AIR-COOLED A (Surprisingly) Cost-Effective Alternative to Water-Cooled Chiller Plants

Similar documents
CHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM

Trane mytest Water-cooled Chiller Performance Validation What you spec is what you get *

Magnitude magnetic bearing centrifugal chillers

Trane Series S CenTraVac Chillers with AdaptiSpeed Technology tons

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

Air-Cooled Series R Chiller

HIGH EFFICIENCY Central Chiller

Magnitude magnetic bearing centrifugal chillers

where we are, where we could be, how we can get there. 12/14/2011

Pathfinder AWV air-cooled screw chillers

Trailblazer AGZ-E air-cooled scroll chillers

that may have a direct effect on your bottom line. The question

Fair City Plaza. Task: Diagnose problems, recommend improvements for small municipal district cooling system

MSYS 4480 AC Systems Winter 2015

Series S CenTraVac Chillers Leading efficiency and proven reliability BEYOND EFFICIENCY. BEYOND RELIABILITY. BEYOND SUSTAINABILITY. LET S GO BEYOND.

Large Tonnage Chillers. Kingsley Hu Technical Support Engineer

The Future. Today. YZ MAGNETIC BEARING CENTRIFUGAL CHILLER

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

CGWN/CCUN indoor liquid chillers The compact AquaStream² solution

CGAM air-cooled scroll chiller. Highly efficient, yet extremely quiet

Next Generation DCP Optimization using MV VSDs

Oil Free Magnetic Bearing Chillers. Lloyd Davis ESTech Energy Ltd

DEDICATED HEAT RECOVERY UNIT (DHRC)

Magnitude magnetic bearing centrifugal chillers

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant

Efficiency of Data Center cooling

Data Center Energy Savings By the numbers

AuraCool Economizer System

Presentation. Guaranteed Energy Savings Performance Project

APPLIED SYSTEM AWS FAMILY FOR LARGE APPLICATIONS PRODUCT LEAFLET. Capacity from 600 to 2,010kWr. Engineered for flexibility and performance

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP

IBM Symposium Data Center Cooling. EC Systems for HVAC architecture and Direct air Cabinet Cooling

GP SERIES Packaged Chillers

MPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers

glide glider kw R134a air cooled liquid chillers AND free cooling chillers FREE COOLING SHELL A C CLASS E C Energy Class RCGROUP SpA

Ecolibrium. Cloud control. Keeping data centres cool. OCTOBER 2018 VOLUME 17.9 RRP $14.95 PRINT POST APPROVAL NUMBER PP352532/00001

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

UC DAVIS THERMAL ENERGY STORAGE (TES) TANK OPTIMIZATION INVESTIGATION MATTHEW KALLERUD, DANNY NIP, MIANFENG ZHANG TTP289A JUNE 2012

Trading TCO for PUE? A Romonet White Paper: Part I

Achieving Operational Excellence

Liebert. HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers

WHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net

Rack cooling solutions for high density racks management, from 10 to 75 kw

Silicon Valley Power Data Center Program Rebate Application

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Energy Action Plan 2015

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Setting New Standards for Ultra High Performance HVAC

Supplement to PM WSC/WDC-1 MicroTech II for Centrifugal Compressor Water Chillers

Energy Performance Contracting

IT Air Conditioning Units

Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling

Energy Efficiency Retrofit Technologies for RTUs

CASE STUDIES. Brevard Community College: Florida Power & Light. Cape Canaveral Air Force Station: NORESCO

DATA CENTER LIQUID COOLING

MAKING MODERN LIVING POSSIBLE. ADAP-KOOL Drive. A New Drive for Energy Efficiency AKD 102 REFRIGERATION & AIR CONDITIONING DIVISION

Ecoflair Air Economizers

FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER. Applications in Diverse Climates within Europe, Middle East and Africa

CLICK TO EDIT MASTER TITLE STYLE. AdvanTEC Solutions CHILLER PLANT HEALTH MANAGER

Water cooled chiller plant (all-variable)

Data Centers. Powerful Solutions That Put You in Control. Energy Management Solutions. Where your energy dollars are used. 1

Designing Ultra-Efficient Building Cooling Systems

Committed to Energy Efficiency

DEEMED SAVINGS TECHNICAL ASSUMPTIONS

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

Precision Cooling for Business-Critical Continuity. Liebert HPC-S. Designed for the Efficient Cooling of Small Data Centers

ASHRAE CHAPTER TECHNOLOGY AWARD Illinois Chapter, Region VI

IN-DEPTH UNDERSTANDING OF HVAC EQUIPMENT & SYSTEM SPECIFICATIONS AND PERFORMANCE 11 & 12 JULY 2016 WISMA IEM

Optimizing Chilled Water Plant Performance. David Herman, PE, LEED AP Principal EnerG Associates, LLC

2017 NEHES Fall Conference Technical Breakout Session: Deep Chiller Plant Optimization

Air-Cooled Chillers. R134a. Performance Matters

VARIABLE REFRIGERANT FLOW SYSTEMS HITACHI SMARTFLEX VRF GEN II FLEXIBILITY, PERFORMANCE AND CONTROL

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:

Precision Cooling. Precision Cooling Advantages

JEFFERSON COLLEGE COURSE SYLLABUS HRA249 COMMERCIAL REFRIGERATION SYSTEMS. 5 Credit Hours. Prepared by William Kaune November 30, 2010

Ultra-Efficiency and Sustainability Meet Affordability

PEX (R410A) High Efficiency, Green Solution Precision Cooling for Data Centers

Setting New Standards for Ultra High Performance HVAC

Prescriptive Program Rebate Application

Climate Technologies Investor Update

Chiller Replacement and System Strategy. Colin Berry Account Manager

Retro-Commissioning Report

Hot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit

Comprehensive Energy Management & Utility Master Plan

T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management

Welcome Association of Energy Engineers to the Microsoft Technology Center

WHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net

a) Provision of a chilled water supply b) Provision of electric power supply and other fuels

LIFE CYCLE COST ANALYSIS, CRITERIA AND DATA SHEETS DOCUMENT NUMBER: APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL

Danfoss Turbocor Learning Center

Danfoss Turbocor Learning Center

District Cooling Marches on in Dubai The Emirates Towers Case Study

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw

Engineered Energy Solutions An Overview. Controls, Automation and Energy Conservation

MOLLIER DIAGRAM CAN BE IMPROVED!

Trane Cold Generator TM. Scroll Chillers. Comfort and Process Cooling Solutions

Transcription:

AIR-COOLED A (Surprisingly) Cost-Effective Alternative to Water-Cooled Chiller Plants By: David Schurk DES., CEM., LEED AP., CDSM., SFP. Heat Transfer Solutions, Director of Healthcare Accounts

The air-cooled chiller is a cost-effective alternative to a water-cooled system, which is typically considered when energy efficiency is a secondary concern to first-cost investment. HTS Texas has discovered that recent technology innovations, combined with advances in manufacturing practices, have resulted in impressive improvements in air-cooled chiller performance, especially in efficiency, sound and footprint. These chillers now stand toe-to-toe with their water-cooled equivalent and provide many additional benefits. This technology has evolved somewhat unnoticed, in part due to the fast-paced innovations in water-cooled technology that now offer sophisticated features such as oil-less compressors with magnetic bearings. The belief that air-cooled chillers are incapable of contributing to efficient building design and maximum energy savings persists despite technology advances. For historical reference, in 1998 air-cooled chillers had efficiency ratings of approximately 1.23kW/ton full load (9.76 EER) and 0.98 kw/ton (12.24 EER) part load -- a far cry from where efficiencies stand today. The aircooled chiller s time is here and its biggest advantage no longer relies soley on contributing to the lowest installed first-cost. What Has Changed? Mono-rotor Screw Compressor Design Enhanced component tolerances, less oil in circulation, the elimination of metal-to-metal sealing surfaces and balancing component radial forces contribute to a superior design that maximizes compression efficiency while reducing mechanical vibration and noise, leading to improved performance and reliability. Some advanced screw compressors use variable frequency drives and refrigerant economizers. 2

Factory-mounted Variable Frequency Drives Variable frequency drives (VFDs) have long been credited with helping reduce the cost of operating both variable torque (dynamic) and constant torque (positive displacement) prime movers. With a chiller, VFDs help match the required refrigeration capacity to the compressor output, allowing reductions in motor speed that take advantage of an accompanying reduction in motor horsepower. One advantage of the screw compressor (positive displacement) is that it can deliver high torque (lift) at very low speeds, a factor that creates complications for centrifugal chillers (dynamic compression), resulting in instability or surge. This allows the screw chiller a wider operational window while avoiding surge, and the advantage of minimizing motor horsepower at low turndowns. Factory-installed Refrigerant Economizer Refrigerant economizers have been used on centrifugal chillers for many years and have recently become available on some screw chillers. Through the addition of a brazed plate heat exchanger and Thermostatic Expansion Valve (TXV) on each refrigerant circuit, the refrigerant is both sub cooled for additional capacity and diverted to the interstage of the screw compressor for increased efficiency. The increase in refrigeration capacity has led to the development of large-tonnage chillers with remarkably small footprints. Without Economizer With Economizer Sub-cooling decreases compressor work and Increases evaporator capacity 3

The Air-Cooled Advantage Many small- to medium-sized chiller plants already use air-cooled chillers in nominal capacities ranging from 150 to 550 tons. Air-cooled screw chillers offer very good performance, particularly at partial load. These compressors are typically modulating (slide valve or VFDs) rather than stepped which produces more accurate control. Advantages of air-cooled chillers include: Positive displacement compression, no surge Avoids cooling towers Avoids city water costs Avoids water waste (improves environmental sustainability) Avoids chemical costs (improves environmental sustainability) In a natural disaster there are no water issues Avoids condenser pumps & piping Avoids high maintenance costs Saves mechanical room space Easier to control (no tower bypass) and operate (no tower freezing) in cold climates Excellent choice for applications where maintenance may be lacking Modern premium air-cooled chillers excel in efficiency. The table below compares two aircooled units, one based on 1998 efficiency levels and the other is one of today s most efficient models. Modern air-cooled chillers can perform at full load efficiencies up to 17 percent higher and part load efficiencies up to 37 percent greater than those models available only a few years ago. Chillers Full Load NPLV 1998 9.75EER 1.23kW/Ton 12.24EER 0.98kW/Ton Today 11.8EER 1.01kW/Ton 19.4EER 0.61kW/Ton 4

Applying Dollars and Sense How does a premium air-cooled chiller really stack up against its present day water-cooled rival? What follows is a simple comparison of four chillers including one premium high-efficiency aircooled screw chiller and three water-cooled centrifugal chillers. The air-cooled chiller was selected at its highest efficiency point, in part because the premium model available from the manufacturer came standard, fully equipped. All water-cooled centrifugal chillers were selected based on the capability of the software to select and rate the unit that contributes to the best life-cycle value, making it the most attractive to own. A high-level, simplified comparison can help determine the available chiller alternatives that can be further explored using site-specific metrics and validation processes. Each chiller analyzed was selected for a job HTS Texas worked on and required a full load capacity of 385 tons, its performance based on standard AHRI conditions. The kw/ton values were calculated by the software and applied to the formula 0.01A + 0.42B + 0.45C + 0.12D (typical of AHRI part load methodology) to derive chiller-only electrical consumption. An allowance of 0.08kW/ton (full load, 0.01A) and 0.06kW/ton (part load, all other points) was then added to each water-cooled chiller to account for the additional cooling tower fan and pump energy required. The assumption was that the tower fans would run at 50 percent speed and the condenser pumps at 100 percent flow during part load operation. Energy cost is based on $0.08/kWh, typical of the utility rate structure in Houston. The tables below illustrate the overall energy costs for each chiller. The results provide a comparison between models showing how they would perform under assigned operational conditions. Premium Efficiency Variable-Speed Air-Cooled Screw Chiller Full Load Tons Applied Value Operational Cost 385 0.632 $102,485 Constant-Speed Water-Cooled Centrifugal Chiller Full Load Tons Applied Value Operational Cost 385 0.587 $89,659 5

Variable-Speed Water-Cooled Centrifugal Chiller Full Load Tons Applied Value Operational Cost 385 0.480 $75,934 Variable-Speed Magnetic Bearing Water-Cooled Centrifugal Chiller Full Load Tons Applied Value Operational Cost 385 0.405 $66,683 The air-cooled chiller had the highest chiller-only operational cost, while costs attributed to each water-cooled chiller dropped as efficiency improved. An owner could maximize operational cost savings by purchasing the water-cooled, magnetic bearing chiller. This finding prompted HTS Texas to explore whether the air-cooled chiller has become a viable efficiency alternative. The Next Step The next step was to factor in the cooling tower water and water treatment costs associated with each water-cooled chiller. Shown below are the most recent City of Houston commercial water rates, with volume water and sewer charges (per 1000 gallons). 6

A comparison of water rates in Houston and other major U.S. cities proved to be challenging because of differences in municipal water rate structures due to various peak, off-peak, service, commodity, and block consumption charges. However, one major Pacific Northwest city published rates between $4.50 - $6.03/1000 gallons and another large Midwestern city showed a simple rate structure of $3.50/1000 gallons (sewer charges not included). While these cities were comparable, it is important to determine the actual water rate structure specific to the location of any project. A recent report in USA Today showed users pay 75 percent more for water today than in 2000. The report predicted water rates will increase by a whopping 5 percent to 15 percent per year, outpaced only by heating oil. The City of Houston water rates are shown above, with a volume charge of $3.74 per 1,000 gallons for commercial users. Unless the customer is separately metering the tower make-up water to account for waste, volume sewer charges (additional $5.30/1000 gallons) also may apply. In Houston a separate water meter must be purchased from the utility company and that cost is not included in this analysis. Of course, water must be accounted for when calculating the total cost of operating water-cooled equipment and will become increasingly important in future. In an effort to determine how much water the cooling tower would consume and what the cost impact would be, a number of variables were considered: the ambient wet bulb temperature, tower loading, tower turn down, chiller/tower control strategy, the type of chemical treatment used, the cycles of concentration allowed, and the type of tower installed. Shown below is our estimated tower water consumption for the water-cooled chillers considered in this article. HTS Texas considers consumption to be waste based on evaporation, drift and blow-down which are all lost to the surrounding atmosphere. Using City of Houston rates, our water consumption would then result in a cost of $19,097 per year. 7 Total make-up water includes: Evaporation Drift Blow down.0.0145/gpm (1) 385 Tons X 3 gpm/ton = 1155 gpm X.0145 = 16.75gpm GPM % Load % Run Time Gal/Yr 16.75 100 1 88,038 16.75 75 42 2,773,197 16.75 50 45 1,980,855 16.75 25 12 264,114 Gal/Yr 5,106,204 Tower Water Consumption

Other cost considerations are maintenance, not included in this analysis, and the cost of chemicals or water treatment. A nominal cost of $3.00 per 1,000 gallons for water treatment was added based on input from facility managers in the Texas Medical Center who maintain large central chilled water plants. Note that costs associated with water treatment may vary considerably based on the specific technology applied. When water and chemical costs are combined, the total reaches $34,409 per year. Water costs can now be added to the chiller-only electrical costs (for each water-cooled chiller) and a more realistic evaluation can be made. The table below ranks each chiller based on total annual operational cost, including electricity and water. The water-cooled magnetic bearing centrifugal chiller still proves to be the most advantageous (op-cost), but the premium air-cooled chiller follows closely behind, decisively outperforming the other two water-cooled options. Chiller Type Applied kw/ton Energy Cost $/yr Water & Chemicals Op-Cost $/yr #2 Premium Air-Cooled 0.632 $102,485 $0 $102,485 #4 CS Centrifugal 0.587 $89,659 $34,409 $124,068 #3 VFD Centrifugal 0.480 $75,934 $34,409 $110,343 #1 Mag-Bearing Centrifugal 0.405 $66,683 $34,409 $101,092 The Total Value Story Sometimes a client s purchasing decision is based solely on energy savings and sometimes the decision is based on first-cost alone. In reality a choice must be made that includes both firstcost and operational cost so a value-based purchase can be made. The pricing shown below helps establish the first cost of each chiller system. It is for the equipment only (chiller included) with contractor mark-up added (installation and labor not included). A cooling tower is added to each water cooled chiller because it is required. Tower pricing includes a single condenser pump, condenser piping, water treatment equipment and additional controls. The tower was valued at $92,400 ($240/ton). Additional refrigerant monitoring and mechanical room ventilation also would be required for the indoor chiller, although this is not included. 8

Chiller Premium Air-Cooled Chiller Traditional CS Cent. Chiller + Tower Traditional VFD Cent. Chiller + Tower Magnetic Bearing Cent. Chiller + Tower Equipment First-Cost #1 $227,487 ($591/ton) #2 $266,542 ($692/ton) #3 $292,320 ($759/ton) #4 $336,574 ($874/ton) The life cycle cost (LCC) for a project or a piece of equipment is its total cost to purchase and operate over its entire service life. This cost should include purchase, operation - including energy cost, maintenance and disposal. (2) While this article does not go into the depth necessary to include all aspects of a true LCC study, it helps establish insight into the cost of ownership for each alternative to determine which offers the best value. Note: the financial impact due to installation labor and materials, maintenance and disposal, tax implications, as well as savings based on unneeded mechanical room space are not included. Although important, this is left for the reader to assign value based on personal experience. Chiller Equipment $ 15-Year Op-Cost Additional Cost of Ownership #1 Premium Air-Cooled Chiller #4 Traditional CS Centrifugal Chiller #3 Traditional VFD Centrifugal Chiller #2 Magnetic Bearing Chiller $227,487 $1,772,316 BASE $266,542 $2,412,102 +$678,841 $292,320 $2,200,528 +$493,045 $336,547 $1,748,226 +$84,970 It is not necessary that the life cycle study period be identical to the equipment s service life and in this case a 15-year time frame was deemed suitable (3). Resulting life-cycle operational 9

costs include a two percent per year escalation added to utility rates. The table above includes both equipment first costs and operational costs for each chiller and reveals that the air-cooled option is capable of delivering the lowest combination. When each chiller was evaluated in this manner it became easier to assign value to the total cost of ownership. The table above ranks each chiller within three key cost categories. It is interesting to note that had any of the water-cooled chillers been judged solely on their chilleronly energy costs (water not included and first cost ignored) each may have been considered superior to the air-cooled unit in contributing more overall value to the owner. When broader views of cost are measured it is demonstrated that the premium air-cooled chiller provides an impressive impact on the owner s bottom line, in this case outperforming other prospects. While this is not a complex study into the overall life-cycle operation of any of the chillers, it provides new information in the process to qualify the true benefits of air-cooled chillers. The table below ranks and compares each chiller based on its ability to perform in the categories of op-cost, first cost and cost of ownership. Where once the air-cooled chiller was considered a low-cost alternative in favor of a more efficient design, it has proven itself to be a surprisingly cost effective contender in the overall value proposition. Item Op-Cost First-Cost Cost to Own Premium Air-Cooled Chiller Traditional CS Centrifugal Chiller Traditional VFD Centrifugal Chiller Magnetic Bearing Chiller #2 #1 #1 #4 #2 #4 #3 #3 #3 #1 #4 #2 References: (1) HVAC Water Chillers & Cooling Towers: Fundamentals, Application & Operation, Herbert W. Stanford, Stanford White Associates, Consulting Engineers. (2) Guide to Energy Management, Capehart,Turner and Kennedy. (3) It is the author s view that emerging technology may render major HVAC equipment purchases made today obsolete and in need of replacement long before its normal service life is over. 10

David Schurk is Director of Healthcare Accounts for Heat Transfer Solutions in Houston, Texas. David Schurk has more than 30-years of HVAC systems based energy-efficiency experience. He can be reached at 920-530-7677 or david.schurk@hts.com About HTS With nearly 400 employees, HTS has offices in 16 cities across the U.S. and Canada, representing more than 80 HVAC suppliers. Delivering Real Success to all involved in its projects, HTS provides HVAC and refrigeration solutions to commercial, institutional, residential and industrial markets that represent leading manufacturers such as Daikin and Haakon Industries. For more information about HTS and its operations in Texas (3350 Yale Street Houston, Texas 77018), visit www.htseng.com (HTS Texas http://texas.htseng.com), call tollfree at 1-866-544-1487 and connect via LinkedIn, Facebook, Twitter and Google+. 11