Single-Axis Counter BDD 611

Similar documents
2-Axis Counter BDD 622

BNI USB A501. USB IO-Link Master User's Guide. english

Z58-6XX SERIES 6 Digits Universal Position Indicator for incremental or absolute encoders

BNI USB A501. User s Guide

TABLE OF CONTENTS. Communication Functions

BNI IOL E012. IO-Link 1.1 sensor/actuator hub with extension port User's Guide

Manual Electronic Identification Systems BIS Processor BIS C-6_0 RS 232 C-6_ _836905_E_0704.p65 Deutsch bitte wenden!

Serial PROFIBUS Interface

11 Serial Communications

Compact Card Dispenser

Industriefunkuhren. Technical Manual. Signal Converter. for DIN Rail Mounting Series 4800xx-yy ENGLISH

BNI PBS Z001 BNI PBS Z001 BNI PBS Z001 BNI PBS Z001 Short Guide

BNI PNT Z015 BNI PNT Z015 BNI PNT Z015 BNI PNT Z015 BNI PNT Z015. IP67 Modules User s Guide

BNI IOL K023 BNI IOL K023. User s Guide

PD1100 STAND-ALONE PROGRAMMING & USER S GUIDE. use the freedom

Installation & Operation

BIC 1B0-ITA50-Q40KFU-SM4A4A BIC 1B0-IT005-Q40KFU-SM4A4A BIC 2B0-ITA50-Q40KFU-SM4A5A. User s Guide

BNI IOL A027 BNI IOL A027

DX 345, DX 346, DX 347, DX 348

BNI DNT Z004 BNI DNT Z005 BNI DNT Z005 BNI DNT Z005 Short Guide

Intrinsically safe batch controller Batching Master 110i

BNI IOL Z046. IO-Link 1.1 Sensor hub with extension port User's Guide

GV204 Impulse Splitter for Incremental Encoders

BNI IOL Z046. IO-Link 1.1 sensor/actuator hub with extension port User's Guide

Hints for Replacement of Obsolete Controller Models BY240 with New Models BY340

BNI IOL Z012 BNI IOL-302-S01-Z012 BNI IOL Z042

BNI IOL K006 BNI IOL K006-C01 BNI IOL-302-S01-K006 BNI IOL-302-S01-K006-C01. IO-Link 1.1 Sensor-Hub / Actuator-Hub User s Guide

BNI IOL Z019. IO-Link 1.1 sensor hub With extension port User s Guide

BNI IOL K023 BNI IOL K023. User s Guide

Mounting Dimensions / Viewing 2 Mounting Options 3. Wiring Configuration 4. Quick Set up Procedure 5. Changing Intensity 6.

BNI IOL K006. IO Link Sensorhub digital User s Guide

DCA - 10 / DCA TTS Systems

Hardware Manual RM CANview

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

BTL6-A_10-M -A1-S115. Data Sheet. english

BIS L x-07-S4

BIS L , BIS Z-EL-...

BNI IOL Z013 BNI IOL-302-S01-Z013. User s Guide

BNI IOL Z026 BNI IOL-302-S01-Z026. User s Guide

BNI IOL Z026 BNI IOL-302-S01-Z026 User s Guide

SERIAL INTERFACE. Series SSW-05

Manual Electronic Identification Systems BIS Processor BIS L-60_0 RS232 L-60_0-RS232_829572_0311_e.p65 Deutsch bitte wenden!

DX 342. Multi Function Counters with 2 Presets, 2 Relay Outputs and Serial RS 232 / RS 485 Interface. Operating Instructions. control motion interface

solartron digital readout model no. DR600 DR700 installation manual

BNI IOL Z036 BNI IOL Z037. Smart Light User s Guide

Compact Card Dispenser

DIGITAL DISPLAY. for Industry Applications. Series WAY-SSI. Key-Features:

BNI IOL K023 BNI IOL K023. User s Guide

BNI PNT Z015 BNI PNT Z015 BNI PNT Z015 BNI PNT Z015. IP67 Modules User s Guide

KYTronics Corp.,Ltd KYT-22XX SPECIFICATIONS B 1 OF kytronics.co.kr. 3 rd Floor, A-Dong, Twin Town-Bldg,

BNI EIP Z016. IP67 Modules, 8 Outputs BNI EIP Z016 BNI EIP Z016 IP67 Modules, 16 Outputs User s Guide

BIS S-6027 Ethernet with TCP/IP-Protocol

BNI PNT Z015. IP67 Modules 4 IO-Link/In-/Outputs,12 In-/Outputs User s Guide

SSI Indicator Multi-Function Unit with Two Relay Outputs and Serial Interface, for Use with Singleturn or Multiturn SSI Encoders

Operating instructions. Speed monitor D / / 2014

GS202 Encoder Switch

PRODIS -SSI Digital Process Meter for SSI position sensors. Instruction Manual. Please read carefully before installation and operation!

BNI PNT Z015. IP67 Modules 16 Input User s Guide

SCHMIDT Sensor interface PROFIBUS Instructions for use

JetWeb JX6-INT1 Function Description

BNI IOL-104-S01-Z012-C02

Series ID / IA / IR Dual position and differential indicators for use with two encoders or measuring systems (SSI absolute or incremental)

Operating Manual. ZX020 Miniature Low Cost Counter for Input Frequencies up to 60 khz. Product Features:

User Guide. Modbus Module. For Digistart soft starters. Part Number: Issue: 3.

BNI PBS Z001 BNI PBS Z001 BNI PBS Z001. Quick start guide

Electronic Preset Counter with 2 Presets and Print interface. NE213 Prog Features

Device manual Profibus encoder. RM30xx RN30xx /00 06/2013

CONFIGURATION: The Reader, LED Indicator, pin numbers for the 9-pin connector and the 25-pin adapter are shown in Figure 1-2.

BNI IOL K006 BNI IOL-106-S01-K006 BNI IOL-106-S01-K006-C01. User s Guide

270 MHz Control Modules

Operating instructions

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

BNI IOL Z012. User s Guide

S7-300 Programmable Controller

Operating instructions AC010S Compact AS-i E-STOP safety module

INSTRUCTION MANUAL WCS-Interface Module, DeviceNet

THT-500-A/R (C5) 1. System Configuration COMMUNICATION INSTRUCTION MANUAL. No. THT5CE

Operating Manual UMB ISO Converter ISOCON Order Number: 8160.UISO

3 Input Multiplexer Operation Manual

BNI IOL K006 BNI IOL K006-C01 BNI IOL-302-S01-K006 BNI IOL-302-S01-K006-C01. IO-Link 1.1 Sensor-Hub / Actuator-Hub User s Guide

hipecs-cio100 CANopen I/O module with 16/16 digital I/O

North American Service Manual

I/O SIGNAL CONDITIONER

USER INSTRUCTION MANUAL FOR LOADCELL TRANSMITTER MODEL TDC/I/0550 (SOFTWARE: VER2A) INDEX

Handbuch Identifikations-Systeme BIS Kompaktauswerteeinheit BIS M S115 M S115_841305_0611_en.p65

Operating instructions. Switching amplifier DN0210 DN / / 2015

General Operating, Maintenance and Installation Manual

Absolute Encoders Multiturn

ESM-5907 MOTORIZED INSERTION STANDARD TYPE MAGNETIC CARD READER & IC CARD READER/WRITER WITH RS-232C INTERFACE

Technical data. General specifications. Linearity error ± 0.1 Functional safety related parameters MTTF d 480 a at 40 C Mission Time (T M ) L 10

BNI IOL Z036 BNI IOL Z037. Smart Light User s Guide

Message Display Operator Panel. UCT-33/36 Industrial Terminal. Manual 32.00

RS485 MODBUS Module 8I8O

Flex Series User Guide

Nokeval. No Manual. Model for serial inputs

Technical data. General specifications. Linearity error ± 0.1 Functional safety related parameters MTTF d 480 a at 40 C Mission Time (T M ) L 10

B63/ NS MS. EtherNet/IP LINK

AD-8923-BCD. Remote Controller (BCD) INSTRUCTION MANUAL 1WMPD

RS485 MODBUS Module 6RO

Operating Manual. English. Digital-Analog Converter DACON8-UMB.

Transcription:

Single-Axis Counter BDD 611 Technical Description, User's Guide english

No. 611-150 D/E. Edition 0705; Subject to modification. Replaces edition 0701. www.balluff.com Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a.d.f. Germany Phone +49 7158 173-0 Fax +49 7158 5010 balluff@balluff.com www.balluff.com

Single-Axis Counter BDD 611-R4Q4-0-54-N-00 BDD 611-R3Q4-0-52-N-00 for Incremental Measuring Systems Hardware version 03 Software version 10 1

1. Introduction 4 2. Safety 5 2.1 Personnel Qualifications 5 2.2 Proper use 5 2.3 Safety Notes 6 2.4 Safety Precautions 6 3. Technical Data 7 4. Commissioning 9 4.1 Installation 9 4.2 Connection 9 4.3 Measuring system supply voltage 14 4.4 Switching Output Logic 14 4.5 Keypad and Front Panel 15 4.5.1 Display 15 4.5.2 Key functions 15 4.6 Parameter and Function Levels 16 4.6.1 Entering parameters, changing the device functions 16 4.6.2 Parameter functions 17 4.6.3 Parameter list 30 5. Operation 32 5.1 Display and function keys 32 5.2 Key 32 5.2.1 F key 32 5.2.2 Shift Right key 32 5.2.3 Up key 32 5.2.4 Enter key 32 5.2.5 Absolute -Incremental mode 33 5.2.6 Erasing the EEPROM 33 2

6. RS232 interface 33 6.1 Connecting to the PC 33 6.2 Introduction 34 6.3 Technical Data 34 6.4 Functions 35 6.5 Format determination 35 6.5.1 Forward control 36 6.5.2 Backward control 36 6.5.3 Data control 37 6.6 Send 38 6.7 Receive 39 6.8 Printer mode 40 6.9 Serial commands 40 7. Part Numbering 41 8. List of Illustrations 41 3

1. Introduction The Balluff Single-Axis Counter is a convenient device for visualizing actual values on a machine. The device has 2 wear-free, short circuit protected driver outputs, PNP sourcing (only with 24V supply voltage). It is especially designed for use with the Balluff series BML-S _-QXY_-M _-Z0- with X = 5, 6 (supply voltage) Y = 1, 3 (signal level) Z = E, F, G, H, K, L, M, N, P, R. (min. edge separation) for Y = 1 encoder signal = RS422 Z = F, G, H, K, L, M, N, P, R. (min. edge separation) for Y = 3 encoder signal = HTL The optional RS232 port can be used for parameter setting as well as for direct connection to a printer having a serial port. 4

2. Safety This operating guide contains instructions for ensuring safe and proper installation and operation. If you have any difficulties which cannot be resolved by consulting this guide, please check with the machine manufacturer or vendor for additional information. Balluff GmbH is not liable for any personal injury or equipment damage resulting from improper commissioning, incorrect operation, misunderstandings or errors contained in this guide or on the display. Balluff GmbH reserves the right to make technical changes to the equipment or operating guide without prior notice. This means that errors in agreement between the equipment and the guide cannot be precluded. Pay particular attention to hazard notices in this operating guide. This equipment description should be carefully read in full before commissioning. Use of the operating guide presumes that the user is technically qualified. 2.1 Personnel Qualifications commissioning, installation and operation are to be performed only by qualified personnel. The personnel must have qualifications which are appropriate to their function and activity, e.g. Instruction and obligation to observe all application-related, regional and in-house regulations and requirements. Training in accordance with the standards of safety technology in the use and care of commensurate safety and work protection equipment. Courses in first aid, etc. 2.2 Proper use This position display has been developed solely for use on industrial machinery. 5

Any further use is considered improper. The manufacturer assumes no liability for damages resulting from such misuse. This risk is assumed solely by the user. 2.3 Safety Notes The following symbols are used for hazards and other important notes: The Hazard symbol warns of errors and hazards in commissioning and operation of the controller. This warning notice means a directly threatening hazard to the health of persons and contains special specifications and instructions as well as imperatives and prohibitions for preventing personal injury and damage to equipment. The Attention symbol means a possible hazardous situation and contains special specifications and instructions as well as imperatives and prohibitions for preventing personal injury and damage to equipment. The Note symbol indicates important and useful information and provides application tips. 2.4 Safety Precautions Since the device can be operated with 115V or 230V supply voltage depending on the model, be especially careful not to touch the unit and to secure the device in accordance with the relevant regulations. The device may not be opened and no screws removed from the housing! 6

3. Technical Data Fig. 1 Dimensions (illustration reduced) 7

Supply voltage 115V or 230 V AC ± 10 % or 24 V AC/DC Please specify when ordering Current draw Display Max. 150 ma, without connected measuring systems 1 x 6 decade LED display Digit height 14 mm Input signals 0 5 V low active 10-30 V high active Measuring system Incremental measuring system A, A/, B, B/, Z, Z/ or A, B, Z Supply voltage 5V or 24V for 24V BDD supply voltage or 5V or 12V for 115V / 230V BDD supply voltage Current draw per channel: < 3mA at 5V < 20mA at 24V Max. 150 ma Max. input frequency: Signal A or B: 1 MHz (RS422,P22 = 1) Min. edge separation for 4x processing: 250ns Signal A or B: 500 KHz (HTL,P22 = 0) Min. edge separation for 4x processing: 500 ns Output signals 2 output drivers 24V, 600 ma, PNP sourcing Operating temperature 0 40 C Storage temperature -20 - + 65 C Relative humidity max. 90 % Installation orientation Enclosure rating any Front side up to IP42 Dimensions 72 x 96 x 71 mm 3 (W x H x D) Installation depth including connector 8

4. Commissioning Most damage to the device is a result of faulty cabling and incorrect parameter values. Therefore commissioning is to be performed only by trained and expert personnel. 4.1 Installation The device is inserted into a control panel with a cutout of approx. 93 x 71 mm² and screwed in place using the holder provided. 4.2 Connection The device is operated with 115V or 230V AC or with 24V DC or AC. With 115V or 230V AC voltage the relevant regulations for contact protection must be observed in order to prevent personal injury. Before connecting, compare the part label on the back of the device with the desired connection voltage. Electrical cables are to be routed in accordance with the respective national regulations (e.g. VDE). Route measuring, signal and power cables separately. We recommend using only shielded cable connected to GND on the device. Ensure that no ground loops are created. 9

J2 low high J1 24V 5V 1 2 3 4 5 6 7 8 9 10 Con2 1 2 3 Con4 Con3 Con1 1 2 3 4 5 1 2 3 4 5 6 7 8 9 10 Fig. 2 Wiring diagram Connector and pinouts CON1 Supply voltage (230V AC) L N PE 1 2 3 4 5 Terminal strip, 5-pin Pin 1 L, max. 100 ma Pin 2 Jumper to Pin 3 Pin 3 Jumper to Pin 2 Pin 4 n Pin 5 PE, protection ground 10

CON1 Supply voltage (115V AC) L N PE 1 2 3 4 5 Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Terminal strip, 5-pin L n L N, max. 100 ma PE, protection ground CON1 Supply voltage (24V AC) L N PE 1 2 3 4 5 Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Terminal strip, 5-pin L, max. 300 ma (note part label!) NC NC n PE, protection ground CON1 Supply voltage (24V DC) +24V GND 1 2 3 4 5 Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Terminal strip, 5-pin +24V, max. 300mA (note part label!) NC NC GND GND 11

CON2 Measuring system input Terminal strip, 10-pin Pin 1 GND Pin 2 +24V, if jumper J1 at left is tied to 24V ( or +12V at 115V, or 230V AC supply voltage) +5V, if jumper J1 at left is tied to 5V Pin 3 Signal A Pin 4 Signal A/ (only for RS422, cf. Parameter P22) Pin 5 Signal B Pin 6 Signal B/ (only for RS422, cf. Parameter P22) Pin 7 Signal Z Pin 8 Signal Z/ (only for RS422, cf. Parameter P22) Pin 9 PE connection for shield Pin 10 PE connection for shield 12

CON3 In-/outputs (unused in-/outputs can be left unconnected) Outputs are available only together with 24V supply voltage version. Pin1 Supply for driver output 2 24 V DC Note part label! Pin 2 Output for driver output 2 (PNP sourcing) Pin 3 Supply for driver output 1 24 V DC Note part label! Pin 4 Pin 5 Output for driver output 1 (PNP sourcing) Switching input 4, input voltage 0 24 V Offset dimension/actual value output via RS232 Pin 6 Switching input 3, input voltage 0 24 V Freeze/Stop,/Absolute-Incremental Pin 7 Switching input 2, input voltage 0 24 V Set Pin 8 Switching input 1, input voltage 0 24 V Reset Pin 9 Pin 10 GND for switching inputs +24V for switching inputs CON4 RS232 interface (Option) Terminal strip, 3-pin Pin 1 Pin 2 Pin 3 RxD TxD GND 13

4.3 Measuring system supply voltage J1 24V 5V In order to set the supply voltage to the desired level, the back cover of the unit must be removed. Jumper 1 can then be used to select the desired voltage. (Observe data sheet for measuring system!) The respective voltage is printed on the circuit board. Jumper left 24V, for 24V supply of the measuring system (or 12V for supply voltage 115V or 230V AC). Jumper right 5V, for 5V supply of the measuring system. 4.4 Switching Output Logic J2 low high The switching input logic can be selected using Jumper J2. The switching states are printed on the circuit board. Jumper left low, inputs switch to GND. Jumper right high, inputs switch to +24V. 14

4.5 Keypad and Front Panel Fig. 3 Front panel 4.5.1 Display The display is used for visualizing the position as well as displaying the parameter values in the parameter levels. 4.5.2 Key functions 1. The F switches from the display level to the calibration and parameter levels and back. 2. The key is used to select a decade (flashing), which then can be edited in one of the function levels by using the key. It is also used for changing the parameter numbers in function level 2. 3. The key is used for editing the flashing decade in one of the function levels. 4. The E key is used for confirming an edited value in the function levels. This key must always be pressed after entering a parameter or calibration value in order to save it. 15

4.6 Parameter and Function Levels 4.6.1 Entering parameters, changing the device functions When changing control and calibration parameters, always take into account the effects on the overall system: The parameters may be protected against unintended changes by using a security code. This may be selected by the machine manufacturer himself. The device provides two levels, one for entering parameters and one for entering the set value (calibration function). 1. Calibration value function level 2. General parameter level The F key is sued to activate and exit function and parameter entry. Use the key to switch back and forth between the levels. To open a level use the E (Enter) key, which also serves to confirm an input value. Changes in the parameter setting can result in malfunction, stopping or failure. Changes to the parameter settings should therefore be made only by knowledgeable personnel. 16

Example: Changing the P 5 parameter in the Func2 level (parameter level): 1. Press the F key (display Func1) 2. Press the key (display Func2) 3. Press the E key (display P 00) 4. Press the key 5 times (display P 05) 5. Press the E key (display e.g. 1) 6. Shift the flashing decade using the key and increment the value using the key. 7. Confirm the value by pressing the E key. (display P 06) 8. Exit parameter entry by pressing the F key twice. (display shows actual value) If the parameter level is code-protected, then after Step 1 you must first enter the corresponding code and confirm by pressing E. 4.6.2 Parameter functions The parameters shown in the following are all performed according to the sample Parameter number Name [unit, minimum/maximum value) Parameter description. Parameters in which P00 is entered as the unit refer to the unit specified in parameter P00 (function level 2). Parameters which are filled with index ro can only be read. 17

Calibration level Func1: P00 Set value [P00/ -99999.999999] Set value which when actuating the Set input or confirming with E is written to the actual value window. Parameter level Func2: P00 Travel distance for factor calculation [any desired length unit/ 1, 10000] Contains any desired travel distance. These two parameters are needed so that the display can be set to various mechanical conditions, such as drives, spindle stroke, etc. 1. Any desired travel distance in the desired unit and resolution (P00). 2. The number of increments sent by the measuring system to the display when traveling this distance (P01). Only if these specifications are entered in P00 and P01 with no rounding error will the display operate correctly over the entire range. Therefore you should always select a travel distance over which a whole-number quantity of increments is sent by the measuring system. P01 Increments / travel distance [resolution of the measuring system/ 1, 65000 ] Number of increments per travel distance entered in P00 (the factor is automatically calculated from P00 and P01). Example 1: The measuring system in use sends 100 increments to the display over a distance of 1.00 mm. You want the display value to be shown in increments of 1/100 mm. Therefore each increment arriving from the measuring system must be accounted for. You should therefore set P00 and P01 to the same value (e.g. 1, 1 or 10.10 or 100, 100). 18

Example 2: The measuring system in use again has a resolution of 1/100 mm. But here you only want the display value to resolve to one place after the decimal point, i.e. 1/10 mm. This means that over a distance of 1 (0.1 mm) 10 increments are sent by the measuring system to the display. You should therefore set P00 to smaller than P01 by a factor of 10 (e.g. 1, 10 or 10.100 or 100, 1000). Example 3: A machine with a spindle drive has the following key data: Spindle rise 5.0 mm / absolute encoder with a resolution of 20 increments per revolution. You want the display to resolve down to one decimal place, i.e. in increments of 1/10 mm. This means that over a distance of 50 (5.0 mm) 20 increments are sent by the measuring system to the display. Therefore you should set P00 to 50 and P01 to 20. For inch settings, enter P00 in inches. P02 Edge evaluation [../1.3] The device can evaluate one, two or 4 edges from the measuring system. This parameter must be set depending on the desired resolution and limit frequency of the measuring system. Input value Edge evaluation 1 1 2 2 3 4 P03 Count direction reversal [../0.1] Changes the count direction of the display from up to down or the reverse. Input value Count direction 0 Count direction standard 1 Count direction inverted 19

P04 Decimal point [Decimal place/ 0, 5] This parameter is used to set the decimal place within the display. 0 = Turn off decimal place 1 = One decimal place, etc. Setting the decimal place has no effect on the display resolution. This is done only with parameters P00 and P01. P05 Code for calibrate level [6 decade number/ 0, 999999] By entering a code you can protect the device from calibration in function level 1. Then you are only able to calibrate to a new value after entering this code. P06 Code for parameter level [6 Decade number/ 0, 999999] By entering a code you can protect the parameter values in function level 2 from being overwritten. Entering parameter values is then only possible after entering this code. 20

P07 Front panel key functions [Function/ 0, 14] The front panel keys beyond the function levels. and E may be assigned special functions Input value Key function 0 Keys have no function 1 E Sets display to 0 2 Sets display to set value 3 Function 1 and 2 active 4 E activates offset dimension If this function is active, the offset dimension function is turned off through the external input! 6 Function 2 and 4 active 8 Incremental/Absolute changeover 9 Function 1 and 8 active 10 Function 2 and 8 active 11 Function 1, 2 and 4 active 12 Function 4 and 8 active 13 Function 1, 4 and 8 active 14 Function 2, 4 and 8 active 16 E Switches the display value, as well as all important parameters, to inches or back to mm 17 Function 1 and 16 active, etc. P08 Reset logic [type of reset/ 0, 1] Input value Reset function 0 Static reset As long as the reset input is active the display remains at 0 1 Dynamic reset The display is set to 0 with the edge of the reset pulse and then resumes counting. 21

P09 Encoder reset [type of encoder reset / 0, 2] Input value Reset function 0 Reset function turned off by index pulse from measuring system. 1 Reset function using index pulse from measuring system with rising edge. 2 Reset function using index pulse from measuring system with falling edge. P10 Set logic [type of set function/ 0, 1] Input value Set function 0 Static set As long as the set input is active, the display remains on the set value. 1 Dynamic set The display is set to the set value with the edge of the reset pulse and then resumes counting. 22

P11 Freeze/Stop/Incremental-Absolute [type of switch function / 0, 2] Selects the function of the Freeze, Stop, Incremental-Absolute input. Input value Freeze, Stop function 0 The display is frozen. The counter continues to count internally. 1 The counter is stopped. Arriving pulses are not processed. 2 The counter switches from absolute to incremental, or the reverse P12 Offset dimension [P00/ -10000, 10000] Enter the offset dimension in units of length, such as xx.x mm or x.xx inches. This value is subtracted from the display value when the offset measurement contact is activated. When the input is deactivated the value is added again. 23

P13 Switching input logic [binary code/ 0.15 ] In machine building both normally open and normally closed devices are used as electrical switches. To be able to adapt the device quickly to any hardware, the switching behavior of the inputs must be determined using this parameter. The respective settings can be found in the tables below. 1. Inputs switch to GND Terminal 5 Terminal 6 Terminal 7 Terminal 8 P13 N.O. N.O. N.O. N.O. 0 N.C. N.O. N.O. N.O. 1 N.O. N.C. N.O. N.O. 2 N.C. N.C. N.O. N.O. 3 N.O. N.O. N.C. N.O. 4 N.C. N.O. N.C. N.O. 5 N.O. N.C. N.C. N.O. 6 N.C. N.C. N.C. N.O. 7 N.O. N.O. N.O. N.C. 8 N.C. N.O. N.O. N.C. 9 N.O. N.C. N.O. N.C. 10 N.C. N.C. N.O. N.C. 11 N.O. N.O. N.C. N.C. 12 N.C. N.O. N.C. N.C. 13 N.O. N.C. N.C. N.C. 14 N.C. N.C. N.C. N.C. 15 24

2. Inputs switch to 24V Terminal 5 Terminal 6 Terminal 7 Terminal 8 P13 N.C. N.C. N.C. N.C. 0 N.O. N.C. N.C. N.C. 1 N.C. N.O. N.C. N.C. 2 N.O. N.O. N.C. N.C. 3 N.C. N.C. N.O. N.C. 4 N.O. N.C. N.O. N.C. 5 N.C. N.O. N.O. N.C. 6 N.O. N.O. N.O. N.C. 7 N.C. N.C. N.C. N.O. 8 N.O. N.C. N.C. N.O. 9 N.C. N.O. N.C. N.O. 10 N.O. N.O. N.C. N.O. 11 N.C. N.C. N.O. N.O. 12 N.O. N.C. N.O. N.O. 13 N.C. N.O. N.O. N.O. 14 N.O. N.O. N.O. N.O. 15 P14 Switching threshold of Outputs 1 [P00/ 0.999999 ] If the value stored here is exceeded by the display value, then Driver Output 1 is switched. P15 Switching threshold of Outputs 2 [P00/ 0.999999 ] If the value stored here is exceeded by the display value, then Driver Output 2 is switched. 25

P16 Output switching characteristic [static,clearing/ 0.1 ] Input value Output switching behavior 0 Static 1 Clearing If the value is set to 1, clearing, then the respective clear times can be set in parameters P17 and P18. P17 Clear time of switching output 1 [sec/ 0,2.50 ] The clear time of Output 1 can be selected within a range of 0 to 2.50 seconds. P18 Clear time of switching output 2 [sec/ 0,2.50 ] The clear time of Output 2 can be selected within a range of 0 to 2.50 seconds. P19 Actual value memory [on, off/ 0.1 ] Setting the parameter to 1 turns off the actual value memory. The position before powering down is no longer displayed after powering up. Cal appears in the display, which reminds the user to recalibrate the counter. P20 Sawblade correction [P00/ -10000,+10000 ] Here a value can be stored which is subtracted from the display value when the Set or Reset function is activated in incremental mode. 26

P21 Switching output logic [Logic/ 0.3 ] The switching outputs can be programmed so that they switch whenever the set upper or lower limits are exceeded. Input value Output function 0 1 switches when overshot 2 switches when overshot 1 1 switches when undershot 2 switches when overshot 2 1 switches when overshot 2 switches when undershot 3 1 switches when undershot 2 switches when undershot P22 Measuring system selection [standard, with inverted / 0.1 ] The device can operate with measuring systems whose supply voltage and signal level is 5V or 10-30V. The measuring system supply voltage can be set using jumpers on the rear side. When using 5V systems, always make sure that tracks A, B Z and their inversions are connected in order to prevent problems. Setting Measuring system 0 Only tracks A, B and Z are evaluated. 1 Tracks A, A/, B, B/ and Z, Z/ are processed. 27

P60 Serial adress [adress/ 11,99 ] When using the serial RS232 interface option enter the unit number here. Do not use adresses like 20, 30, 40,.., 90. These adresses are reserved for unit groups. A unit will not send any answer when communication with such a adress. P61 Baudrate [baud/ 1,4 ] The following baud rates are available. Setting Baudrate/ Baud 1 4800 2 9600 3 19200 4 38400 28

P62 RS232 Mode [mode/ 0,3 ] There are different modes for serial communication available. 0 Standard RS232 protocoll according to DIN 66019. 1 For printer usage. The display value will be send periodically to a printer in a time intervall set in parameter P63. 2 For printer usage. The display value will be send to a printer when pushing the E key. 3 For printer usage. The display value will be send to a printer when activating Con/ Pin5. P63 Time intervall to transmit actual value [seconds/ 0.00, 650.00 ] When parameter P62 is set to 1 the display value will be send periodically after reaching this time. P99 Actual value for RS232 transmission [P00/ -99999,999999] When parameter P62 is set to 0 the display value can be read out of the unit by adressing P99. 29

4.6.3 Parameter list For service purposes it is advisable to document the stored parameters stored in the controller when the machine was shipped. You can use the following table for this. Parameter Specific machine setting Function Level 1 --- P00 set value (calibration value) Function Level 2 --- P00 Distance for factor calculation P01 Pulses/distance P02 Edge evaluation P03 Count direction reversal P04 Decimal point P05 Code for calibration level P06 Code for parameter level P07 Key function P08 Reset logic P09 Encoder reset P10 Set logic Freeze/Stop,/Absolute-Incremental P12 Offset dimension P13 Switching output logic P14 Switching threshold Output 1 P15 Switching threshold Output 2 P16 Switching characteristic of the outputs P17 Clear time Output 1 P18 Clear time Output 2 P19 Actual value memory P20 Sawblade correction P21 Switching output logic P22 Selecting the measuringsystem 30

P60 Serial adress P61 Baud rate P62 RS232 mode P63 Time intervall to transmit actual value P99 Actual value for RS232 transmission 31

5. Operation 5.1 Display and function keys Function Shift Right Up Return Fig. 4 Function keys, displays 5.2 Key 5.2.1 F key Switches from display mode to the function levels and back. 5.2.2 Shift Right key Increments the parameter number, or shifts the flashing decade to be edited. 5.2.3 Up key Increments the number inside the flashing decade by 1. 5.2.4 Enter key Confirms the entry and switches to the next parameter number. 32

5.2.5 Absolute -Incremental mode To distinguish between absolute and incremental mode, a small "r" appears in the display to indicate incremental (relative) mode. Therefore in incremental mode there are only 5 decades in the positive and 4 decades in the negative range available. 5.2.6 Erasing the EEPROM Should it happen that a unit can no longer be initialized after powering up, there could be non-permitted values in the EEPROM memory. This memory can be deleted and the parameters set to their initialization values. To do this, turn on the device while holding down the Function, Up and Enter keys. 6. RS232 interface 6.1 Connecting to the PC An RS232 connection consists of at least 3 lines. RxD TxD GND Receive Data Transmit Data Ground A 9-pin Sub-D female on the PC is used. RxD and TxD must be cross-connected, since the sender of the one device is connected to the receiver of the other device. 33

6.2 Introduction The protocol is based on DIN 66019, ISO 1765, ANSI X3.28. These standards describe a control procedure in the data link of a transmission system. Only the host unit has the function of the bus master, and the units connected to it are slaves with individual addresses. Slaves are not permitted to send by themselves, but rather only when requested by the master. There are three call types for communication between master and slave. Send Receive Broadcast 6.3 Technical Data 7-bit ASCII 2400, 4800, 9600, 19200, 38400 baud 1 Stop bit 1 Start bit 1 Parity bit (even) 34

6.4 Functions Common to the control procedures below is that the transmission control characters specified in the code table per DIN 66 003 are used for data transfer. The transmission characters are used for determining format, for forward control, backward control, and synchronization. EOT: Control character (Hex04) End of Transmit AD1: Unit address, high byte AD2: Unit address, low byte STX: Control character (Hex02) Start of Text C1: Parameter code, high byte C2: Parameter code, C3: Parameter code, C4: Parameter code, low byte XXX: Data ETX: Control character (Hex03) End of Text BCC: Block check character ENQ: Control character (Hex05) Enquiry NAK: Control character (Hex15) Not acknowledge ACK: Control character (Hex06) Acknowledge 6.5 Format determination The transmission character sequence is the format for data transfer. The following transmission control characters are used for indicating the format: STX: ETX: Control character Ctrl B (Hex02) Start of Text Control character Ctrl C (Hex03) End of Text These characters appear only once in the format. All data are sent in ASCII code. 35

6.5.1 Forward control The following transmission control characters are used by the control station or by the send station for specifying the transmission phases: EOT: Control character (Hex04) End of Transmit (end of transmission) ENQ: Control character (Hex05) Enquiry (station enquiry) 6.5.2 Backward control Each transmission character sequence, each receive poll and each control command issued to one or more receive stations which does not end the receive state must be confirmed with a reply. The following transmission control characters are used for this: NAK: Control character (Hex15) Not acknowledge (negative reply) ACK: Control character (Hex06) Acknowledge (positive reply) 36

6.5.3 Data control In the data command the information for activating the parameters, set points and actual values are coded with the axes. Parameters are implemented as a dual array. All data are handled like parameters. This results in very easy handling of all the data to be managed. Parameter[Number][Axis] C1,C2 C3,C4 Each device is modular, and has the character of a slot. There is always a General Level and at least one Axis Level. The various levels are distributed as follows. Data command 20XX General Level (calibration value) Data command 21XX Axis 1 37

6.6 Send Send transfers data from the master to the slave. EOT AD1 AD2 STX C1 C2 C3 C4 XXXXXXXX ETX BCC The data string XXXXXXXX may consist of any number of numerical characters and can contain leading zeros as well as a sign. The Block-Check-Character BCC is the exclusive-or of all characters from "C1 to "ETX (all-inclusive) To prevent the BCC from ending up in the value range of the transmission control characters, Hex20 is added as soon as it is less than Hex20. If reception was correct, the module answers with "ACK, and in all other cases with "NAK. All parameters sent to the module are first stored in a data buffer. These parameters do not become active until the "activate data" command is sent. Example: Send the parameter value P01 100 to a device with Address 11. EOT 11 STX 2101 100 ETX BCC The device responds for a display value with "Ack 38

6.7 Receive The receive is used for requesting values from the modules. EOT AD1 AD2 STX C1 C2 C3 C4 ENQ When addressing is correct and the parameter code is correct, the station replies: STX C1 C2 C3 C4 XXXXXXX ETX BCC The data string XXXXXXXX may consist of any number of numerical characters and can contain leading zeros as well as a sign. The Block-Check-Character BCC is the exclusive-or of all characters from "C1 to "ETX (all-inclusive) To prevent the BCC from ending up in the value range of the transmission control characters, Hex20 is added as soon as it is less than Hex20. If the request string contains an invalid or unknown parameter code, the station replies: STX C1 C2 C3 C4 EOT In all other cases with "NAK Example: Request the display value from a device with Address 11. EOT 11 STX 2199 ENQ The device replies for a display value of 12 STX 2199 12 ETX BCC 39

6.8 Printer mode If a printer is connected to the device using an RS232 interface, the following data string is sent cyclically or on demand. AD1 AD2 ± XXXXXX LF CR The device sends its address, followed by the actual value, Line Feed and Carriage Return. Data can be read from the device or written to it even while printer mode is active. Note however that two transmissions in succession cannot take place, since otherwise erroneous data may be on the bus. 6.9 Serial commands 3 commands can be sent over the serial interface. 1. Activate data, data string number 137 2. Save data in EEPROM, data string number 138 3. Calibrate, data string number 139 Data command 2152 is used to transmit a command. Example: Send the Activate data command to a device with Address 11. EOT 11 STX 2152 138 ETX BCC 40

7. Part Numbering The following variants of the BDD 611 are available: BDD 611-R4Q4-0-54-N-00: Supply voltage 115 / 230V AC No digital outputs 4 digital inputs No serial port BDD 611-R3Q4-0-52-N-00 Supply voltage 24V DC/AC 2 digital outputs (transistor output), PNP sourcing 4 digital inputs No serial port 8. List of Illustrations Fig. 1 Dimensions (illustration reduced)... 7 Fig. 2 Wiring diagram... 10 Fig. 3 Front panel... 15 Fig. 4 Function keys, displays... 32 41

42