C-DIAS Profibus DP Slave module CPB 021

Similar documents
Profibus DP slave. dual ported RAM 2Kbyte. Maximum length for I/O data. Maximum length for output data. Status display

Table 1 Specifications Software Required for Configuration

C-DIAS Serial Interface CSI 021

Auxiliary Board MP-Bus HZS 562

C-DIAS EtherNet/IP Slave CIP 022

C-DIAS-Temperature Recording module CAI x Temp. inputs 50 C to +150 C

VARAN Manager PCI Insert module PCV 521 Versatile Automation Random Access Network

VARAN Splitter Module VSV 041

DIAS Interface Module VARAN DIV 511

VARAN Bus Coupler Module VBC 021 For connecting two VARAN bus systems

VARAN Splitter PROFINET VSP 044

ISE 021 S-DIAS Interface Module RS232 / RS485

Expansion Module HZS 541-1S

VARAN Splitter Module VSV 043

Manual Fiber Optic Interfaces

Processor module DCP 642

VARAN Splitter PROFINET VSP 042

Keyboard Unit Sigmatek

C-DIAS Digital Input Module CDI 161 with 16 inputs

Protected VARAN Digital Mixed Module PVDM 086

Hardware Manual RM CANview

PSI-MODEM-SHDSL/PB. Broadband PROFIBUS extender, SHDSL PROFIBUS leased line modem. Data sheet _en_03. 1 Description. 1.

Technical Data. C-DIAS-MULTI l/o MODULE CIO 013

VARAN Digital Combined Module VDM 086

C-DIAS VARAN Control Module CIV x VARAN-In 1 x VARAN-Out (Optional Ethernet (VtE))

C-DIAS Analogue Output Module CAO 081 for eight 10V DC outputs

VARAN Client Board VEB 011/012 Versatile Automation Random Access Network

Installation and Operating Instructions. webremote

PA ROUTERS. The following criteria can be applied when choosing the network transition:

PHOENIX CONTACT

W&T. Universal Fiber Optic Interface Converter W&T. Manual. Universal FO Interface Converter. Model Release 1.0. Subject to error and alteration

L5353 Profibus-DP Communications Interface

ETT 352 Touch Operating Panel

VARAN-INTERFACE VAC 012

Complete the Installation SKINTOP MS-SC. Color Code: Approvals: Nominal Outer Diameter

Hardware Manual ipc-i 320/PCI II Intelligent PC/CAN Interface

PSI-MOS-PROFIB/FO 850 T

AO 081 S-DIAS Analog Output Module

SI 021 S-DIAS SSI Interface Module

C-DIAS Analogue Conversion Module CAM 124 for eight 0 10V DC inputs and four 10V outputs

Bus Cover Description for Shaft Encoder

PAS 300, PROFIBUS Slave Interface Module

This manual may not be reproduced in whole or in part by any means, without written permission of Accuenergy.

ETT 312 Build-In Touch Terminal

Extract from the online catalog

TSY 041 Training System Extension Motion

Wiring Section 3-3. NQ-Series communication ports support various types of (serial) communication.

C-DIAS Temperature sensing module CAI x temp. inputs C 8 x digital outputs +24V

MGate 4101-MB-PBS Series

Operating Manual UMB ISO Converter ISOCON Order Number: 8160.UISO

Introduction. General Ratings

Moxa TCC-100 Series Hardware Installation Guide

PCAN-Router FD Universal, programmable Converter for CAN FD and CAN. User Manual. Document version ( )

PROFIBUS Technology Products

SUBCON-PLUS-PROFIB...

TO 161 S-DIAS Digital Output Module

Communication module to connect M-bus devices to POL6xx.xxx controllers.

D2 RMSM/ T1K RSSS Remote I/O System

The TRSUN is the complete solution for the remote monitoring of photovoltaic plants.

Technical Manual. HA Issue 4. Copyright Parker SSD Drives, Inc 2008

Internal Buffer/Boiler Module HZS 534

VersaMax IP Input Module

ADAM-4510 RS-422/RS-485 Repeater ADAM-4510S Isolated RS-422/485 Repeater ADAM-4520 Isolated RS-422/485 Converter Startup Manual

Installation and Setup

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

Valve terminal RE-10 with Multi-pin, AS-Interface or bus connection 4 12 valve stations, 300 Nl/min (0.305 Cv)

HZS Solar Module

Interface RS485-TTL CODE: INTR. v.1.0 EN* Edition: 3 from

EX-RC1 Remote I/O Adapter

Moxa TCC-100 Series User s Guide

EX-RC1 Remote I/O Adapter

HZS Internal Controller Expansion

DF PROFI II CPCI. Installation Instructions V Project No.: 5302 Doc-ID.: DF PROFI II CPCI KUNBUS

DF PROFI II PCIe. Installation Instructions V Project No.: 5302 Doc-ID.: DF PROFI II PCIe KUNBUS

DM 161 S-DIAS Digital Mixed Module

C-DIAS Analog Module CAO 086 For eight ±10 V Outputs

Serial PROFIBUS Interface

Accessories / 7XV5662

ICA 012 S-DIAS Interface Module CAN

LVX Control Unit. Features:

Cardax FT Controller 3000

Inclinometer. 4-20mA and RS232

SAI Active Universal Pro

Technical data. General specifications. Linearity error ± 0.1 Functional safety related parameters MTTF d 480 a at 40 C Mission Time (T M ) L 10

EX-RC1 Remote I/O Adapter

PSM-ME-RS232/TTY-P Interface converter for RS-232 to TTY transmission systems

Modular controllers CECX

FOURSTAR PROFIBUS HUB. FS-PBHUB-4 FS-PBHUB-6 User Manual

SK TU4-PBR Part number:

USB to RS-232/RS422/485. US-101-I USB To Serial Operation Manual

USB RS485 High Isolated Industry Converter Box for DIN Rail - product #248

PROFIBUS. Connectors Repeaters FO Wireless system Communication

IM IM in the RS485 variants features: 9-pin Sub-D socket for connection to PROFIBUS DP

to 12a Added Standard and Electrical requirements for UL table 1.1

MODEL: R1M-D1. PC Recorders R1M Series. SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.)

Technical data. General specifications. Linearity error ± 0.1 Functional safety related parameters MTTF d 480 a at 40 C Mission Time (T M ) L 10

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

DF PROFI II PC/104-Plus

Modbus TCP/RTU Gateway

Dupline. Data Logger. Types G , G Product Description. Ordering Key G Type Selection. Input/Output Specifications

Transcription:

C-DIAS Profibus DP Slave module CPB 021 The C-DIAS Profibus DP slave module CPB 021 serves as an interface module between the C-DIAS control system and Profibus. This module supports a galvanically separated Profibus slave. Technical Data Performance data Number of channels 1 Field bus Communications interface netx50 C-DIAS Data transfer rate RS485 Electrical interface Status display Profibus DP slave (V0) 64-Kbyte Dual Port Memory (DPM) up to 12 MBit/s RS485 / 9-pin DSUB socket Yes 30.09.2009 Page 1

Electrical requirements Voltage supply from C-DIAS bus +24 V Current consumption Typically 80 ma Maximum 100 ma Voltage supply from C-DIAS bus +5 V Current consumption Typically 40 ma Maximum 60 ma Output voltage Load capacity +5 V (no supply voltage; for bus termination only) Maximum 20 ma Miscellaneous Article number 12-057-021 Hardware version 1.x Standard Approbations UL 508 (E247993) cul, UL Environmental conditions Storage temperature -20 +85 C Operating temperature 0 +60 C Humidity EMV stability 0-95 %, uncondensed According to EN 61000-6-2:2001 (industrial area) Shock resistance EN 60068-2-27 150 m/s² Protection Type EN 60529 IP 20 Page 2 30.09.2009

Mechanical Dimensions 104,10 (Bemaßung inkl.auflagen) 109,2 129 24,90 30.09.2009 Page 3

Connector Layout Page 4 30.09.2009

X1: Profibus Interface (9-pin DSub socket) C-DIAS PROFIBUS DP SLAVE MODULE CPB 021 Pin Signal Function 1 Not used - 2 Not used - 3 RxD / TxD P Receive / Transmit Data P Data Line B 4 CNTR-P Repeater Control Signal 5 D GND Data Ground 6 VP Positive Power Supply 7 Not used - 8 RxD / TxD - N Receive / Transmit Data N Data Line Inverse A 9 Not used - Shield Shield SW1: DIP-Switch (4-pin) Pin Signal Function 1 ON / OFF Termination ON/OFF 2 ON / OFF Termination ON/OFF 3 ON / OFF - 4 ON / OFF - Dipswitch Termination Dipswitch 1 2 1 2 Profibus: open Profibus: terminated 3 4 3 4 Not used. 30.09.2009 Page 5

Status Displays LED number LED color Definition 1 Yellow / Green PB SYSTEM Yellow: READY Green: RUN 2 Green / Red PB COM Green: STATUS Red: ERROR 3 Yellow PB TXD 4 Green PB RXD 5 Green DC OK Description PB SYSTEM PB COM PB TXD PB RXD Boot loader programmed only Programming firmware; waiting for configuration Configuration loaded; no communication Yellow / Green blinking Off Yellow Off Green Red blinking Yellow Off Green Red blinking Off Off Communication Green Green Yellow lights during data exchange Green lights during data exchange Page 6 30.09.2009

Profibus Termination Example: Cable Type A Cable Type B Baud rate > 500 kbaud < 500 kbaud R1 390 Ohm 330 Ohm R2 220 Ohm 120 Ohm Cable type: Profibus cable A or B In this module, termination resistors are provided for cable type A. All resistors are at least 1/3 Watts. In a Profibus system, both end modules must be terminated. The Profibus termination resistance using spread resistors can be set in the first and last modules only. This is necessary to avoid transmission errors caused by reflections in the line. Pins 6 (VP) and 5 (D-GND) should not be connected to the Profibus cable, rather are reserved for the termination resistors. 30.09.2009 Page 7

Example Page 8 30.09.2009

Connectors Applicable connectors 1. Phoenix Contact SUBCON9 With a 90 angled cable outlet. 2. Siemens Profibusconnector 6ES7972-0BB10-0XA0 With Bus termination switches On the topside, an additional socket is provided, to which additional Profibus plugs can be connected. 3. ERNI Profibus connector Variants with and without termination. CAUTION: With use of the Profibus connectors mentioned above, the C-DIAS housing cover cannot be used/closed! Cable Profibus cable specifications The Profibus standard defines cable type A as follows: (see also http://www.profibus.com/support.html/ under FAQs.) Wellenwiderstand: 35 bis 165 Ohm bei Frequenzen von 3 bis 20 MHz Betriebskapazität: < 30 pf pro Meter. Adernquerschnitt: > 0,34 mm², entsprechend AWG 22. Kabeltyp: Twisted-pair Kabel. 1x2 oder 2x2 oder 1x4 Adern. Schleifenwiderstand: < 110 Ohm per km. Signaldämpfung: max. 9 db über die Gesamtlänge der Verbindung. Abschirmung: CU-Abschirmgeflecht oder CU-Abschirmgeflecht und CU- Abschirmfolie. Max. Bus Length: 200 m bei 1500 kbit/s, bis zu 1,2 km bei 93,75 kbit/s. Erweiterbar durch Repeater. Verwendbare Profibus-Kabel Zum Beispiel: Lapp Kabel: UNITRONIC BUS PA; PROFIBUS-PA für die Prozess-Automation - Für feste Verlegung Phoenix Contact PSM-CABLE-PROFIB/FC Profibus-Kabel Typ A für feste Verlegung bis 12 MBit/s nach EN 50 170, Typ A 30.09.2009 Page 9

Wiring Guidelines To ensure a good bus connection, several wiring guidelines must be followed: To ensure error-free operation, a careful wiring method must be followed. The 0 V connection of the supply voltage must be connected with the 0 V assembly point over the shortest route possible. The Profibus cable used must be designed for the data transfer rate The shielding must be connected over a large area and the shortest possible route. CAUTION: Fundamentally, the connectors/cables or wiring must meet the Profibus specifications! Page 10 30.09.2009