VARAN Splitter PROFINET VSP 044

Similar documents
VARAN Splitter Module VSV 043

VARAN Splitter Module VSV 041

VARAN Splitter PROFINET VSP 042

VARAN Bus Coupler Module VBC 021 For connecting two VARAN bus systems

VARAN Manager PCI Insert module PCV 521 Versatile Automation Random Access Network

DIAS Interface Module VARAN DIV 511

VARAN Digital Combined Module VDM 086

Protected VARAN Digital Mixed Module PVDM 086

C-DIAS VARAN Control Module CIV x VARAN-In 1 x VARAN-Out (Optional Ethernet (VtE))

VARAN-INTERFACE VAC 012

VARAN Client Board VEB 011/012 Versatile Automation Random Access Network

C-IPC Expansion VM 052 (C-IPC VARAN Manager 052) Versatile Automation Random Access Network

VI 021 S-DIAS VARAN Control Module

Expansion Module HZS 541-1S

C-DIAS Digital Input Module CDI 161 with 16 inputs

C-DIAS EtherNet/IP Slave CIP 022

HZS Internal Controller Expansion

TSY 041 Training System Extension Motion

SE 051 S-DIAS Splitter Ethernet

C-DIAS Analogue Output Module CAO 081 for eight 10V DC outputs

AO 081 S-DIAS Analog Output Module

to 12a Added Standard and Electrical requirements for UL table 1.1

Technical Data. C-DIAS-MULTI l/o MODULE CIO 013

TO 161 S-DIAS Digital Output Module

Auxiliary Board MP-Bus HZS 562

C-DIAS Temperature sensing module CAI x temp. inputs C 8 x digital outputs +24V

ISE 021 S-DIAS Interface Module RS232 / RS485

Internal Buffer/Boiler Module HZS 534

C-DIAS Analogue Conversion Module CAM 124 for eight 0 10V DC inputs and four 10V outputs

C-DIAS Serial Interface CSI 021

ETT 312 Build-In Touch Terminal

HZS Solar Module

PC 521 Data Recording PC

DM 161 S-DIAS Digital Mixed Module

Ha-VIS mcon 3000 Next Generation Introduction and features

Technical data. General specifications. Functional safety related parameters B 10d Electrical specifications Operating voltage U B

C-DIAS Profibus DP Slave module CPB 021

Profibus DP slave. dual ported RAM 2Kbyte. Maximum length for I/O data. Maximum length for output data. Status display

VersaMax IP I/O Module

RO 051 S-DIAS Relay Output Module

ICA 012 S-DIAS Interface Module CAN

C-DIAS-Temperature Recording module CAI x Temp. inputs 50 C to +150 C

GIN-SAM4. Hardware User Manual. Version: 1.02 Date: Language: English

GFK-2415A March Type of sensor connection

DC S-DIAS Axis Module

Operating and mounting instructions

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

ILBIB24DO16-DSUB. Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors

Industrial Ethernet Switch

SI 021 S-DIAS SSI Interface Module

NI REM Remote I/O Overview DATASHEET. Bus Coupler for Remote I/O

Technical data. General specifications. Linearity error ± 0.1 Functional safety related parameters MTTF d 130 a at 40 C Mission Time (T M ) L 10

Added Standard and Electrical requirements for UL table Switching-off inductive loads 1.2

KL 181 S-DIAS +24 V Potential Distributor Module

User Manual. MS657140X Industrial Fast Ethernet Switch 8x 10/100Base-TX

Ha-VIS econ 2000 Fast and Full Gigabit Ethernet Basic. Features

DI572 Digital Input Module

Version 1.7. August Publication ERSC-1050

AO561 Analog Output Module

Industrial Ethernet Switch. Signamax Connectivity Systems. Industrial Ethernet Switch. Model A Series. User s Guide

Hardened Ethernet Switch. Signamax Connectivity Systems. Hardened Ethernet Switch. Model G Series. User s Guide

DI561 Digital Input Module

C-DIAS Analog Module CAO 086 For eight ±10 V Outputs

Keyboard Unit Sigmatek

User Manual. MS657208X Industrial Gigabit Ethernet Switch 8x 10/100/1000Base-T

TAE 1921 Touch Display Unit

General information. Display. Supply voltage. Input current. Encoder supply. Output current

C-DIAS Analogue Output Module CAO 082 for eight ±10V DC respectively eight 0 20mA DC outputs

S SENECA. Installation Manual Z-TWS4. Z-PC Line. Web Multifunction Controller Straton / Linux

Technical data. General specifications. Linearity error ± 0.1 Functional safety related parameters MTTF d 480 a at 40 C Mission Time (T M ) L 10

General information. Display. Supply voltage. Input current

AI561 Analog Input Module

F1000 User's Manual. (Version: V1.01)

USB 2.0 RG2304GE-LAN. 4-Port USB 2.0 Gigabit Ethernet LAN Extender System. User Guide

General information. Display. Supply voltage. Input current. Encoder supply. Output current

General information. Display. Supply voltage. Input current. Encoder supply. Output current

User Manual Gateway component for EtherNet/IP

General information. Display. Supply voltage

Micropulse Transducers

General information. Display. Supply voltage

Rugged Industrial Media Converter

General information. Display. Supply voltage. Input current

DX561 Digital Input/Output Module

Technical data. General specifications. Linearity error ± 0.1 Functional safety related parameters MTTF d 480 a at 40 C Mission Time (T M ) L 10

Connection Cables for Operating Devices

10/100Base-TX Industrial Ethernet Extender

IPC 221 Industrial PC

General information. Display. Supply voltage

PS 101 S-DIAS Power Supply Module

DC562, digital input/output module,

PIGEON RB100-CM3. Features. Applications

C-DIAS Analogue Conversion Module CAM 011 for 3 x 0-10V DC inputs 2 x PT100 inputs and 1 x ±10V output

TN-5308 Quick Installation Guide

USB 3.1 CAT6A/7 EXTENDER

General information. Display. Supply voltage. Input current. Encoder supply. Output current

PCD3.C90. Date Modification Asked by: Version E/A Bus Connector PCD2.K106 change to PCD3.K106 Müller.R 1.1

IXXAT CME/PN. CANopen-PROFINET Gateway HARDWARE MANUAL ENGLISH

Hardened 4-Port 10/100/1000M DIN-Rail Mount Switch GATB. User's Manual (V1.0 Version)

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

PCAN-Repeater 2-Channel CAN Repeater with galvanic isolation. User Manual V1.0.0

Transcription:

VARAN SPLITTER PROFINET VSP 044 VARAN Splitter PROFINET VSP 044 With its 3 VARAN Out ports, the VARAN VSP 044 splitter module allows a VARAN bus system to be configured in a tree structure. The VARAN Out ports have a continuous +24 V supply for the VARAN bus. With this supply, special VARAN peripheral devices can be connected to the VSP 044 and supplied with +24 V without an additional power cable. At the Ethernet port(ip), incoming Ethernet packets are similar to using a HUB distributed to all other Ethernet ports in the VARAN bus system and the VARAN manager (and therewith the CPU) using VtE. In addition, the VSP 044 has an integrated VARAN-PROFINET Gateway for integrating a Siemens servo amplifier (Sinamics S120) into the VARAN system. until HW 1.x since HW 2.x 10.04.2018 Page 1

VSP 044 VARAN SPLITTER PROFINET Technical Data Performance Data Interfaces 1 x VARAN In (RJ45) 1 x ETHERNET Port VtE (RJ45) 10/100Mbit 3 x VARAN-Out (RJ45) +24 V supplied over VARAN 1 x PROFINET Sinamics Gateway (RJ45) (maximum cable length: 100 m) Internal data memory (SPI-Flash) 4 Mbits Electrical Requirements Supply voltage Current consumption of voltage supply 18 30 V DC The current consumption is dependent on the connected loads (200 ma module + 3 x VARAN Out 500 ma per port) (until HW 1.x) (100 ma module + 3 x VARAN Out 500 ma per port) (since HW 2.x) Miscellaneous Article number 16-023-044 Hardware version 1.x, 2.x Environmental Conditions Storage temperature -20 +85 C Environmental temperature 0 -+60 C Humidity EMC stability *) EMC noise generation 0 95 %, non-condensing in accordance with EN 61000-6-2 (industrial area) in accordance with EN 61000-6-4 (industrial area) Shock resistance EN 60068-2-27 150 m/s² Protection type EN 60529 IP 20 *) Control box mounting required Page 2 10.04.2018

Mechanical Dimensions until HW 1.x VARAN SPLITTER PROFINET VSP 044 10.04.2018 Page 3

VSP 044 VARAN SPLITTER PROFINET Mechanical Dimensions since HW 2.x Page 4 10.04.2018

VARAN SPLITTER PROFINET VSP 044 Connector Layout Connector Layout until HW 1.x Connector Layout since HW 2.x 10.04.2018 Page 5

VSP 044 VARAN SPLITTER PROFINET X1: ETHERNET Port VtE (IP) Pin 1 TX/RX + 2 TX/RX - 3 RX/TX + 4-5 not connected 6 RX/TX - 7 8 GND LEDs Yellow Green ACTIVE LINK LED Color Description ACTIVE Yellow Lights when data is exchanged over the Ethernet port. Link Green Lights when the connection between the both PHYs is established. Green Blinks when data is received via the Ethernet port. X2: VARAN In Pin 1 TX/RX + 2 TX/RX - 3 RX/TX + 4-5 not connected 6 RX/TX - 7 8 GND LEDs Yellow Green ACTIVE LINK LED Color Description ACTIVE Yellow Lights when data is exchanged over the VARAN bus. Link Green Lights when the connection between the both PHYs is established. Green Blinks when data is received over the VARAN bus Page 6 10.04.2018

VARAN SPLITTER PROFINET VSP 044 X3 X5: VARAN Out 1 3 Pin 1 TX/RX + 2 TX/RX - 3 RX/TX + 4-5 not connected 6 RX/TX - 7 8 GND LEDs Yellow Green ACTIVE LINK LED Color Description ACTIVE Yellow Lights when data is exchanged over the VARAN bus. Link Green Lights when the connection between the both PHYs is established. Green Blinks when data is received over the VARAN bus 24 V / 500 ma per VARAN Out port 10.04.2018 Page 7

VSP 044 VARAN SPLITTER PROFINET X6: PROFINET Sinamics Gateway Pin 1 TX/RX + 2 TX/RX - 3 RX/TX + 4-5 not connected 6 RX/TX - 7 8 GND LEDs Yellow Green ACTIVE LINK LED Color Description ACTIVE Yellow Lights when data is exchanged over the PROFINET port. Link Green Lights when the connection between the both PHYs is established. Green Blinks when data is exchanged over the PROFINET port. X7: Power Plug Pin 1 +24 V supply 2 GND Applicable Connectors Connectors with spring terminals: Phoenix Contact: FK-MCP 1.5/ 2-ST-3.5 The complete CKL 141 connector set with spring terminals is available from SIGMATEK under the article number 12-600-141. Page 8 10.04.2018

VARAN SPLITTER PROFINET VSP 044 Addressing More information on the VARAN bus can be found in the VARAN bus specifications! Description of PROFINET Sinamics Gateway The Profinet port of the VSP 042 is used to integrate a Siemens Sinamics S120 servo amplifier into the VARAN system. A point-to-point Profinet connection between the VSP 042 and the Sinamics S120 is thereby made. Other Profinet participants cannot be connected. For the Sinamics S120 servo amplifier, a special Firmware is required. Wiring Guidelines for VARAN General Information Since the components are supplied with power through VARAN, the maximum cable length (without new 24 V supply is highly dependent on the cross section of the VARAN cable and the number of connected modules. In the VSP 044, the voltage can be supplied to the following modules via the RJ45 connector of the VARAN Out port. This does NOT comply with the VARAN specification. The VARAN Out ports of the SV 044 can only then be connected when the VARAN module is suitable for a 24 V supply (e.g.: VDM 08x, PVDM 08x, PVAI 011, VEB 02x,...). With the VSP 044, the 24 V supply is not switchable over VARAN and is continuously on. CAUTION! VARAN modules, which are not suitable for the 24 V supply over VARAN can be damaged when connected to modules with an active 24 V supply. Pin 3 of the RJ45 connector of the VARAN Out port has permanent 24 V potential. With the VSP 044, normal VARAN modules can then be used only when the VARAN cable does not connect to pin 3 of the RJ45 connector. 10.04.2018 Page 9

VSP 044 VARAN SPLITTER PROFINET Recommended Shielding for VARAN The VARAN real-time Ethernet bus system exhibits a very robust quality in harsh industrial environments. Through the use of IEEE 802.3 standard Ethernet physics, the potentials between an Ethernet line and sending/receiving components are separated. In the event of an error, the VARAN Manager resends messages to a bus participant immediately. The shielding described below is mainly recommended. For applications in which the bus is operated outside the control cabinet, the correct shielding is required. This is especially important, if due to physical requirements, the bus cables must be placed next to sources of strong electromagnetic noise. It is recommended to avoid placing VARAN bus lines parallel to power cables whenever possible. SIGMATEK recommends the use of CAT5e industrial Ethernet bus cables. An S-FTP cable should be used for the shielding. An S-FTP bus is a symmetric, multi-wire cable with unshielded pairs. For the entire shielding, a combination of foil and braiding is used. A non-laminated variant is recommended. The VARAN cable must be secured at a distance of 20 cm from the connector for protection against vibration! Page 10 10.04.2018

VARAN SPLITTER PROFINET VSP 044 1. Wiring from the Control Cabinet to an External VARAN component If the Ethernet lines are connected from a VARAN component to a VARAN node located outside the control cabinet, the shielding should be placed at the entry point of the control cabinet housing. All noise can then be deflected from the electronic components before reaching the module. 10.04.2018 Page 11

VSP 044 VARAN SPLITTER PROFINET 2. Wiring Outside of the Control Cabinet If a VARAN bus line must be connected outside of the control cabinet only, no additional shield support is required. A requirement therefore, is that only IP67 modules and connectors can be used outside the control cabinet. These components are very robust and noise resistant. The shielding for all sockets in IP67 modules are electrically connected internally or over the housing, whereby voltage spikes are not dissipated through the electronics. Page 12 10.04.2018

VARAN SPLITTER PROFINET VSP 044 3. Shielding for Wiring within the Control Cabinet Sources of strong electromagnetic noise located within the control cabinet (drives, Transformers, etc.) can induce interference in a VARAN bus line. Spike voltages are dissipated over the metallic housing of a RJ45 connector. Noise is conducted through the control cabinet housing without further action from the electronic components. To eliminate sources of noise during data exchange, it is recommended that the shielding for all electronic components be connected within the control cabinet. 10.04.2018 Page 13

VSP 044 VARAN SPLITTER PROFINET 4. Connecting Noise-Generating Components With the connection of power components, which generate strong electromagnetic interference, it is also critical to ensure correct shielding. The shielding should be placed before a power element (or group of power elements). Page 14 10.04.2018

5. Shielding Between Two Control Cabinets VARAN SPLITTER PROFINET VSP 044 If two control cabinets must be connected over a VARAN bus, it is recommended that the shielding be located at the entry points of both cabinets. Noise can be thereby stopped from reaching the electronics within the control cabinet. 10.04.2018 Page 15

VSP 044 VARAN SPLITTER PROFINET Page 16 10.04.2018