UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

Similar documents
VAV Modular Assembly (VMA) 1410/1420

XT-9100 Technical Bulletin

Variable Air Volume Modular Assembly (VMA) 1400 Series

FX-PCX Expansion Input/Output Modules Catalog Page Code No. LIT Issued April 17, 2015

TC-9102 Terminal Controller

FX Input/Output (I/O) Modules XM07 and XM14

Onboard Inputs and Outputs. Remote User Interface. Integral LCD User Interface

Custom Controller Installation Instructions

Lab and Central Plant Controller

Smart Equipment Controls (SEC)

FX14 Field Controller

FXVMA Variable Air Volume (VAV) Box Controller

Modular Room Control (MRC) Series Expansion Board

ACCESS 9340/9360 Meter Input/Output Module

DS A 10/99 MN 500 I/A SERIES MICRONET MN 500 CONTROLLERS APPLICATION SPECIFICATION

P216 Series Condenser Fan Speed Controller

Hardware Installation. Tracer MP581 Programmable Controller CNT-SVN01C-EN

FX06 Field Controller

LN Series Remote Input/Output (I/O) Modules

rcc.1081 Installation Instructions

LX Series Free Programmable LX-PRG6x0-11 Controllers and LX Series Input/Output (I/O) Extension Modules

P216. Condenser fan speed controller. Product bulletin. Features

PEAK TM. PEAK TM controllers. Mid-Market BAS Smart equipment controllers. HVAC/R controllers

Input/Output Module (IOM) Series Controllers Catalog Page Code No. LIT Issued June 2018

S66 Series Electronic Fan Speed Control

CONTROL MICROSYSTEMS and 5407 Relay Output Module. Hardware Manual

Installing the Tracer MP503 Input/Output Module Ordering number: ,

Input/Output Module (IOM) Series Catalog Page

Tracer Controls. Tracer MP501 Controller BAS-PRC008-EN. January 2005

Extended Digital Controller

Analog Voltage Combination Module

INSTALLATION INSTRUCTIONS

LN Series Free Programmable LN-PRG6x0-12 Controllers and LN Series Input/Output (I/O) Extension Modules

LN Series Input/Output (I/O) Extension Modules

LX Series Remote Input/Output (I/O) Controller

MXIO. Compact I/O module. Summary. Application Compact I/O module for data acquisition and HVAC control systems. Function

Specification Sheet For electronically commutated motors

RWD68U Universal Controller

Field Equipment Controller (FEC) Series Catalog Page Code No. LIT Issued June 2018

Wireless General Purpose Adapter (WGA100) Installation Instructions

Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control

clarity 3 Programmable Controller

Submittal Data Sheet WAGO Node for itm

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

Bulletin 817 Thermistor Protection Relay

BA/BS4S Temperature Sensor Installation & Operating Instructions

Network Control Engine Catalog Page

FX-2 Control Board ASY-360-XXX Setup and Configuration Guide

Hardware Installation Guide

Temperature controller Ducted systems

TB21. NO - Relay. Relay. Common - Relay. NC - Relay. Input J23. Ground TB22 TB23. NO - Relay Common - Relay NC - Relay Input Ground.

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

Standard Options. Model 4100 Position Indicating Meter. Three Phase Motor Control. Positran Transmitter

Expansion Module HZS 541-1S

TX-I/O Product Range. Features. Description. Document No January 24, 2007

LTEC Heat Pump DDC Controller

Input/Output Module (IOM) Series Controllers Catalog Page Code No. LIT Issued December 2017

PGR-3200 MANUAL INSULATION MONITOR

LN Series Input/Output (I/O) Extension Modules and LN Communicating Sensors Subnetwork for LN-VAVCF-12 and LN-PRGxxx-12 Application Note

Rack Input Module Installation Instructions

Infosystem Remote Touchscreen Installation Instructions

Advanced Application Field Equipment Controller (FAC) Catalog Page

Installation Instructions

DX-9100 Digital Controller, Version 2

SLX Series. Application Specific Controllers (SLX-ASC-FCU-L, SLX-ASC-HPU-L, SLX-ASC-RTU-L, SLX-ASC-UV-L)

PLC Racks IC697CHS782/783

T775S Series 2000 Expansion Module

FX-DIS1710 Local Controller Display Installation Instructions Part No , Rev. B Issued April 2016

Installation Instructions

Installation and Operation. Tracer MP501 Controller CNT-SVX08B-EN

ATS22D75S6 soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)/500V(45kW)

Non-communicating room controllers

Troubleshooting the NAE/NIE

FX80 Supervisory Controller Installation Instructions

FEC26 Field Equipment Controller

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR

FEC - FAC. Metasys controllers. Complex BAS Programmable controllers. Catalog Page. Field Equipment Controllers

4100/4120-Series and 4010ES Relay Modules Installation Instructions

Output Relay Electrical Function Module

Field selectable application type and room module series, via dip-switches on controller

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY

ATV12P037F1 variable speed drive ATV kW hp V - 1ph - on base plate

MicroTech II Vertical Self-contained Systems Unit Controller

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

Datasheet. ECB-PTU Series. 1/14. BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

ATV12HU22M3 variable speed drive ATV12-2.2kW - 3hp V - 3ph - with heat sink

Measurement Systems Datascan Installation and User Guide

HMISBC Rear Module controller panel - Dig 8 inputs/8 outputs +Ana 4 In/2 Out

TEMPERATURE CONTROLLER 2 HEAT/ 2 COOL with Digital Room Temperature Display. Made in Australia 100% Australian Owned Company

SED2 Variable Frequency Drives Conventional Bypass (C-Bypass) Options

PACSystems RX7i IC698CHS009/119

Immersion Temperature Sensors

ATV12H018M2 variable speed drive ATV kW hp V - 1ph

Product Catalog. Tracer Controller MP501 BAS-PRC008-EN. May 2012

ETM-2050/ETM-2051 Service Manual

Output Relay Latched Function Module

This Datasheet for the IC697CHS790. Rack, 9 Slots, Rear Mount.

Thermocouple Input Module Product Specifications and Installation Data

ATS22D62Q soft starter-ats22-control 220V-power 230V(15kW)/ V(30kW)

Tracer Controllers. Tracer MP503 Input/Output Module BAS-PRC009-EN. January 2005

Transcription:

1 2 8 4 AI6 R R Installation Bulletin UNT1100 Issue Date 0309 UNT1100 Series Introduction The Unitary (UNT) controller (UNT1100 Series) is a digital controller with applications for air handling units, packaged rooftop units, unit ventilators, fan coils, heat pumps, and other terminal units serving a single zone. Figure 1 shows the UNT1100 controller, and Table 1 lists UNT1100 specifications. For information on related literature, see Table 2. 157 mm (6.2 inch) Width Binary Output s 162 mm (6.4 inch) Height N2 Addressing AI Switches BO OUT Options W3 AO1 W4 AO1 W8 AO2 AI3 W9 AO2 W14 W18 AO3 AO3 W20 W23 AO4 AO4 AI Switches Job Information N2 Address AI3 AI4 AI4 AI5 AI6 AI5 N2+ N2- Ref RECV 16 32 64 128 12345678 ADDR 0 = ALL W28 W29 W30 W34 W35 W39 W40 W41 W44 XMIT (UP) BO4 BO3 BO2 W45 W50 W51 BO1 W49 W52 AS-UNT11xx W56 W55 PWR PWR IN: 24VAC, 2AMP, CLASS 2 BIN OUT: 24VAC, 2A, CLASS 2, PILOT DUTY RY10029 Rev J 24VAC COM Binary Output LEDs N2 Communication Connection W1 W2 W5 W6 W10 W11 W12 W15 W16 W17 W21 W22 +15VDC +15VDC COM ZBUS BI BI1 BI2 BI1 BI BI2 BI3 BI4 BI3 BI BI4 BI6 BI7 BI6 BI BI7 Zone Bus LED Analog Input Configuration Switches O 1 2 3 4 5 6 N CTS 206-6 TB40 O 1 2 3 4 5 6 N CTS 206-6 TB40 W25 W26 W27 W31 W32 W36 W37 W38 W42 W43 W46 W47 W48 W53 42 mm (1.7 inch) Depth Phone Jack Connection for Zone Bus *Note: See Figure 6 for additional information Din Rail Release UNT1100c Spade Lug Terminal Connections Figure 1: UNT11xx 2009 Johnson Controls, Inc. 1 Part No. 24-9534-7, Rev. A www.johnsoncontrols.com

Table 1: UNT1100 Specifications Product Name Unitary Controller (UNT1100 Series) Product Code Number AS-UNT1108-0 AS-UNT1126-0 AS-UNT1144-0 Analog Inputs (1K ohm RTD, 0-10 VDC, 0-2 VDC) Binary Inputs ( Dry Contact) Analog Outputs (0-10 VDC @ 10 ma) Binary Outputs (Class 2 -- 2A relay @ ) Supply Voltage Power Consumption Ambient Operating Ambient Storage Conditions Terminations Optional Terminations Controller Addressing Communications Bus Mounting Standards Compliance 6 6 6 6 6 6 0 2 4 8 6 4 20-30 VAC at 50 or 60 Hz Class 2 transformer 7 VA maximum (relay and valve requirements not included) -40 to 60 C (-40 to 140 F) -40 to 70 C (-40 to 158 F) 1/4 in spade lugs except communications, which are screw terminals 2 or 3 position removable screw terminals that plug over spade lugs DIP Switch (N2 only) use Addresses 1-253. Addresses 0, 254, 255 reserved. Metasys N2 between UNT and network supervisory controller (2-wire + ref.). Zone Bus between UNT controller and room sensor (8-pin phone jack or wire to spade lugs) Surface mount using screws or DIN rail UL 916 Listed CSA C22.2 No. 205 UL 94-5VB (Enclosure) CE Directive (89/336/EEC) C-tick Australia/NZ EN 61000-3-2,-3 EN 61000-4-5,-11 EN50081-1: EN 55011 - Class B (emissions) EN 50082-2 (1995): EN 61000-4-2, -4 EN 50140 (1993), EN50204, EN5041 (1993) CFR47: FCC Part 15 Class B (verified) Class A (certified) FCC Part 15 Label - Note: This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at their own expense. Table 2: Related Literature Description Unitary (UNT) Controller 1100 Series User s Guide UNT Applications Application Note (HVAC PRO ) Unitary Controller (UNT1100 Series) Product Bulletin Literature Number LIT-6363083 LIT-6375100 LIT-635066 2 UNT1100 Series Installation Bulletin

Mounting Instructions Switches and s Mount the controller on a flat surface or 35 mm DIN Rail. The overall dimensions of the UNT11xx are 162 x 157 x 42 mm (6.4 x 6.2 x 1.7 in.) H x W x D. To surface mount the UNT1100: 1. Place the UNT1100 in the proper mounting position so the wiring connections are easily accessible. 2. Attach the UNT1100 to the mounting surface using No. 10 Torx head (or equivalent) screws. Note: Overtightening can strip screw threads. Make sure screws do not interfere with wiring or access. To DIN rail mount the UNT1100: 1. Attach a 35 mm DIN rail to the panel. 2. Position the UNT1100 along the rail. 3. Snap the lower edge of the UNT1100 into place. Configure Analog Input (AI) switches for resistance/temperature input, 0 to 2 VDC, or 0 to 10 VDC. Figure 2 shows the two banks of DIP switches to set the configuration. 1 2 3 4 5 6 1 2 3 4 5 6 SW1 SW2 TEMP OFF ON 2V OFF OFF 10V ON OFF AI Figure 2: AI Switches In N2 applications, set the address of the controller using the N2 address switches (Figure 3). The numbers are in binary format and horizontally arranged, with the least significant digit on the left. For example, if the desired controller address is 17 (decimal), the binary representation is 10001000. Switches 1 and 5 must be set to the closed (down) position (1+16=17) as shown. Note: N2 Addresses 0, 254, and 255 are invalid and should not be used. 1 2 48 16 32 64 128 12345678 (UP) N2Switch Figure 3: N2 Address Switches UNT1100 Series Installation Bulletin 3

Each Binary Output (BO) has both isolated normally open and normally closed contacts available at the terminal. The common point of each relay may be independently jumpered to the terminal, or wired to an external isolated supply. Place the jumper clip to the (right) position to connect the Relay Common (OUTx) to the signal. When the jumper clip is placed in the open (left) position, the relay common must be externally supplied. See Figure 4 for typical binary output connections. BOx Clip Open NOx OUTx NCx Factory Installed Output Load To Next BO Circuit BOjumper Figure 4: Typical BO Connections Terminal Identification Figure 5 shows an example of the UNT1100 front label, which identifies each terminal point. The terminal points are also identified on the circuit board. Label and terminal point identification are different for each UNT1100 model. Terminal Identification BO OUT Options AI Switches Job Information N2 Address N2+ N2- Ref RECV XMIT 1 2 8 4 16 32 64 128 (UP) 12345678 ADDR 0 = ALL RY10029 Rev J Newmod 4 UNT1100 Series Installation Bulletin Figure 5: Terminal Identification for UNT1126

LEDs (Light-Emitting Diodes) Each binary output on the UNT1100 controller connects to a green LED. The LED is on when the relay is energized and the Normally Open contact is closed (and the Normally Closed contact is open). The Zone Bus transmit line ties to a green LED which is on whenever a high state is transmitted on the Zone Bus. Since the UNT1100 controller continuously transmits, the LED flickers. The N2 Communication card has two green LEDs, one of which is on whenever a high state is detected on the Bus. The other green LED lights whenever the UNT1100 transmits a reply. Wiring Follow these precautions when wiring: Precautions Make all wiring connections in accordance with the National Electrical Code (NEC) and local regulations. Locate equipment and route wiring so that it is separated from power wiring. Make all wiring connections to the UNT1100 using only copper conductors. Daisy chain the N2 module. Do not use wire smaller than 22 AWG. Do not run N2 Bus, Zone Bus, Analog Input (AI), Binary Input (BI), Analog Output (AO), or Binary Output (BO) wiring in the same conduit or bundle as line voltage wiring (30 VAC or above). Do not run N2 Bus, Zone Bus, AI, BI, AO, or BO wiring in the same conduit or bundle as wiring that switches power to highly inductive loads such as contactors, coils, motors, or generators Run only shielded N2 Bus wiring in the same conduit or bundle as power wiring. Run Zone Bus, AI, AO, and BI wiring in the same bundle or conduit. If the binary output wiring is not wired through other switches or contacts and it is powered by a Class 2 transformer, bundle it with other I/O wiring. Use either no earth ground connection or one earth ground connection, which must be at the transformer secondary common connected to PWR COMMON on the controller (whether one or multiple controllers are powered by the same transformer). UNT1100 Series Installation Bulletin 5

Wiring Table 3: UNT1100 Wiring Point Typical Application Range Analog Inputs: AI-1 to AI-6 Binary Inputs: BI-1 to BI-6 Temperature and humidity sensing Occupancy sensor, pressure sensor 1k ohm Ni, Si, or Pt 0-10 VDC, 0-2 VDC 0-30 VAC 0-30 VDC Input or Load Impedance (ohms) Maximum Voltage 5 VDC 10 VDC 2 VDC 6.23k (AC) 9.9k (DC) 30 VAC 30 VDC Maximum Current Maximum Cable Length in Meters (ft) 1.4 ma 150 (500) 30 (100) 4.8 ma AC 1 3.0 ma DC 150 (500) 150 (500) Wire Size AWG (mm2) Analog Outputs: AO-1 to AO-4 2 Binary Outputs: BO-1 to BO-8 2 N2 Bus Zone Bus Room Sensor Cable +15 VDC (Output) + (Input) Binary Input Source 8 (Output) Proportional control: fan, valves, humidity On-Off: normally open or normally closed valves, motors, lighting relays, electric heat Network communication Room sensor communication AI-1, AI-2, AI-3, Zone Bus, and + DC transducer supply AC supply voltage Binary Input 0-10 VDC at 10 ma ; 5-28 VDC 1k minimum 0-5 VDC (100 unit loads) 0-5 VDC (35 unit loads) See AIs, Zone Bus, and Binary Input Source in this table 15-18 VDC 360 minimum 22-30 VAC, 50/60 Hz 19.2 to 30 VAC 30 VAC 28 VDC 10 VDC 10 ma 150 (500) 60 (200) 2A (AC) 3,6 3.8 (12.5) 0.9 (3.1) 1A (DC) 6 7.6 (25.0) 1.9 (6.2) 5 VDC 60 ma 1500 (5000) 5 VDC 775 ma 1500 (5000) 20 (0.8) 20 (0.8) 30 (100) eight conductor phone cable 30 VAC RMS 0.2 maximum 18 VDC 50 ma 4 30 VAC RMS (See VA ratings.) 3.2 (10.5) 5,6 23 (75) 6,7 100 ma 9 150 (500) 30 (100) Notes: All field terminals are power limited per Class 2 transformer. 1 Contact clean spike of 300 ma contact close 2 As available to the model 3 15A inrush, 60 VA maximum, 450 VA inrush (inductive PF=0.6, 60 Hz) 4 See Table 4 for maximum current specifications. 5 Assumes 2A of current load on all BOs combined. Shortest wires are recommended. 6 Assumes a 2.8% voltage drop due to length of cable and gauge of wire. 7 Assumes all BO power is wired separately from UNT. Shortest wires are recommended. 8 Maximum combined current of R and at phone jack total < 2.4 VA (100 ma) 9 Binary outputs are relay isolated. 6 UNT1100 Series Installation Bulletin

Table 4: +15 VDC Output Capacity Controller Maximum AO Current (ma)* Maximum Available +15 V External Current (ma) UNT1108 0 60 UNT1126 20 37 UNT1144 40 16 * If the maximum AO current is known to be less than the amount shown, the difference can be added to the maximum available +15V external current.! CAUTION: Disconnect all power services, including before wiring. To wire the UNT1100: 1. Terminate wiring per engineering drawings. 2. Install the Metasys N2 Bus to the UNT1100. Grounding and Isolation for UNT1100 with Single Transformer Grounding and Isolation for UNT1100 with Separate Load Transformer Typical Wiring Connections Examples Power Transformer to isolation transformers for UNT1100 Series controllers are not mandatory. Load Isolation UNT1100 Series controllers do not require an isolation relay, however you must connect the jumper wire from the terminal to the adjacent terminal if the contact loads are grounded (via the single earth ground connection at the transformer secondary common). In this case, all loads are configured for high side switching. A separate load transformer may be necessary because of transformer VA limitations or to completely isolate loads from the UNT1100 digital circuitry for noise reduction. You can connect the separate load power transformer secondary to earth ground as long as doing so is compatible with equipment being controlled. In this case, remove the jumper from to the adjacent terminal, and attach the second transformer to the terminal. Figure 6 shows typical UNT1100 wiring connections for power, analog output, binary output, binary input, voltage analog input, and typical resistive analog input. UNT1100 Series Installation Bulletin 7

Typical Power Connection Typical Binary Input Connection Typical Resistive Analog Input Connection BI1 BI2 50/60 Hz BI1 BI BI2 W49 W36 W37 W38 W1 W2 W5 W6 W52 W56 W55 COMMON Pressure Switch 0-2K Potentiometer PWR Typical Voltage Analog Input Connection 1K Nickel Temperature Sensor Typical Analog Output Connection +15VDC + - 2-Wire Proportional Valve Actuator 50/60 Hz W1 W2 W5 W6 W25 W49 AO1 W56 Differential Pressure Sensor 0-2V Humidity Sensor 0-10V W3 W4 AO1 W52 W55 PWR COMMON Typical Binary Output Connection R Heating R 50/60 Hz W14 W18 W19 W20 W23 W24 Cooling W49 W56 BO6 BO5 BO Factory W52 W55 COMMON PWR transformer Figure 6: Typical UNT1100 Connections Controls Group www.johnsoncontrols.com 507 E. Michigan Street Printed in U.S.A. P.O. Box 423 Milwaukee, WI 53201 8 UNT1100 Series Installation Bulletin