type and room module series, via dip-switches on controller

FEC26 Field Equipment Controller

4600 Series RAID-Enabled

M-Tool. Features and Benefits System Configuration and Project Management. Allows fast adjustment and commissioning of systems

HAWK 8000 Controller GENERAL. Product Data. Fig. 1. HAWK 8000

Extended Digital Controller

Metasys System Extended Architecture

BT300 HVAC Drives. Designed for HVAC. Description. Technical Specification Sheet Document No March 4, 2013

Metasys Web Access. Provides full access to M-Alarm for monitoring and acknowledging alarm messages and generating alarm reports

Advanced Graphics Application Catalog Page

Commercial Comfort System (CCS)

Field Advanced Display

RCM Room Command Module New Style

NAE55/NIE55. Installation Instructions. MS-NAE55xx-x MS-NIE55xx-x. Application. Installation. North American Emissions Compliance.

AS-CVTPROx00-0 Zone Bus/N2 Bus Interface Converter

2009 Cisco Systems, Inc. All rights reserved. This document is Cisco Public Information. Page 1 of 6

controller data sheet JACE 8000 PRODUCT DEFINITION HARDWARE SPECIFICATIONS

LCS85 Installation and Upgrade Instructions

Transcription:

Network Integration Engine (NIEx9) for Third-Party Integrations Catalog Page MS-NIE29xx-0, MS-NIE39xx-x, MS-NIE49xx-x, MS-NIE59xx-x, MS-NIE89xx-x Code No. LIT-1900881 Software Release 9.0 Issued December 2017 Refer to the QuickLIT website for the most up-to-date version of this document. Important: NIEx9s are compatible with Metasys system Release 7.0 and later. You may apply the dual trunk integration feature to NIEx9s purchased prior to the current release by using the NIEx9 Driver Manager tool. For information on how to apply the latest package and license files that support dual trunks, refer to the NIEx9 Driver Manager Application Note (LIT-12011919). Network Integration Engines (NIEx9s) for third-party integrations enable IP connectivity and web-based access to Metasys Building Management Systems (BMSs). NIEx9s leverage standard building management communication technologies, including BACnet protocol; LONWORKS protocol; N2 Bus protocol; Modbus, M-Bus (EN 1434-3), and KNX protocols; and third-party proprietary protocols to monitor and supervise a wide variety of HVAC, lighting, security, fire, electrical and thermal measuring, and access control equipment. For third-party integrations, one NIEx9 can support two Modbus integrations, two M-Bus integrations, or one integration of each. The NIE89 is a high-capacity server model that integrates large networks into a Metasys network. The NIE89 supports either 10,000 or 25,000 objects. Modbus Integrations use a Vendor Generator Express (VGE) tool that creates vendor Modbus definition (VMD) tables for specific third-party equipment. You can purchase tables from the System Integration Services North America (SIS-NA) or the SIS-Europe office, or you can create them with the VGE tool. The VGE tool requires certification and licensing for its use. To obtain a license, attend the training listed in Refer to the Network Engines Product Bulletin (LIT-12012138) for important product application and single point of contact information. If the NIEx9 fails to operate within its specifications, replace the unit. For a replacement NIEx9, contact the nearest Johnson Controls representative. Figure 1: NIE59 Network Integration Engine NIEx9s provide comprehensive equipment monitoring and control, scheduling, alarm and event management, energy management, data exchange, data trending, and data storage. NIEx9s feature an embedded Site Management Portal (SMP) UI, support multiple concurrent web browser sessions with password and permission access control, and provide the protection of industry-standard IT security. The NIE29 models enable compact and combined solutions including supervisory and control capacity. They can be used in smaller facilities where an all-in-one (supervisory, control, and integration) platform is required. The NIE39/NIE49 models enable cost-effective NIEx9 connectivity and control in smaller facilities, and can extend NIEx9 supervisory functions in larger facilities. The NIE59 models support a comprehensive set of supervisory features and functions for large facilities and technically advanced buildings and complexes. Features and Benefits Communication Using Commonly Accepted IT Standards at the Automation and Enterprise Level Allows you to install a system on your existing IT infrastructure within a building or enterprise and use standard IT communication services over the company intranet, WAN, or public Internet with firewall protection. Web-Based User Interface Allows you to access system data in the NIEx9s from any supported web browsing device connected to the network, including remote users connected by dial-up telephone or an Internet service provider (ISP). Support for Web Services at the Automation Network Level Allows you to develop facility-specific advanced data interfaces and applications. Embedded Site Management Portal System Configuration Software Provides you with password-protected access to system configuration, monitoring, commanding, diagnosis, and cloud-based applications from any device with web browser software without the need for separate workstation software. Supervision of Controller Networks Including BACnet MS/TP, BACnet IP, N2 Bus, LONWORKS, Modbus RTU, Modbus TCP, M-Bus (EN 1434-3) serial and IP, KNX IP, and third-party protocol devices Supports connectivity to open network standards for complete flexibility in the selection of field devices. Support for Dual Trunks Significantly improves the flexibility and extends the investment of integrations to third-party equipment. The dual trunk feature potentially reduces the number of NIEx9s required on a project and allows you to add integrations to existing NIEx9s that 1

are at Release 7.0 and later. You can more easily adapt to the requirements of projects that have fewer devices that require integration but use separate networks and different protocols. Ordering Information - NIEx9 Models Contact a Johnson Controls representative to order an NIE. Specify the desired product code from the following engine and accessory tables. Table 1: NIE29 Ordering Information 1 MS-NIE29xx-x (base features on each NIE29) MS-NIE2910-0 MS-NIE2916-0 MS-NIE2920-0 MS-NIE2926-0 MS-NIE2960-0 MS-NIE2966-0 Each NIE29 Series model requires a 24 VAC power supply and includes one RS-232-C serial port, one USB serial port, one SA Bus port, one RS-485 or LON port, one Ethernet port, and an MS-BAT1020-0 Data Protection Battery. Each NIE29 Series model supports 33 hard-wired Input/Output points. Up to two ports can be defined for third-party integration. The other ports have to be defined in order to use standard protocols (N2, BACnet MS/TP, or LON). Supports BACnet IP network. Supports two third-party trunks (Modbus RTU 2 or TCP, M-Bus 3, or KNX 4 ) and one N2 Bus. The number of supported devices on the third-party trunk depends on the protocol. For the N2 Bus, up to 32 devices are supported. Supports two third-party trunks (Modbus RTU 2 or TCP, M-Bus 3, or KNX 4 ) and one N2 Bus. The number of supported devices on the third-party trunk depends on the protocol. For the N2 Bus, up to 32 devices are supported. Includes integral display screen. Supports two third-party trunks (Modbus RTU 2 or TCP, M-Bus 3, or KNX 4 ), and one LONWORKS trunk. The number of supported devices on the third-party trunk depends on the protocol. For the N2 Bus, up to 32 devices are supported. For the LONWORKS trunk, up to 32 devices are supported. Supports two third-party trunks (Modbus RTU 2 or TCP, M-Bus 3, or KNX 4 ), and one LONWORKS network trunk. The number of supported devices on the third-party trunk depends on the protocol. For the LONWORKS trunk, up to 32 devices are supported. Includes integral display screen. Supports two third-party trunks (Modbus RTU 2 or TCP, M-Bus 3, or KNX 4 ) and one BACnet MS/TP (RS-485) trunk. The number of supported devices on the third-party trunk depends on the protocol. For the BACnet MS/TP trunk, up to 32 devices are supported. Supports two third-party trunks (Modbus RTU 2 or TCP, M-Bus 3, or KNX 4 ) and one BACnet MS/TP (RS-485) trunk. The number of supported devices on the third-party trunk depends on the protocol. For the BACnet MS/TP trunk, up to 32 devices are supported. Includes integral display screen. 1 For repair parts, add -700 after the code number (for example, MS-NIE2910-700). 2 Modbus RTU (RS-485) may require an RS-232/RS-485 converter. See Table 7. 3 M-Bus protocol requires the addition of an external level converter. M-Bus can also be used over either serial or IP. See Table 8. 4 KNX protocol can only be used over IP and requires the addition of the KNX IP gateway. See Table 9. Table 2: NIE39 Ordering Information 1 MS-NIE39xx-x (Base Features of Each NIE39) MS-NIE3910-2 MS-NIE3920-2 Each NIE39 Series model requires a 24 VAC power supply. Each model includes two RS-232-C serial ports, one USB serial port, one RS-485 or LON port, one Ethernet port, and an MS-BAT1020-0 Data Protection Battery. Up to two ports can be defined for third-party integration. The other ports have to be defined in order to use standard protocols (N2, BACnet MS/TP, or LON). Supports BACnet IP network. Supports two third-party trunks (Modbus RTU 2 or TCP, M-Bus 3, or KNX 4 ) and one N2 Bus or one BACnet MS/TP (RS-485) trunk. The number of supported devices on the third-party trunk depends on the protocol. For the N2 Bus or BACnet MS/TP trunk, up to 50 devices are supported. Supports two third-party trunks (Modbus RTU 2 or TCP, M-Bus 3, or KNX 4 ) and one LONWORKS trunk. The number of supported devices on the third-party trunk depends on the protocol. For the LONWORKS trunk, up to 64 devices are supported. 1 For repair parts, add -702 after the code number (for example, MS-NIE3910-702). 2 Modbus RTU (RS-485) may require an RS-232/RS-485 converter. See Table 7. 3 M-Bus protocol requires the addition of an external level converter. M-Bus can also be used over either serial or IP. See Table 8. 4 KNX protocol can only be used over IP and requires the addition of the KNX IP gateway. See Table 9. 2

Table 3: NIE49 Ordering Information 1 MS-NIE49xx-x (Base features of each NIE49) MS-NIE4910-2 MS-NIE4920-2 Each NIE49 Series model requires a 24 VAC power supply. Each model includes two RS-232-C serial ports, one USB serial port, one RS-485 or LON port, one Ethernet port, and an MS-BAT1020-0 Data Protection Battery. Up to two ports can be defined for third-party integration. The other ports have to be defined in order to use standard protocols (N2, BACnet MS/TP, or LON). Supports BACnet IP network. Supports two third-party trunks (Modbus RTU 2 or TCP, M-Bus 3, or KNX 4 ) and one N2 Bus or one BACnet MS/TP (RS-485) trunk. The number of supported devices on the third-party trunk depends on the protocol. For the N2 Bus or BACnet MS/TP trunk, up to 100 devices are supported. Supports two third-party trunks (Modbus RTU 2 or TCP, M-Bus 3, or KNX 4 ) and one LONWORKS trunk. The number of supported devices on the third-party trunk depends on the protocol. For the LONWORKS trunk, up to 127 devices are supported. 1 For repair parts, add -702 after the code number (for example, MS-NIE4910-702). 2 Modbus RTU (RS-485) may require an RS-232/RS-485 converter. See Table 7. 3 M-Bus protocol requires the addition of an external level converter. M-Bus can also be used over either serial or IP. See Table 8. 4 KNX protocol can only be used over IP and requires the addition of the KNX IP gateway. See Table 9. Table 4: NIE59-3 Ordering Information 1 MS-NIE59xx-3 (Base Features of Each NIE59) MS-NIE5960-3 MS-NIE5920-3 Each NIE59-3 Series model requires a 24 VAC power supply. Each model includes two RS-232-C serial ports, two USB serial ports, two RS-485 ports, one Ethernet port, and one MS-BAT1010-0 Data Protection Battery. Supports up to 100 devices on each N2 or BACnet Master-Slave/Token-Passing (MS/TP) trunk and up to 100 devices on the integration trunk. Up to two ports can be defined for third-party integration. The other ports have to be defined in order to use standard protocols (N2, BACnet MS/TP, or LON). Supports BACnet IP network. Supports two third-party trunks (Modbus RTU 2 or TCP, M-Bus 3, or KNX 4 ) and two N2 or BACnet MS/TP (RS-485) trunks. The number of supported devices depends on third-party protocol. For the N2 or BACnet MS/TP (RS-485) trunk, up to 100 devices are supported. Supports two third-party trunks (Modbus RTU 2 or TCP, M-Bus 3, or KNX 4 ), two N2 or BACnet MS/TP (RS-485) trunks, and one LONWORKS Network trunk. The number of supported devices depends on protocol. For each N2 or BACnet MS/TP (RS-485) trunk, up to 100 devices are supported. For the LONWORKS trunk, up to 255 devices are supported. 1 For repair parts, add -702 after the code number (for example, MS-NIE5960-702). 2 Modbus RTU (RS-485) may require an RS-232/RS-485 converter. See Table 7. 3 M-Bus protocol requires the addition of an external level converter. M-Bus can also be used over either serial or IP. See Table 8. 4 KNX protocol can only be used over IP and requires the addition of the KNX IP gateway. See Table 9. Table 5: NIE89 Ordering Information MS-NIE89SW-0 1 MS-NIE89SW-6 1 MS-MODBUSN89-0 2 MS-MBUSN89-0 2 MS-KNXN89-0 2 MS-15KUPG-0 New NIE89 software only; for new installations or projects Upgrade NIE89 software; for existing NIE89s Modbus driver for NIE89; supports up to 4 Modbus integrations. M-Bus driver for NIE89; supports up to 4 M-Bus integrations. KNX driver for NIE89; supports up to 4 KNX integrations. 15,000 object expansion upgrade for NIE89 (one expansion only per NIE89) 1 Standard NIE89 models support 10,000 objects; an expansion upgrade is available to support an additional 15,000 objects. 2 Must be ordered and licensed with the NIE89 in order to use this protocol. Table 6: NIEx9 Accessories Ordering Information MS-BAT1010-0 MS-BAT1020-0 Replacement data protection battery for NAE55 and NIE59. Rechargeable gel cell battery: 12 V, 1.2 Ah, with a typical life of 3 to 5 years at 21 C (70 F) Replacement data protection battery for NAE35, NIE39, NAE45, NIE45, NIE49, NCE25, or NIE29. Rechargeable NiMH 3.6 VDC, 500 mah battery with a typical life of 5 to 7 years at 21 C (70 F). (Higher operating temperatures reduce battery life.) 3

Table 7: Modbus Accessories Ordering Information IU-9100-8401 (Europe) 1 IU-9100-8404 (Europe) or BM485-CIP (North America) 1 RS232-to-RS485 converter, 230 VAC RS232-to-RS485 converter, 24 VAC 1 European market: order this accessory in AOMS from the Essen Distribution Center. North American market: order this accessory from dutec (http://www.interfaceconverter.com or 1-800-248-1632), specify vendor #290904. Table 8: M-Bus Accessories Ordering Information SIS-MBUSSCSL-0E 1 RS232-to-M-Bus level converter for up to 6 unit loads; 24 VAC/VDC SIS-MBUSSCLL-0E 1 RS232-to-M-Bus level converter for up to 100 unit loads; 24 VAC/VDC SIS-MBUSRPLL-0E 1 RS232-to-M-Bus level repeater for up to 100 unit loads; 24 VAC/VDC SIS-MBUSRPLH-0E 1 RS232-to-M-Bus level repeater for up to 100 unit loads; 230 VAC SIS-MBUSNCLL-0E 1 IP-to-M-Bus level converter for up to 100 unit loads; 24 VAC/VDC SIS-MBUSNCLH-0E 1 IP-to-M-Bus level converter for up to 100 unit loads; 230 VAC INT-DX-KAB01 1 Optional connection cable SUB-D to RJ-12 for use with SIS-MBUSSCLL-0E 1 European market: order this accessory in AOMS from the Essen Distribution Center. Table 9: KNX Accessories Ordering Information SIS-KNXNIXL-0E 1 KNX IP interface module to connect KNX line through Ethernet to an NIEx9 SIS-KNXNRXL-0E 1 KNX IP router to connect KNX line through Ethernet to an NIEx9, including line or area coupler functionality 1 European market: order this accessory in AOMS from the Essen Distribution Center. Modbus Integrations require one or more vendor Modbus definition (VMD) tables for specific third-party equipment. You can purchase tables from your regional System Integration Services (SIS) office, or you can create the tables with the VMD Generator Express (VGE) tool. To obtain a license, attend the training listed in the following table. Table 10: VGE Tool Training C-10077 VGE Tool Software Training (North America) The VGE tool is required to generate custom Modbus mapping tables for the NIE. PTK-CONT-26 VGE Tool Software Software Training (Europe and Asia) The VGE tool is required to generate custom Modbus mapping tables for the NIE. 4

Technical Specifications Table 11: NIE29 Power Requirement Power Consumption Dedicated nominal 24 VAC, Class 2 power supply (North America), safety extra-low voltage (SELV) power supply (Europe), at 50/60 Hz (20 VAC minimum to 30 VAC maximum) 25 VA maximum for NCE25 only The 25 VA rating does not include any power supplied to devices connected at the NIE binary outputs (BOs). Binary output devices connected to and powered by an NIE can require an additional 125 VA (maximum). Ambient Operating Conditions Ambient Storage Conditions Data Protection Battery Processors 0 to 50 C (32 to 122 F); 10 to 90% RH, 30 C (86 F) maximum dew point -40 to 70 C (-40 to 158 F); 5 to 95% RH, 30 C (86 F) maximum dew point Supports data protection on power failure. Rechargeable NiMH battery: 3.6 VDC 500 mah, with a typical life of 5 to 7 years at 21 C (70 F); : MS-BAT1020-0 Supervisory Controller: 192 MHz Renesas SH4 7760 RISC processor Field Controller: 20 MHz Renesas H8S2398 processor Memory Supervisory Controller: 128 MB flash nonvolatile memory for operating system, configuration data, and operations data storage and backup and 128 MB synchronous dynamic random access memory (SDRAM) for operations data dynamic memory Operating System Network and Serial Interfaces Field Controller: 1 MB flash and 1 MB RAM Microsoft Windows CE embedded MS-NIE291x-0 (MS/TP) or MS-NIE296x-0 (N2) MS-NIE292x-0 (LON) Analog Input/Analog Output Resolution and Accuracy Dimensions (Height x Width x Depth) One Ethernet port: 10/100 Mbps; 8-pin RJ-45 One optically isolated RS-485 FC Bus port or N2 Bus port; with a pluggable and keyed 4-position terminal block One optically isolated RS-485 SA Bus port; with a pluggable and keyed 4-position terminal block One RS-232-C serial port: standard 9-pin sub-d s, that support all standard baud rates One USB serial port: standard USB to Analog Input Points: 16-bit resolution One Ethernet port: 10/100 Mbps; 8-pin RJ-45 One optically isolated RS-485 SA Bus port; with a pluggable and keyed 4-position terminal block One RS-232-C serial port: standard 9-pin sub-d s, that support all standard baud rates One USB serial port: standard USB to One LONWORKS port; FTT10 78 Kbps; pluggable, keyed 3-position terminal block Analog Output Points: 16-bit resolution and +200 mv accuracy on 0-10 VDC applications 155 x 270 x 64 mm (6.1 x 10.6 x 2.5 in.) Minimum mounting space required: 250 x 370 x 110 mm (9.8 x 14.6 x 4.3 in.) Housing Plastic housing Plastic material: ABS and polycarbonate Protection: IP20 (IEC60529) Mounting Shipping Weight Compliance On flat surface with screws on three mounting clips or a single 35 mm DIN rail 1.2 kg (2.7 lb) United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management Equipment, FCC Compliant to CFR47, Part 15, Subpart B, Class A Canada: UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal Equipment, Industry Canada Compliant, ICES-003 Europe CE Mark - Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive. Australia and New Zealand RCM Mark, Australia/NZ Emissions Compliant BACnet International: BACnet Testing Laboratories (BTL) 135-2010 Listed BACnet Building Controller (B-BC) Table 12: NIE39 and NIE49 Power Requirement Power Consumption Ambient Operating Conditions Ambient Storage Conditions Data Protection Battery Dedicated nominal 24 VAC, Class 2 power supply (North America), SELV power supply (Europe), at 50/60 Hz (20 VAC minimum to 30 VAC maximum) 25 VA maximum 0 to 50 C (32 to 122 F); 10 90% RH, 30 C (86 F) maximum dew point -40 to 70 C (-40 to 158 F); 5 95% RH, 30 C (86 F) maximum dew point Supports data protection on power failure. Rechargeable NiMH battery: 3.6 VDC 500 mah, with a typical life of 5 to 7 years at 21 C (70 F); : MS-BAT1020-0 5

Table 12: NIE39 and NIE49 Processor Memory Operating System Network and Serial Interfaces Housing 192 MHz Renesas SH4 7760 RISC processor 128 MB flash nonvolatile memory for operating system, configuration data, and operations data storage and backup and 128 MB SDRAM for operations data dynamic memory Microsoft Windows CE embedded MS-NIE3910-2/MS-NIE4910-2 (MS/TP) One Ethernet port: 10/100 Mbps; 8-pin RJ-45 One optically isolated RS-485 port: 9,600, 19.2k, 38.4k, or 76.8k baud; pluggable and keyed 4 position terminal blocks Two RS-232-C serial ports: standard 9-pin sub-d s, that support all standard baud rates Two USB 2.0 serial ports: standard USB s Plastic housing material: ABS + polycarbonate MS-NIE3920-2/MS-NIE4920-2 (LON) One Ethernet port: 10/100 Mbps; 8-pin RJ-45 One optically isolated RS-485 port: 9,600, 19.2k, 38.4k, or 76.8k baud; pluggable and keyed 4 position terminal blocks Two RS-232-C serial ports: standard 9-pin sub-d s, that support all standard baud rates Two USB 2.0 serial ports: standard USB s One LONWORKS port; FTT10 78 Kbps; pluggable, keyed 3-position terminal block UL94-5VB Protection: IP20 (IEC 60529) Mounting Dimensions (Height x Width x Depth) On flat surface with screws on three mounting clips or a single 35 mm DIN rail 131 x 270 x 62 mm (5.2 x 10.6 x 2.5 in.) Minimum space for mounting NIE: 210 x 350 x 110 mm (8.3 x 13.8 x 4.3 in.) Shipping Weight Compliance 1.2 kg (2.7 lb) United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management Equipment; FCC Compliant to CFR47, Part 15, Subpart B, Class A UL Listed, File S4977, UUKL 864-9th Edition, Smoke Control Equipment (MS-NIE39x0-2U and MS-NIE49x0-2U models only) Canada: UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal Equipment; Industry Canada Compliant, ICES-003 Europe: CE Mark Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive. Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant BACnet International: BTL 135-2010 Listed B-BC Table 13: NIE59xx-3 Power Requirement Power Consumption Ambient Operating Conditions Ambient Storage Conditions Data Protection Battery Clock Battery Processor Memory Dedicated nominal 24 VAC, Class 2 power supply (North America), SELV power supply (Europe), at 50/60 Hz (20 VAC minimum to 30 VAC maximum) 50 VA maximum 0 to 50 C (32 to 122 F); 10 to 90% RH, 30 C (86 F) maximum dew point -40 to 70 C (-40 to 158 F); 5 to 95% RH, 30 C (86 F) maximum dew point Supports data protection on power failure. Rechargeable gel cell battery: 12 V, 1.2 Ah, with a typical life of 3 to 5 years at 21 C (70 F); : MS-BAT1010-0 Maintains real-time clock through a power failure. Onboard cell: typical life of 10 years at 21 C (70 F) 1.46 GHz Intel Atom Bay Trail E3815 processor for MS-NIE59xx-3 models 16 GB flash nonvolatile memory for operating system, configuration data, and operations data storage and backup for MS-NIE59xx-3 models. 2 GB DDR3 SDRAM for operations data dynamic memory for all models Operating System Johnson Controls OEM Version of Microsoft Windows Embedded Standard 7 with SP1 (WES7) 6

Table 13: NIE59xx-3 Network and Serial Interfaces Housing MS-NIE5960-1 (MS/TP) One Ethernet port: 10/100/1,000 Mbps; 8-pin RJ-45 Two optically isolated RS-485 ports: 9,600, 19.2k, 38.4k, or 76.8k baud; pluggable and keyed 4 position terminal blocks Two RS-232-C serial ports: standard 9-pin sub-d s, that support all standard baud rates Two USB 2.0 serial ports: standard USB s support an optional, user-supplied external modem Plastic housing with internal metal shield MS-NIE5920-1 (LON) One Ethernet port: 10/100/1,000 Mbps; 8-pin RJ-45 Two optically isolated RS-485 ports: 9,600, 19.2k, 38.4k, or 76.8k baud; pluggable and keyed 4 position terminal blocks Two RS-232-C serial ports: standard 9-pin sub-d s, that support all standard baud rates Two USB 2.0 serial ports: standard USB s One LONWORKS port; FTT10 78 Kbps; pluggable, keyed 3-position terminal block Plastic material: ABS + polycarbonate; Protection: IP20 (IEC 60529) Mounting Dimensions(Height x Width x Depth) On flat surface with screws on four mounting feet or on dual 35 mm DIN rail 226 x 332 x 96.5 mm (8.9 x 13.1 x 3.8 in.) including mounting feet Minimum space for mounting: 303 x 408 x 148 mm (12.0 x 16.1 x 5.8 in.) Shipping Weight Compliance 4.15 kg (9.15 lb) United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management Equipment, FCC Compliant to CFR47, Part 15, Subpart B, Class A Canada: UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal Equipment, Industry Canada Compliant, ICES-003 Europe: CE Mark - Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive. Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant BACnet International: BTL 35-2010 Listed B-BC Table 14: Computer Recommendations for NIE89 Installation/Upgrade MS-NIE89SW-0 Network Integration Engine Software for 10,000 objects (new projects only software) Recommended Computer Platform Intel Xeon E5506, 2.13 GHz, 4 MB Cache 2 x 160 GB 7.2K SATA, 8.9 cm (3.5 in.) Cabled 3 Gbps, RAID 1 configuration with add-in SAS6/iR (SATA/SAS Controller) Recommended Memory Hard Disk Supported 64-bit Operating Systems and Software 8 GB RAM minimum 160 GB minimum Windows Server 2016 (64-bit) Windows Server 2012 R2 with Update 1 (64-bit) Windows Server 2012 (64-bit) Note: Microsoft.NET Framework 3.5 Service Pack (SP) 1 and Microsoft.NET Framework 4.6.1 are required for any of the operating systems. Supported Operating Systems for Metasys Client Computers Windows 10 Pro and Enterprise Editions with Anniversary Update (version 1703) (64-bit) Windows 8.1 Pro and Enterprise Editions with Update 1 (64-bit) Windows 7 Professional, Enterprise, and Ultimate Editions with SP1 (64-bit) Windows 7 Professional, Enterprise, and Ultimate Editions with SP1 (32-bit) Apple macos 10.12 Sierra Apple OS X 10.11 El Capitan Apple OS X 10.10 Yosemite Note: Apple operating systems are supported for Metasys client computers only. Also, in Apple OS X, you cannot view Graphics+ graphics in the Site Management Portal UI. Internal Optical Drive DVD ROM, SATA 7

Table 14: Computer Recommendations for NIE89 Installation/Upgrade Supported Web Browser Software for Metasys Site Management Portal Client Computers Windows Internet Explorer 11.0.9600.18816 Update version 11.0.47 or later Note: In Internet Explorer 11, select the Use Microsoft compatibility lists option, found under Tools > Compatibility View Settings, to ensure that websites appear and function correctly. Google Chrome version 61 or later Apple Safari 11 or later Other browsers, such as Mozilla Firefox, may also be used but are not fully supported. Supported Virtual Environments Network Communication Microsoft Hyper-V, VMWare Selectable Network Interface (if computer has multiple network cards, during NIE89 installation, select the network card that was configured for Metasys system use before installation) Ethernet network interface card 10/100/1000 Mbps (100 Mbps or better recommended) Recommended Data Protection Uninterruptible power supply (UPS) Smart-UPS SC 450VA, 280 W, 120 VAC input/output, NEMA 5-15R output connections, OEM Part No. SC450RM1U The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products. Building Technologies & Solutions 507 E. Michigan Street, Milwaukee, WI 53202 Metasys and Johnson Controls are registered trademarks of Johnson Controls. All other marks herein are the marks of their respective owners. 2017 Johnson Controls Published in U.S.A. www.johnsoncontrols.com 8