RS485 MODBUS Module 8AO

Similar documents
SDM-8AO. Expansion Module 8 analog outputs. Manufactured for

RS485 MODBUS Module 6RO

RS485 MODBUS Module 16I-M

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for

RS485 MODBUS Module 8I8O

RS 485 Mini Modbus 1AO

SDM-8I8O. Expansion Module 8 digital inputs, 8 digital outputs. Manufactured for

RS485 MODBUS Module 8I8RO

RS485 IO Slim Module MOD-ETH

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

isma-b-fcu FCU Hardware User Manual Global Control 5 Sp. z o.o. Warsaw, Poland

NetBiter I/O Extender User Manual

Real Time Clock with Temperature Sensor and RS485/Modbus Comunications

ASTAT XB/XBm Remote Operator

Intech Micro 2300-RO4 analogue input station MODBUS RTU slave application supplementary manual.

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.

MU110-6U. Analog output module 6 channel. User guide

Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual.

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)

Intech Micro 2300-RTD6 analogue input station MODBUS RTU slave application supplementary manual.

KTA-250 Anemometer Alarm Card

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE

Copyright: December 2017 Nidec Issue: E

3 CH Analog Output module / CANopen

VPGate Manual PROFIBUS to serial

Message Runner KP3H. Text Display. Small messages on your machine. Compact DIN 36 x 72 profile. Green and orange character display.

SmartMod DC Digital Input Module HE359DIM610 12/24VDC Negative Logic

SC2004MBS 20x4 Characters MODBUS RTU Slave LCD

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

Carbon Monoxide Sensor - ModBus

SIC184 Manual Stepper motor servo controller

DL-10. User Manual. RS-485 Remote Temperature and Humidity. English Ver. 1.0, Jul. 2017

EE870 Modular CO 2 Transmitter

Millenium 3 logic controllers

APPLICATION NOTE. OJ-DRHX Modbus protocol OJ DRHX A DRIVES PROGRAMME DEDICATED TO ROTARY HEAT EXCHANGERS /17 (OSH) 2017 OJ Electronics A/S

Serial Communication Converters & Adapters Instruction Manual

MOD-MUX MODBUS TCP I/O PRODUCTS

IFC 100 Supplementary instructions

The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance.

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE

NA-9171 / 9173 (RS-232) (RS-485) User Manual. MODBUS Adapter CREVIS Co.,Ltd. Version FnIO MODBUS Adapter NA-9171, NA-9173 FnIO S-Series

ProfiPro Distributed PROFIBUS I/O Modules User Manual

Warranty. Warning. Copyright. Contact Us

Application Note: Using Modbus With the Conext CL Series. Important Safety Instructions

INSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3

BQ & BQ370-01N MODBUS ANALOG INPUT DEVICE USER MANUAL

IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description

RS-485 I/O Modules: ADAM-4000

MODEL: R2K-1 SEN TRONIC AG. R2K Series

USER MANUAL Z-SG / Z-SG-L. Advanced Digital Strain gauge converter. Via Austria, PADOVA ITALY

DI-917MB/DI-918MB. Heavy-duty 1A solid-state relays provide dependable on/off control of industrial devices. Analog Output Module. Four Analog Outputs

ATK3 I/O Module (Modbus Slave)

Product Specification for SAB-S-MODBUS

Submittal Data Sheet WAGO Node for itm

1. Introduction. 2. Installation MODBUS INTERFACE

XT-9100 Technical Bulletin

DCC-8 DIGITAL TO EIGHT CURRENT LOOP CONVERTER OPERATING MANUAL

A36D/TPSD DNP 3.0 & Modbus SCADA INTERFACE

SSI-1016H Specifications and Operation Manual

PL400 PROGRAMMABLE LOGIC CONTROLLER WITH INDUCTIVE LOOP DETECTOR

DUAL LOOP DETECTOR WITH MODBUS COMMUNICATIONS

iologik R1200 Series User s Manual

Climatix TM Climatix Controller. For controlling, switching and monitoring functions

Measuring transducers MI4x0 series Programmable transducers for RTD sensors MI450

E2 Modbus RTU Register Map Revision History Version Comments Author Date 1.02 Previous version PAE 11/06/ Revised to new format PAE 09/03/09

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1

MVS RAIL ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

INSTRUCTION SHEET. Eaton Logic Controller DeviceNet Distributed I/O Adapter Module. [Applicable Distributed I/O Adapter Module] ELC-CADNET

TM3AI4 module TM3-4 analog inputs

VP Process Inc. Model: VP-EC-RDU Modbus RTU LCD Display

Manual and Protocol Description

CEM M-RS485 INSTRUCTION MANUAL (M014B A)

ABB Drives. User s Manual Modbus Adapter Module FMBA-01

Communications Quick-Start Guide

E2 Modbus RTU Register Map

Serial Data DIN Fiber Link System

ELSETA IOMOD 8DI8DO. User manual. Elseta 3/2017 V1.0

SMI2. RS485 Display. User guide

I-7520: RS-232 to RS-485. Input: RS-232 protocol Output:RS-485/RS-422 Speed: Self Tuner 'inside, auto switching baud rate, 300~ BPS

iologik R1200 Series User s Manual

Expansion Module HZS 541-1S

The RS-485 user manual for B800 series communication

mbc082 Bus Converter

USER MANUAL 2012 V1.1

Energy Management Modular DC Energy analyzer Type VMU-E and VMU-X

Manual 601: : USB/RS232. Specifications. Contents. Options

Energy Management Modular DC Energy analyzer Type VIM-E and VIM-X

MODEL: R1M-D1. PC Recorders R1M Series. SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.)

Universal Serial/PROFIBUS DP Gateway GT200-DP-RS User Manual V6.1 SST Automation

Characteristics and functioning

Small distributed I/O module

User Guide. Modbus Module. For Digistart soft starters. Part Number: Issue: 3.

Kramer Electronics, Ltd. USER MANUAL. Model: TP Channel UXGA/Audio/RS-232 to CAT 5 Transmitter

Measurement Systems Datascan Installation and User Guide

DEEP SEA ELECTRONICS PLC

8 Channel Analog Input Module Datasheet. Address / Baud rate / range configurable by the user

FACTORY AUTOMATION MANUAL WCS-MBG110 WCS MODBUS RTU INTERFACE MODULE

iologik R1200 Series User s Manual

UNIVERSAL TRANSDUCER AR594

MODEL: R1M-P4. PC Recorders R1M Series. SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.)

Transcription:

Version 1.3 12/02/2013 Manufactured for

Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have been prepared with utmost care by our professionals and serve as a description of the product without incurring any liability for the purposes of commercial law. This information does not release you from the obligation of own judgment and verification. We reserve the right to change product specifications without notice. Please read the instructions carefully and follow the recommendations contained therein. WARNING! Failure to follow instructions can result in equipment damage or impede the use of the hardware or software. Version 1.3-12/02/2013 2 / 15

1. Safety rules Before first use, refer to this manual RS485 MODBUS Module 8AO Before first use, make sure that all cables are connected properly Please ensure proper working conditions, according to the device specifications (eg: supply voltage, temperature, maximum power consumption) Before making any modifications to wiring connections, turn off the power supply 2. Module Features 2.1. Purpose and description of the module The 8AO module has a set of 8 analog outputs that could work as a current output (0-20mA or 4-20mA) or as a voltage output (0-10V). Setting the output curent or voltage value is done via RS485 (Modbus protocol), so you can easily integrate the module with popular PLCs, HMI or PC equipped with the appropriate adapter. This module is connected to the RS485 bus with twisted-pair wire. Communication is via MODBUS RTU or MODBUS ASCII. The use of 32-bit ARM core processor provides fast processing and quick communication. The baud rate is configurable from 2400 to 115200. The module is designed for mounting on a DIN rail in accordance with DIN EN 5002. The module is equipped with a set of LEDs used to indicate the status of inputs and outputs useful for diagnostic purposes and helping to find errors. Module configuration is done via USB by using a dedicated computer program. You can also change the parameters using the MODBUS protocol. Version 1.3-12/02/2013 3 / 15

2.2. Technical Specifications Power Supply Outputs Temperature Connectors Size Voltage 12-24 V DC ± 20% Maximum Current No of outputs 8 Voltage output Current output Current output Measurement resolution ADC processing time Work Storage Power Supply Communication Outputs Quick connector Configuration Height Length Width 120 ma @ 12V / 100 ma @ 24V 0V do 10V (resolution 1.5mV) 0mA do 20mA (resolution 5μA) 4mA do 20mA (value in 1000 steps) (resolution 16μA) 12 bits 16ms / channel -20 C - +65 C -40 C - +85 C 2 pins 3 pins 2 x 10 pins IDC10 Mini USB 120 mm 101 mm 22,5 mm Interface RS485 Up to 128 devices Version 1.3-12/02/2013 4 / 15

2.3. Dimensions of the product RS485 MODBUS Module 8AO Look and dimensions of the module are shown below. The module is mounted directly to the rail in the DIN industry standard. Power connectors, communication and IOs are at the bottom and top of the module. USB connector configuration and indicators located on the front of the module. Version 1.3-12/02/2013 5 / 15

3. Communication configuration 3.1. Grounding and shielding RS485 MODBUS Module 8AO In most cases, IO modules will be installed in an enclosure along with other devices which generate electromagnetic radiation. Examples of these devices are relays and contactors, transformers, motor controllers etc. This electromagnetic radiation can induce electrical noise into both power and signal lines, as well as direct radiation into the module causing negative effects on the system. Appropriate grounding, shielding and other protective steps should be taken at the installation stage to prevent these effects. These protective steps include control cabinet grounding, module grounding, cable shield grounding, protective elements for electromagnetic switching devices, correct wiring as well as consideration of cable types and their cross sections. 3.2. Network Termination Transmission line effects often present a problem on data communication networks. These problems include reflections and signal attenuation. To eliminate the presence of reflections from the end of the cable, the cable must be terminated at both ends with a resistor across the line equal to its characteristic impedance. Both ends must be terminated since the direction of propagation is bidirectional. In the case of an RS485 twisted pair cable this termination is typically 120 Ω. 3.3. Setting Module Address in RS485 Modbus Network The following table shows how to set switch to determine the address of the module. The module address is set with the switches in the range of 0 to 31. Addresses From 32 to 255 can by set via RS485 or USB. Addr SW5 SW4 SW3 SW2 SW1 0 OFF OFF OFF OFF OFF 1 OFF OFF OFF OFF ON 2 OFF OFF OFF ON OFF 3 OFF OFF OFF ON ON 4 OFF OFF ON OFF OFF 5 OFF OFF ON OFF ON 6 OFF OFF ON ON OFF 7 OFF OFF ON ON ON 8 OFF ON OFF OFF OFF 9 OFF ON OFF OFF ON 10 OFF ON OFF ON OFF Addr SW5 SW4 SW3 SW2 SW1 11 OFF ON OFF ON ON 12 OFF ON ON OFF OFF 13 OFF ON ON OFF ON 14 OFF ON ON ON OFF 15 OFF ON ON ON ON 16 ON OFF OFF OFF OFF 17 ON OFF OFF OFF ON 18 ON OFF OFF ON OFF 19 ON OFF OFF ON ON 20 ON OFF ON OFF OFF 21 ON OFF ON OFF ON Addr SW5 SW4 SW3 SW2 SW1 22 ON OFF ON ON OFF 23 ON OFF ON ON ON 24 ON ON OFF OFF OFF 25 ON ON OFF OFF ON 26 ON ON OFF ON OFF 27 ON ON OFF ON ON 28 ON ON ON OFF OFF 29 ON ON ON OFF ON 30 ON ON ON ON OFF 31 ON ON ON ON ON Version 1.3-12/02/2013 6 / 15

3.4. Types of Modbus Registers There are 4 types of variables available in the module RS485 MODBUS Module 8AO Type Beginning address Variable 1 00001 Digital Outputs 2 10001 Digital Inputs 3 30001 Input Registers 4 40001 Output Registers Access Bit Read & Write Bit Read Registered Read Registered Read & Write Modbus Command 1, 5, 15 2 3 4, 6, 16 3.5. Communication settings The data stored in the modules memory are in 16-bit registers. Access to registers is via MODBUS RTU or MODBUS ASCII. 3.5.1. Default settings You can restore the default configuration by the switch SW6 ( see 3.5.2 - Restore the default configuration) Baud rate 19200 Parity Data bits 8 Stop bits 1 Reply Delay [ms] 0 Modbus Type No RTU 3.5.2. Restore the default configuration To restore the default configuration: turn off the power turn on the switch SW6 turn on the power when power and communication LED flash turn off the switch SW6 Caution! After restoring the default configuration all values stored in the registers will be cleared as well. Version 1.3-12/02/2013 7 / 15

3.5.3. Configuration registers Modbus Dec Hex Address Name 40003 2 0x02 Baud rate 40005 4 0x04 Parity 40004 3 0x03 Stop Bits LSB 40004 3 0x03 Data Bits MSB Values 0 2400 1 4800 2 9600 3 19200 4 38400 5 57600 6 115200 other value * 10 0 none 1 odd 2 even 3 always 1 4 always 0 1 one stop bit 2 two stop bits 7 7 data bits 8 8 data bits 40006 5 0x05 Response delay Time in ms 40007 6 0x06 Modbus Mode 0 RTU 1 ASCII Version 1.3-12/02/2013 8 / 15

4. Indicators 8 outputs state Power Supply Communication Indicator Power supply Communication Outputs state Description LED indicates that the module is correctly powered. The LED lights up when the unit received the correct packet and sends the answer. LED indicates that the output is on. Version 1.3-12/02/2013 9 / 15

5. Module Connection Version 1.3-12/02/2013 10 / 15

6. Setting output mode To change output mode from current to voltage you should set appropriate values of registers (40069 40076) and change the position of jumper inside the module according to following picture. 7. Switches Switch Function Description 1 Module address +1 2 Module address +2 3 Module address +4 4 Module address +8 5 Module address +16 6 Restoring default settings Setting module address from 0 to 31 Restoring default settings (see 3.5.1 - Default settings and 3.5.2 - Restore the default configuration). Version 1.3-12/02/2013 11 / 15

8. Modules Registers 8.1. Registered access Modbus Dec Hex Register Name Access Description 30001 0 0x00 Version/Type Read Version and Type of the device 30002 1 0x01 Switches Read Switches state 40003 2 0x02 Baud rate Read & Write RS485 baud rate 40004 3 0x03 Stop Bits & Data Bits Read & Write No of Stop bits & Data Bits (see 3.5.3) 40005 4 0x04 Parity Read & Write Parity bit 40006 5 0x05 Response Delay Read & Write Response delay in ms 40007 6 0x06 Modbus Mode Read & Write Modbus Mode (ASCII or RTU) 40009 8 0x08 Watchdog Read & Write Watchdog 40033 32 0x20 Received packets MSB Read & Write 40034 33 0x21 Received packets LSB Read & Write 40035 34 0x22 Incorrect packets MSB Read & Write 40036 35 0x23 Incorrect packets LSB Read & Write 40037 36 0x24 Sent packets MSB Read & Write 40038 37 0x25 Sent packets LSB Read & Write No of received packets No of received packets with error No of sent packets 30051 50 0x32 Outputs Read Bit is set if value 0 40053 52 0x34 Analog output 1 Read & Write 40054 53 0x35 Analog output 2 Read & Write 40055 54 0x36 Analog output 3 Read & Write 40056 55 0x37 Analog output 4 Read & Write 40057 56 0x38 Analog output 5 Read & Write 40058 57 0x39 Analog output 6 Read & Write 40059 58 0x3A Analog output 7 Read & Write 40060 59 0x3B Analog output 8 Read & Write 40061 60 0x3C Default output 1 value Read & Write 40062 61 0x3D Default output 2 value Read & Write 40063 62 0x3E Default output 3 value Read & Write 40064 63 0x3F Default output 4 value Read & Write 40065 64 0x40 Default output 5 value Read & Write 40066 65 0x41 Default output 6 value Read & Write 40067 66 0x42 Default output 7 value Read & Write 40068 67 0x43 Default output 8 value Read & Write Value of analog output: in mv for voltage output (max 10240) in μa for current output 0-20mA (max 20480) in for current output 4-20mA (max 1000) Default value of output set when power is on or when watchdog reset occurs 40069 68 0x44 Output 1 setting Read & Write Setting of output mode: Version 1.3-12/02/2013 12 / 15

Modbus Dec Hex Register Name Access Description 40070 69 0x45 Output 2 setting Read & Write 40071 70 0x46 Output 3 setting Read & Write 40072 71 0x47 Output 4 setting Read & Write 40073 72 0x48 Output 5 setting Read & Write 40074 73 0x49 Output 6 setting Read & Write 40075 74 0x4A Output 7 setting Read & Write 40076 75 0x4B Output 8 setting Read & Write 0 output disabled 1 voltage output 2 current output 0-20mA 3 current output 4-20mA Caution! For the change to take effect, you must also set the jumper inside the module. 8.2. Bit access Modbus Address Dec Address Hex Address Register name 801 800 0x320 Output 1 Read 802 801 0x321 Output 2 Read 803 802 0x322 Output 3 Read 804 803 0x323 Output 4 Read 805 804 0x324 Output 5 Read 806 805 0x325 Output 6 Read 807 806 0x326 Output 7 Read 808 807 0x327 Output 8 Read Access Description If voltage or current is greater than 0 then according bit is set. Version 1.3-12/02/2013 13 / 15

9. Configuration software RS485 MODBUS Module 8AO Modbus Configurator is software that is designed to set the module registers responsible for communication over Modbus network as well as to read and write the current value of other registers of the module. This program can be a convenient way to test the system as well as to observe real-time changes in the registers. Communication with the module is done via the USB cable. The module does not require any drivers. Configurator is a universal program, whereby it is possible to configure all available modules. Version 1.3-12/02/2013 14 / 15

Table of content 1. Safety rules...3 2. Module Features...3 2.1. Purpose and description of the module...3 2.2. Technical Specifications...4 2.3. Dimensions of the product...5 3. Communication configuration...6 3.1. Grounding and shielding...6 3.2. Network Termination...6 3.3. Setting Module Address in RS485 Modbus Network...6 3.4. Types of Modbus Registers...7 3.5. Communication settings...7 3.5.1. Default settings...7 3.5.2. Restore the default configuration...7 3.5.3. Configuration registers...8 4. Indicators...9 5. Module Connection...10 6. Setting output mode...11 7. Switches...11 8. Modules Registers...12 8.1. Registered access...12 8.2. Bit access...13 9. Configuration software...14 Manufactured for: Aspar s.c. ul. Kapitańska 9 81-331 Gdynia Poland ampero@ampero.eu www.ampero.eu tel. +48 58 351 39 89; +48 58 732 71 73 Version 1.3-12/02/2013 15 / 15

Output No Current output (default) Voltage output 1 2 3 4 5 6 7 8