Plus-X IIU / ICRU Installation Guide

Similar documents
Plus-X 300. Installation and Operation Manual

ARC Plus Version 3. Instruction Manual. ARC Plus. ARC Plus SL. AutoLoad Plus software. Rev A (September 2012) ARC Plus firmware version 3.

Plus-X 600. Installation and Operation Manual

Plus-X Dual IP-8 Adapter. Installation and Operation Manual

ARC PLUS SL Slimline Remote Control

Plus-X RP-8 Adapter. Installation and Operation Manual

Plus-X AC-8. User Guide

PlusConnect GatesAir Sigma

Instruction Manual. ARC Plus SL. ARC Plus firmware version 5.0 Rev. B

PlusConnect Nautel GV PlusConnect Nautel NV PlusConnect Nautel NVLT PlusConnect Nautel VS PlusConnect Nautel XR

Plus-X I/O Units. Manual Supplement Configuring Units with and without DHCP

PlusConnect BDI DPS-100D. Installation and Operation Manual

Connecting a Cisco Input Module

Helios PD Large Display Meter Quick Start Guide

SERIES. ProVu PD6200 Analog Input Rate/Totalizer. Quick Start Guide. MeterView Pro. 233 South Street Hopkinton MA USA

NUBIX H.264 DVR Setup Guide

INSTALLATION INSTRUCTION MANUAL

BiPAC 8501/8521. SHDSL.bis (VPN) Firewall Bridge/Router. Quick Start Guide

BiPAC 6404VP/VGP. VoIP/(802.11g) Broadband Firewall Router. Quick Start Guide

STEP 1 SETTING UP YOUR DIGTIAL VIDEO RECORDER (DVR) FREE DYNAMIC DNS SERVICE

Omega 4K/UHD Scaler for HDBaseT and HDMI with USB

ILF-100WD User Manual. Router Watchdog / Connection Monitor 2007 Stealth Laboratories, LLC Patent Pending

Manual# Installation Manual. 200E Series. DCU 210E/208E Engine Panel RP 210E/220E Remote Panel

Innovative Electronics for a changing world MANUAL POE 4+4 GM

BiPAC 7402R2. ADSL2+ VPN Firewall Router. Quick Start Guide

Ethernet Interface Module

Ethernet/Network Communications Module. Installation and Programming Manual. LINQ2 - Two (2) Port Connectivity Module. More than just power.

SWC1090 configuration software for G.M. International Isolators series D1000 and E1000. Installation and use manual

Setting Up Your Cisco Unified Videoconferencing 3515 MCU

Cascade Configuration Tool

D-Link (Europe) Ltd. 4 th Floor Merit House Edgware Road London HA7 1DP U.K. Tel: Fax:

GV-IP Decoder Box Plus User s Manual

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Raritan DANGER!

Hardware Installation

Brother HL-5370DW Configuration

ST-HD-CVR4CH ST-HD-CVR8CH ST-HD-CVR16CH. Professional Digital Video Recorders QUICK START GUIDE

Quick Start Guide. GV-Video Server. 1 Introduction. Packing List

NVR CH Network Video Recorder. Quick Installation Guide v1.0

Connecting a Cisco Output Module

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Product Overview. Raritan DANGER!

ADDENDUM. Lynx Software Version 5.1

Setting Up Your Cisco Unified Videoconferencing 3500 Gateway

Connecting a Cisco Reader Module

User s Manual. Version 1.0 PAGE 1 OF 38

Business Internet Video Camera with Audio

Quick Start Guide. GV-Video Server

PACSystems* RX3i and Series 90*-30 IC694ALG223 and IC693ALG223

B5021 Ethernet Base Supplemental User Guide

Internet Key Administration

BiPAC 5200 Series. (802.11g) ADSL2+ Modem/Router. Quick Start Guide

1 Hardware Installation

ZAVIO Indoor Box Camera. Quick Installation Guide

ST-HVR8704 ST-HVR8708 ST-HVR8716. Professional Digital Video Recorders QUICK START GUIDE

DaqBoard/3000USB Series USB 1-MHz, 16-Bit Data Acquisition Boards

Quick Start Guide. Industrial Managed Gigabit Ethernet PoE+ Switch LPH2008A-4GSFP

Synergy Controller Application Note 1 September 2014, Revision F Tidal Engineering Corporation 2014

Agilent Technologies 16700B-Series Logic Analysis Systems. Installation Guide. Publication number November 2002

BCM2 Series Branch Circuit Monitors Quick Setup Guide

Mini IP Cameras. Installation manual INSTALLATION MANUAL. RP Series. RP SERIES - MINI IP CAMERAS Page: 1

Obsolete. BR Series USB Tech Kit. B l u e R i d g e. T e c h n o l o g i e s. User Guide. Page 1. Hardware and Software Instructions

VENTEV INNOVATIONS BTRM200 Battery Test Remote Monitoring System User Guide V1.0. Innovations BTRM200. Battery Test Remote Monitor User Guide

Fairfield University Using Xythos for File Storage

Thank You for Choosing the CRICKET CROSSWAVE

Getting Started with IBM Cognos 10 Reports

Energy Client. Version Feb Electrocom Rødeledsvej 95 DK-5700 Svendborg Denmark Tel:

Gigabit Ethernet Switch. Quick Installation Guide MS400834M

BIPAC Broadband Firewall Router. Quick Start Guide

For additional information, please consult the Read-Me and Help documentation or contact Electro-Voice or Dynacord technical support.

1. General Description

Series 3000 Model R-197A. Audio Relay Panel With Ethernet Interface. Instruction Manual

Trident & Trident X2 PD765

Print Manager Plus 2010 Workgroup Print Tracking and Control

ARC-16. Transmitter Remote Control System. INSTALLATION & OPERATION MANUAL Firmware Versions 4.6 & Above

Chapter A2: BankLink Books clients

Installing the Cisco Unified Videoconferencing 3545 MCU

ZAVIO Outdoor IR Mini Dome. Quick Installation Guide

FAC-R Frequency to Analog Converter Installation, Operating & Maintenance Manual

Web-based Configuration. First, setup motion detection windows in the web-based configuration of the camera.

Product names mentioned in this manual may be trademarks or registered trademarks of those products.

ViZion DR + Wireless Install Guide

Alarm Distribution Shelf (ADS)

Quick Start Guide. Hybrid DVR DS-9000HFI-ST Series Hybrid DVR. NVR DS-9600NI-ST Series NVR. First Choice For Security Professionals

MOP for Replacing a CXCI with a CXCI+

EC-11 Ethernet Converter

PDW30 Point-to-Point Wireless Bridge Installation Guide

Innovative Electronics for a Changing World INDEX

EMC ApplicationXtender Web Access.NET eroom Integration 6.0

ACCESSORY KIT INSTALLATION INSTRUCTIONS S Simplicity Transporter Setup Instructions

Overview. Read Before Use CHAPTER

F3102 / F3107 / F3110 / F3115 / F3210 / F3215 PN: 86085K K

Create a worksheet that collects, displays and saves temperature data

SonicWALL Security Appliances. SonicWALL SSL-VPN 200 Getting Started Guide

Lite H.264 DVR Setup Guide

SR-201 Network Relay Quick Start Guide

Setup Guide for Wi-Fi Hotspot Boosting Kit

Quick Start Guide. GV-Video Server

DUAL SWITCH CONTROLLER

READ BEFORE USING THE EQUIPMENT EN

POWER. allows users to interface a third party control system with the devices on a VN Matrix network.

VisionTouch 5 Software

Transcription:

Installing the Plus-X IIU & ICRU Plus-X IIU / ICRU Installation Guide The Plus-X Integrated Input Unit (Plus-X IIU) and Plus-X Integrated Command Relay (Plus-X ICRU) are used to connect site equipment to the ARC Plus. Each Plus-X IIU connects up to 16 metering and 32 * status channels, and each Plus-X ICRU connects 16 relays or 8 pairs of raise/lower relay outputs. Units are connected to the ARC Plus via LAN or WAN. Up to 32 Plus-X devices can be connected to the ARC Plus. The Plus-X IIU accepts 16 metering or status channels (left side of panel) and 16 status channels (right side of panel). The Plus-X ICRU accepts 8 raise and 8 lower channels. Network Settings Prior to operation, each Plus-X IIU and Plus-X ICRU must be configured for your network. To configure the unit, open a web browser and enter the unit s IP address in the address bar. Prior to network configuration, the Plus-X IIU/ICRU operates on a default IP address of 192.168.0.100. When the log on screen appears, enter the user name and password for the unit. The user name is admin and the default password is password. After logging on, click the Configuration link in the menu bar, opening the Network Settings page. Enter the appropriate values where prompted (consult your network administrator if needed). Note that the default Plus-X port of 45000 will work in most installations. However, if you have changed the Plus-X port during ARC Plus configuration the Plus-X port you enter here must match that setting. The ARC Plus IP address field calls for the IP address of the ARC Plus that will host the channels of this Plus-X device. Press the Save button when you are finished. * 16 inputs are dedicated to status. 16 inputs may be used as meter or status, for a total of up to 32 status channels.

Connecting Plus-X IIUs and Plus-X ICRUs to the ARC Plus If you have not already done so, install the units in the equipment rack. If you wish, you may distribute the units in multiple racks, or at different locations. To add the channels from the Plus-X unit to the ARC Plus: 1. Start by downloading the Plus-X IIU and Plus-X ICRU XML files from the support section of www.burk.com. These files contain data that AutoLoad will need in order to configure the Plus-X unit. Save the files in the Plus-X folder, usually located in c:\program Files\Burk Technology\AutoLoad Plus. 2. Launch AutoLoad Plus and connect to the ARC Plus site to which the Plus-X unit will be linked. 3. From the Edit menu, selected Plus-X Devices and click New. 4. When the Plus-X Settings window appears, select Plus-X IIU or Plus-X ICRU from the device type drop-down. Enter a description of the Plus-X unit for your own reference, followed by the IP address and Plus-X port, as already configured on the Plus-X unit. 5. Check the box marked Map Default Set of Channels to add all channels for this Plus-X unit to the ARC Plus. If you are not using all channels, or if you do not wish for them to appear in sequential order, you will need to manually map these channels alter. In this case, leave this checkbox unchecked. 6. Press OK to close the Plus-X Settings window. Press OK to close the Plus-X Devices window. 7. To manually map Plus-X channels to the ARC Plus, click the Meter, Status, or Command tabs, as appropriate. Locate an unused channel and click the [ ] button in the Override column. This will bring up the Override Channel dialog. Click the Plus-X channel button and choose the Plus-X channel you wish to use. 8. Configure labels, limits, and alarms for the newly added Plus-X channels. 9. Lastly (Plus-X IIU only), you will need to calibrate the metering channels. If you have not already connected the input connector blocks, do so now. Then click the Calibration icon in the AutoLoad Plus toolbar to complete the calibration process. Restoring Factory Configuration To reset the unit to its default configuration, press and hold the MASTER INIT button for three seconds. The Power LED will blink to confirm the configuration has been reset. Note that restoring the default configuration will reset the unit s password to password and the IP address to 192.168.0.100. 2

Connecting Analog and Status Inputs (Plus-X IIU) Input Channel Pinouts Each Plus-X IIU connects up to 16 metering inputs (±10VDC) and 16 status inputs (0-28VDC or switch closure). Meter inputs may be used as status channels by setting the high and low voltage thresholds (see below). Metering channels 1-8 are the top left bank of pins and 9-16 are the bottom left bank of pins row pins. Status channels 1-8 are the top right bank and 9-16 are the bottom right bank: Each channel has a pin for common ground (left) and a pin for the signal voltage (right), as shown in the table below. CH 1 CH 2 CH 3 CH 4 CH 5 CH 6 CH 7 CH 8 - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + - + CH 9 CH 10 CH 11 CH 12 CH 13 CH 14 CH 15 CH 16 Plus-X IIU Rear Panel Connector Pinouts. Analog and status pinouts are identical. Channels numbers are for reference on this unit only. ARC Plus channel numbers are assigned when the Plus-X IIU is added to the ARC Plus (see above). Four 16-pin connector blocks are included to facilitate equipment wiring, two blocks for analog channels, and two for status channels. Analog channels are connected on the left side of the Plus-X IIU rear panel, and status channels are connected on the right, as shown below. Using Metering Inputs for Additional Status Each of the 16 metering inputs on the Plus-X IIU can be used as a status input (either as an alternative to the metering input or in addition to it). To configure the metering input behavior, use a web browser to connect to the Plus-X IIU. Click on the Configuration link in the menu bar, and click on Meter Channels from the sidebar. 3

Assign the low and high threshold (in Volts) for each channel that will be used as a status input. These inputs can be assigned to status channels on the ARC Plus using AutoLoad. If desired, one input can be used for both metering and status on the ARC Plus. In this case, the metering channel will show the analog value read on the input, and the status channel will show the status using the low and high thresholds defined here. Input Diagnostics The main page of the Plus-X IIU web interface shows the actual voltage read for each metering input (not its calibrated value), its associated status (applicable only where metering channels are used for status), and the state of each status input. This page is provided for diagnostic purposes, and may be useful during initial setup or troubleshooting. The values on this page are not updated in real time, and should not be used for daily operation. Labeling Analog and Status Inputs The accessory kit supplied with the Plus-X IIU includes labels to identify the ground pin and supply voltage pin for each channel. To align and affix the labels: 1. Start by designating one of the 16-pin connector blocks for metering channels 1-8. 2. Orient the connector block with the set screws facing toward you and below the wiring terminals. 3. Peel off the label identifying ground and supply voltage for channels 1-8 and align the label on top of the connector block with the ground symbol above the left-most input and the CH 1 designator above the second input from the left. When the label is aligned correctly, the designator for CH 8 will be positioned above the right-most wiring input and there will be a small amount of overhang on each side of the label. 4. Wrap the overhang around the side of the connector. 5. Next, label a new connector block for metering channels 9-16, followed by the two connector blocks for status channels. On subsequent Plus-X IIUs, apply labels for channels 17-32, 33-48, etc. in the same way. Note: If you wish, you can apply the label directly on the rear panel of the Plus-X IIU instead of on the connector block. Wiring the Input Channels Once you have labeled the connector blocks for your input channels, attach wiring for each remote control channel to the connector block using the connector labels as a guide. Secure the wiring using the built-in set screws before attaching the connector block to the appropriate rear panel connector. 4

Connecting Command Channels (Plus-X ICRU) Command Channel Connector Pinouts The Plus-X ICRU connects 8 raise and 8 lower channels using two identical 24-pin connector blocks. Raise channels connect to the left set of 24 pins on the rear panel, and lower channels connect to the right set of 24 pins, so shown below: Closeup of Form C contacts on the Plus-X ICRU rear panel. Each channel has three pins: a pin for common (left), and pins for the normally open or normally closed contact. Pinouts for raise channels 1-8 and lower channels 1-8 are identified on the chart below. 1 2 3 4 5 6 7 8 C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC Plus-X ICRU rear panel pinouts. Pinouts for raise channels (left side of Plus-X ICRU rear panel) are identical to the pinouts for lower channels (right side of Plus-X ICRU rear panel). Pairing Relays The 16 relays on the Plus-X ICRU may be used individually as up to 16 channels, or in raise/lower pairs (8 channels). To configure the relay behavior, use a web browser to connect to the Plus-X ICRU. Click on the Configuration link in the menu bar, and click on Relay Settings from the sidebar. Click the Pair checkbox in the center column to pair the associated relays (1 and 9, 2, and 10, etc). When paired, the relays will behave as one raise/lower channel. When not paired, each relay behaves independently. Relay Diagnostics The main page of the Plus-X ICRU web interface shows the state of each relay. This page is provided for diagnostic purposes, and may be useful during initial setup or troubleshooting. The values on this page are not updated in real time, and should not be used for daily operation. 5

Labeling Command Channels The accessory kit supplied with the Plus-X ICRU includes labels to identify each command channel. To align and affix the labels: 1. Start by designating one of the 24-pin connector blocks for raise channels 1-8. 2. Orient the connector block with the set screws facing toward you and below the wiring terminals. 3. Peel off the label identifying channels 1-8 and align the label on top of the connector block so that the CH 1 segment of the label corresponds with the first three pins on the left side of the connector block. CH 2 corresponds with the next set of three pins, and so on. When the label is aligned correctly, the three pins on the far right of the connector block are identified as CH 8 and there will be a small amount of overhang on each side of the label. 4. Wrap the overhang around the side of the connector. 5. Next, label the second connector block for lower channels 1-8. On subsequent Plus-X ICRUs, apply labels for channels 9-16, 17-24, etc. in the same way. Note: If you wish, you can apply the label directly on the rear panel of the Plus-X ICRU instead of on the connector block. Wiring Command Channels Once you have labeled the connector blocks for your command channels, attach wiring for each channel to the connector block using the connector labels as a guide. Secure the wiring using the built-in set screws before attaching the connector block to the appropriate rear panel connector. 6