APC APPLICATION NOTE #126

Similar documents
Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

APC APPLICATION NOTE #146

Using CFD Analysis to Predict Cooling System Performance in Data Centers Ben Steinberg, P.E. Staff Applications Engineer

APC APPLICATION NOTE #114

Close-coupled cooling

Reducing Data Center Cooling Costs through Airflow Containment

Optimizing Cooling Performance Of a Data Center

APC APPLICATION NOTE #74

InRow Chilled Water. Up to 70kW. Close-coupled, chilled water cooling for medium to large data centers. Row-Based Cooling.

Efficiency of Data Center cooling

Recapture Capacity for Existing. and Airflow Optimization

Current Data Center Design. James Monahan Sept 19 th 2006 IEEE San Francisco ComSoc

HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.

MSYS 4480 AC Systems Winter 2015

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

Power & Cooling Considerations for Virtualized Environments

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Variable Density, Closed-Loop, Water-Cooled Data Center Solution

Power and Cooling for Ultra-High Density Racks and Blade Servers

Reducing Energy Consumption with

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

200 kw, Tier 3, Chilled Water, 5250 ft 2

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions

DATA CENTER LIQUID COOLING

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group

Close Coupled Cooling for Datacentres

3300 kw, Tier 3, Chilled Water, 70,000 ft 2

A Green Approach. Thermal

ECOBAY: Closed loop water cooled server cabinet for data centers

Data Center Temperature Rise During a Cooling System Outage

INNOVATE DESIGN APPLY.

INNOVATE DESIGN APPLY.

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Chiller Replacement and System Strategy. Colin Berry Account Manager

2000 kw, Tier 3, Chilled Water, Prefabricated, sq. ft.

Data Center Design: Power, Cooling & Management

New Techniques for Energy-Efficient Data Center Cooling

Optimiz Chilled January 25, 2013

Retro-Commissioning Report

Data Center Design: Power, Cooling & Management

Application of TileFlow to Improve Cooling in a Data Center

The Efficient Enterprise. All content in this presentation is protected 2008 American Power Conversion Corporation

HIGH DENSITY RACK COOLING CHOICES

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP

Modbus Register Map: InRow ACRD60x / ACRC60x

MPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers

Ten Cooling Solutions to Support High-density Server Deployment. Schneider Electric Data Center Science Center White Paper #42

Overcoming the Challenges of Server Virtualisation

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

MCFCW-08-4LS-1 (4-Pipe) Low Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 24,000 BTUH

Chilled Water Distribution Design Considerations in Super Tall Buildings. Dusan Mrdalj, Associate, ChapmanBDSP

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden

Data Center Trends: How the Customer Drives Industry Advances and Design Development

HP Modular Cooling System: water cooling technology for high-density server installations

Impact of Air Containment Systems

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

ACFD12-T ACFD12-B. Technical Data

Server Room & Data Centre Energy Efficiency. Technology Paper 003

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA

Total Modular Data Centre Solutions

APC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011

Motivair MLC-SC Air-Cooled Scroll Chillers Tons

Liquid Cooling Package LCP Cooling Systems

High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach

System Overview. Liquid Cooling for Data Centers. Negative Pressure Cooling Without Risk of Leaks

Switch to Perfection

Rittal White Paper 506: Cold Aisle Containment for Improved Data Center Cooling Efficiency By: Daniel Kennedy

Cooling Solutions & Considerations for High Performance Computers

MCFCW-20-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 60,000 BTUH

Performance Evaluation for Modular, Scalable Cooling Systems with Hot Aisle Containment in Data Centers. Final Report

Energy Efficiency Solutions for Your Data Center

Virtualization and consolidation

Impact of Hot and Cold Aisle Containment on Data Center Temperature and Efficiency

ENCLOSURE HEAT DISSIPATION

MCFCW-06-4HS-1 (4-Pipe) High Static Chilled/Hot Water Ceiling Concealed Cased Fan Coil 208/230V 4-Pipe Heating & Cooling Fan Coil 18,000 BTUH

LCS Value Proposition November 2014

IT Air Conditioning Units

Datacenter Efficiency Trends. Cary Roberts Tellme, a Microsoft Subsidiary

PEX+ High Efficiency, Low Operating Cost Precision Solution for Data Centers

The Energy. David L. Moss Dell Data Center Infrastructure

SYRACUSE UNIVERSITY GREEN DATA CENTER NYSERDA MONITORING PLAN BHP ENERGY LLC. February 17, 2010 Revised

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

Next Generation Cooling

Optimization in Data Centres. Jayantha Siriwardana and Saman K. Halgamuge Department of Mechanical Engineering Melbourne School of Engineering

Calculating Total Power Requirements for Data Centers

Improving Rack Cooling Performance Using Blanking Panels

What s New for Data Centers in Title Jeff Stein, PE Taylor Engineering

Green IT and Green DC

Rethinking Datacenter Cooling

Rack cooling solutions for high density racks management, from 10 to 75 kw

LCP Hybrid Efficient performance with heat pipe technology

Liebert DCW CATALOGUE

1008 kw, Tier 2, Chilled Water, ft 2

DATA CENTER PRECISION COOLING: The Need For A Higher Level Of Service Expertise

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

Transcription:

#16 Selection Procedure for Inow Chilled Water Products By Greg Uhrhan, P.E. and Scott Buell Abstract Proper selection of Inow chilled water cooling systems requires an engineer or technical salesperson to assess a number of variables to ensure customer satisfaction. These variables include but are not limited to the room layout, load profile of the servers and IT equipment, user s desired cold aisle temperature, and available or desired chilled water temperatures. Introduction With new APC Inow products, a number of variables are needed to be calculated. Among those variables are the entering water temperature, expected water side temperature difference, expected hot aisle temperature, chiller capacity, and Cooling Distribution Units in use. All of these factors must also be factored in with the overall data center layout as this will also have significant effect on how the cooling units perform. For information about best practice of data center layout, refer to Application Note 9, Best Practices for Designing Data Centers with the Inow C. Calculation of Hot Aisle Temperature The biggest and most complex variable is the hot aisle temperature calculation. Generally, servers are rated for typical power and airflow draw. This makes it simple to calculate a temperature difference for the air through the server. Δ T air 316 ( / kw In addition to server loads, Inow Power must be considered. Inefficiencies inherent in the transformers, rectifiers, power distribution units, and UPS units lead to an increased heat load that must be accounted for and neutralized by the cooling units. Table 1 Symmetra PX Thermal Characteristics Product Heat Output (kw Air Flow (S [m^3/hr] Symmetra PX40 3.5 180 [306] Symmetra PX80 7.0 40 [714] 1 _

Then, for a given cell (probably a set of rows forming a common hot aisle, the hot aisle temperature can be taken as the users desired cold aisle temp plus the average weighted Δ T. While there is some error associated with using this on a larger scale, it can be sized down to smaller groups of equipment to provide a good estimate of peak local hot aisle temperatures. ΔT ΔT average average ( ΔT ( CMH ΔT CMH air air or its analog ΔT average 316 ΔT average 1861 kw kw CMH The Cooling Correction Multiplier (CCM found in Table, accounts for extra room temperature air that is mixed with the hot air leaving the servers before being conditioned in the air-conditioner. Table Cooling Correction Multiplier Configuration Multiplier, CCM Open Aisle.70 HACS.95 ACS.95 The hot aisle temperature can then be calculated as This T ΔT CCM + T hot average T hot is then used as the entering air temp for the air conditioner. cold

Water Variables The water variables are almost entirely dependent on user preferences, or in the case that the user is connecting to a building chilled water system, building system design and operation. The ACC and ACP products can tolerate a wide variety of entering water temperatures, currently cataloged as 4 F to 60 F [5.6 C to 15.6 C]. If building chilled water is available in sufficient quantity, it can be used. In that scenario, the entering water temperature would be the chilled water system s low temperature main. A facility engineer would need to be consulted to determine what water side temperature rise is acceptable for smooth and efficient operation of the building system. Also, the facility engineer would need to be consulted to ensure that the building chilled water system does not go into a setback mode during non-occupied hours, as that would adversely effect the data center operation. Available pump head will also determine the amount of water flow that can be obtained. The maximum available flow for an ACC can be back solved by the pressure loss equation: where back solved by the pressure loss equation: (.076 V& +.1669 V& Δ P.31 [ Δ P (.9053 V& + 31.43 V& ] Δ P is in psi [Pa] and V & is in Gallons per minute [L/s]. The maximum available flow for an ACP500 series can be (.0306 V& +.0537 V& Δ P.31 [ Δ P (.3635 V& + 10.11 V& ] where Δ P is in psi [Pa] and V & is in Gallons per minute [L/s]. For dedicated chiller loops that are designed to meet the datacenter s cooling load only, one should consult the published Technical Data Manual for performance specifications, water flow rates, and pressure drops. If the user is setting up a dedicated loop to their datacenter, then nearly any temperature is attainable in the given range. APC recommends use of 45 F [7. C] entering water temperature and a 10 F [5.6 C] temperature rise for optimal performance and minimal latent capacity waste. For increased electrical efficiency, entering water temperature leaving the chiller can be increased, however the user must consider the capacity loss of the C/P and adjust the datacenter design accordingly if high enough densities are present. Pumps should be sized to ensure that the pressure drop of not only the air conditioner are included, but also any building piping, CDU pressure drop (APC Skus ACFD1-T and ACFD1-B, or pex piping pressure loss. CDU pressure loss is given by : (.0498 V& +.0313 V& Δ P.31 [ Δ P (.5916 V& + 5.8940 V& ] 3

And pressure loss through the pex piping is given by: ΔP L eq (.054 V& +.1705 V&.31 ΔP (.149 V& Leq + 105.95 V& There also can be flexible hoses used for vibration isolation and ease of installation and placement. Table 3 shows the pressure drop induced by the stainless hoses. Length Table 3 Stainless Steel Hose Cv D1.00 [DN5] D1.5 [DN30] 36 [914mm] 35 57 7 [189mm] 4 38 Glycols Frequently, in areas where freeze protection is required or desired for safety of system integrity, glycol solutions are used to depress the freezing point to prevent pipe freezing. Either ethylene or propylene glycol can be used at any proportion, however, ASHAE recommends a maximum of 30% ethylene glycol or 35% propylene glycol due to the decrease heat carrying capacity and higher viscosity of glycol mixtures (ASHAE Fundamentals Handbook 001 p. 1.5. Table 4 lists the derating factors used for glycols. Percentage Glycol (% Capacity Multiplier Ethylene Glycol Table 4 Glycol Adjustment Multiplier Capacity Multiplier Propylene Glycol Pressure Drop Multiplier Ethylene Glycol Pressure Drop Multiplier Propylene Glycol 0 1.00 1.00 1.00 1.00 10.97.96 1.04 1.09 0.93.90 1.13 1.0 30.88.8 1.1 1.35 40.81.77 1.31 1.5 4

The above factors assume a constant flow rate as rated for the given conditions in the technical data manual. Altitude In properly estimating the capacity of a chilled water unit, many locations may require use of an altitude correction factor. All values found in APC Technical Data manuals are based on sea level performance. Table 5 gives the Altitude Correction Factors. Note that while APC can adequately predict cooling equipment performance, we cannot predict how a user s servers will perform in high altitude applications. Although, it is generally a fair assumption that as altitude increases, the server outlet temperature, for a given server, will increase and as a result the hot aisle temperature will slightly increase. Table 5 Altitude Correction Factors (ACF Altitude (ft [m] ACF (- 0 [ 0 ] 1.00 1000 [305].98 000 [610].96 3000 [914].93 4000 [119].91 5000 [154].88 6000 [189].86 7000 [134].85 8000 [438].83 Chilled Water Inow CACs ACC 100 series The ACC is a sensible-only half rack wide Inow cooling product. It has a nominal capacity of 17 kw at 85 F [9.4 C] Entering Air Temperature and 45 F [7. C] EWT with a 10 F [5.6 C] temperature rise on the water side and running its full capacity, 900 S [4900 CMH], of air. The actual capacity can be modulated from 0 to 30 kw depending on actual conditions. The unit is fully capable of modulating both airflow and water flow rate to maintain leaving air temperature and cold aisle temperatures within a user defined range. 5

ACP 500 series The ACP is a precision, full rack wide Inow cooling product. It has a nominal capacity of 37 kw at 85 F [9.4 C] EAT and 45 F [7. C] EWT with a 10 F [5.6 C] temperature rise on the water side and running its full capacity, 6900 S [11,700 CMH], of air. The actual capacity can be modulated from 0 to 70 kw depending on actual conditions. The unit is fully capable of modulating both airflow and water flow rate to maintain leaving air temperature and cold aisle temperatures within a user defined range. Furthermore, the unit is capable of reheat and humidification for precision room control. ACC 500 series The ACC500 series is alike is capacities to the ACP, however has no humidity control or reheat ability and therefore is not precision air conditioning. Checking a Solution Three checks must be run to make sure that the system will satisfy all needs and redundancy requirements: a capacity check, an airflow check, and a supply air temperature check. If any of these fail, application engineering must determine what must be done to make the system operate as planned or determine whether the other variables are enough to compensate. The capacity check verifies that the unit performance is adequate to meet the user requirements. If a user requires N redundancy on a row basis, the engineer must ensure each row has more cooling than power input. If the user requires N+1, one more unit than is required to meet the cooling needs must be installed. In mixed mode applications, it must be assumed that the redundant unit is always the highest capacity unit. The airflow check ensures that the cooling units are drawing at least as much air as required to maintain the calculated entering air temperature. Therefore, for N redundancy * CCM > CAC Servers If this is not true, then additional cooling units must be added to ensure all air is captured by the cooling units and hot air is not recycled into the servers. To define N+1 or greater redundancy, particularly in mixed mode applications, assume a loss of the highest flow unit and ensure, * CCM highestflowunit > CAC Servers Finally, an inlet air temperature check should be run. This ensures that at the maximum air flow rate, the cooling units have adequate cooling to maintain a sufficient inlet air temperature to the servers. To perform this check, 3415 kw T 1.08 T hot T outlet 3415 1.84 hot T outlet CMH 6 kw

Verify that T outlet is less than the cold aisle setpoint. Sample Procedure Take Figure 1 as our example data center located in Denver. Each rack is loaded to 5 kw and each have an associated minimum airflow per kw. User assigns the cold aisle temperature to be 70 F. Four ACC 100 units are placed in the space with open aisle configuration, as shown, and supplied with 45 F ethylene glycol at 0% solution and a desired water temperature rise of 10 F. Determine the cooling system characteristics and redundancy. Total rack airflow is shown in Table 6. Table 6 ack Power Table Power Draw (kw /KW Airflow ( ow A ack 1 5 800 ack 5 800 ack 3 5 105 55 ack 4 5 800 ow B ack 5 5 800 ack 6 5 105 55 ack 7 5 800 ack 8 5 800 totals 40 5850 7

Figure 1 Sample Datacenter Cluster Cold Aisle FONT C C 100% 100% 100% 100% BACK Hot Aisle BACK C C 100% 100% 100% 100% FONT Cold Aisle Therefore, by calculating, the temperature rise can be determined, and ΔT kw 40 316 316 1. 5850 o average 6 F Thot ΔTaverage CCM + Tcold 1.6.70 + 70 85. 1 From there, the capacity and performance specifications of the chilled water air-conditioner can be determined. Look up tables from the technical data manual for pure water at sea level and interpolation indicates a sensible performance of 6,000 BTU/hr. Water flow required is found as 13. GPM. Adjusting for the altitude in Denver (580 ft ASL yields an altitude correction factor of.875, and the adjustment for 0% ethylene glycol yields a correction factor of.93. Therefore the actual capacity is 6,000BTU / hr.93.875 50,400BTU / hr 14. 8kW o F From here a number of checks must be run. First is the airflow check. The racks require 5850 S. Each ACC unit produces 900 S. In order to achieve the required airflow, the use of 3 ACC units is required, however, the overage will be 1390 S taking into account the CCM. Therefore, the system, as designed with four C units, is N+1 from the airflow vantage. Thermally, the system requires 40 kw of cooling capacity. At 50,400 BTU/hr, the converted capacity is 14.8 kw. 8

Therefore, from the thermal standpoint, the system is also N+1. Finally, we must check the leaving air temperature. Maximum supply temperature will be attained at full airflow rate, therefore, the maximum supply temp is found to be 68.9 F. This value is below the desired setpoint of 70 F, so the third check is satisfied. The system can be declared to be N+1. At this point any room or partial room layout needs to be looked at from the perspective of the actual physical configuration. The proximity of heat loads relative to coolers is critical in an Inow configuration. It is possible that the total cooling capacity is sufficient to handle the total heat load and yet can not be configured in such a manner that all of the heat will be captured by the necessary coolers. Please refer to Application Note 9, Best Practices for Designing Data Centers with the Inow C for more information. About the Authors: Greg Uhrhan is a Mechanical Engineer for APC. He is responsible for cooling system design, technical data, and system applications. Greg received a Bachelor s degree in Mechanical Engineering from University of Illinois at Urbana - Champaign in 001, Masters in Mechanical Engineering from Georgia Tech in 005, is a member of ASHAE and ASME, and is a licensed Professional Engineer in the State of Missouri. Scott Buell is a Senior Mechanical Engineer for APC. He is responsible for cooling system design, technical data, and system applications. Scott received a Bachelor s degree in Mechanical Engineering from the University of Minnesota in 199. 9