Issued to: SIEMENS AG LOW VOLTAGE SIEMENSSTRASSE 10 93055 REGENSBURG GERMANY This is to certify that representative samples of CIRCUIT BREAKERS, MOLDED CASE AND CIRCUIT- BREAKER ENCLOSURES See Addendum Page Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate. Standard(s) for Safety: Additional Information: UL 489 and CSA C22.2 No.5, Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures See the UL Online Certifications Directory at www.ul.com/database for additional information Only those products bearing the UL Certification Mark should be considered as being covered by UL's Certification and Follow-Up Service. Look for the UL Certification Mark on the product. Any information and documentation involving UL Mark services are provided on behalf of (UL) or any authorized licensee of UL. For questions, please Page 1 of 8
This is to certify that representative samples of the product as specified on this certificate were tested according to the current UL requirements. Models: USL / CNL 3VA Standard Circuit Breaker Series Twopole and Threepole devices. Twopole Types MFAS, HFAS, CFAS Catalog Numbers (MLFB) 3VA52, followed by 1 or 2, followed by 0, 1, 2, 5 or 7, followed by -5EC61-, -6EC61-, -7EC61-, -5ED61-, -6ED61- or - 7ED61-, followed by 0 or 1, followed by A, B, C, D, H, J, K or L, followed by A, B, C, D, E, F, G, H, J, K, L or M, followed by 0 Threepole Types MFAS, HFAS, CFAS Catalog Numbers (MLFB) 3VA52, followed by 1 or 2, followed by 0, 1, 2, 5 or 7, followed by -5EC31-, -6EC31-, -7EC31-, - 5ED31-, -6ED31- or -7ED31-, followed by 0 or 1, followed by A, B, C, D, H, J, K or L, followed by A, B, C, D, E, F, G, H, J, K, L or M, followed by 0 Nomenclature Breakdown 3VA5 2 10 4 ED 3 1 0 A A 0 I II III IV V VI VII VIII IX X XI I II Series Designation Always 3VA5 - Frame Size 2 250A III - Rated Current 10-100A 11-110A 12-125A 15-150A 17-175A 20-200A 22-225A 25-250A IV - Short Circuit Level 5 - MFAS 6 HFAS 7 - CFAS Any information and documentation involving UL Mark services are provided on behalf of (UL) or any authorized licensee of UL. For questions, please Page 2 of 8
Nomenclature Breakdown (Cont.) V VI - Trip Unit ED - Type FTFM EC - Type FTAM - Number of poles 3 Three Pole 6 Two Pole VII - Connector 1 No connectors provide for line and load side 2 Nut keeper kit for line and load side 3 No connectors for line side and nut keeper kit for load side 4 - No connectors for line side and Aluminum wire connector for load side 5 - Aluminum wire connector for line side and no connector for load side 6 - Aluminum wire connector for line and load side VIII - Version 0 - Standard Version 1 - Naval Version IX - Factory Installed Accessories 1 A - Without Auxiliary Trip B - Undervoltage Release (UVR) 24 Vdc C - Undervoltage Release (UVR) 120 127 Vac D - Undervoltage Release (UVR) 208 230 Vac H - Shunt Trip Left (STL) 12-30Vdc, 24Vac J - Shunt Trip Left (STL) 110-127Vdc, 110-127Vac K - Shunt Trip Left (STL) 220-250Vdc, 208-277Vac L - Universal Release (UNI) 24Vdc Any information and documentation involving UL Mark services are provided on behalf of (UL) or any authorized licensee of UL. For questions, please Page 3 of 8
Nomenclature Breakdown (Cont.) X - Factory Installed Accessories 2 XI - Always 0 A - Without Auxiliary Switch B - 2 Standard Switch Type HP C - 2 Standard Switch Type HQ D 3 Standard Switch Type HQ E 4 Standard Switch Type HQ F 1 Standard Switch + 1 Trip Alarm Type HQ G - 1 Standard Switch + 1 Trip Alarm Type HP H - 2 Standard Switch + 1 Trip Alarm Type HQ J - 2 Standard Switch + 1 Trip Alarm Type HP K - 1 Standard Switch + 1 Trip Alarm + 1 Electrical Alarm Type HQ L - 2 Standard Switch + 1 Trip Alarm + 1 Electrical Alarm Type HQ M 2 Standard Switch + 1 Short Circuit Alarm Type HQ Any information and documentation involving UL Mark services are provided on behalf of (UL) or any authorized licensee of UL. For questions, please Page 4 of 8
RATINGS: The current ratings are 100A, 110A, 125A, 150A, 175A, 200A, 225A, 250A. The maximum ac voltage rating for all breakers is 600Vac, 480Vac, 240Vac The maximum dc voltage rating for three pole breakers is 600Vdc, for two pole breakers 500Vdc. Short circuit interrupting ratings: Max. Voltage Number Marked Rating (RMS Amps) of poles Version Version Version CFAS MFAS HFAS 240 Vac 3 85 ka 100 ka 200 ka 480 Vac 3 35 ka 65 ka 100 ka 600 Vac 3 18 ka 25 ka 35 ka 500 Vdc 2 3 50 ka 85 ka 100 ka poles in series 600 Vdc 3poles in series 3 50 ka 85 ka 100 ka Circuit Breaker ending with 1AA0 may be marked with the following 1) The word "NAVAL" at any convenient location, except the rear side of the breaker. 2) "50 C" Any information and documentation involving UL Mark services are provided on behalf of (UL) or any authorized licensee of UL. For questions, please Page 5 of 8
Wire Connectors: These circuit breakers are for use with the following UL Listed or Recognized wire connectors. These wire connectors are also marked with Siemens numbers which are used as the reference marking on the circuit breaker. Type TA1.4 TC1.4 TA2.2 TA2.3 *TA2.6 TS1.2 Siemens Part No. Wire Range [AWG] kcmil] Torque [in-lbs] 3VA9233-0JG12 6-2 140 3VA9234-0JG12 3VA9233-0JB12 3VA9234-0JB12 3VA9233-0JK12 1-350 275 3VA9234-0JK12 3VA9233-0JD12 3VA9234-0JD12 3VA9233-0JC13 2-350 275 3VA9234-0JC13 3VA9233-0JJ13 3VA9234-0JJ13 3VA9233-0JC22 4-300 275 3VA9234-0JC22 3VA9233-0JJ22 3VA9234-0JJ22 3VA9233-0JF60 3VA9234-0JF60 2-6 62 8-14 55 3VA9233-0JA11 10-4 105 3VA9234-0JA11 3-3/0 140 3VA9143-0JA12 3VA9144-0JA12 Any information and documentation involving UL Mark services are provided on behalf of (UL) or any authorized licensee of UL. For questions, please Page 6 of 8
Wire Connectors (Cont.): TS1.4 3VA9233-0JA12 3VA9234-0JA12 3VA9243-0JA11 3VA9244-0JA11 4-1 70 1/0-350 140 Busbar- B1.3.1 ST/HE250 Rear stud ST250 UL Wiring terminals 3VA9273-0QB00 3VA9274-0QB00 3VA9233-0QF00 3VA9231-0QF20 3VA9231-0QF10 3VA9233-0QE00 3VA9231-0QE20 3VA9231-0QE10 3VA9270-0WC00 14-18 2Nm Enclosure: These breakers were tested in a steel enclosure measuring 785mm by 232mm by 129mm. Accessories: These circuit breakers may be used with this manufacturer s Listed circuit breaker accessories described in file E354102. Any information and documentation involving UL Mark services are provided on behalf of (UL) or any authorized licensee of UL. For questions, please Page 7 of 8
Adjustable Instantaneous Trip: These thermal magnetic constructions have adjustable instantaneous trip elements with adjustments as follows: Continuous Current Rating [A] Magnetic Trip Range [A](RMS) 100 500 1000 110 550 1100 125 625 1250 150 750-1500 175 875-1750 200 1000-2000 225 1125-2250 250 1250-2500 Any information and documentation involving UL Mark services are provided on behalf of (UL) or any authorized licensee of UL. For questions, please Page 8 of 8