PROFIBUS DP Option. for FlexDrive II, Flex+Drive II and MintDrive II. Reference Manual 10/02 MN1911

Similar documents
DeviceNett Option. for FlexDrive II, Flex+Drive II and MintDrive II. Reference Manual 10/02 MN1910

CAN Option for FlexDrive II, Flex+Drive II and MintDrive II. Reference Manual 10/02 MN1909

Profibus DP Expansion Board

DeviceNet Expansion Board

Resolver to Digital Expansion Board

CAN & Auxiliary I/O Option for Flex+Drive II and MintDrive II. Reference Manual 05/07 MN1908

Designing a NextMove PCI Breakout Unit

Profibus DP Expansion Board

Master Pulse Reference/ Isolated Pulse Follower Expansion Board

OPERATING AND SERVICE MANUAL. Universal Interface Device 47

OPERATING AND SERVICE MANUAL. Universal Interface Device 47

Wallstations for use with Grafik 3000 and 4000 Series Systems

It s Under Control. Installation and Operation Guide CPB-1. Control Port Connecting Block V 1.1

DCS-E 1kW Series, DLM-E 3kW & 4kW Power Supplies

MN1954 Fieldbus Option

KBMG MULTI-SPEED BOARD

Mint Configuration Tool

SIAC-PS 3G SIGNAL ISOLATOR WITH POWER SUPPLY (PART NO. 8890) INSTALLATION INSTRUCTIONS

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01

User Guide. Control Box. RoscoLED TM.

OPERATING AND SERVICE MANUAL. Universal Interface Device 45

User Manual Revision English

Tornado F-5. Motor Backspin Detect Relay And Probe For F-5 Motor Controller

PMDX-105. I/O Option Riser Board User s Manual. Document Revision: 1.1 Date: 7 September 2004 PCB Revision: PCB-443A

EA014 TORQUE CALIBRATION ADAPTER OPERATION MANUAL

PDS8u POWER DISTRIBUTION SYSTEM USER'S MANUAL

Xxxxx Xxxxxx Bridge / Strain Gauge Data Logger

Name Specifications Model Standards RS-422A Converter. Converts RS-233C to RS-422A/RS-485. CJ1W-CIF11 UC1, N, L, CE

User s Guide. POWERVAR Single Phase Power Conditioners

MiniModules. Reference Manual. Series R CT 3002 V 1.0 MiniModule USB Service Adapter and Software

PS8 - II. Professional Power Sequencer. User s Manual

FNet Repeater Installation & Operator s Instruction Manual

Power Quality Recorder

AC4G-D User s Manual

87421/22A Power Supply. Operating and Service Manual

Xxxxx Xxxxxx OM-CP-QUADVOLT. OM-CP-OCTVOLT 8-Channel Low Level DC Voltage Data Logger. 4-Channel Low Level DC Voltage Data Logger INSTRUCTION SHEET

VDI Pro Voltage & Dry Contact Interface Installation and programming Guide MODEL VDI MK2

Conductive Level Controller

9040/9040UK. Users Manual. Phase Rotation Indicator

PCM-7140 Pulsed Current Source Operation Manual

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL

PIM-Mini Pulsed Current Source Operation Manual

CEM M-RS485 INSTRUCTION MANUAL (M014B A)

User Manual Revision English

CPCI-PS24 24V-Power Supply

INTMOD485-LH Protocol Converter

ABB Drives. User s Manual. Analogue I/O Extension Module RAIO-01

Three Channel XLR Balanced Patch Bay. Artcessories. User's Manual

Model VT120 Fast Timing Preamplifier Operating and Service Manual

User Manual Revision English

Flex+Drive II and MintDrive II Brushless AC Servo. Controls. Product Characteristics Overview

SAFETY PRECAUTIONS CAUTION WARNING CAUTION. Thank you for purchasing ig5a Series Profibus Communication Module

Name Specifications Model Standards. Converts RS-233C to RS-422A/RS-485. CJ1W-CIF11 UC1, N, L, CE

LEDsmart+ Slave Relay Device

HDMI Extender over Cat5e/6

E-BEAM SWEEP NILES ELECTRONICS

EA003 OPTICAL TACHOMETER CALIBRATION ADAPTER OPERATION MANUAL

VP Process Inc. Model: VP-EC-RDU Modbus RTU LCD Display

NE1A-SCPU Series. Safety Network Controller. Achieve Safety Control through Programming. Ordering Information. Specifications.

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

Installation Instructions for Eaton Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2

SATA II HDD Canister KISS DA 435 Quick Reference Guide

Install Motor Controller User Manual

Dual Channel Active Direct Box. Artcessories. User's Manual

User s Guide. OM-CP-PRHTEMP2000 Pressure, Humidity and Temperature Data Logger with LCD

SUPPLEMENT TO THE MDC-360C MANUAL MDC-361C. Film Deposition Controller. IPN Rev. C

MAXIMA + Series ROTARY LEVEL CONTROL

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Sonic Ruptor 400. User Manual

CAN Test Box. User s Guide

BNI PBS Z001 BNI PBS Z001 BNI PBS Z001 BNI PBS Z001 Short Guide

Model P4017 Single Channel USB Oscilloscope. Quick Start Guide

WARRANTY & LIMITATION OF LIABILITY

TDM-170 TIMER DISPLAY

M3 4-Slot Ethernet Cradle. User Guide. Cradle Model: A-4CR-00ED-110-R00. Compatible Device: M3 RED, GREEN and SKY. Version 2.1 Released in March 2013

SCHMIDT Sensor interface PROFIBUS Instructions for use

iconverter 2-Module Power Chassis

OPERATOR MANUAL OSD361 FIBER OPTIC CCTV TRANSMITTER MODULE

User Manual Revision English

CK3W-PD048 CSM_CK3W-PD048_DS_E_DITA_1_2

Power Quality Recorder

OPERATIONS MANUAL PCM-I/O48

FTC-200 X-ray Tube Controller Users Manual

Two Channel 48 Volt Phantom Power Supply. Artcessories. User's Manual

3-4 SAS/SATA II HDD Canister Entry version USER S MANUAL XC-34D1-SA10-0-R. Document number: MAN A

NextMove PCI Motion Controller

User Manual Revision English

OPERATION MANUAL BO BLASTER S OHMMETER

XCD EDGE Controller Driver

Seven Channel Remote Control

CM17215HR 100Mb/s Fiber CM17212HR 10/100Mb/s UTP PC/104-Plus Dual Ethernet utilitymodule. User s Manual

I/O Expansion Box Installation & Operator s Instruction Manual

CF15118 CompactFlash Carrier utilitymodules User s Manual

DCM Digital Control Modules

AMAX-2750SY Series. 32-ch AMONet RS-485 Isolated Digital I/O Slave Modules. User Manual

Serial PROFIBUS Interface

MULTIPLEXER MX4. Operation and Installation Manual. Pacific Micro Systems

AD-7830 Servo Amplifier

M3 Snap-On. User Guide. Product Model: A-SNO-ATYP-110-R00 (A type), A-SNO-BTYP-110-R00 (B type) Compatible Device: M3 GREEN and SKY

Contents. HP E1586A Rack Mount Terminal Panel User s Manual

Transcription:

PROFIBUS DP Option for FlexDrive II, Flex+Drive II and MintDrive II Reference Manual 10/02 MN1911

Contents 1 General Information... 1-1 2 Introduction... 2-1 2.1 PROFIBUS DP option... 2-1 2.2 Units and abbreviations... 2-2 3 Input / Output... 3-1 3.1 Introduction... 3-1 3.2 Connector and LED location... 3-1 3.2.1 Profibus - X14... 3-2 3.2.2 Bus activity LED... 3-3 3.2.3 PROFIBUS DP setup... 3-3 4 Telegram Formats... 4-1 4.1 Introduction... 4-1 4.1.1 Command telegram format... 4-1 4.1.2 Response telegram format... 4-2 4.1.3 Bytes 8-27... 4-2 MN1911 Contents i

ii Contents MN1911

1 General Information 1 LT0157A00 Copyright Baldor (c) 2002. All rights reserved. This manual is copyrighted and all rights are reserved. This document or attached software may not, in whole or in part, be copied or reproduced in any form without the prior written consent of BALDOR. BALDOR makes no representations or warranties with respect to the contents hereof and specifically disclaims any implied warranties of fitness for any particular purpose. The information in this document is subject to change without notice. BALDOR assumes no responsibility for any errors that may appear in this document. Mintt is a registered trademark of Baldor. PROFIBUS is a trademark of PROFIBUS International. Limited Warranty: For a period of two (2) years from the date of original purchase, BALDOR will repair or replace without charge controls and accessories which our examination proves to be defective in material or workmanship. This warranty is valid if the unit has not been tampered with by unauthorized persons, misused, abused, or improperly installed and has been used in accordance with the instructions and/or ratings supplied. This warranty is in lieu of any other warranty or guarantee expressed or implied. BALDOR shall not be held responsible for any expense (including installation and removal), inconvenience, or consequential damage, including injury to any person or property caused by items of our manufacture or sale. (Some countries and U.S. states do not allow exclusion or limitation of incidental or consequential damages, so the above exclusion may not apply.) In any event, BALDOR s total liability, under all circumstances, shall not exceed the full purchase price of the control. Claims for purchase price refunds, repairs, or replacements must be referred to BALDOR with all pertinent data as to the defect, the date purchased, the task performed by the control, and the problem encountered. No liability is assumed for expendable items such as fuses. Goods may be returned only with written notification including a BALDOR Return Authorization Number and any return shipments must be prepaid. Baldor UK Ltd Mint Motion Centre 6 Bristol Distribution Park Hawkley Drive Bristol, BS32 0BF Telephone: +44 (0) 1454 850000 Fax: +44 (0) 1454 850001 Email: technical.support@baldor.co.uk Web site: www.baldor.co.uk Baldor Electric Company Telephone: +1 479 646 4711 Fax: +1 479 648 5792 Email: sales@baldor.com Web site: www.baldor.com Baldor ASR GmbH Telephone: +49 (0) 89 90508-0 Fax: +49 (0) 89 90508-491 Baldor ASR AG Telephone: +41 (0) 52 647 4700 Fax: +41 (0) 52 659 2394 Australian Baldor Pty Ltd Telephone: +61 2 9674 5455 Fax: +61 2 9674 2495 Baldor Electric (F.E.) Pte Ltd Telephone: +65 744 2572 Fax: +65 747 1708 Baldor Italia S.R.L Telephone: +39 (0) 11 56 24 440 Fax: +39 (0) 11 56 25 660 MN1911 General Information 1-1

Product Notice Only qualified personnel should attempt the start-up procedure or troubleshoot this equipment. This equipment may be connected to other machines that have rotating parts or parts that are controlled by this equipment. Improper use can cause serious or fatal injury. Only qualified personnel should attempt to start-up, program or troubleshoot this equipment. Safety Notice Intended use: Drives incorporating the PROFIBUS DP option are intended for use in stationary ground based applications in industrial power installations according to the standards EN60204 and VDE0160. They are designed for machine applications that require variable speed controlled three-phase brushless AC motors. These drives are not intended for use in applications such as: H H H H H Home appliances Medical instrumentation Mobile vehicles Ships Airplanes. Unless otherwise specified, this drive is intended for installation in a suitable enclosure. The enclosure must protect the drive from exposure to excessive or corrosive moisture, dust and dirt or abnormal ambient temperatures. The exact operating specifications are found in the main installation manual supplied with the drive. The installation, connection and control of drives is a skilled operation, disassembly or repair must not be attempted. In the event that a drive fails to operate correctly, contact the place of purchase for return instructions. 1-2 General Information MN1911

Precautions WARNING: WARNING: WARNING: WARNING: WARNING: Do not touch any circuit board, power device or electrical connection before you first ensure that no high voltage is present at this equipment or other equipment to which it is connected. Electrical shock can cause serious or fatal injury. Only qualified personnel should attempt to start-up, program or troubleshoot this equipment. Be sure that you are completely familiar with the safe operation and programming of this equipment. This equipment may be connected to other machines that have rotating parts or parts that are controlled by this equipment. Improper use can cause serious or fatal injury. Only qualified personnel should attempt to program, start-up or troubleshoot this equipment. Be sure the system is properly earthed/grounded before applying power. Do not apply AC power before you ensure that earths/grounds are connected. Electrical shock can cause serious or fatal injury. Improper operation or programming of the drive may cause violent motion of the motor and driven equipment. Be certain that unexpected motor movement will not cause injury to personnel or damage to equipment. Peak torque of several times the rated motor torque can occur during control failure. The motor circuit might have high voltages present whenever AC power is applied, even when the motor is not moving. Electrical shock can cause serious or fatal injury. CAUTION: CAUTION: To prevent equipment damage, be certain that input and output signals are powered and referenced correctly. To ensure reliable performance of this equipment be certain that all signals are shielded correctly. MN1911 General Information 1-3

1-4 General Information MN1911

2 Introduction 2 2.1 PROFIBUS DP option PROFIBUS DP is available as a factory-fitted option (option P) on the FlexDrive II, Flex+Drive II and MintDrive II range of drives. The PROFIBUS DP option allows a PLC (or any other PROFIBUS DP master device) to: H H Perform simple motion, controlled using polled messages. Read/write data using the drive s onboard Comms array. (On FlexDrive II, only the extended comms array locations may be accessed - see the MintMT help file.) The inclusion of the PROFIBUS DP option can be easily identified by the extra 9-pin female D-type connector (X14) and Bus Activity LED on the front panel of the drive. It is also indicated in the drive s catalog number, which will have the letter P in the last four characters, for example MDH1A05TB-RP23, or FDH1A02TB-EP23. The catalog number is marked on the front of the unit, just below the Baldor logo. MN1911 Introduction 2-1

2.2 Units and abbreviations The following units and abbreviations may appear in this manual: LED... Light Emitting Diode MintMT... The control language used by Baldor drives PLC... Programmable Logic Controller WorkBench v5... The Windows application software for the Baldor drives 2-2 Introduction MN1911

3 Input / Output 3 3.1 Introduction Connections to the PROFIBUS DP option are made using the 9-pin female D-type connector X14. An additional LED is also present on the front panel, labeled Bus Activity. This LED shows various status conditions of the PROFIBUS DP option - see section 3.2.2. 3.2 Connector and LED location Bus Activity LED II Bus Activity X14 Profibus Pin Description Profibus X14 1 (NC) 2 (NC) 3 RX/TX Data B (Red) 4 TX Control + 5 0V for termination 6 +5V for termination 7 (NC) 8 RX/TX Data A (Green) 9 (NC) Figure 1 - PROFIBUS DP option connector and LED locations MN1911 Input / Output 3-1

3.2.1 Profibus - X14 Location Name Description Connector X14 Mating connector (not supplied): 9-pin male D-type PROFIBUS DP node terminating connector Profibus Standard female 9-pin D-type connector. 9 6 5 1 Connections to X14 should always be made using specially constructed PROFIBUS DP node terminating connectors. These typically contain a resistor chain and switch to ensure correct termination is present while the device is attached or removed from the network. Line inductors are often included to maintain correct impedance at high data rates. Standard D-type connectors should not be used. Only cables specified as suitable for PROFIBUS DP should be used. These consist of shielded red/green conductors and have a characteristic impedance of 150Ω. Node terminating connector Baldor control X14 from previous node to next node PROFIBUS DP cable PROFIBUS DP cable Off On Off On +5V (6) 0V (5) RX/TX Data B (3) RX/TX Data A (8) Figure 2 - Connection details The TX Control+ signal present on pin 4 (not shown) is used when the node is connected to a repeater. The signal indicates when the node is sending data, allowing the repeater to switch mode accordingly. For most applications repeaters are not used, so it does not need to be connected. 3-2 Input / Output MN1911

3.2.2 Bus activity LED After the initial power-on (or reset) sequence the LED is used to display the PROFIBUS DP bus status: LED status LED off LED green LED red Description The drive is switched off or has lost power. The master is present on the bus. The unit is being polled, is on line and is operating correctly. The master on the bus is absent or has failed to configure the unit correctly (e.g. by using an unsupported baud rate or telegram format), or the drive is using the same node ID as another slave device on the network. Check that the master is switched on and operating correctly. Confirm that the network is terminated properly. There is often a switch on a PROFIBUS DP node terminating connector which must be switched on to include the drive on the network. Check that the telegram format being sent by the master is correct. Check that the drive s node ID is not being used by another node on the network. The drive s node ID can be determined in WorkBench v5, either by selecting the Network tool or by typing Print NODE in the Command window. 3.2.3 PROFIBUS DP setup The PROFIBUS DP option can be configured in WorkBench v5, using the Network Wizard. The Network Wizard is displayed automatically as part of the Commissioning Wizard, but it can be selected at any time from the Setup section of the Toolbox. A number of MintMT keywords beginning with BUS... can also be used to configure and report activity of the PROFIBUS DP option. The node ID of the drive can be set using the SW1 front panel DIP switches, from WorkBench v5, or by using the NODE keyword. See the MintMT help file and the main installation manual supplied with your drive for further details. MN1911 Input / Output 3-3

3-4 Input / Output MN1911

4 Telegram Formats 4 4.1 Introduction The Baldor drive containing the PROFIBUS DP option can only act as a slave device, responding to telegrams received from the controlling PLC. The following sections describe the format for commands sent by the PLC and the response transmitted by the Baldor drive. 4.1.1 Command telegram format The format of the command telegram sent by the controlling PLC is shown in Table 1: Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 Control byte 1 Axis / Channel number 2 3 Command number (highbytefirst) 4 5 6 Data value 0 7 8-11 12-15 16-19 20-23 24-27 Optional: Data value 1 Optional: Data value 2 Optional: Data value 3 Optional: Data value 4 Optional: Data value 5 Table 1 - Command telegram format One byte is used to control major drive status conditions, such as enable/disable and stop. One byte sets the axis or channel number for which the command is destined. Two bytes contain the command number. Four bytes contain the actual data value to be sent to the drive as part of the command. Some or all of these bytes might not be used, depending on the command. For information about bytes 8-27, see section 4.1.3. MN1911 Telegram Formats 4-1

4.1.2 Response telegram format Each time the drive is polled by the master, it returns a response telegram. The frequency at which the information in the response telegram is updated can be altered to suit the application. The format of the telegram transmitted by the Baldor drive is shown in Table 2: Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 Control byte 1 Limits and move status 2 3 Error code (highbytefirst) 4 5 6 Data value 0 7 8-11 12-15 16-19 20-23 24-27 Optional: Data value 1 Optional: Data value 2 Optional: Data value 3 Optional: Data value 4 Optional: Data value 5 Table 2 - Response telegram format One byte is used to return major drive status conditions, such as enable/disable and stop. One byte is used to return information about limit switches and the move status. Two bytes are used to return error values relating to the last command that was processed. Four bytes are used to return data, if required by the command. For information about bytes 8-27, see section 4.1.3. 4.1.3 Bytes 8-27 Bytes 8-27 are optional, since the drive is classified as a modular slave. This means that the telegrams can be of variable length according to how many additional process data channels are required. Each channel requires 4-bytes, as shown in Tables 1 and 2. These extra bytes can be assigned in the PROFIBUS master (PLC) configuration application. For full details of the command and response telegram formats, see the MintMT help file. 4-2 Telegram Formats MN1911

MN1911 Telegram Formats 4-3

4-4 Telegram Formats MN1911

Baldor Electric Company P.O. Box 2400 Ft. Smith, AR 72902-2400 U.S.A. Visit www.supportme.net for the latest documentation and software releases. Australia Australian Baldor PTY Ltd Tel: +61 2 9674 5455 Fax: +61 2 9674 2495 Europe Baldor ASR GmbH, Germany Tel: +49 (0) 89 905 080 Fax: +49 (0) 89 905 08491 Europe (Southern) Baldor ASR AG, Switzerland Tel: +41 52 647 4700 Fax: +41 52 659 2394 Japan Baldor Japan Corporation Tel: +81 45 412 4506 Fax: +81 45 412 4507 Mexico Baldor de Mexico Tel: +52 477 761 2030 Fax: +52 477 761 2010 Singapore Baldor Electric PTE Ltd Tel: +65 744 2572 Fax: +65 747 1708 United Kingdom Baldor UK Ltd Tel: +44 1454 850000 Fax: +44 1454 859001 U.S.A. (Headquarters) Baldor Electric Company Tel: +1 479 646 4711 Fax: +1 479 648 5792 For additional office locations visit www.baldor.com LT0157A00