SECTION THERMAL UTILITY METERING INTERFACE

Similar documents
UW Purchase Specification Section Central Cooling Water Meter Page 1 of 6

DUKE UNIVERSITY DESIGN & CONSTRUCTION STANDARDS

Series TFXB Ultra. Transit Time Ultrasonic Flow Meter, Clamp-on, Liquid, Single-Channel

Scanner 2000 Steam Mass Flow Transmitter

Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control

CombiTemp TFRN/TFRH. Operating instructions. Temperature sensor. Operating Instructions: EN.

SOLUTIONS ONICON. Innovative HVAC Flow and Energy Measurement Solutions PRECISE, RELIABLE, TRUSTED

Flow Measurement Applications

JT400 Multivariable Transmitter

DigitalFlow GC868 Panametrics Clamp-On Gas Ultrasonic Flowmeter. GE Sensing. Applications. Features

Scanner 2000 microefm QuickStart. Installing the Scanner Remote Mount. Direct Mount NUFLO. Part No , Rev. A

Ultrasonic Flow Meter Brochure

accurate measurement of compressed air consumption and leakage detection Calibration certificates and continous calibration, OEKD calibration service

Model HU-224/225. Technical Information TI.224/ Humidity Transduce r FOR ADDITIONAL INFORMATION SEE HU-224/225 DATA SHEET

CONTENTS CONTROLLERS room controllers room units control units PRODUAL 3 CATALOGUE

Immersion Temperature Sensors

Insertion Flowmeter for compressed air and gases DN50 - DN700 (2-28 )

INTRINSICALLY SAFE INSTRUMENTATION FOR HAZARDOUS AREAS

EE360. High-End Moisture in Oil Transmitter. Typical applications. Features EE360 EE360. (+34)

Purpose of Today s Presentation

Oil & Gas. Control Control. every move. Pressure Temperature Level Flow

ASI Systems ML5740A Series

ASI Systems ML5720A Series

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

Electric Actuated Ball Valves 2-way Stainless Steel, Full Port 1/4 to 2 NPT

SYRACUSE UNIVERSITY GREEN DATA CENTER NYSERDA MONITORING PLAN BHP ENERGY LLC. February 17, 2010 Revised

Temperature sensors and accessories for heat and cooling measurement points

Humidity goes Digital

KUHLMAN INSTRUMENT COMPANY 5000K WARRANTY

Output Signal. Temperature 22DTH-56M BACnet DC V, DC V. Electrical Data Power Supply DC V, ±10%, 0.7 W

Installation and Operating Manual FM50 IOM 2-18 DRAFT

The SF-586b Insertion Flow Meter For Compressed Air, Gases And Exhaust Air (up to 400 C) In Pipe Diameters From 25mm to 5000mm

Industrial Wet/Wet Differential Pressure Transducer

EMP1 OPERATING & INSTALLATION INSTRUCTIONS

Explosion-Proof Gauge Pressure Transmitter

HMT330 Series Humidity and Temperature Transmitters for Industrial Applications

Rosemount 1595 Conditioning Orifice Plate

CDD4 Duct Carbon Dioxide Transmitter

EE771 Series. Flowmeter for compressed air and gases in Industrial Applications. EE771 Compact. EE771 remote probe

SECTION SOFTWARE FOR PROGRAMMING LOCAL CONTROL UNIT

LAKEWOOD INSTRUMENTS MODEL 1575e WATER TREATMENT CONTROLLER

ECL Comfort V a.c. and 24 V a.c.

Multiphase Flowmeter FlowSys TopFlow Multiphase Meter Operations Manual

Installation and Operation Manual. ETV Platinum Plus. Electronic Tempering Valve with Safeguard WARNING

SCADAPack Modbus multivariable transmitter

Conductivity Transmitters

Temperature measurement TER8 Front-flush and low-invasive resistance thermometers

red-y industrial series product information Thermal Mass Flow Meters and Controllers for Gases with IP67 & Ex Protection

Type 330SA High-Performance Electric Actuator

TFR5. Room or outdoor temperature sensor. Operating instructions for temperature sensor. English page 1...5

THERMASGARD TM 65. Immersion screw-in duct temperature measuring transducer, calibratable, with multi-range switching and active output TECHNICAL DATA

Rosemount 1595 Conditioning Orifice Plate

Pump Data Sheet - Patterson HVAC Pumps Company: Intermountain Hydron Name: Cache County Mountain Crest Date: 09/24/2018

Rosemount 1595 Conditioning Orifice Plate

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

RHE27. Rack/Panel Mount Multifunction Coriolis Flow Transmitter

SCC Inc. TS-D Series. Technical Instructions. Document No. TS-3000 March 10, Deaerator, Surge and/or Condensate Control Panel.

RHE21. Exd / Exd(e) Extreme Environment Multifunction Coriolis Flow Transmitter

Electropneumatic miniature control valves Mounting Connectors Minisolenoid valves Indicators LED seals LED Valve modules Poppet 3/2 single pilot 4/2 s

Rosemount 1595 Conditioning Orifice Plate

2-PORT SEAT VALVES PN16 WITH FLANGED CONNECTIONS STAZ-16, STBZ-16, STCZ-52 DATASHEET

SCADAPack Modbus multivariable transmitter

Precision temperature control/sensing

XONIC 100L ULTRASONIC TRANSIT-TIME FLOWMETER. User s Manual FOR LIQUID FLOW. Industrial & Military Instruments. January 2016

RHE21. Exd / Exd(e) Extreme Environment Multifunction Coriolis Flow Transmitter

J3C-H20DPS 25Nm Smart Electric Actuator Type: J3C Model: H20DPS

B. AVM321S/AVM322S: 1000N Actuator with analog SUT positioner

Easy Flow Indicator Magnetisch-Induktiver Durchflussmesser. Type 8024 For Insertion Fittings. Analog Flow Rate Indicator, 1/2"-16"; P=87 PSI

HYGROPHIL-F, Moisture Analyzer, Type , -11, -12, -13 series A

red-y industrial series Thermal Mass Flow Meters and Controllers for Gases

LineGuard Specification Sheet Issued 8/24/10 VA Revision 0. Valve Automation

Series DMHF Heat Meter

M5100 Heavy Industrial Pressure Transducer

Zone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions

DMTFP Portable Ultrasonic Flow Meters

Specification and Design Catalog. Waterside Economizer

A Guide to Management of Change -

Surface-mounting Thermostats AM Series with 1 or 2 single-pole snap-action switches IP40 protection

DVZ - Vortex Flowmeter and Switch

Control Head for the integrated mounting on process valves

MST2000 Loop Powered Multivariable SMARTFLOW Transmitter

VESSEL FUEL MEASUREMENT & MANAGEMENT SYSTEM (VFMMS)

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000

Series 3730 Electropneumatic Positioner Type

IHP24. Intelligent Hydraulic Positioner D HP- PL

RHE26. Rack/Panel/DIN Rail Mount Multifunction Coriolis Flow Transmitter

SonoMeter 30 Ultrasonic energy meter for heating and cooling applications

HTZ. Description. Features. Smart HART Humidity and Temperature Transmitter

Zone Pressure Touch (ZPT) Sensor - Standard Range

Installation & Operation Manual. IMPORTANT: This manual contains important information. READ AND KEEP FOR REFERENCE. Series 380 Impeller Btu System

Clamp-On Transit Time Ultrasonic Flow Meters

Rosemount 0085 Pipe Clamp Sensor

Carbon Monoxide Sensor - ModBus

Screw-in resistance thermometers with terminal head Form B

M3P..G/A, M3P..F/A Modulating control valves (PN16) for chilled and hot water systems

Technologic 502 Variable Speed Pump Controller

Vane wheel probe BFA25 for flow measurement of gases and liquids with integrated, configurable transducer UFA in Ex-d housing

DPC DPC PRECISION DIGITAL MASS FLOW CONTROLLER WITH MULTI-GAS FUNCTIONALITY

Indicating Digital Transmitter for Differential Pressure and Flow. Media 6 with LCD Media 6 with LED

PP-8516 & PP Electronic Static Pressure Controllers and Transmitters for Cental Air Supply Systems General Instructions

Transcription:

SECTION 25 33 13 THERMAL UTILITY METERING INTERFACE GENERAL 1.1 SUMMARY A. Section includes metering and monitoring for interface points for utility chilled water, hot water, and steam fed to each building, and specifies interface valves. B. Stanford University distributes chilled water, utility hot water, and steam from central production facilities on campus. This section describes the building level metering and interface control requirements for these respective utilities. Devices listed within this section are for utility metering & do not include building side instrumentation. Metering instrumentation will interface to a local Utility Interface panel within the building. The metering points as needed can be shared with the local building control system via a local network connection. Consult with Stanford s Sustainability & Energy Management team for project specific requirements. Stanford will supply the Utility Interface enclosure, internal I/O and programming for field installation by the contractor. C. See section 16211 for building level electrical metering requirements. D. Related Sections 1. 25 05 53 Identification 1.2 REFERENCES A. Stanford FDG Drawing MS-10 B. Stanford FDG Drawing MS-11 C. Stanford FDG Drawing MS-17 D. Stanford FDG Drawing MS-68 E. Stanford FDG Drawing MC-01 F. Refer to 25 00 00 Integrated Automation 1.3 DEFINITIONS A. Refer to 25 06 11 Integrated Automation Definitions 1.4 SYSTEM DESCRIPTION A. Systems described below interface with the Thermal Utility Metering Interface Panel. B. Systems include metering for : 1. Chilled Water Metering Utility Hot Water Metering 2. Steam Metering C. Control valves for: 1. Chilled Water Interface Control Valve 2. Utility Hot Water to Heating Hot Water Interface Control Valve 3. Utility Hot Water to Domestic Hot Water Interface Control Valve 4. Steam to Hot Water Interface Control Valve February 2017 Page 1 of 6 2018 FDG Section 25 33 13

1.5 SUBMITTALS A. Product data sheets including construction materials and assembly methods B. Valve Schedule: 1. Indicate size, location and model of each control valve. 2. Indicate unique tag numbers for each device, equipment item or system served. 3. Include shut-off head required, actuator air pressure or force required to meet shut-off head, torque requirements for rotary valves, actual flow requirements based on equipment shop drawings, and calculation of actual pressure drops. 4. Include charts, graphics or similar items used in making selections. 1.6 QUALITY ASSURANCE A. Obtain adequate system information necessary for valve and flow meter sizing. B. Refer to section 25 00 00 for additional requirements. PRODUCTS 2.1 CHILLED WATER BTU METER A. Ultrasonic Flowmeter/Calculator 1. Manufacturer: Kampstrup a. Multical-801 b. Include 4-wire temperature sensors with connection head c. Include 90mm sensor pockets 2. Part Number: Type 67-L-Y-67-8-0-1-546 3. Calibration and Sizing: a. Flow Tube size and calibration shall be approved by Stanford s Energy Operations team. B. Power and Wiring Requirements: 1. A dedicated 120 VAC power circuit is required to the Utility Interface Panel. The circuit should be fed from emergency power if available. 2. A dedicated 120 VAC power circuit is required to the utility interface valve. This circuit can be used for both the chilled water and utility hot water valve if present. 3. A lockable power disconnect is required at the btu meter and chilled water interface valve so that the devices can be safely serviced without having to shut off power to all components. Use Leviton model 1201-2L. The transmitter shall be fed emergency power if available. C. Communications: 1. The BTU meter will communicate with the Utilities Interface Panel via Modbus RTU and share the following points in real time: a. Demand (tons) b. Totalized consumption (ton-hours) c. Water flow (gpm) d. Supply temperature (deg F) e. Return temperature (deg F) 2.2 UTILITY HOT WATER BTU METER A. Ultrasonic Flowmeter/Calculator 1. Manufacturer: Kampstrup February 2017 Page 2 of 6 2018 FDG Section 25 33 13

a. Multical-801 b. Include 4-wire temperature sensors with connection head c. Include 90mm sensor pockets 2. Part Number: Type 67-L-Y-67-8-0-1-246 3. Calibration and Sizing: a. Flow Tube size and calibration shall be approved by Stanford s Energy Operations team. B. Power and Wiring Requirements: 1. A dedicated 120 VAC power circuit is required to the Utility Interface Panel. The circuit should be fed from emergency power if available. 2. A dedicated 120 VAC power circuit is required to the utility interface valve. This circuit can be used for both the utility hot water and chilled water valve if present. 3. A lockable power disconnect is required at the btu meter and utility hot water interface valve so that the devices can be safely serviced without having to shut off power to all components. Use Leviton model 1201-2L. The transmitter shall be fed emergency power if available. C. Communications: 1. The BTU meter will communicate with the Utilities Interface Panel via Modbus RTU and share the following points in real time: a. Demand (btu/hour) b. Totalized consumption (btu) c. Water flow (gpm) d. Supply temperature (deg F) e. Return temperature (deg F) 2.3 UTILITY INTERFACE TEMPERATURE TRANSMITTERS A. Manufacturers: Weed (by Ultra Electronics) or approved equivalent B. Use 100 Ohm platinum RTD with a 4500H 2 wire, 4-20 ma current output signal proportional to specified temperature span of transmitter 1. Accuracy:... ± 0.12% at 32 F (Class B) 2. Temperature Operating Range for Chilled Water..-20 to 170 F 3. Humidity Operating Range:... 0 to 99% RH 4. Conformance:...... DIN-IEC 751 5. Range:... Consult with Owner before ordering C. Include thermowell with spring loaded sensor D. Calibration and Sizing 1. Calibrated range for chilled water service is 30 to 80 o F 2. Calibrated range for hot water service is 80 to 220 o F E. Weed Part Numbers: 1. Head: 5A00A1 2. Spring Loaded Sensor: 305-01B-A-4-C-xxx.x-z006 (xxx.x equals length to nearest 0.1 ) 3. Thermowell: ¾-S260-Ux.x0-Tx-316SS (x.x equals insertion length, x=lagging dimension) 4. Transmitter: 4HQT4U+030+0080F (chilled water), 4HQT4U+080+0220F (hot water) 2.4 UTILITY INTERFACE PRESSURE TRANSMITTERS A. Manufacturers: Setra, Ashcroft, Dwyer February 2017 Page 3 of 6 2018 FDG Section 25 33 13

B. Include pressure sensor and integral transmitter. Transmitters shall use capacitance sensing element. C. Performance: 1. Power... 24VDC loop powered (2-wire) 2. Output... Linear, 4-20mA (2-wire loop) 3. Accuracy... + 0.25% of calibrated span 4. Linearity... +0.1% of calibrated span 5. Hysteresis... +0.05% of calibrated span D. Calibration and Sizing 1. Calibrated range for pressure transmitters shall be 0-150 psig. E. Setra Part Number 1. 2561-150P-G-xx-11-x (contractor will select x s with their needs) 2.5 STEAM FLOW METER A. Vortex Flow Meter with integrated Transmitter: 1. Manufacturers: Rosemount, or approved equivalent. 2. The following instruments shall be used: a. Flow Meter: Rosemount Model No. 8800D-R-Size-S-A1-N-1-D-1-M5. b. Pressure Transmitter: Rosemount Model No. 2088-G-3-S-22-A-1-N5-S5. c. Pressure Transmitter Manifold: Rosemount Model No. 0306-R-T-2-2-BA-1-1. d. Temperature Transmitter: Rosemount Model No. 3244PD-D1-A-1-NA-XA-M5. e. Temperature Element and Thermowell: Rosemount Model No. 0068-N-2-1-N-00-A- (immersion length)-t26-xa. 3. Calibration and Sizing: a. Calibrated range for pressure transmitters shall be 0-300 psig. b. Calibrated range for the temperature transmitters shall be 200-400 degrees F. c. Flow meter size and calibration shall be approved by Stanford s Facilities Energy Management team. 4. Power and Wiring Requirements: a. Meter is loop powered from the Stanford Utilities Interface panel. 2.6 CHILLED WATER INTERFACE CONTROL VALVE A. The chilled water interface control valve shall be line sized with near zero pressure drop, normally closed (N.C.) and able to shut off against sixty (60) PSI differential pressure with no more than 0.1% of maximum flow leakage. B. The chilled water interface valve controller shall be capable of receiving a digital input from the campus utilities interface panel that will serve to command the valve closed in case of a utility distribution emergency. C. Manufacturer: Belimo or approved equivalent D. Shall be a characterized ball valve for valves up to 6. For valves larger than 6, contact Stanford s Energy Operations department for job specific requirements. E. Characteristics: 1. Turndown ratios..... 40:1 2. Flow Characteristics... Modified equal percentage 3. Body Type...... Threaded ends 2 and smaller, flanged 2.5 and larger February 2017 Page 4 of 6 2018 FDG Section 25 33 13

4. Body Material...... Stainless Steel 5. Stem...... Stainless Steel F. Valve Actuator 1. Actuators shall have fail closed return. 2. Actuator shall close against 125 percent of the maximum differential to which they are subjected. 3. Modulating actuator input signals shall be 4-20ma. 4. Actuators shall be Brushless DC Motor Technology with stall protection. 5. Actuators shall be protected from weather (water) as needed. 2.7 UTILITY HOT WATER TO HEATING HOT WATER INTERFACE CONTROL VALVE A. The utility hot water interface control valve shall be normally closed (N.C.) and able to shut off against sixty (60) PSI differential pressure with no more than 0.1% of maximum flow leakage. B. The UHW interface valve controller shall be capable of receiving a digital input from the campus utilities interface panel that will serve to command the valve closed in case of a utility distribution emergency. C. Manufacturer: Belimo or approved equivalent D. Shall be a characterized ball valve for valves up to 6. For valves larger than 6, contact Stanford s Energy Operations department for job specific requirements. E. Characteristics: 1. Turndown ratios..... 40:1 2. Flow Characteristics... Modified equal percentage 3. Body Type...... Threaded ends 2 and smaller, flanged 2.5 and larger 4. Body Material...... Stainless Steel 5. Stem...... Stainless Steel F. Valve Actuator 1. Actuators shall have fail closed return. 2. Actuator shall close against 125 percent of the maximum differential to which they are subjected. 3. Modulating actuator input signals shall be 4-20ma. 4. Actuators shall be Brushless DC Motor Technology with stall protection. 5. Actuators shall be protected from weather (water) as needed. 2.8 UTILITY HOT WATER TO DOMESTIC HOT WATER INTERFACE CONTROL VALVE A. The DHW interface control valve shall be a 2-way valve configured to fail closed on loss of power or signal. B. The DHW interface valve controller shall be capable of receiving a digital input from the campus utilities interface panel that will serve to command the valve closed in case of a utility distribution emergency. February 2017 Page 5 of 6 2018 FDG Section 25 33 13

EXECUTION 3.1 Controls contractor to coordinate with piping trade for location and installation details. 3.2 If emergency power if furnished to the building, then power the Utility Interface Panel and associated devices to an emergency power circuit. 3.3 CHILLED WATER METER A. The upstream and downstream runs of the flow meter shall be straight meter sized piping without taps, feed-ins, or thermowells for the following number of meter size pipe diameters: 1. Upstream - 10 pipe diameters, minimum. 2. Downstream - 5 pipe diameters, minimum. B. Meter shall be installed on the supply line before any heat exchangers or building loads. C. Grounding straps are provided and must be bonded to pipe on both sides of meter. D. Pressure transmitters that have a sensing port greater than 6 above ground shall be mounted on a wall or pipe stand. Mounting orientation of pressure transmitters shall be as shown in MS-17. E. Refer to MS-10 for further details. 3.4 UTILITY HOT WATER METER A. The upstream and downstream runs of the flow meter shall be straight meter sized piping without taps, feed-ins, or thermowells for the following number of pipe diameters: 1. Upstream - 10 pipe diameters, minimum. 2. Downstream - 5 pipe diameters, minimum. B. Meter shall be installed on the supply line before any heat exchangers or building loads. C. Pressure transmitters that have a sensing port greater than 6 above ground shall be mounted on a wall or pipe stand. Mounting orientation of pressure transmitters shall be as shown in MS-17. D. Refer to MS-68 for further details. 3.5 STEAM METER A. The flow meter shall be installed before the pressure-reduction station. Refer to MS-20. The upstream and downstream runs of the flow meter shall be straight meter sized piping without taps, feed-ins, or thermowells for the number of diameters as follows : 1. Upstream - 20 pipe diameters, minimum. 2. Downstream - 5 pipe diameters, minimum. B. Pressure transmitters shall be mounted on wall or pipe stand. Mounting orientation of pressure transmitters shall be as shown in MS-17. C. Refer to MS-68. END OF SECTION February 2017 Page 6 of 6 2018 FDG Section 25 33 13