Technical Note PLX82-MNET-61850

Similar documents
Technical Note. MVI56(E)-MNETR Add-On Instruction Installation Guide

Technical Note. ProSoft Technical Publications. RLXIC-Sx Serial Cellular Radio Application Setup Guide

Technical Note. Converting Modbus applications from a 3150-MCM to an MVI46-MCM. Document Code: TN Author: Steve Crippen Date:

Technical Note. Rockwell Automation ControlLogix PLC Communications with 4B Watchdog Super Elite via a ProSoft Technology PLX31-EIP-MBTCP

MVI56E-LDM QUICK START GUIDE. ControlLogix Platform. C Programmable Linux Application Development Module

IMC-BHx-AC INSTALLATION GUIDE. Industrial Media Converter. Ethernet over Belden 9463 Blue Hose

PLX35-NB2 RELEASE NOTES. Network Bridge Stand Alone Gateway. July 20, 2018

DISCONTINUED IEC Slave to PROFIBUS DP Master Gateway

The client device could be another PLC (Quantum, M340, Premium...) or any other device that supports Modbus TCP client communication.

Using Add-On Instruction and CIPconnect TM

ICX35-HWC. Industrial Cellular Gateway 3G/4G LTE RELEASE NOTES

EAFC Export Utility USER MANUAL

RS485 I/O Expansion System

ILX34-MBS QUICK START GUIDE. Quick Start Guide. March 10, 2014

EtherNet/IP to Allen-Bradley DH+ or Remote I/O Gateway AN-X-AB-DHRIO

Technical Note. Typical Scenario Performance Test

PC56-HIST-xxxxLX ControlLogix Platform In-Rack PC with Data Historian

PS69-DPS. CompactLogix or MicroLogix Platform Profibus DP Slave Communication Module USER MANUAL

Using RLX2-IHx Bridging Client on Cisco Wireless Infrastructure

Stand-Alone Industrial Gateways

ILX34-MBS. User Manual Modbus Serial Module for CompactLogix L1 and Point I/O Adapters USER MANUAL

ProLinx REFERENCE GUIDE. Standalone Gateways Configuration and Troubleshooting 10/13/2009

MBP DRIVER MANUAL. ProLinx Gateway Modbus Plus. July 10, 2018

DH485 DRIVER MANUAL. ProLinx Gateway DH485 Interface. August 27, 2009

DeltaV Discovery for Life Science Research Laboratory Applications

PTQ-103M USER MANUAL. Quantum Platform IEC Master. June 30, 2009

PLX35-NB2 USER MANUAL. Network Bridge. September 22, 2017

MNETC PROTOCOL MANUAL. ProLinx Gateway Modbus TCP/IP Client. May 11, 2011

104S v2 PROTOCOL MANUAL. ProLinx Gateway IEC Server (Firmware v2.xx) March 19, 2010

RED HAT LEARNING SUBSCRIPTION

5209-MNET-CCLINK SETUP GUIDE

Mimic Simulated IO Drivers

PTQ-104S USER MANUAL. Quantum/Unity Platform IEC Server Communication Module. October 05, 2009

PTQ-DNPSNET-Q. Quantum / Unity Platform Distributed Network Protocol Interface Module USER MANUAL

PLX51-DL USER MANUAL. Data Logger Data Storage Module. April, 2018

MVI-ADM. 'C' Programmable Application Development Module DEVELOPER'S GUIDE

The max number of C910 controllers is 8 per ProtoNode.

Wireless I/O System USER GUIDE

PTQ-DNP. Quantum Platform Distributed Network Protocol Interface Module USER MANUAL

PM Sync User Manual 31 July 2012

6201-WA-MNET to 6201-WA-MNET

101M ProLinx Gateway IEC Master

6201-WA-ASCII to 6201-WA-DFNT

Universal Mobile Ad Package

Ethernet I/O Card. Ethernet I/O Card. Introduction. DeltaV Product Data Sheet. Easy to use. Powerful integration solution. Modular, flexible packaging

Parallel Redundant Protocol (PRP)

MVI56-MNET. ControlLogix Platform Modbus TCP/IP Interface Module USER MANUAL

DeltaV Executive Portal

Perceptive Enterprise Deployment Suite

Spirent TestCenter Virtual Controller Set up Guide

PC56 USER MANUAL. ControlLogix Platform In-Rack Industrial PC. November 18, 2009

IntelliBridge EC10 & EC5

How to Take Your Company Global on a Shoestring A low risk path to increasing your international revenues

The Economist rate card 2017 (GBP)

DeltaV Virtual Ethernet I/O Card

If it s embedded, it s Kontron.

Vertical Scaling of Oracle 10g Performance on Red Hat

MVI56E-MNETR. ControlLogix Platform Modbus TCP/IP Interface Module with Reduced Data Block USER MANUAL

ACSC100 ACSC101. Structural Calculations For Seismic Anchorage. Prepared for: APC Corp. August 28, 2006 RMJ Job No Structural Page 1 Engineers

nvent RAYCHEM NGC-40 SYSTEM OVERVIEW

[ Quick Start Guide ]

The Economist rate card 2017 (USD)

EA/Studio Installation Guide

KeyLink notes. Highlights SWIFT

Plant Messenger. Introduction. DeltaV Product Data Sheet. Delivers the information you want when and where you want it

MVI-ADM. 'C' Programmable 'C' Programmable Application Development Module DEVELOPER'S GUIDE

Acterna Mobile Service Tester 4200S Series. What s the fastest way to get a comprehensive picture?

ScholarOne Manuscripts. Reviewer User Guide

IntelliBridge EC10 and EC5

Symantec Encryption Desktop Version 10.2 for Mac OS X Release Notes. About Symantec Encryption Desktop

DeltaV SIS with Electronic Marshalling - Virtual Simulation

HP V5061u / V5061Au. Digital Camcorder. Quick Start Guide

How to View Cases and Customize the Homepage in Customer Service Central Cisco and/or its affiliates. All rights reserved. 1

MVI56E-MCMR. ControlLogix Platform Enhanced Modbus Master/Slave Communications Module with Reduced Data Block SETUP GUIDE

QuickPanel* View/Control Memory Module Quick Install Guide

Arc Premium Whisper Paging

MVI46-MNET. SLC Platform Modbus TCP/IP Interface Module USER MANUAL

BIOCLASS AND ICLASS SE BIOMETRIC READER COMPATIBILITY APPLICATION NOTE

Release Notes. Illustra Connect

MVI56E-MNETC. ControlLogix Platform Modbus TCP/IP Client Enhanced Communication Module USER MANUAL

Prisma II High Density Dual Reverse Receiver (HD-RXR) Software- Devtype Mismatch Technical Bulletin

Log on to a better way to work EncoreAnywhere patient management system

MVI56E-MNETR. ControlLogix Platform ControlLogix Enhanced Modbus TCP/IP Communication Module with Reduced Data Block SETUP GUIDE

Whitepaper. at a glance

Acterna optical test kits

DeltaV OPC History Server

OPC Data Access Server Redundancy

Quick Start Guide. Sabre 1400 Hand-held Scanner

R&S ELEKTRA EMC Test Software Swift and reliable measurement of electromagnetic disturbances

OPC Mirror. Introduction. OPC Server. Bi-directional data flow. Easy configuration. Fast data transfer. OPC Data Access compliant.

Navigator for ArcGIS an Introduction

Symantec Industrial Control System Protection (ICSP) Support for DeltaV Systems

INTERNAL USE ONLY (Set it to white if you do not need it)

Acterna optical test kits

Worldwide Consumer Digital Camera Forecast Summary:

Product Retirement Notice

Laptops and Netbooks: Mobile Broadband Traffic Across Regions

OPC Mirror Redundancy

Loading Configuration from TEC2000 to TEC2 using DCMLink. Configuration Instructions TEC2-LOAD-1001 Rev. 1 September 2015

Rapid SQL 7.6 Installation Guide

Transcription:

Performance Measurement Document Code: TN-004-11- Author: Marcio Rodrigues. Kentaro Seki, Neven Grgas Date: 11/08/11

Document Information Author Marcio Rodrigues, Kentaro Seki, Neven Grgas Description Performance Measurement Date 11/08/2011 Revision 1.00.005 Product Name Document Code TN-004-11_ Technical Note Document Code: TN-004-11- ProSoft Technology 5201 Truxtun Ave., 3rd Floor Bakersfield, CA 93309 +1 (661) 716-5100 +1 (661) 716-5101 (Fax) www.prosoft-technology.com Copyright 20011. All Rights Reserved. November 8, 2011 ProSoft Technology ProLinx, inrax, ProTalk, and RadioLinx are Registered Trademarks of ProSoft Technology, Inc. All other brand or product names are or may be trademarks of, and are used to identify products and services of, their respective owners. How to contact us: Sales & Support All ProSoft Technology products are backed with unlimited technical support. Contact our worldwide Technical Support team directly by phone or email: Asia Pacific +603.7724.2080, support.asia@prosoft-technology.com Languages spoken include: Chinese, Japanese, English Europe Middle East Africa +33 (0) 5.34.36.87.20, support.emea@prosoft-technology.com Languages spoken include: French, English europe@prosoft-technology.com, fax to +33 (0) 5.61.78.40.52 North America +1.661.716.5100, support@prosoft-technology.com Languages spoken include: English, Spanish orders@prosoft-technology.com, fax to +1 661.716.5101 Latin America (Sales only) +1.281.298.9109, latinam@prosoft-technology.com Languages spoken include: Spanish, English Brasil +55-11.5084.5178, brasil@prosoft-technology.com Languages spoken include: Portuguese, English November 8, 2011 Page 2 of 8

Document Code: TN-004-11- Contents Document Information... 2 OVERVIEW... 4 Introduction... 4 Hardware Requirements... 4 Software Requirements... 4 OVERVIEW... 5 TEST RESULTS... 7 November 8, 2011 Page 3 of 8

Overview Technical Note Document Code: TN-004-11- Introduction The purpose of this document is to report the performance measurement results. The test evaluates how the module performance is affected by number of data attributes and number of IEDs. Hardware Requirements The following table indicates the equipment required for the tests: Part Number Quantity Short Vendor Application Description 3 EUT Prosoft Equipment Under Test S80 SEPAM 2 IED Schneider Electric IED for report performance measurement SEL-751A 1 IED Schweitzer Engineering IED for MMS performance measurement Laboratories F650 By Controller 1 IED GE IED for GOOSE performance CPU65160 1 Modbus TCP/IP server Schneider Electric measurement Modbus TCP/IP server Software Requirements The following table indicates the software required for the tests: Software Vendor Version Application Prosoft 61850 Configuration Prosoft Technology 1.0.0.96 Module configurator Manager Anvil Triangle Microworks 3.00.0022 IED Simulator Ethereal Ethereal 1.1.0 Data capture SFT850 Schneider Electric 2.0.28 Schneider IED configuration AcSelerator Architect SEL 1.1.98 SEL IED configuration November 8, 2011 Page 4 of 8

Document Code: TN-004-11- Overview Performance Measurement In monitoring direction: it was measured the time interval between receiving a 61850 message from the IED (MMS read, report and GOOSE) and sending the Modbus TCP/IP write message to the server : 61850 message Measured time interval Modbus TCP/IP write In controlling direction: it was measured the time interval between the module receiving a Modbus TCP/IP write request and sending MMS write operation to a controllable data attribute in the IED: Modbus TCP/IP write Measured time interval MMS Write November 8, 2011 Page 5 of 8

Document Code: TN-004-11- The time interval is measured through data capture analysis. The tests are measured for two scenarios: Performance according to number of data attributes It was measured the performance while increasing the number of data attributes for the same IED. Performance according to number of IEDs Measures the performance while increasing the number of IEDs. The performance is measured for a real IED while the IED count is increased by adding simulated IEDs to the network. The following IEDs were used according to the IEC-61850 message type: Message Type IED Number of test repetitions GOOSE SEPAM S80 20 Report SEPAM S80 20 MMS Read SEL-751A 20 MMS Write SEPAM S80 10 Test Setup The performance is measured using a real IED according to the previous section. For the tests that requires more than one IED it was used simulated IEDs. The Unity processor (Schneider Electric) was used as a Modbus TCP/IP server: Modbus TCP/IP Server Simulated IEDs Measured IED IEC61850 Modbus TCP/IP November 8, 2011 Page 6 of 8

Document Code: TN-004-11- Test Results MMS Read Tests According to number of IEDs Number of IEDs Minimum (ms) Maximum (ms) Average (ms) 1 3.960 21.880 13.199 2 4.568 22.776 15.358 5 5.602 22.559 11.612 20 6.678 54.861 20.220 45 18.989 1105.8 37.655 According to number of Data Attributes Number of DAs Minimum (ms) Maximum (ms) Average (ms) 1 7.900 31.483 15.975 2 7.085 25.220 14.704 5 7.115 32.642 16.758 50 6.988 24.234 16.597 100 6.166 30.010 18.714 Report Tests According to number of IEDs Number of IEDs Minimum (ms) Maximum (ms) Average (ms) 1 3.336 4.356 3.553 2 3.385 4.604 3.729 5 3.676 5.692 4.682 20 4.295 204.69 48.601 45 13.892 764.504 213.895 According to number of Data Attributes Number of DAs Minimum (ms) Maximum (ms) Average (ms) 1 3.293 5.115 3.678 2 3.569 11.006 6.362 5 4.313 24.390 12.762 50 16.151 54.868 22.210 100 10.262 84.906 50.645 November 8, 2011 Page 7 of 8

Document Code: TN-004-11- GOOSE Tests According to number of IEDs Number of IEDs Minimum (ms) Maximum (ms) Average (ms) 1 2.155 3.747 2.643 2 2.176 63.050 14.903 5 2.181 226.238 36.529 20 648.320 3440.307 1755.598 45 2254.365 4575.712 3525.888 According to number of Data Attributes Number of DAs Minimum (ms) Maximum (ms) Average (ms) 5 2.180 63.050 14.900 50 15.908 1251.192 1051.487 100 33.784 1204.699 798.204 MMS Write Tests According to number of IEDs Number of IEDs Minimum (ms) Maximum (ms) Average (ms) 1 0.004 0.011 0.007 20 0.004 0.014 0.008 45 0.013 0.262 0.017 November 8, 2011 Page 8 of 8