District Cooling Marches on in Dubai The Emirates Towers Case Study

Similar documents
Best Tall Building Middle East & Africa Region The Index, Dubai Passive Design for the Middle Eastern High-rise

CASE STUDIES. Brevard Community College: Florida Power & Light. Cape Canaveral Air Force Station: NORESCO

AHMED HUSSIEN MOSTAFA

District Cooling Workshop

Energy Management of the Refrigeration Systems at Zurich Airport. Burkhard Bein. Schaffhausen,

Next Generation DCP Optimization using MV VSDs

FACT SHEET: IBM NEW ZEALAND DATA CENTRE

Efficiency of Data Center cooling

where we are, where we could be, how we can get there. 12/14/2011

Achieving Operational Excellence

Data Centre Energy Efficiency. Duncan Clubb EMEA Data Centre Practice Director CS Technology

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

Excellent location for Data Center Campus in Hanko

Report to: General Committee Date Report Authored: January 18, 2012

Comprehensive Energy Management & Utility Master Plan

Silicon Valley Power Data Center Program Rebate Application

DEDICATED HEAT RECOVERY UNIT (DHRC)

DISTRICT COOLING GCC AND QATAR. Presented By: Marafeq Qatar

Bremner Transformer Station and Cable Tunnel PROGRESS OF THE CLASS ENVIRONMENTAL ASSESSMENT STUDY

HIS ROYAL HIGHNESS SHAIKH HAMDAN BIN MOHAMMED BIN ZAYED BIN SULTAN AL NEHAYAN

Switch to Perfection

MSYS 4480 AC Systems Winter 2015

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Welcome. Hardeep Singh Service and Parts Director Trane Middle East & Africa

TEMPORARY POWER, COOLING & WATER

Analyze and Implement: Modernizing an Airport Central Utility Plant

7th Annual Statewide Energy Efficiency Forum Applying Building Technologies to Realize Savings June 16, 2016

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Air-Cooled Series R Chiller

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling

International 6SigmaDC User Conference CFD Modeling for Lab Energy Savings DCSTG Lab Temperature Setpoint Increase

Energy Performance Contracting

The City of St. Petersburg (City) initiated

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

Green Data Centers A Guideline

EDX DC-3 environmental monitoring solution

Indirect Adiabatic and Evaporative Data Center Cooling

Case study on Green Data Center. Reliance Jio Infocomm Limited

MEASURE MONITOR UNDERSTAND

multi-utility metering a total systems approach

The Energy. David L. Moss Dell Data Center Infrastructure

Utility System Infrastructure

Green IT and Green DC

18 th National Award for Excellence in Energy Management. July 27, 2017

Fair City Plaza. Task: Diagnose problems, recommend improvements for small municipal district cooling system

OPPORTUNITIES IN THE MIDDLE EAST

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Construct Chiller Plant, Phase I

Indirect Adiabatic and Evaporative Data Centre Cooling

Chiller Replacement and System Strategy. Colin Berry Account Manager

Water cooled chiller plant (all-variable)

Application of Green Technology For Data Centre

Green Computing and Sustainability

Cisco s Green Story. Connected Urban Development

Saving Energy with Free Cooling and How Well It Works

Nominee: Riello UPS with The Rosebery Group

5 Servicing Capacity Assignment for Aurora, East Gwillimbury and Newmarket

that may have a direct effect on your bottom line. The question

Retro-Commissioning Report

Beyond BREEAM Excellent DCs. Cobalt Data Centre Campus

Ecolibrium. Cloud control. Keeping data centres cool. OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001

CenturyLink Data Center Services Omaha, Nebraska

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

Vodafone Sustainability & Innovation in emerging market

Improving the climate for data centers

Engineered Energy Solutions An Overview. Controls, Automation and Energy Conservation

LEADERS IN MEP, COMMISSIONING & ICT FOR BOSTON AND THE NORTHEAST

Regional Seminar Series. Critical Facilities, Data Center,& IT

LIFE CYCLE COST ANALYSIS, CRITERIA AND DATA SHEETS DOCUMENT NUMBER: APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL

Approval of Navy Yard Chiller Joint Development Agreement

Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design.

Industry leading low energy evaporative fresh air cooling.

Presentation. Guaranteed Energy Savings Performance Project

CLICK TO EDIT MASTER TITLE STYLE. AdvanTEC Solutions CHILLER PLANT HEALTH MANAGER

Energy Action Plan 2015

EP s approach to Power & Energy efficiency in DCs & paradigms

A Step Ahead and a Vision to be Greater. EnviroFocus Technologies (EFT) Tampa,FL

Trane mytest Water-cooled Chiller Performance Validation What you spec is what you get *

Measuring and Managing a Data Center Cooling Shutdown

NEXT GENERATION Data Centres FOR NEW GENERATION. Technology

Technology Solutions Group Specialized Real Estate Services

Dealing With a Disaster and Its Effect on the Utility Operation

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw

BENEFITS OF ASETEK LIQUID COOLING FOR DATA CENTERS

3300 kw, Tier 3, Chilled Water, 70,000 ft 2

Driving Proactive Facility Operations with Automated HVAC Diagnostics

M+W Group s Visionary Delta Datacenter

a) Provision of a chilled water supply b) Provision of electric power supply and other fuels

Data Centers. Powerful Solutions That Put You in Control. Energy Management Solutions. Where your energy dollars are used. 1

Optimiz Chilled January 25, 2013

Climate Technologies Investor Update

University Central Chilled Water Plants: Campus Planning, Sustainable and Building Planning Factors

Exploiting Temporal Diversity of Water Efficiency to Make Data Center Less "Thirsty"

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER. Applications in Diverse Climates within Europe, Middle East and Africa

SUPERSAVER. Energy Efficiency Optimization Software for Freecooling Systems

Case Study Leicester City Council

Large Tonnage Chillers. Kingsley Hu Technical Support Engineer

Transcription:

District Cooling Marches on in Dubai The Emirates Towers Case Study RETROFITTING JUMEIRAH EMIRATES TOWERS with DISTRICT COOLING Presented by: Samer Khoudeir Chief Sales & Marketing Officer Empower Tariq AlYasi Chief Operations & Maintenance Officer Empower June 29 th 2015

CONTENTS 1. Empower profile 2. The Project Overview 3. Objectives of the Project 4. Jumeirah Emirates Towers 5. Existing System used 6. Empower s DIFC plant 7. Challenges 8. How we connected 9. Benefits / Advantages 10. Schematic Diagram 11. Conclusion

EMPOWER Empower (Emirates Central Cooling Systems Corporation) Established in 2003 by Dubai Ruler s decree Set up as a joint venture between Dubai Electricity and Water Authority (DEWA) and TECOM Investments, a member of Dubai Holding. Completed 11 years of its operations in December 2014. The World s Largest District Cooling Provider Total cooling Capacity : 1,045,000 RT (2014) Number of Plant Rooms : 62 (2014) Buildings Served : 746 (2014) Number of Customers : 50,000+ Number of Employees : 700+ Length of transmission Pipeline : 195+Km (2014)

The Project - Overview Empower retrofitted landmark building in Dubai Jumeirah Emirates Towers, by replacing its chillers with district cooling. The project consists of 300 metres of chilled water pipe network and an Energy Transfer Station (ETS). The twin towers are supplied from Empower s DIFC (Dubai International Financial City) plant, which is having a total capacity of 65,000 RT, and primarily supplying to buildings in DIFC district.

The Project - Objectives Main objectives of this project are replacing the existing conventional cooling system used in the twin towers with district cooling system and thus save on: Energy / Electricity efficiency Space to utilize for other commercial purposes Overhead cost and maintenance, replacement of equipment etc. Reduce Carbon Footprint

JUMEIRAH EMIRATES TOWERS Facts Official Name - Jumeirah Emirates Tower (JET) Purpose - Mixed Use (Offices & Hotel & Retail) Completion - 2000 Rankings: Global Ranking : #31 Tallest in the World Regional Ranking : #11 Tallest in Middle East National Ranking : #9 Tallest in United Arab Emirates City Ranking : #8 Tallest in Dubai Source: wikipedia

SYSTEM USED Existing System Used JET used conventional air-cooled chillers, placed adjacent to the towers. These chillers occupied valuable space of the complex, which can be used for other purposes including building restaurants and other facilities. A total of 18 chillers with the capacity of 350RT each (total capacity: 6,300 RT) were working continuously for the towers. These chillers used to consume around 18 MW.

SYSTEM USED Jumeirah Emirates Towers and old (air-cooled) Chillers

SYSTEM USED Old (air-cooled) Chillers sky view

SYSTEM USED Old (air-cooled) Chillers inside

DIFC DC PLANT Empower s DIFC District Cooling Plant Empower s district cooling plant in Dubai International Financial Centre (DIFC) was commissioned in 2004 with a total capacity of 65,000RT. The plant serves mainly to buildings in DIFC district. Empower uses TSE technology at this plant and thus saves huge on potable water.

CHALLENGES Challenges in implementing the project Concept Design JET - building designed for conventional stand-alone system, served air cooled chillers Delta T (DT) of the building system was: 10 F Existing cooling capacity was 6,300 RT. However, Empower re-assessed the required capacity for the buildings and fixed it on 4,000-5,000 RT. The contract is signed as 5,000 RT + 1,000 RT as stand-by for 3 years. Switching over between the stand alone system and the DC system with Zero Downtime considering the elite profile and the importance of the building, given the fact the Ruler of Dubai and Prime Minister of UAE s office is situated in JET. Considering these features, Empower waived Temperature Surcharge.

CHALLENGES Challenges in implementing the project Challenges of Connecting Paving the network from DIFC plant to JET, along with important and busy road in Dubai- Road 312. (Road 312 is the key road which provide access to Dubai World Trade Center and World Trade Center Exhibition Halls which hosts international exhibitions throughout the year). The chilled water network was constructed on the opposite side of the Road where JET was located and the challenge was crossing the road to reach JET, without completely closing Road 312, or temporary traffic diversion. Carried out by NDRC (Non Destructive Road Crossing) by means of micro tunneling for a length of approximately 100m. The supply and return pre-insulated pipes of 26 outer diameter each was installed inside one concrete tunnel 2.5m wide at a depth of approximately 10m below the road level

HOW WE CONNECTED ETS Micro Tunnel ends Micro Tunnel starts Emirates Towers Complex EMPOWER DIFC PLANT

HOW WE CONNECTED Main determinations required to complete the connection to the Emirates Towers 1. Determining the source of the cooling 2. Determining the Location of the Energy Transfer Station 3. Determining the physical connection including the chilled water pipe route 4. Determining the method of connection considering No interruption of cooling services to the buildings

HOW WE CONNECTED 1. Determining the source of the cooling Emirates Towers DIFC PLANT Existing Air Cooled Chiller Plant Considering the available capacity in the DIFC Plant and its near proximity to the towers, it was decided to connect the DIFC Plant to the Emirates Towers

HOW WE CONNECTED 2. Determining the Location of the Energy Transfer Station Several locations have been explored and it was decided to locate the ETS within the Mechanical Room where the primary and secondary pumps are located

HOW WE CONNECTED 2. (cont.) Determining the Location of the Energy Transfer Station (Cont.) Fitting Heat Exchangers in the available space was a very challenging exercise due to the tight working space and working around existing systems.

HOW WE CONNECTED 3. Determining the physical connection including the chilled water pipe route Extension of the main pipe line Tapping from the main line and crossing the road through micro tunneling method Extending the pipes through landscape area to the ETS Location

HOW WE CONNECTED 3. (cont.) Determining the physical connection including the chilled water pipe route Excavating for Driving & Receiving Pits Installation of micro tunneling equipment at Driving Pit Driving the concrete pipes sleeves Completion of micro tunneling at Receiving Pit Installation of chilled water pipes inside the concrete sleeves

HOW WE CONNECTED 4. Determining the method of connection considering No interruption of cooling services to the buildings The flow originally oriented to the air cooled chillers plant needed to be diverted toward the heat exchangers located in the ETS A suitable location was determined and Hot Tapping (to avoid shutting down the system) connections were tapped from this location The chilled water flowing towards the air cooled chiller plant needed to be stopped to enable the removal of the plant and the associated pipes

HOW WE CONNECTED 4. Determining the method of connection considering No interruption of cooling services to the buildings Location for Hot Tapping to divert the flow to the ETS Room To & From Air Cooled Chillers Plant

HOW WE CONNECTED 4. (cont.) Determining the method of connection considering No interruption of cooling services to the buildings Water Stopping Fitting, all pipes downstream these fittings were removed. Hot Tapping Location

HOW WE CONNECTED 4. (cont.) Determining the method of connection considering No interruption of cooling services to the buildings (Cont.) Chilled Water flows toward s the ETS Room instead of the Air Cooled Chillers Plant

EMIRATES TOWER CHILLED WATER SCHEMATIC DIAGRAM

HOW WE CONNECTED Emirates Towers No Longer need the Air Cooled Chillers Plant Air Cooled Chillers Plant will be removed for a future a development to be constructed

BENEFITS OF DISTRICT COOLING Significant reduction in Electrical energy consumption. a) Electrical Energy Consumption steeply reduced by 40% in comparison with the same period previous year. b) A Net saving of 4,000,000 kwh realized by Customer.

BENEFITS OF DISTRICT COOLING Elimination of Noise Pollution from Air-Cooled Chillers 95 dba. 30,000 Square Feet. Of Plot available for commercial purpose. Demand side management Peak electrical demand load of 10.8 MW reduction on Power generation. We estimate an Annual Electrical energy consumption of 12.8 million kwh. Environmental benefit : Annually 6,386 ton of carbon di-oxide emission reduced.

THANK YOU