Room Pressurization Controller Pneumatic Output

Similar documents
Room Pressurization Controller Electronic Output

BACnet PTEC Terminal Box (VAV) Controller. Control Applications. Product Numbers. Product Description. Warning/Caution Notation

TEC VAV with 0-10V AO Heat. Modulation and CO2 Monitoring. Controller. Control Applications. Product Description. Accessories.

BACnet PTEC Heat Pump Multi-Stage Controller. Control Applications. Product Description. Product Numbers. Warning/Caution Notation

Siemens TEC Extended I/O Controller

TEC Heat Pump Multi-Stage Controller. Control Applications. Accessories. Product Description. Product Numbers. Warning/Caution Notation

TEC Terminal Box (VAV) Controller

TEC Unit Conditioner Controller

BACnet PTEC Unit Conditioner/Fan Coil P. Controller. Control Applications. Accessories. Product Description. Warning/Caution Notation

Terminal Equipment Controller Enclosure

LTEC Heat Pump DDC Controller

LTEC Unit Ventilator DDC Controller

TRUNK TX RX + - S + - S DO LEDS FLN TRUNK TERMINATIONS INPUT/OUTPUT TERMINATIONS TRANSMIT LED

Unit Vent Controller 0-10 V Output

Siemens BACnet Programmable TEC Constant Volume

PXC Compact Unitary Equipment Controller (UEC)

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

BACnet Terminal Box (VAV) Controller

Siemens BACnet Programmable TEC VAV with Series Fan and 3-Stage Electric Heat Controller

Launch Pad User Guide

Siemens BACnet VAV Actuator

Siemens BACnet Programmable TEC Unit Conditioner Controller

oom Pressurization Con

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller

Siemens BACnet Programmable TEC Unit Vent Controller

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

Application MC User Guide

Dual Duct Controller - One Air Velocity

OpenAir Electronic Damper Actuator GDE/GLB Rotary Non-spring Return

Open Processor with Square D Driver

Actuator Commissioning Tool

Open Processor with Carrier CCN DataLink Driver

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules

Siemens BACnet Programmable TEC Unit Vent Controller for Smoke Control

XTM 1050 Replacement Parts Installation

TEC Controller Extended I/O Application 2497 with Slave Mode Application Application Note Building Technologies

Actuating Terminal Equipment Controller (ATEC) VAV with Reheat. Start-up Procedures Building Technologies Restricted

Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control

Replacing the Power Supply

SQM5 Reversing Actuators, with Multiple Analog Control Input Signals

Actuating Terminal Equipment Controller (ATEC) VAV with Reheat - Cooling and Heating, Application Application Note

TALON Network Manager- 2 & 6 Express

BAC-9000 Series VAV Controller Installation Guide

MS/TP Point Pickup Module Owner's Manual

TECH/DATA SHEET. Application. Model Chart. Installation. slon-v1. slon-v2. slon VAV Controller

Free Energy Band RCC30U Room Temperature Controller for Four-pipe Fan Coil Unit

RWD68U Universal Controller

HP UPS R/T3000 ERM. Overview. Precautions. Installation Instructions

E1135C PDU and Pod Upgrade Procedure

VAV Modular Assembly (VMA) 1410/1420

SED2 VFD NEMA Type 3R Bypass/Air Conditioner

SQM5 Reversing Actuator with Analog Input Signal

HIMatrix Safety-Related Controller Maintenance Manual

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Floating Control

BTU 4 & Sensors. Installation and Operation Manual

RDF Series Room Temperature Controllers

BACnet Driver on the TC Series Platform

Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2. Cisco CRS 3-Phase AC Power Distribution Unit 2

SLX Series. Application Specific Controllers (SLX-ASC-FCU-L, SLX-ASC-HPU-L, SLX-ASC-RTU-L, SLX-ASC-UV-L)

Rack Installation Instructions

ON/OFF HUMIDIFIER CONTROL (ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET OVERVIEW WALL CONTROLLER INSTALLATION (TCY-BH-T-U)

PS/IO Circuit Board Retrofit

BTU-4D/BTU-4D-I Digital Temperature Unit & Sensors. Installation and Operation Manual

599 Series Zone Valve Actuator SF Series Electronic Valve Actuator, 2-position Control

1. Carefully unpack the um260 s shipping carton and check the contents for damage.

INSTALL INSTRUCTIONS RSXMR-9886-P-48

Service Bulletin. MiTek. RoofTracker Roof Truss Roller Press. Machinery Affected: Adding an Operator Platform. Machinery Division

TX-I/O Product Range. Description. Technical Specification Sheet Document No July 18, 2013

Unitary Controller. Features. Description. Technical Specification Sheet Rev. 6, March, 2000

M5 and M10 Routers Power Supply and Power Cord Component Replacement Instructions

HP R/T2200 UPS. Overview. Precautions. Installation Instructions. The HP UPS R/T2200 features power protection for loads up to 2200 VA/1600 W.

Firmware Revision 3.5 Release Notes

Part Name/Description Part Number Quantity

EXN4000 Storage Expansion Unit Installation and Setup Instructions

TX-I/O Product Range. Features. Description. Technical Specification Sheet Document No January 24, 2007

Power Open Processor/Open Processor

EAP110-Outdoor. Installation Guide. 300Mbps Wireless N Outdoor Access Point

Powers TM Controls RL 243 MP Multi-Purpose Relay

Smart Multivariable Transmitter (SMV 3000) Electronics Module Replacement Kit Instruction

HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions

BACnet VAV Actuator Start-up Guide IM 1040

Heat Containment System (HCS)

MNL-V1RVx MNL-V2RVx. Application. Model Chart. TAC I/A Series MicroNet Variable Air Volume Controllers Installation Instructions

RMB Peripheral Units Installation Guide

Eaton LCD Lift Flat Panel Display System. Installation Guide

EMC 10T "CE" Mechanical Upgrade Procedure

BACnet PTEC Controller Constant Volume - Cooling Only, Application Application Note Building Technologies

IBM. Rack Installation Instructions

Installation Instructions Model ZAM-180

MODEL SW6000 & SM6100 CENELEC INSTRUCTIONS

Three Phase Residential Solution for Australia, System Design and Installation Guidelines

AutoScan to MultiScan Replacement Kit

TX-I/O Product Range. Description. Technical Specification Sheet Document No February 20, 2018

TECHKNOW, INC. Kiosk Order Confirmation System INSTALLATION MANUAL. Revision Date: July 11, 2012 Part # Version 3.2

Installation Instructions for Installing the Advanced Video Input Board in a D9032 Encoder

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION

Junos WebApp Secure 5.0 Hardware Guide

Plasma Panel Replacement Guide DU-42PX12X

599 Series Zone Valve Actuator SF Series Electronic Valve Actuator, 2-position Control

Transcription:

Document No. 540-1032 Room Pressurization Controller Pneumatic Output Product Description These instructions explain how to field install (pages 1 through 3) or replace (pages 3 through 4) a Room Pressurization Controller Pneumatic Output with or without Autozero Modules. Product Number 540-716 Room Pressurization Controller Pneumatic Output 540-717 Room Pressurization Controller Pneumatic Output with Autozero Modules 540-514N Room Pressurization Controller Board Pneumatic Output (replacement) Shipping carton includes a pre-assembled metal enclosure with controller board and cover, pneumatic output modules, Autozero Modules with brackets (optional), and four self-tapping/drilling screws. Installation Conventions Required Tools Equipment damage or loss of data may occur if you ds not follow procedures as specified. Electro-Static Discharge (ESD) wrist strap Small flat-blade screwdriver Medium flat-blade screwdriver Medium-duty electric drill 1/4 in. (6.35 mm) hex nut bit Portable Operator s Terminal with Controller Interface Software Rev. 2.0 or later (required for controller replacement only) Additional tools needed if not using self-tapping option: 1/4 in. (6.35 mm) hex nut driver 1/8 in. (3 mm) bit Prerequisites (Optional) Room temperature sensor installed Air velocity sensors installed in ducts A source of 24 Vac Class 2 power available Supply power to the unit is OFF An air supply line is available at the controller Expected Installation Time New controller installation Replacement (old controller has removable terminal blocks) 10 minutes 6 minutes Replacement (old controller does 16 minutes not have removable terminal blocks) NOTE: You may require additional time for database work at the field panel. New NOTE: These steps only refer to new installations. For replacement instructions, refer to pages 3-4. For Autozero Module installation, refer to instruction 540-199. The following tasks can be performed by the electrician: 1. Loosen, but do not remove, the cover screws and remove the enclosure cover. Using the rear panel of the enclosure as a template (Figures 1 and 2), mark the location for the four screw holes where you will install the enclosure. 2. Do one of the following: If using the self-tapping screws: Using the drill and the hex nut bit, start the screws. (Screws do not require starter holes.) If not using the self-tapping screws: Drill four 1/8 in. (3 mm) pilot holes for the screws. Using the hex nut driver, start the screws. Item Number: 540-1032, Rev. FA Page 1 of 7

Figure 1. Room Pressurization Controller Pneumatic Output without Autozero Modules. 3. Mount the enclosure on the screws and tighten them down with either the drill or hex nut driver. 4. Remove the appropriate knockouts. 5. Place the ESD wrist strap on your wrist and attach it to a good earth ground. 6. Connect the Local Area Network (LAN) trunk (Figure 4). Run the wiring through knockout. Page 2 of 7 Do not connect an earth ground to the Shield (S) terminal. 7. Connect the point wiring for the appropriate application. See Figure 7. See Table 1 for application descriptions. Run the wiring through knockout. The Controller s Digital Outputs (DOs) control 24 Vac loads only. The maximum rating is 12 VA for each DO. For higher VA requirements, 110 or 220 Vac requirements, separate transformers used to power the load, or DC power requirements, use an interposing 220 V 4-relay module (TEC Relay Module P/N 540-147). NOTE: Each DO provides a Normally Open (NO) and a Common (C) terminal. Terminate both connections of a 24 Vac load directly to the controller board. NOTE: The 24 Vac H terminal is switched through a TRIAC to the NO terminations when the associated DO is energized. 8. If using a pressure mode switch, then follow the Room Pressurization Controller (RPC) Pressue Mode Switch nstallation Instructions (540-719) included with the switch. 9. After the pressure mode switch is installed, wire the switch to DO8 and AI3 as described in the instructions. 10. Plug the Room Temperature Sensor cable into the RTS port on the controller board. See Figure 1. Run the cable through knockout. 11. Connect the power trunk as shown in Figure 5. DO NOT apply power to the controller. Run the wiring through knockout. 12. Replace the enclosure cover and tighten the cover screws.

The following task can be performed by the fitter: 13. Connect the tubing from the air velocity sensor pickups to the HI and LO ports outside of the enclosure. The supply pickup goes to the supply AVS ports, and the exhaust pickup goes to the exhaust AVS ports on the side of the enclosure. Make sure that the HI and the LO pressure sides of the sensors are connected to the HI and LO sensor ports on the controller (Figure 1) or Autozero Modules (Figure 2). Refer to Table 2 for air velocity sensor connections. The installation is complete. Replacement Instructions Replacement of a TEC requires you to record, re-enter, or update the initial point values of the controller you are replacing. These are the points marked with an asterisk (*) on the Controller Interface Software (CIS) display. NOTE: CIS Rev. 2.0 or later is required for controller replacement. The following tasks can be performed by the system specialist: 1. Place the ESD wrist strap on your wrist and attach it to a good earth ground. 2. Before disconnecting the old controller, do one of the following: NOTE: If the new controller has a newer firmware revision than the old controller, then skip to the third bullet. If the old controller communicates with the field panel, then update the controller initial values at the field panel. If the old controller does not communicate with the field panel, but communicates with the CIS, or if the controller is stand-alone, then record the initial values (those marked with an asterisk (*) on the CIS display). Record the values. If the old controller is not communicating at all, or if the controller you are installing has a newer firmware revision than the old controller, then while at the field panel, follow these steps: a. Obtain a field panel Point Definition Report for the LCTLR point. Record the values. b. View the initial value block. (This information is valid only since the last update was made). Record the values. c. Delete the LCTLR point from the field panel. 3. Replace the old controller as follows: The following tasks can be performed by the electrician: a. Remove power from the controller. b. If the old controller has the RTS plug between the LAN trunk and point terminations, then disconnect the wires from the power trunk terminal block. If the old controller has the RTS plug on the opposite end of the board from the power trunk terminal block, then remove the power trunk terminal block. c. Remove, in the following order, the controller s: LAN trunk terminal block DO8, AI3, and DI2 only room temperature sensor d. Loosen, but do not remove, the mounting screws. e. Lift and remove the old enclosure. f. Mount the new enclosure on the mounting screws and tighten them down with either the drill or hex nut driver. g. Remove the appropriate knockouts. h. If the old controller has the RTS plug between the LAN trunk and point terminations, then remove all terminal blocks (except the power trunk) from the new controller. If the old controller has the RTS plug on the opposite end of the board from the power trunk terminal block, then remove all terminal blocks. Page 3 of 7

i. Plug, in the following order, the controller s: pre-wired LAN trunk DO8, AI3, and DI2 j. If the old controller has the RTS plug between the LAN trunk and point terminations, then rewire power to the power trunk terminal block. If the old controller has the RTS plug on the opposite end of the board from the power trunk terminal block, then plug the power trunk terminal block from the old controller into the new controller. k. Connect the room temperature sensor. Run the wiring through knockout. l. Power up the controller. The following tasks can be performed by the fitter: m. Label and remove the polyethylene tubing from the old enclosure. n. After the new enclosure is in place, reconnect the polyethylene tubing. The following tasks can be performed by the system specialist: 4. Set the address and application at the new controller. 5. Based on what you did in Step 2, do one of the following: If you updated the initial values from the old controller at the field panel, then when you set the address and application for the new controller, the field panel will automatically send the initial values down to the new controller. Once this takes place, replacement is complete. If you manually recorded the initial values in the table, then enter them into the new controller. If a field panel is present, then update the controller s initial values. Replacement is complete. If there was no communication at the old controller, or the new controller has a newer firmware revision than the old controller, then enter the initial values into the new controller. At the field panel, add the LCTLR point and update the controller s initial values. The replacement is complete. Figure 2. Room Pressurization Controller Pneumatic Output with Autozero Modules. Page 4 of 7

Figure 3. Dimensions. Figure 4. FLN Trunk Wiring. Figure 5. Power Trunk Wiring. Page 5 of 7

Table 1. Application Descriptions. Application Description Figure 2215 CAV/VAV Room Pressurization with Hot Water Reheat 2217 VAV Room Pressurization with Hot Water Reheat 2219 CAV Room Pressurization with Hot Water Reheat 7 7 7 NOTE: When wiring any actuator that uses a 0 to 10V control signal and ties AC neutral to DC common, an additional wire must connect the actuator AC neutral to the DC common of the PTEC/TEC AO being used to control the actuator. Table 2. Air Velocity Sensor Connections. Application Supply AVS HI and LO Exhaust AVS HI and LO 2215 Supply Pickup Exhaust Pickup 2217 Supply Pickup Exhaust Pickup 2219 Supply Pickup Exhaust Pickup The Room Pressurization Controller Pneumatic Output controls 24 Vac loads only. The maximum rating is 12 VA for each DO. For higher VA requirements, 110 or 220 Vac requirements, separate transformers used to power the load, or DC power requirements, use an interposing 220V 4-relay module (TEC Relay Module P/N 540-147). Actuator Symbol Figure 6. 24 Vac Modulating Control. TEC Connection Function Terminal Connection Standard Color 1 H Supply (SP) G Red 2 C Neutral (SN) G0 Black 8 AO3 15 (+) -- C to AO3 16 (-) 0 to 10V input signal Common jumper Y Gray -- -- NOTE: Refer to the unit wiring diagrams or consult with the local representative if terminations are missing or are different. Page 6 of 7

Figure 7. Point Wiring for Applications 2215, 2217, and 2219 with Hot Water Reheat. Refer to Table 1 for Application Descriptions. Cyber security disclaimer Products, solutions and services from Siemens include security functions to ensure the secure operation of building automation and control, fire safety, security management, and physical security systems. The security functions on these products, solutions and services are important components of a comprehensive security concept. Drafting, implementing and managing a comprehensive and up-to-date security concept, customized to individual needs, is nevertheless necessary, and may result in additional plant- or site-specific preventive measures to ensure secure operation of your site regarding building automation and control, fire safety, security management, and physical security. These measures may include, for example, separating networks, physically protecting system components, user training, multi-level defensive measures, etc. For additional information on security as part of building technology and our product, solution and service offerings, please contact your Siemens sales representative or project department. We strongly recommend to always comply with our security advisories on the latest security threats, patches and other related measures. http://www.siemens.com/cert/en/certsecurity-advisories.htm Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. 2017 Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 USA Tel. 1 + 847-215-1000 Your feedback is important to us. If you have comments about this document, please send them to SBT_technical.editor.us.sbt@siemens.com. Document No.540-1032 Printed in the USA Page 7 of 7