VT7200 Series 24 Vac Low Voltage Zoning Thermostats For Commercial HVAC Applications

Similar documents
LonWorks Integration Manual ITG-VT72_73-PIR-LON-E07 ( R7 Issue Date: February 3, 2009)

LonWorks Integration Manual ITG-VT(R)72_73-PIR-LON-E08 ( R8 Issue Date: January 17, 2013)

PIR Ready SE72xx & SE73xx Series 24 VAC Fan Coil and Zoning Controllers For Commercial and Lodging HVAC Applications LonWorks Integration Manual

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification

VZ7000 Series. BACnet Commercial Zoning System

PIR Ready VT7600 Series Programmable & Non-Programmable Thermostats For Commercial HVAC Applications. LonWorks Integration Manual (September 1, 2010)

Installation- & user instructions

CORRIGO R10. LonMark Functional Profile: Chilled Ceiling Controller Corrigo R10 LonWorks Interface: LonMark Chilled Ceiling Controller

SE7600E Series Application Guide

LonWorks Integration Instructions

Packaged Fresh Air Unit With Tracer LCI-I

KITS AND ACCESSORIES. Prodigy LonTalk MODULE KIT INSTALLATION INSTRUCTIONS FOR LONTALK MODULE KIT (54W27) USED WITH ENERGENCE ROOFTOP UNITS.

Room Controllers VTR8300 Line Voltage Fan Coil Controller with VC3000 Relay Pack Technical Cut Sheet

CONTENTS. Installation Guide. PIR Ready VT7200 Series 24 VAC Low Voltage Zoning Terminal Equipment Controller

VC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide

RCM Room Command Module New Style

MODEL 2000T Initial Draft

SEZ7000 Series. Wireless Commercial Zoning System

Installation- & user instructions


SmartStruxure SmartStruxure Lite ZENO InnPoint. ZENOcontrols.com. compatible with

SE8300 Room Controller

LX Series Application-Specific Controllers

MicroTech 2000 Water Source Heat Pump Unit Controller Protocol Information

BACnet Integration Manual September 1, 2010

Stryker Lon Configurable Controllers

SEZ7260X5x45B Installation Guide for BACnet MS/TP Zone Controller

Stryker Lon Configurable Controllers

March 13 th, 2012 / R2

SEZ7656R1045B / SEZ7656H1045B

ExactLogic BACnet Communicating Pressure Dependent VAV Damper Control with Heat EXL01820 Sequence Datasheet


SER8300 Room Controller

Room Controllers SER8300 Line Voltage Fan Coil Controller with SC3000 Relay Pack

LONWORKS Compatible DX-9200 Digital Controller

Installation and Operation. Tracer MP501 Controller CNT-SVX08B-EN

ExactLogic BACnet Communicating Zone Damper EXL01710 Sequence Datasheet

System Controls Suggested Specification

VZ7656B1000B Series BACnet RTU Thermostats For Commercial Zoning Systems

SEZ7656E1045B. Installation Guide for BACnet MS/TP RTU Terminal with IAQ Control CONTENTS

TAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta

VZ7260X5X00W BACnet Zone Room Controller. Installation Guide. April 2017

Excel 10 W7751B,D,F VAV II Controllers

VZ7656B1000W Series Wireless RTU Thermostats For Commercial Zoning Systems

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller


ExactLogic BACnet Communicating Thermostat EXL01816 Sequence Datasheet

THERMOSTATS & CONTROLLERS

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

VT8300 Room Controller

VTR8300 User Interface Guide VTR8300 Room Controller Series

ECP-VAV Series. ECP-VAV Series. 10-Point Single Duct VAV / VVT Free Programmable Controller. Applications. Features

Siemens BACnet Programmable TEC Constant Volume

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

TC-9102 Terminal Controller

TEC Zoning Control System for Stand-Alone and BACnet MS/TP Networked Applications

Room Controllers. SER8300 Line Voltage Fan Coil Room Controller with SC3000 Relay Pack

TAC Xenta 121-FC Programmable Fan Coil Application

Communicating Thermostats. Add More Flexibility to Building Automation with. Communicating Thermostats

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

FXVMA Variable Air Volume (VAV) Box Controller

Siemens BACnet Programmable TEC Unit Conditioner Controller

HLS34 Modbus FCU/VAV Controllers installation instructions

Field selectable application type and room module series, via dip-switches on controller

Installation Guide. VZ7656F1000B BACnet MS-TP RTU Terminal Equipment Controller with Modulating Heat. February 2017 /

SE8300 User Interface Guide SE8300 Series Room Controller

BACnet Integration Manual ITG-VWG-50-BAC-E01.doc ( R1 Issue Date: January 10 th, 2012)

FCU-4 FAN COIL CONTROLLER

SE7600F Series. Installation Guide for RTU with Modulating Heat CONTENTS

ExactLogic BACnet Communicating Thermostat EXL01716 Sequence Datasheet Duel Deck VAV

MicroTech III Water Source Heat Pump Unit Controller Protocol Information

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller

Room Controllers. SC3000 Relay Pack

SE7600E Series Application Guide

Tracer Controls. Tracer MP.501 Controller BAS-PRC008-EN. June 2001


Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control

Modbus Integration Integration for Modbus Functionality for VTR8300 Series

SE7600E Series. Installation Guide for Commerical HVAC Applications CONTENTS

VZ7656F1000W Zigbee Wireless RTU Terminal Equipment Controller with Modulating Heat. Installation Guide

Room Controllers SER8300 Line Voltage Fan Coil Controller with SC3000 Relay Pack

BACnet Terminal Box (VAV) Controller

Excel 10 W7752D,E,F,G AND W7754K,P,Q,R,S,T,V FAN COIL UNIT CONTROLLERS LNS PLUG-INS

LonMark Certified Powered Fan Coil Configurable Controllers. Overview

Viconics VT7682S Wireless Central Manager Application Guide

FUME HOOD CONTROLLER (FHC)

RCF-230CTD. Room controller for fan-coil applications with outputs for two thermal or one 3-position actuator or function for an electric heater

TAC Xenta 121-HP Programmable Heat Pump Application

NT10 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

Tracer Controls. Tracer MP501 Controller BAS-PRC008-EN. January 2005

Fan coil (FCU) application guide

Pre-programmed room controller with display and communication

VT8600 Series Installation Guide. Rooftop Unit, Heat Pump and Indoor Air Quality Controller

ECON-ZIP-BASE. ZIP Economizer Base Unit. Wiring Diagram USA CANADA LATIN AMERICA / CARIBBEAN

SER8300 Series Line Voltage Room Controller with Optional PIR Sensor Installation Guide

CONTENTS CONTROLLERS room controllers room units control units PRODUAL 3 CATALOGUE

ECC-VAVS and ECC-VAV Series

BACnet Integration Manual ITG-VZ7xxx-BAC-E04.doc ( _R4 Issue Date: May 31 st, 2012)

Submittal Data Sheet intelligent Touch Manager DCM601A71

M1000 INTELLIGENT ZONE CONTROL SYSTEM

Transcription:

Product overview VT7200 Series 24 Vac Low Voltage Zoning Thermostats For Commercial HVAC Applications 1 The VT7200 PI thermostat family is specifically designed for zoning applications. Typical applications include local hydronic reheat valve control and pressure dependent VAV with or without local reheat. The product features a backlit LCD display with dedicated function menu keys for simple operation. Accurate temperature control is achieved due to the product s PI proportional control algorithm, which virtually eliminates temperature offset associated with traditional, differential-based thermostats. Models are available for 3 point floating and analog 0 to 10 Vdc control. In addition remote room sensing is available. They all contain an SPST auxiliary switch that can be used to control lighting or auxiliary reheat. All devices are also available with Echelon or BACnet MS-TP network adapter. The additional following documentation is available on www.viconics.com Information on the LON models (VT72xxX1000E), is available on document ITG-VT7200-LON-E01 Information on the BACnet models (VT72xxX1000B), is available on document ITG-VT7200-BAC-E01 For more application information including detailed wiring, specific configuration and sequences of operation, please refer to online document APP-VT7200-E01. Models available Viconics number VT7200C1000 VT7200C1000B (BACnet) VT7200C1000E (Echelon) VT7200F1000 VT7200F1000B (BACnet) VT7200F1000E (Echelon) Control outputs 2 x Tri-state floating 2 x Analog 0 to 10 Vdc 1 x Auxiliary or reheat contact 1 x Auxiliary or reheat contact Features and benefits Features Advanced occupancy functions 3 configurable inputs Pre-configured sequences of operation Unique configuration setup utility Lockable keypad Available for 24 Vac On/Off, Floating or Analog control Auxiliary output Available with various open industry standards communication adapters Benefits Through the network or smart local occupancy sensing Adds functionality One model meet more applications Reduces project delivery cost Minimizes parameter tampering Tamper proof, no need for thermostat guards Meet advanced applications requirements Can be used for lighting or reheat Adds network integration functionality for additional savings 2005/10/04 LIT-VT7200-E0.doc www.viconics.com sales@viconics.com

2 Thermostat Objects VT7200 Space Comfort Controller Object Type #8500 nvispacetemp Mandatory Network Variables nvospacetemp nvounitstatus SNVT_hvac_status nvioutdoortemp nvisetpoint nviauxheatenable SNVT_switch nviocccmd SNVT_occupancy nviapplicmode SNVT_hvac_mode nviheatcool SNVT_hvac_mode Optional Network Variables nvodischairtemp nvoeffectoccup SNVT_occupancy nvoterminalload SNVT_lev_percent Configuration Properties Send Heartbeat (mandatory) Temperature Setpoints (mandatory) Minimum Send Time (optional) Receive Heartbeat (optional) nviremlockout SNVT_count nviauxout SNVT_switch Manufacturer Network Variables nvosccstate SNVT_state_64 Manufacturer Configuration Properties Please see the manual for details. Plug-In for configuration provided.

3 SNVTs and SCPTs Table Per Model Model Number VT7200C1000E VT7200F1000E No Sub Point Name N/A: Not applicable on this model 0 nvispacetemp X X 1 nvioutdoortemp X X 2 nvisetpoint X X 3 nvispacerh N/A N/A 4 nvifanspeedcmd N/A N/A 5 nviauxheatenable X X 6 nviocccmd X X 7 nviapplicmode X X 8 nviheatcool X X 9 nviremlockout X X 10 nvidhumilck N/A N/A 11 nviauxout X X 12 nvospacetemp X X 13 nvodischairtemp X X 14 nvospacerh N/A N/A 15 nvoeffectoccup X X 16 nvounitstatus X X 1 mode x x 2 heat_output_primary x x 4 cool_output x x 6 fan_output N/A N/A 7 in_alarm x x 17 nvosccstatus X X 1 StateTerminal BO2 x N/A 2 StateTerminal BO1 x N/A 3 StateTerminal BO4 x N/A 4 StateTerminal BO3 x N/A 5 StateTerminal BO5 x x

Model Number VT7200C1000E VT7200F1000E 4 No Sub Point Name N/A: Not applicable on this model 6 FanLow N/A N/A 7 FanMed N/A N/A 8 FanHigh N/A N/A 9 UI 3 Status x x 10 BI 2 Status x x 11 BI1 Status x x 12 Service Alarm x x 13 Filter Alarm x x 14 Window Opened x x 15 Dehumidification Active N/A N/A 18 nvoterminalload X X 19 ncisetpts X X 1 occupied_cool x x 3 unoccupied_cool x x 4 occupied_heat x x 6 unoccupied_heat x x 20 ncirhmodel N/A N/A 1 RHdisplay N/A N/A 2 RHsetpoint N/A N/A 3 DehumHyst N/A N/A 4 DehumCool N/A N/A 5 RHcalib N/A N/A 21 ncigenopt X X 1 Control Type x N/A 2 Drive Time x N/A 3 Cycles Per Hour x N/A 4 Reverse Acting Output N/A x 5 BI1 x x 6 BI2 x x 7 UI3 x x 8 Menu Scroll x x

Model Number VT7200C1000E VT7200F1000E 5 No Sub Point Name N/A: Not applicable on this model 9 Auto Mode x x 10 Temperature Scale x x 11 Pipes # Main out config x x 12 Fan Menu N/A N/A 13 Heat Maximum setpoint x x 14 Cool Minimum setpoint x x 15 Setpoint Type x x 16 Temporary Occ Time x x 17 Door Time x x 18 Deadband x x 19 Calibration Room Sensor 20 Auxiliary Contact Config 21 Reheat Time Base x x 22 ncisccmodel X X 1 Thermostat Model x x 2 Software Version x x 23 ncihvactype X X 24 ncisndhrtbt X X 25 nciminouttm X X 26 ncircvhrtbt X X 27 ncimajver X X 28 nciminver X X x x x x

6 Specifications Thermostat power requirements: 19-30 Vac 50 or 60 Hz; 2 VA Class 2 Operating conditions: 0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing Storage conditions: -30 C to 50 C ( -22 F to 122 F ) 0% to 95% R.H. non-condensing Sensor: Local 10 K NTC thermistor Resolution: ± 0.1 C ( ± 0.2 F ) Control accuracy: ± 0.5 C ( ± 0.9 F ) @ 21 C ( 70 F ) typical calibrated Occupied and unoccupied setpoint range 12.0 to 37.5 C ( 54 to 100 F ) cooling: Occupied and unoccupied setpoint range 4.5 C to 32 C ( 40 F to 90 F ) heating: Room and outdoor air temperature display -40 C to 50 C ( -40 F to 122 F ) range Proportional band for room temperature Cooling & Heating: 1.1 C ( 2.0 F ) control: Binary inputs: Dry contact across terminal BI1, BI2 & UI3 to Scom Contact output rating: Triac output: 30 Vac, 1 Amp. Maximum, 3 Amp. in-rush Analog: 0 to 10 Vdc into 2KΩ resistance min. Wire gauge 18 gauge maximum, 22 gauge recommended Dimensions: 4.94 x 3.38 x 1.13 Approximate shipping weight: 0.75 lb ( 0.34 kg ) Agency Approvals: FCC Class A & culus. CE ( Pending ) Drawing & dimensions 3.38" [86 mm] 4.94" [125 mm] Important notice All VT7200 series controls are for use as operating controls only and are not safety devices. These instruments have undergone rigorous tests and verifications prior to shipment to ensure proper and reliable operation in the field. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user / installer / electrical system designer to incorporate safety devices ( such as relays, flow switch, thermal protections, etc ) and/or alarm system to protect the entire system against such catastrophic failures. Tampering of the devices or miss application of the device will void warranty. 1.13" [29 mm] Fig.13 Thermostat dimensions

7 Product overview VT7300 Series 24 Vac Low Voltage Fan Coil Thermostats For Commercial and Lodging HVAC Applications The VT7300 PI thermostat family is specifically designed for fan coil control. The product features a backlit LCD display with dedicated function menu buttons for simple operation. Accurate temperature control is achieved due to the product s PI proportional control algorithm, which virtually eliminates temperature offset associated with traditional, differential-based thermostats. Models are available for On/Off, 3 point floating and analog 0 to 10 Vdc control. All models contain can control three, two or single fan speed. 3 additional inputs are also provided for various functions. All models feature configurable System and Fan button functions to meet all possible applications. They all contain an SPST auxiliary switch that can be used to control lighting or auxiliary reheat. The additional following documentation is available on www.viconics.com Information on the LON models (VT73xxX1000E), is available on document ITG-VT7300-LON-E01 Information on the BACnet models (VT73xxX1000B), is available on document ITG-VT7300-BAC-E01 For more application information including detailed wiring, specific configuration and sequences of operation, please refer to online document APP-VT7300-E01.. Models available Viconics number VT7300A1000 VT7300C1000 VT7350C1000 VT7305A1000 VT7305C1000 VT7355C1000 VT7300F1000 VT7350F1000 VT7305F1000 VT7355F1000 Application 2 & 4 Pipe On/Off 2 & 4 Pipe Floating & On/Off 2 & 4 Pipe On/Off 2 & 4 Pipe Floating & On/Off 2 & 4 Pipe Analog 0-10 Vdc RH sensor No No Yes No No Yes No Yes No Yes Market Commercial / Institution Hotels / Lodging Commercial / Institution Hotels / Lodging Features and benefits Features Benefits Models available with internal humidity sensing Increased occupant comfort through dehumidification Advanced occupancy functions Through the network or smart local occupancy sensing 3 configurable inputs Adds functionality Configurable sequences of operation Single model meets more applications Configurable fan functions button Meets more applications with a single model Unique configuration setup utility Minimizes parameter tampering Multi level lockable keypad Tamper proof, no need for thermostat guards Auto Fan speed mode Increased occupant comfort in cooling mode by reducing humidity and offer less fan noise in all mode of operation Available for 24 Vac On/Off, Floating or Analog control Meet advanced applications requirements Auxiliary output Can be used for lighting or reheat 2005/10/06 LIT-VT7300-E01.doc www.viconics.com sales@viconics.com

8 Thermostat Objects VT7300 Space Comfort Controller Object Type #8500 nvispacetemp Mandatory Network Variables nvospacetemp nvounitstatus SNVT_hvac_status nvioutdoortemp nvisetpoint nvispacerh SNVT_lev_percent nvifanspeedcmd SNVT_switch Optional Network Variables nvodischairtemp nvospacerh SNVT_lev_percent nvoeffectoccup SNVT_occupancy nvoterminalload SNVT_lev_percent nviauxheatenable SNVT_switch nviocccmd SNVT_occupancy nviapplicmode SNVT_hvac_mode nviheatcool SNVT_hvac_mode Configuration Properties Send Heartbeat (mandatory) Temperature Setpoints (mandatory) Minimum Send Time (optional) Receive Heartbeat (optional) nviremlockout SNVT_count nvidhumidlck SNVT_switch nviauxout SNVT_switch Manufacturer Network Variables nvosccstate SNVT_state_64 Manufacturer Configuration Properties Please see the manual for details. Plug-In for configuration provided.

9 SNVTs 1 and SCPTs 2 Table Per Model Model Number VT7300A1000E VT7300C1000E VT7350C1000E VT7305A1000E VT7305C1000E VT7355C1000E VT7300F1000E VT7350F1000E VT7305F1000E VT7355F1000E VT7300M1000E No Sub Point Name N/A: Not applicable on this model 0 nvispacetemp X X X X X X X X X X X 1 nvioutdoortemp X X X X X X X X X X X 2 nvisetpoint X X X X X X X X X X X 3 nvispacerh N/A N/A X N/A N/A X N/A X N/A X N/A 4 nvifanspeedcmd X X X X X X X X X X X 5 nviauxheatenable X X X X X X X X X X X 6 nviocccmd X X X X X X X X X X X 7 nviapplicmode X X X X X X X X X X X 8 nviheatcool X X X X X X X X X X X 9 nviremlockout X X X X X X X X X X X 10 nvidhumilck N/A N/A X N/A N/A X N/A X N/A X N/A 11 nviauxout X X X X X X X X X X X 12 nvospacetemp X X X X X X X X X X X 13 nvodischairtemp X X X X X X X X X X X 14 nvospacerh N/A N/A X N/A N/A X N/A X N/A X N/A 15 nvoeffectoccup X X X X X X X X X X X 16 nvounitstatus X X X X X X X X X X X 1 mode x x x x x x x x x x x 2 heat_output_primary x x x x x x x x x x x 4 cool_output x x x x x x x x x x x 6 fan_output x x x x x x x x x x x 7 in_alarm x x x x x x x x x x x 17 nvosccstatus X X X X X X X X X X X 1 StateTerminal BO2 x x x x x x N/A N/A N/A N/A N/A 2 StateTerminal BO1 N/A x x N/A x x N/A N/A N/A N/A N/A 3 StateTerminal BO4 N/A x x N/A x x N/A N/A N/A N/A N/A 4 StateTerminal BO3 x x x x x x N/A N/A N/A N/A N/A 5 StateTerminal BO5 x x x x x x x x x x x 6 FanLow x x x x x x x x x x N/A 7 FanMed x x x x x x x x x x N/A

Model Number VT7300A1000E VT7300C1000E VT7350C1000E VT7305A1000E VT7305C1000E VT7355C1000E VT7300F1000E VT7350F1000E VT7305F1000E VT7355F1000E VT7300M1000E 10 No Sub Point Name N/A: Not applicable on this model 8 FanHigh x x x x x x x x x x x 9 UI 3 Status x x x x x x x x x x x 10 BI 2 Status x x x x x x x x x x x 11 BI1 Status x x x x x x x x x x x 12 Service Alarm x x x x x x x x x x x 13 Filter Alarm x x x x x x x x x x x 14 Window Opened x x x x x x x x x x x 15 Dehumidification Active N/A N/A x N/A N/A x N/A x N/A x N/A 18 nvoterminalload X X X X X X X X X X X 19 ncisetpoints X X X X X X X X X X X 1 occupied_cool x x x x x x x x x x x 3 unoccupied_cool x x x x x x x x x x x 4 occupied_heat x x x x x x x x x x x 6 unoccupied_heat x x x x x x x x x x x 20 ncirhmodel N/A N/A X N/A N/A X N/A X N/A X N/A 1 RHdisplay N/A N/A x N/A N/A x N/A x N/A x N/A 2 RHsetpoint N/A N/A x N/A N/A x N/A x N/A x N/A 3 DehumHyst N/A N/A x N/A N/A x N/A x N/A x N/A 4 DehumCool N/A N/A x N/A N/A x N/A x N/A x N/A 5 RHcalib N/A N/A x N/A N/A x N/A x N/A x N/A 21 ncigenopt X X X X X X X X X X X 1 Control Type N/A x x N/A x x N/A N/A N/A N/A N/A 2 Drive Time x x x x x x N/A N/A N/A N/A N/A 3 Cycles Per Hour x x x x x x N/A N/A N/A N/A N/A 4 Reverse Acting Output N/A N/A N/A N/A N/A N/A x x x x x 5 BI1 x x x x x x x x x x x 6 BI2 x x x x x x x x x x x 7 UI3 x x x x x x x x x x x 8 Menu Scroll x x x x x x x x x x x 9 Auto Mode x x x x x x x x x x N/A 10 Temperature Scale x x x x x x x x x x x 11 Pipes # Main out config x x x x x x x x x x x

Model Number VT7300A1000E VT7300C1000E VT7350C1000E VT7305A1000E VT7305C1000E VT7355C1000E VT7300F1000E VT7350F1000E VT7305F1000E VT7355F1000E VT7300M1000E 11 No Sub Point Name N/A: Not applicable on this model 12 Fan Menu x x x x x x x x x x N/A 13 Sequence of Operation x x x x x x x x x x N/A 14 Heat Maximum setpoint x x x x x x x x x x x 15 Cool Minimum setpoint x x x x x x x x x x x 16 SetpointType x x x x x x x x x x x 17 Temporary Occ Time x x x x x x x x x x x 18 Door Time x x x x x x x x x x x 19 Deadband x x x x x x x x x x x 20 Calibration Room Sensor 21 Auxiliary Contact Config x x x x x x x x x x x x x x x x x x x x x x 22 Reheat Time Base x x x x x x x x x x x 22 ncisccmodel X X X X X X X X X X X 1 Thermostat Model x x x x x x x x x x x 2 Software Version x x x x x x x x x x x 23 ncihvactype X X X X X X X X X X X 24 ncisndhrtbt X X X X X X X X X X X 25 nciminouttm X X X X X X X X X X X 26 ncircvhrtbt X X X X X X X X X X X 27 ncimajver X X X X X X X X X X X 28 nciminver X X X X X X X X X X X

12 Specifications Thermostat power requirements: 19-30 Vac 50 or 60 Hz; 2 VA Class 2 Operating conditions: 0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing Storage conditions: -30 C to 50 C ( -22 F to 122 F ) 0% to 95% R.H. non-condensing Sensor: Local 10 K NTC thermistor Resolution: ± 0.1 C ( ± 0.2 F ) Control accuracy: ± 0.5 C ( ± 0.9 F ) @ 21 C ( 70 F ) typical calibrated Occupied and unoccupied setpoint range 12.0 to 37.5 C ( 54 to 100 F ) cooling: Occupied and unoccupied setpoint range 4.5 C to 32 C ( 40 F to 90 F ) heating: Room and outdoor air temperature display -40 C to 50 C ( -40 F to 122 F ) range Proportional band for room temperature Cooling & Heating: 1.1 C ( 2.0 F ) control: Binary inputs: Dry contact across terminal BI1, BI2 & UI3 to Scom Contact output rating: Fan relay output: 30 Vac, 1 Amp. Maximum, 3 Amp. in-rush Valve triac output: 30 Vac, 1 Amp. Maximum, 3 Amp. in-rush Valve analog: 0 to 10 Vdc into 2KΩ resistance min. Wire gauge 18 gauge maximum, 22 gauge recommended Dimensions: 4.94 x 3.38 x 1.13 Approximate shipping weight: 0.75 lb ( 0.34 kg ) Agency Approvals: FCC Class A & culus. CE ( Pending ) Drawing & dimensions 4.94" [125 mm] Important notice All VT7300 series controls are for use as operating controls only and are not safety devices. These instruments have undergone rigorous tests and verifications prior to shipment to ensure proper and reliable operation in the field. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user / installer / electrical system designer to incorporate safety devices ( such as relays, flow switch, thermal protections, etc ) and/or alarm system to protect the entire system against such catastrophic failures. Tampering of the devices or miss application of the device will void warranty. 3.38" [86 mm] 1.13" [29 mm] Fig.13 Thermostat dimensions