System Controls Suggested Specification

Similar documents
MANUAL INSTALLATION + SERVICE. Price Intelligent Controller. PIC Series. v400 Issue Date: 12/18/ Price Industries Limited. All rights reserved.

MANUAL INSTALLATION. Price Rooftop Unit Controller. PRTU Series. v200 Issue Date: 05/11/ Price Industries Limited. All rights reserved.

Underfloor Controllers

FUME HOOD CONTROLLER (FHC)

BACnet Flow Controller for Fan Filter Units

Smart Equipment Controls (SEC)

Commercial Controls. Advanced control for saving time and money

ExactLogic BACnet Communicating Zone Damper EXL01710 Sequence Datasheet

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

SE7600E Series Application Guide

ExactLogic BACnet Communicating Pressure Dependent VAV Damper Control with Heat EXL01820 Sequence Datasheet

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification

SE7600E Series Application Guide

M1000 INTELLIGENT ZONE CONTROL SYSTEM

BACnet Product Overview

Siemens BACnet Programmable TEC Constant Volume

Siemens BACnet Programmable TEC Unit Conditioner Controller

FCU-4 FAN COIL CONTROLLER

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

Siemens BACnet VAV Actuator

The Simply Smart Way to Optimize Building Control and Performance

SEZ7000 Series. Wireless Commercial Zoning System

Tracer Controls. Tracer ZN517 Unitary Controller BAS-PRC012-EN

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control

BACnet Terminal Box (VAV) Controller

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller

VZ7000 Series. BACnet Commercial Zoning System

Product Catalog. Tracer Controls Tracer ZN517 Unitary Control BAS-PRC012-EN. August 2010

Siemens BACnet Programmable TEC VAV with Series Fan and 3-Stage Electric Heat Controller

UPDATING CONTROLLERS USING PRISM 2 Updating the VCB-X / VCC-X Controller

FCU-4 FAN COIL CONTROLLER

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

clarity 3 Programmable Controller

SEZ7656E1045B. Installation Guide for BACnet MS/TP RTU Terminal with IAQ Control CONTENTS

MANUAL INSTALLATION. Prodigy. Prodigy Smart Diffusers. v200 Issue Date: 11/01/ Price Industries Limited. All rights reserved.

Millennium Simplicity Elite Parameter Points and Quirks

Field selectable application type and room module series, via dip-switches on controller

ExactLogic BACnet Communicating Thermostat EXL01716 Sequence Datasheet Duel Deck VAV

ECLYPSE Series Connected IP and Wi-Fi Product Series and Accessories

Installation and Operation. Tracer MP501 Controller CNT-SVX08B-EN

UPDATING CONTROLLERS USING PRISM 2 Updating the VCC-X Controller

Networkable Dual Duct VAV Controller Specification and Installation Instructions

MANUAL INSTALLATION ADV. Advantage Digital VAV Diffuser. version 1 April 1, Acutherm. All rights reserved.

Siemens BACnet Programmable TEC Unit Vent Controller

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules

SEZ7656R1045B / SEZ7656H1045B

VT7200 Series 24 Vac Low Voltage Zoning Thermostats For Commercial HVAC Applications

Key Features and Benefits

Installation and Operation Instructions

CONTENTS. Installation Guide. PIR Ready VT7200 Series 24 VAC Low Voltage Zoning Terminal Equipment Controller

SEZ7260X5x45B Installation Guide for BACnet MS/TP Zone Controller

ExactLogic BACnet Communicating Thermostat EXL01816 Sequence Datasheet

TC-9102 Terminal Controller

Room Controllers VTR8300 Line Voltage Fan Coil Controller with VC3000 Relay Pack Technical Cut Sheet

Siemens BACnet Programmable TEC Unit Vent Controller for Smoke Control

Daikin HVAC Controls Guide Specification

Tstat8. Bacnet Thermostat

TEC Zoning Control System for Stand-Alone and BACnet MS/TP Networked Applications

ECB-VAVS. Features and Benefits. Applications Cooling Only VAV Boxes Cooling with Reheat VAV Boxes Room Pressurization.

Buy American Facility Explorer Products Facility Explorer Product Management Authorized Building Controls Specialists (ABCS)

SECTION REMOTE CONTROL PANELS

Daikin HVAC Controls Guide Specification

Features and Benefits of XeteX Controls. Other Unit Control Functions. Energy Recovery Functions

FXVMA Variable Air Volume (VAV) Box Controller

Viconics BACnet Zoning System Application Guide VZ7260X5x00B and VZ7656X5000B Controllers

DataNab it8: Intelligent Communicating Thermostat

Introduction. To use Carrier wireless sensors, you must have: A i-vu v6.5 or later system v6-00 or later drivers

SECTION GRAPHICS

MLM Integration with BMS Network Protocols

Product Catalog. Tracer Controller MP501 BAS-PRC008-EN. May 2012

Andover ContinuumTM b3865/866 VAV Controllers with Built-in Actuator

Prodigy Control System Premium Rooftop Unit Control

Viconics Zoning System Application Guide VZ7200F5x00W and VZ7656B1000W Thermostats

Webselect VAV Selection/Pricing Quick Start User Guide for Manufacturer Rep Users

NB-VAV Family Protocol Implementation Conformance Statement (PICS)

BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

NB-ASC Family Protocol Implementation Conformance Statement (PICS)

BACnet PTEC Controller Constant Volume - Cooling Only, Application Application Note Building Technologies

VT8600 Series User Interface Guide Rooftop Unit, Heat Pump and Indoor Air Quality Controller

clarity 3 VAV Programmable Controller

Datasheet. ECB-PTU Series. 1/14. BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

BACnet FF Configuration Wizard Guide

L Connection Network Control System For Energence Rooftop Units

SE8600 Series BACnet Integration Rooftop Unit and Indoor Air Quality Controller

PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP

WSHP-IOP-2 May Installation, Operation, and Programming. Tracer ZN510 Controller

BACnet MS/TP Interface User s Guide

Description. descriptors, makes set-up and monitoring very user friendly.

HARDWARE GUIDE. VAV Zone Controller C1000 Series. Specifications and Operational Guide

SER8300 Room Controller

ETM-2050/ETM-2051 Service Manual

CUYAMACA COLLEGE SCIENCE AND MATHEMATICS CENTER HVAC UPGRADE BID B SUMMARY OF THE WORK. Project Overview

75F Smart VAV with Reheat

Installation and Maintenance Manual IM

Tracer Controls. Tracer MP501 Controller BAS-PRC008-EN. January 2005

BAC-9000 Series VAV Controller Installation Guide

INSTALLATION INSTRUCTIONS

VZ7260X5X00W BACnet Zone Room Controller. Installation Guide. April 2017

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

VTR8300 User Interface Guide VTR8300 Room Controller Series

Transcription:

1. Description A. Rooftop Unit Controller The Rooftop Unit Controller shall come equipped with a proportional-integral (PI) controller for accurate temperature control. The rooftop unit controller shall feature individual LEDs to show status of power, inputs, outputs, coded such that GREEN LED = ACTIVE, RED LED = FAULT, and YELLOW LED = NETWORK OVERRIDE. Each output shall be protected by a thermal fuse. The Rooftop Unit Controller shall come complete with a backlit LCD thermostat having password protected menus that allow full configuration and setup of the controller in the field. The controller assembly shall come with BACnet MS/TP connectivity. The Rooftop Unit Controller shall function in either stand-alone mode (not networked to any zone controllers) or networked mode to poll zone controllers (Price Intelligent Controller PIC, Prodigy Smart Diffuser) via BACnet MS/TP. Network polling mode to include option of using 3 preset strategies: average polling (weighting each zone equally), non-majority polling (giving specified zones more weight ie board rooms or any temperature sensitive spaces), or optimal comfort mode (on a 1% call for cooling, cooling is enabled). The rooftop unit Controller shall be digital and utilize a microcontroller with EEPROM for storing setup and calibration variables. Indicator LED s shall be on all outputs to indicate current status. All network connections shall be pluggable terminal blocks and/or RJ-45 jacks for error-proof field connections. Rooftop Unit Controller shall poll each and every zone controller over BACnet reading its zone PI to calculate rooftop unit PI and flip the rooftop into heating, cooling or neutral mode. In case of network communication loss of less than 50% of network devices, Rooftop Unit Controller shall poll the remaining zones left on the network. If the Rooftop Unit Controller loses communication with more than 50% of the network devices, the Rooftop Unit Controller shall control based on the setpoint and zone PI local to the Rooftop Unit Controller s own thermostat, while still maintaining all other settings such as scheduling, temperature limits etc. Rooftop unit controllers calculating rooftop PI based on a sample measured from various single function space sensors with the sole purpose of reporting back to the rooftop unit controller shall not be accepted. The Rooftop Controller shall consist of the following but shall not be limited to: On board Real Time Clock and Calendar for scheduling Super Capacitor backup keeps time clock running during power failures. Battery backup shall not be accepted. Discharge Air Temperature (D.A.T.) monitoring prevents excessive temperature swings that can trip safeties and waste energy Return Air Temperature (R.A.T.) monitoring prevents freeze up of coil(s) or overheating that can trip safeties and waste energy [2] Binary Inputs (contact closure) [6] Analog 10 k Thermistor inputs [6] Analog (0-10 VDC) inputs [10] binary outputs rated at 0.5 amps each and protected with a thermal fuse (RED status LED on trip) with automatic recovery when fault is corrected Switch for selecting binary output type (Internal 24 VAC HOT, COMMON or external power source) [4] analog outputs (0-10 VDC) fully configurable for Fan, Heating, Cooling and spare Multi-level surge protection with user replaceable MINI type fuse Pluggable terminal blocks to simplify wiring BACnet MS/TP Client/Server stack for polling zones for data LED s for BACnet wiring fault, BACnet network fault, and MS/TP termination 1

B. Thermostat The LCD thermostat with Motion Sensor shall support [1] occupied/unoccupied schedule per day. Thermostat communication to rooftop unit controller board shall be accomplished with 1 plenum rated CAT5 cable with RJ45 connections. Thermostat shall include onscreen menus and have the following features: Backlit 14x2 LCD thermostat with true character display Motion Sensor on thermostat allows automatic occupancy mode with adjustable timeout feature Password protected menu Easy to read MENU for system setup Local thermistor with +/- 1 accuracy and room temperature adjustable offset Service port for use with Price LINKER software accessible without removing thermostat from wall Included RJ45 plenum rated cable for fast, error free hookup Setup Wizard walk through setup of PRTU when first powered up The configurable LCD + Key Pad combination will allow for the following on screen functions/modes: a) Customer Mode Setpoint adjustment (only if Rooftop Unit Controller is operating in standalone PI) Date and time Current PI (whether standalone or networked), current occupancy status (occupied, or unoccupied) b) Info Mode for Networked Controllers (display only no adjustments) MAC address Network Health (communication status) # of Zones up % of zones polled heat % of zones polled cool % of zones polled neutral Pending mode (heat, cool, or neutral Occupancy status c) Service Mode (password protected) Strategy Setpoint Inputs Outputs BACnet settings Stat Setup Diagnostic (BACnet) Polling Time/Date set Schedule set Operation Setup Wizard 2

C. Return Air Temperature and Discharge Air Temperature Probes The rooftop unit controller shall be shipped complete with Return Air Temperature (RAT) and Discharge Air Temperature (DAT) probes to ensure that rooftop does not overheat or overcool air past configurable heating and cooling limits by disabling stages of heat or cooling as required. These safety features are designed to prevent icing of coils and prevent high temperature limit tripping of HVAC equipment. Rooftop units controllers without DAT and RAT probes with integrated safety programming as mentioned above shall not be accepted. D. Optional Web Server package The Web Server shall allow a user to be able to log in through the internet into the building s HVAC network and monitor/override certain values pertaining to all zone controllers and rooftop units. The login shall be password protected and be routed through the building s local area network. In addition to all aforementioned equipment, the optional Web Server Package shall include: System Web Server IP System Router BACnet MS/TP Router The Web Server Package shall allow remote access to building HVAC controls and conditions and allows the user to make adjustments to any writable points on any networked controller. Web Server shall come complete with preloaded graphics for every type of zone controller, as well as the rooftop unit. Preloaded graphics for each zone controller shall include but not be limited to: Occupancy Status Supply Air Temperature Airflow (Pressure Independent Controllers Only) Airflow Target (Pressure Independent Controllers Only) Room Setpoint Room Temperature Damper Position Damper Target (Pressure Dependent Models Only) Room Setpoint Override Room Load PI Preloaded graphics for the rooftop unit controller shall include but not be limited to: Occupancy Status Temperature Local to the Rooftop Controller Thermostat Rooftop Return Air Temperature Rooftop Discharge Air Temperature Stages of Heat/Cool Energized Rooftop Status (Heat/Cool/Neutral) Rooftop Control Polling Strategy Number of Zones Number of Zones Up Polled Cooling Demand % Polled Heating Demand % Polled Deadband Demand % Network Status (active, or down) 3

Webserver shall also be able to support custom graphics such as building floor plans for quickly being able to locate zone conditions/points for a given space. Web Additional Package (Optional): The standard package shall include an additional BACnet router in order to connect multiple rooftop controllers to the system Web Server: BACnet MS/TP Router IP switch (for netowrks with more than 3 rooftop controllers/bacnet routers) Key Features: Access via any web browser with free ADOBE FLASH plug-in installed No additional software or USB keys (licensing) required BACnet IP support High resolution graphics Supports multiple users with individual access level control 2. Manufacturers A. Price Industries or approved equal 3. Electrical A. Rooftop unit controller and optional web server package shall run on 24 VAC power and shall get power from the rooftop unit terminal block. 4. Interfacing to EMS/BMS A. The VAV Zone Controller shall interface with the building management system (BMS) to allow remote monitoring of room parameters or permit settings adjustments over the building network. B. BMS shall use BACnet MS/TP network protocol to view points or status of room space. The use of BACnet protocol shall be native to the device and shall not require the use of an external gateway. C. Thermostat shall include ability to change MAC address, device instance and baud rates (9600, 19200, 38400, 76800) for proper interfacing to BACnet network. D. Device shall support on board network termination for the MS/TP network. E. The VAV Zone Controller shall be BTL listed. F. Manufacturer shall be a member of BACnet International. G. BACnet points shall include Device Object, Analog Input (AI), Analog Output (AO), Binary Input (BI), Binary Output (BO), Multi-state (MSV). All temperature set points and VAV airflows shall be adjustable from the BACnet network. 5. Factory supplied documentation A. Manufacturer shall provide documentation for each device to address typical wiring, sequence of operation, physical dimensions of components and installation procedures and requirements. 4

6. Installation A. Mechanical contractor, controls contractor, or factory authorized commissioning contractor shall install & wire the components of the rooftop unit Controller. This includes the Thermostat, rooftop unit controller, DAT and RAT probes, optional web server and associated routers, and all network wires and zone controllers. B. Rooftop unit controller and optional webserver package to ship with length of DIN rail for easy wall mounting and removal/reinstallation of devices should it be necessary to relocate etc. C. All BACnet networking of zone controllers to Rooftop Unit Controller shall be completed using factory shipped plenum rated CAT 5 cables with RJ45 ends to ensure uniform polarity and network coms throughout network, and to ensure error-proof installation. D. Cable/wire Requirements Factory supplied 35 plenum rated RJ-45 Cat 5 cable for connecting thermostat to the rooftop unit Controller. Factory supplied 35 plenum rated RJ-45 Cat 5 cable for networking to Zone Controllers (if networked cables included with zone controllers). All other cables/wires to be provided by installing contractor. 7. Start-up/commissioning A. Start-up shall include verifying proper installation, testing & airflow control, setting all parameters & set points, Configuring and verifying network communication (if applicable). B. The TAB (Test and Balance) contractor shall be responsible for final verification of airflow measurement. 8. Warranty A. Warranty shall begin upon the date of shipment and continue for a period of 18 months. The warranty shall cover all products from manufacturer defect and include any replacement parts only during the coverage period. The manufacturer shall not include the cost of labor to replace or recalibrate, if necessary, any components found to be defective. This warranty does not cover any product failure which results from, either directly or indirectly, any damage which occurs to the device by improper installation or from failure to comply with the preventative maintenance required per the manufacturers' instructions or by codes set by local or facility authorities. Extended warranty shall be available at additional cost from manufacturer. 9. Closeout activities A. Manufacturer or Manufacturer s Representative shall provide a minimum of four hours of owner training to facilities personnel or other parties as required. 5