RCF-230CTD. Built-in or external sensor The controller has a built-in sensor. Alternatively, the input for an external PT1000-sensor can be used.

Similar documents
RCF-230CTD. Room controller for fan-coil applications with outputs for two thermal or one 3-position actuator or function for an electric heater

RCF-230CAD. Communicating room controller for fan-coil applications with two analogue V DC outputs

RCF-230CD. Communicating room thermostat for fan-coil applications with on/off outputs

RCF-230CAD. Room controller with communication for fancoil applications with two analogue V DC outputs

RC-CDTO. Pre-programmed room controller with display, communication and three-point control

Pre-programmed room controller with display and communication

Pre-programmed room controller with display and communication

WE TAKE BUILDING AUTOMATION PERSONALLY MANUAL RCF

Room controller STRA-17

STRA-17 Room controller. Installation and maintenance manual. Content

OP10. Pre-programmed, configurable controller for simple applications

Evolution TH. Pre-configured controller with display, clock and communication. Evolution. Applications. TH version. Sensors

EXOcompact. Third generation freely programmable controllers

Semi Flush-mount Room Temperature Controllers with LCD

AIAS. Technical description

Non-communicating room controllers

FCU-4 FAN COIL CONTROLLER

Field selectable application type and room module series, via dip-switches on controller

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

TAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta

Room Temperature Controllers

Room Temperature Controller

Semi flush-mounted room temperature controllers with LCD

Communicative controller for VAV systems

Room Temperature Controller

FCU-4 FAN COIL CONTROLLER

Non-communicating room controllers

UC102 basic version with display and knob UC102BL version with display, knob and backlight UC102DK version without knob and display

Semi flush-mounted room temperature controllers with LCD

MOD-RI Room Interface Modules with Modbus

TAC Xenta 121-FC Programmable Fan Coil Application

Temperature controller Ducted systems

RDF301 RDF CE1N3171en 02 Jun 2010 Building Technologies

Free Energy Band RCC30U Room Temperature Controller for Four-pipe Fan Coil Unit

KNX temperature control panel

Temperature Controller

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

ECL Comfort V a.c. and 24 V a.c.

FCU-MULTI Modbus Fan Coil Unit Controller

FANCOIL CONTROLLER UNIT TC17B01KNX. Product Handbook

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

Supplementary operating instructions for your air curtain system Controller TMC 500

Small distributed I/O module

7-day room temperature controller

TC-8900 Controller Units with PM-8900 Power Modules

EXOcompact. Freely programmable controller

Master room unit for RRV controllers

CONTENTS CONTROLLERS room controllers room units control units PRODUAL 3 CATALOGUE

O P T I G O R E A D Y - S T E A D Y - G O Optigo OP5U Manual Copyright AB Regin, Sweden, 2012

RXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13

NT10 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

TF243 Series Digital Thermostat Fan Coil Unit Control

MOD-IO9 Modbus Input / Output Modules, Wall Mounted

BACnet Product Overview

HLS34 Modbus FCU/VAV Controllers installation instructions

7-day room temperature controller

EC-PU4. Processor unit with 4 communication ports

TAC Xenta 121-HP Programmable Heat Pump Application

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

RXTP ROOM TEMPERATURE

Temperature Controller (Heat Pumps)

Heating Circuit Controller

RDF Series Room Temperature Controllers

Corrigo E. Version 3.0 (ventilation), 3.0 (heating), 1.1 (boiler). Controllers for heating, boiler and ventilation applications in buildings.

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

DEVIwet 230V room thermostats for hydronic floor heating

LLR-MOD Modbus Light Level and Occupancy Sensor

EYE 200: DDC single-room controller, ecos200

Weekday / weekend room temperature controller

RS-485 FClink Networking Room Thermostats with LCD for Fan Coil Units

Room thermostat with KNX communications For VAV heating and cooling systems

RXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications

RXTH DUAL ROOM SENSOR / SWITCH

Weekday / weekend room temperature controller

Extension module for lighting control

Room Temperature Controller with 7-Day Time Switch, LCD and opt. Remote Temperature Sensor

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

Electrical Actuators

Fan coil (FCU) application guide

RTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions

Electrical Actuators

BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

Specification Sheet For electronically commutated motors

R7426A TEMPERATURE CONTROLLER WITHOUT REAL-TIME CLOCK. MicroniK 200. Order Numbers

Room thermostats with KNX communications

Universal Modules. Synco 700. Extension modules for use with controls of the Synco 700 family. Use

Technical data sheet

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000

Datasheet. ECB-PTU Series. 1/14. BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

Heating Circuit Controller

XPSMC16Z safety controller XPS-MC - 24 V DC - 16 input - 30 LEDs signalling

Control systems. Efficient room control

RS-485 Modbus RTU Networking Room Thermostats with LCD for Fan Coil Units

ExactLogic BACnet Communicating Thermostat EXL01816 Sequence Datasheet

Room unit with PPS2 interface

CDR Room CO 2 and Temperature Sensor with Modbus

ED-T7. External touch display, 7 inch. Function. Installation The display can be mounted, for example, on the operation panel of the control cabinet.

Automation System TROVIS 5400 District Heating Controller TROVIS 5476

RS-485 Modbus RTU Networking FCU Thermostats with 0(2)-10 VDC Fan Output

Application Guide. Fan Coil (FCU) Application Guide. VTR8000 Series Room Controllers. Control Performance Energy savings Better building management

Transcription:

revision 01 2015 RCF230CTD Communicating room controller for fancoil applications with outputs for two thermal or one 3position actuator or function for an electric heater RCF230CTD is intended to control heating and/ or cooling in 2 or 4pipe installations. Setpoint and fan speed are set using the buttons on the front. RCF 230CTD offers communication via Modbus, ACnet or EXOline. RCF230CTD is a controller for controlling heating and/or cooling in a room. It is intended for control of thermal actuators or an actuator with 3position function (increasedecrease), and also has a function for threespeed fan control (for fancoil). The controller has supply voltage 230 V AC. It has triac outputs for 230 V AC heating/cooling and builtin 230 V AC fan relays, which means that a separate relay module is not required for the fan and actuators. For integration into a system, RCF230CTD has communication via RS485 (Modbus, ACnet or EXOline). The device can be configured using the application Regio tool, which can be downloaded from the Regin web site (www. regincontrols.com). Applications The controller is suitable in buildings where you want optimal comfort and reduced energy consumption, for example offices, schools, shopping centres, airports, hotels and hospitals etc. Simple installation The modular design with a separate bottom plate for wiring makes the controller easy to install and commission. The bottom plate can be put into place before the electronics are installed. Mounting is directly on the wall or on a wall socket. Control function The controller controls heating and/or cooling in a room. Control parameters like Pband and Itime can be set via the display, or alternatively via Regio tool. The setpoint can be changed using the ICREASE ( ) and DECREASE ( ) buttons on the front. See also the section Display information and handling on page 3. uiltin or external sensor The controller has a builtin sensor. Alternatively, the input for an external PT1000sensor can be used. Short facts about RCF230CTD Supply voltage 230 V AC uiltin relays for a 3speed fan, 230 V AC Input for occupancy detector or window contact Function for an electric heater Input for automatic changeover cooling/heating Tapproved as of software version 1.2100 (ACnet stack 3.0.4) Output function for thermal actuators This function is activated on delivery. When using thermal actuators, the controller works with timeproportional output, which gives continuous setting of the opening position for the valve. Actuators which can be used are RTAM230 or RTAOM230 from Regin together with a suitable valve. Using thermal actuators, the controller can control heating and cooling in sequence with one actuator for heating and one for cooling. Output function for 3position actuators This function can be configured to be used instead of the above factory setting via the display, or alternatively via Regio tool. When using an actuator with 3position function, RCF230CTD will control it using an increasedecrease signal, in order to achieve continuous opening of the valve that varies with the temperature requirement. For optimal function, the correct running time for the actuator should be set in the controller (factory setting = 120 s). An actuator with 3position function can only be used in 2pipe systems or when only controlling a cooling or a heating valve.

Communication protocols The room controller uses automatic detection and switching between Modbus and EXOline. ACnet, however, must be set manually by using the display or Regio tool. Function for control of an electric heater RCF230CTD has a function for pulse/pause control of an electric heater, similar to control of a thermal actuator. When using an electric heater, the fan will continute to run for 2 minutes after the heater has been switched off in order to cool down the heater. When using an electric heater, an external unit (e.g. PUSERADD or a solid state relay) is to be connected between RCF230CTD and the battery. ote: RCF230CTD does not indicate fan breakdown or overheating of the heating coil. Therefore, all connections must be made externally. An overheating protection or similar can be used to disconnect the supply voltage. 2 and 4pipe installations In 2pipe installations, the same pipe system is used for heating and cooling. Chilled water is distributed in the system during summer and heated water during winter When RCF230CTD is configured for a 2pipe system, output DO4 is used for control of heating or cooling (depending on the season (fluid temperature)) via an actuator, a valve or similar (changeover function). When using an actuator with 3position function, the actuator is connected to DO4 and DO5 for increasedecrease function. WITER SUMMER In 4pipe installations, there are two separate pipe systems for heating and cooling with separate valves. The controller uses two outputs for control of heating and cooling in sequence with two thermal actuators. Automatic changeover cooling/heating (socalled changeover function) RCF230CTD has an input for changeover which is used when the controller is configured for 2pipe installations. It sets output DO4 to operate with heating or cooling function depending on the fluid temperature (season). The changeover input can be connected to a potentialfree relay contact or a PT1000sensor. The input function for the relay contact can be set to normally open (O) or normally closed (C). If the changeover input is not used, we recommend that it is left disconnected and set to O (factory setting). When using a sensor, it must be mounted so that it can measure the temperature on the supply pipe to the coil. To ensure satisfactory function, the system must also have continuous primary circuit circulation. Using a sensor, the output function is set to heating when the fluid temperature exceeds 28 and to cooling when the temperature falls below 16. At heating function HEAT is shown in the display and at cooling function COO is shown. When using an electric heater and the changeover function is set to heating, the sequence of operation for RCF230CTD will be heating/heating and DO5 will be activated first. If a changeover sensor is not connected, the sequence will be heating/heating. If cooling is to be used in the sequence, parameter 2 (changeover mode) must be changed manually. Occupancy detection for saving energy y connecting an occupancy detector or a keycard switch (in hotels) to a digital input, it is possible to change between Comfort and Economy mode. This way you can control the temperature according to requirement, which saves energy and keeps the temperature at a comfortable level. Using occupancy detection, it is possible to delay activation and/or inactivation of Comfort mode, to avoid switching mode if a person temporarily enters or leaves the room. Alternatively, a window contact can be connected to the input. This sets the controller to Off if a window is open with the purpose of minimising energy consumption. Operating modes There are four different operating modes, Comfort, Economy (Standby), Off and Window. Switchover between these modes is performed locally or through the master system. Comfort: is shown in the display and the room is in use. The temperature is held at the comfort level with a neutral zone (ZC) between activation of heating and cooling (factory setting for ZC = 2 K ()). Economy (Standby): Standby is shown in display. The room is in energy save mode and is not used at the moment. This can for example be during nights, weekends, evenings etc. or during daytime when there is no one in the room. The controller is prepared to change operating mode to Comfort if someone enters the room. The heating and cooling setpoints are freely adjustable. Factory settings: heating=15, cooling=30. 2

Off: Off is shown in the display and the backlight is switched off. The controller does not heat or cool and the fan stops (unless mould protection has been selected or the cooldown function for the electric heater is running, in which case the fan will still run). Off mode is selected by pressing the On/Off button. Window: is shown in the display, the controller is off and the fan stops (unless mould protection has been selected or the cooldown function for the electric heater is running, in which case the fan will still run). Fan speed control The current fan speed is shown in the display and can be set manually to owàmediumàhighàauto by pressing the fan button. In Auto mode, the fan speed is controlled by the controller output. When there is no heating or cooling demand in the Auto position, the fan will run at the lowest speed. This can be changed in parameter 31 so that the fan stops when there is no heating or cooling demand. The fan is inactive in the Off and Window modes. However, it will continue to run if mould protection has been configured. If the fan has been configured not to be affected by the heating or cooling demand, AUTO will not be shown when pressing the fan button. Mould protection When this function has been configured, the fan will continually run (at its lowest speed, if not set otherwise) and circulate air in the room so as to minimise the risk of mould growth in the fancoil unit. The function is deactivated on delivery. Automatic exercise of valves The controller has a function for exercising the valves, even during periods when they are not being used, to ensure proper function. Every 23 hours (factory setting), the output is overridden to close for a moment in order to open and close the valves. The exercise interval can be set individually for heating and cooling. The exercise function can also be inactivated if desired. Display information and handling The display has the following indications: Setpoint Indoor / outdoor temp. Off mode (only the temperature is shown) Auto/Man indication for the fan Fan Current fan speed (ow, Medium, High) Changeable value Occupancy indication Current room temperature or setpoint in to one decimal point Open window The display is handled using the buttons on the controller: On/Off button ICREASE setpoint DECREASE setpoint Fan speed On/Off button y pressing the On/Off button, RCF230CTD will switch between Off mode and Comfort/Economy mode. Setpoint buttons The ICREASE and DECREASE buttons are used for changing the setpoint value. The basic setpoint can be changed in parameter 64 (factory setting=22). Fan button y pressing the fan button, you set the fan speed to ow, Medium, High and Auto. locking In order to prevent access by unauthorized individuals, it is possible to block buttons, the configuration menu and manual fan control. Configuration The factory settings can be changed in the display using the buttons on the controller, or alternatively via Regio tool. The parameter values are changed with the ICREASE and DECREASE buttons and changes are confirmed with the On/Off button. The parameter list can be found in the instruction for RCF230CTD. Display configuration What is shown in the display can be configured via the parameter list. There are four alternatives: 1. The actual value is shown, or, when the setpoint has been changed via the ICREASE and DECREASE buttons, the setpoint value is shown in the display (together with the setpoint (thermometer) symbol). 2. The actual value is shown, or, when the setpoint has been changed via the ICREASE and DECREASE buttons, the setpoint adjustment value is shown in the display (together with the setpoint (thermometer) symbol). 3. The setpoint value is shown (factory setting). 4. The setpoint adjustment is shown. STADY: Economy mode indication SERVICE: Setting parameters COO/HEAT: Shows if the unit controls according to the heating or cooling setpoint 3

Control principles Control principle at cooling function, 2pipe installations When the controller is set to cooling, the output starts to increase when the temperature exceeds the setpoint value. Control principle at 4pipe installations At Comfort mode, neither heating nor cooling is used when the temperature is in the neutral zone, in order to minimise the energy consumption. The heating output is activated when the temperature falls below the set value for the neutral zone. The cooling output is activated when the temperature exceeds the set value for the neutral zone. The neutral zone is divided into two equal parts with one part below and one part above the setpoint. See the figure below. The factory setting for ZC is 2 K. Control principle at heating function, 2pipe installations When the controller is set to heating, the output starts to increase when the temperature falls below the setpoint value. The above schematic drawings of the control principle show the corresponding requirement of the controller function. This requirement is recalculated by the controller to a value for the actuator output, depending on the selected output function. 4

Technical data Supply voltage 230 V AC ±10 %, 50/60 Hz Power consumption 3 W, class II construction Ambient temperature 0...50 Storage temperature 20...70 Ambient humidity Max. 90 % RH Protection class IP20 Communication RS485 (Modbus or EXOline) using automatic detection/switching, or ACnet Modbus 8 bits, 1 or 2 stop bits. Odd, even (FI) or no parity. ACnet MS/TP slave and master Communication speed 9600, 19200, 38400 bps (EXOline, Modbus and ACnet) or 76800 bps (ACnet only) Pollution degree 2 Overvoltage category 3 Display CD with backlight uiltin temperature sensor TC type, measuring range 0...50 Terminal blocks ift type for maximum cable area 2.1 mm 2 Material, casing Polycarbonate, PC Colour Cover Polar white RA9010 ottom plate ight gray Mounting Indoor, wall mounting, fits on a standard wall socket Dimensions (HxWxD) 120 x 102 x 29 mm Weight 0.18 kg ow Voltage Directive (VD) standards / EMC emissions & immunity standards: This product conforms to the EMC and VD requirements in the European harmonised standards E 607301:2000 and E 6073029:2002 and carries the CE mark. RoHS: This product conforms to the Directive 2011/65/EU of the European Parliament and of the Council. Inputs External sensor, AI1 PT1000sensor. Suitable sensors are TGR5/PT1000, TGUH/PT1000 and TGA1/PT1000 from Regin. The setpoint range is 5 35. Changeover, UI1 Potentialfree contact or PT1000sensor. A suitable sensor is TGA1/PT1000 from Regin. Occupancy/window contact, DI1 Potentialfree contact. A suitable occupancy detector is IR24P from Regin. Outputs Fan control, DO1, 2, 3 Actuator, DO4, DO5 Communication Modbus Communication speed 3 outputs for speed I, II and III, 230 V AC, max. 3 A fancoil 2 outputs, 230 V AC, 300 ma max. (20 A max. 20 ms) RS485 (Modbus or EXOline) with automatic detection/switchover 8 bits, 1 or 2 stop bits. Odd, even (FS) or no parity. 9600 bps (not changeable); communication variables are in the manual for RCF, available via Regin s website (www.regincontrols.com). Settings Factory setting (FS) asic setpoint 5...50 22 Internal sensor calibration 10...10 K 0 K External sensor calibration 10...10 K 0 K Pband 1...300 10 Itime 0...1000 s 300 s ZC, neutral zone at Comfort 0.1...10 K 2 K Installation type 2 or 4pipe or electric heating 2pipe Input DI1 ormally open (O) or normally closed (C) O Input UI1 O or C, when used as a relay contact input O Output DO4 O or C C Output DO5 O or C C Valve exercise Individually settable for heating and cooling outputs 23 hours interval 5

Wiring 10 230 V AC ine Supply voltage 11 ot connected 12 230 V AC eutral Power supply (internally connected to terminal 13) 13 Fancoil common / 230 V AC eutral Common fancoil connector (internally connected to terminal 12) 20 DO1 Fancoil output 1 for fan control Relay, 230 V AC*, 3 A 21 DO2 Fancoil output 2 for fan control Relay, 230 V AC*, 3 A 22 DO3 Fancoil output 3 for fan control Relay, 230 V AC*, 3 A 30 ot connected 31 DO4 Digital output 4 for heating/cooling or opening with 3point actuator Digital output. 230 V AC, max. 300 ma. Max. 2 A during 20 ms. 32 CDO45 Common DO4 & 5 Common connection for digital outputs 4 and 5 33 DO5 Digital output 5 for cooling (or heating when using an electric heater) or closing with 3point actuator Digital output. 230 V AC, max. 300 ma. Max. 2 A during 20 ms. 40 DI Digital input Floating (potentialfree) window contact or occupancy contact. Configurable for O/C. 41 Agnd Analogue ground 42 AI Analogue input External PT1000 instead of the internal TC 43 UI Universal input Changeover input. Potentialfree switch (configurable for O/C) or PT1000. 44 Agnd Analogue ground 50 Agnd Analogue ground 5152 ot connected 53 A RS485 communication A 54 RS485 communication *The sum of the current through DO1DO3 is protected by a fuse Automatic changeover cooling/heating Wiring diagram for thermal actuator Wiring diagram for 3point actuator 6

230 V AC 230 V AC 40 DI 41 AGnd 42 AI 43 UI 44 AGnd 10 11 12 13 40 DI 41 AGnd 42 AI 43 UI 44 AGnd 10 11 12 13 50 51 DO1 DO2 DO3 20 21 22 I II III M 50 51 DO1 DO2 DO3 20 21 22 I II III M 52 52 53 30 53 30 54 DO4 CDO45 31 32 EECTRIC HEATER 54 DO4 CDO45 31 32 PUSERADD DO5 33 DO5 33 1 2 U 3 4 U I I EECTRIC HEATER Wiring diagram for electric heater Wiring diagram with PUSERADD for electric heater Dimensions 120 mm 29 mm 102 mm Product documentation Document Instruction RCF230CTD Manual RCF Type Instruction for RCF230CTD Manual for the RCF range The documents can be downloaded from www.regincontrols.com. Head Office Sweden Phone: 46 31 720 02 00 Web: www.regincontrols.com Mail: info@regin.se