Data Sheet. Surge protection devices - A technical overview

Similar documents
Application Note TAN MTL Surge Technologies. Lightning surge protection for electronic equipment - a practical guide.

Technical Data Sheet Medium Current Power Surge Filters

LPI SG + SS480 Spark Gap Surge Filters

LPI SG + SST Spark Gap Surge Filter

LPI SST Surge Filters

Tel: Web: Lightning and surge protection help pages

ENGR. MARITES R. PANGILINAN, P.E.E.

MDSP-Series 90kA, 150kA, 300kA Modular Distribution Surge Protector Type 2 Class II Surge Arrester

Systems which use a conventional POTS subscriber line to dial a compatible system and transfer digital data.

BS th Edition wiring regulations Furse overview

GLOSSARY OF TERMS. Surge and Lightning Protection ERICO Inc.

Introduction to Surge Protection

Fundamentals of Thyristor Overvoltage Circuit Protection

CATEGORY C CATEGORY B CATEGORY A. The Power to Protect

Hazardous Area Protection

Lightning Current Equipotential Bonding SPDs

LIGHTNING PROTECTION of SCADA AND TELEMETRY SYSTEMS

After the storm leaves the area, you pat yourself on the back for protecting your data and equipment. The worry is over. Or is it?

AC Line Voltage Transients and Their Suppression

Surge Protection Products for the small office/home office and professional grade

Application Note. Table 1. Test requirements by equipment type

DBPApplication. PD Devices Ltd. Unit 1, Old Station Yard, South Brent, Devon. TQ10 9AL (0)

3 Design of the electrical installation protection system

THE SOLLATEK SUPPRESSOR RANGE Instruction manual

Technical Requirements for High-voltage DC Power Feeding Interfaces of ICT equipment

2 Principle of lightning protection

SPM Series Plug-in Surge Protector Type 2/3 (Test Class II/III) Single & Three Phase Surge Arresters

SURGE PROTECTIVE DEVICES

SPM Series. Plug-in Surge Protection

Surge Current Capacities

Lightning and Surge Protection of Photovoltaic Installations. Leutron GmbH 2013 Leinfelden-Echterdingen, Germany

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

Data Line Transient Protection

YOU NEED A WHOLE- HOUSE PROTECTION SYSTEM

SPM Series Plug-in Surge Protection

Overvoltage Protection

glossary GE Digital Energy Power Quality Surge Protective Devices (SPDs)

Surge Protection. The effects of transient voltages on business and the benefits of installing Surge Protection Devices

An Overview of Surge Protection for the Smart Grid IEEE PES/SPDC WG Matt Wakeham, Chair

Lightning and Surge Protection for PV Systems

White Paper. AC Surge Protection. Evaluation of Series Element Surge Protective Device for Protection of Electronic Equipment and Systems

LIGHTNING AND SURGE PROTECTION

White Paper Transient Surges and Suppressor Technologies

INTRODUCTION LIGHTNING MAGNITUDE AND FREQUENCY

White Paper Surge Current Characteristics: 570 Hybrid Surge Protective Device

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA

Ethernet Protection A Whole Solution Han Zou, ProTek Devices

Designing with Thermally Protected TCMOV Varistors for Type 1 and Type 2 UL1449 3rd Edition Applications

CPS block & CPS nano UL rd Ed. Surge protective devices (SPD)

PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment

Dirty Power... A Guide to Surge Suppression & Filtering. Surge & Signal Protection for Business-Critical Continuity. EmersonNetworkPower.

The ABC s of Lightning TO BE SURE, USE DEHN

Data Line Transient Protection

AC Line Voltage Transients and Their Suppression

Revised Standards Provide Design Options for Primary and Secondary Protection TELECOM PROTECTION WHITE PAPER

Common Mode Noise The Often Neglected Tenth Power Problem

Technology Live Workshop

Mitigation of Voltage Swells I

Surge Protector. Esma Khatun

17 th Edition (BS 7671:2008) incorporating Amendment No 1

DSP 600 SERIES Distribution Surge Protector

TECH NOTE #: CPS-1 SUMMARY OF APPLICABLE UL AND IEEE STANDARDS

SAMPLE. MOVs are sometimes referred

Operating Instructions

Cirprotec Technical Article No. 5

Surge & Filter Protection Addressing your industrial power quality needs.

ITU-T K.118. Requirements for lightning protection of fibre to the distribution point equipment SERIES K: PROTECTION AGAINST INTERFERENCE

Zinc Oxide Varistor Series ( Standard Surge ) :

LIGHTNING PROTECTION

The Wave Breaking Factor and it s Vital Role in Surge Protection Device Coordination. Hans Slagter, DEHN + SOHNE

Engineering Notes. Transient Surges and Surge Suppressor Technologies: Comparing Apples to Oranges. Transient Surges Defined and Discussed 6

TDX Series. Transient Discriminating TM TVSS

Chapter J. Protection against voltage surges in LV. Contents. General. Overvoltage protection devices. Choosing a protection device

Application Note TAN MTL Surge Technologies. Surge protection for electrical power installations. Synopsis

TVS Voltage Characteristics for an Electrostatic Discharge Pulse

HyperLink Brand Weatherproof PTZ Camera Lightning and Surge Protector Model: AL-VDP Series

Maximize Your Uptime: Reducing Risk of Power Supply Failure

Overvoltage Protection Devices

NEW surge protective devices

Product Overview 2Pro AC Devices Provide Overcurrent/Overvoltage/ Overtemperature Protection for AC Industrial and Appliance Applications

The following standards are the basis of design, manufacture, and test of SPD equipment: Guide for Surge Voltages in Low-Voltage AC Power Circuits

CUS150M1 Instruction Manual

CONNECT AND PROTECT. nvent ERICO Critec SRF N-Series. Surge Reduction Filters

UL Recognised Fusible Resistors

METAL OXIDE VARISTORS

Making the Right Choices In Lightning & Surge Arrestors Some Basics:

M ISCELLANEOUS A CCESSORIES O BSTRUCTIONS LIGHTS MISCELLANEOUS ACCESSORIES OBSTRUCTION LIGHTS

AN4275 Application note

Electromagnetic Compatibility ( EMC )

This is a preview - click here to buy the full publication TECHNICAL REPORT

POWER QUALITY (UNIT-3) ELECTRICAL TRANSIENT:

Surge Protection for Surveillance Systems

Plugstrip and Wallmount Surge Protectors

First Principles of a Gas Discharge Tube (GDT) Primary Protector

AN579 Application note

Characterisation of surge suppressors

LV UltraMOV Low Voltage, High Surge Current Varistor Design Guide (Preliminary Version)

4-W HDSL/56Kbps Isolation Card With 130/190V Span Powering. Description & Installation P30140

Protection of PHOTOVOLTAIC SYSTEMS against LIGHTNING and OVERVOLTAGE. Surge Protection Device

Commercial and Industrial LV Power Protection

Transcription:

Data Pack K Issued March 1997 232-5985 Data Sheet Surge protection devices - A technical overview Introduction This data sheet covers the following topics: Types of electrical disturbance. Sources of surges & RFI. Problems caused by surges & RFI. How surges & RFI enter a system. Magnitude of voltage voltages. Surge protection components. Note: Specifications/installation engineers should refer to BS 6651: 1992 - "Code of practice for protection of structures against lightning", so that they are familiar with the details of its guidance and information. Warning: Attention is drawn to the danger of carrying out maintenance work on lightning protection systems or surge protection devices during a storm. Types of electrical disturbances Disturbance Definition Where they occur Spike Short transient deviation of Power, data (commonly line voltage from the and telecom referred to as nominal operating level lines a surge) RFI Radio frequency interference. Power data High frequency burst of and telecom low voltage, low energy lines spikes Overvoltage Long duration rise in voltage ac power lines lasting for 1 / 2 s. or more Surge Short duration rise in voltage ac power lines lasting for less than 1 / 2 s. Undervoltage Long duration decrease in ac power lines voltage lasting for 1 / 2 s or more. Sag Short duration decrease in ac power lines voltage lasting for less than 1 / 2 s. Power cut Complete loss of power ac power lines Note: "Spikes" are often referred to as "surges" or "transients" which, by the above definition, is incorrect. However, this is common and accepted practice and the term "surge" is used to mean "spike" throughout this data sheet. Voltage surges are momentary increases in the normal working voltage of a system. Often referred to as "spikes", or "transient overvoltages", these surges can appear on power cables and data/telephones cables alike, causing anything from data loss to the total destruction of. They are generally associated with radio frequency interference (RFI). Sources of surges and RFI Lightning Power stations and sub-stations during transformer tap switching Power station and sub-station faults Distribution line faults Power-cross faults Generators Factory Photocopiers Air conditioners Refrigerators Electric drills Lift drive motors Induction from earth bonding tapes Switching of fluorescent lights Fuses blowing. Most of these sources incorporate components that switch power on and off in some way and, therefore, create switching surges. These surges exhibit fast rise and fall times and are one of the major causes of problems for computers. Problems caused by surges and RFI Spurious crashing of computer Corruption of data being transferred over communication cables Failure of power and interface circuits High energy surges, on power or communication lines, can cause immediate hardware failure. Low energy surges can cause gradual component degradation leading to eventual and unexpected failure of hardware. How surges and RFI enter a system Conduction via. cabling including power-cross faults (contact between power and communication cables). Direct lightning strike to the building structure, radio antennae and external cabling. (Figure 1) Induction from nearby surge energy, commonly from localised lightning strikes. (Figures 2, 3 and 4) The worst voltage surges are usually caused by nearby lightning activity (lightning does not need to hit building or cabling systems to induce massive voltage surges) and can reach up to 6,000V within a building's cabling system, with potential current surges of up to 3,000A.

Direct coupling Surge energy present on incoming cables Generally caused by lightning strikes, power distribution fault or power-cross Direct input of energy to. Should a building actually have a lightning conductor scheme to protect its structure, then a lightning strike onto this scheme will generate a large electromagnetic pulse of energy, which will be picked up by nearby cables in the form of a destructive voltage surge. Figure 1 Direct coupling Resistive coupling (ground potential rise) Potential difference between earths of connected buildings Caused by nearby lightning strikes Communication interface circuits stressed by endto-end earth difference. HELP!! Figure 4 Resistive coupling Earth voltages at each end of the cable differ by several hundred kv. Inductive coupling Electromagnetic field created by flow of current through a conductive path Caused by lightning strikes to tall objects, typically trees, and radio antennae Surge currents are induced in nearby power and communication cables. Figure 2 Inductive coupling Magnetic Field Induced loop current AGH! Comms Surge current flows along cable and discharges into ports Ground potential 0 Distance from strike point Comms The lightning causes a massive raise in ground voltage in the immediate vicinity. This rise is picked up by electrical earthing systems (earthed pipework, etc.) and travels around the buildings electrical system, causing damage to any electronics in its path. Any data or telecoms cables connecting the affected building to a second building will allow the lightning currents to travel into that building and cause damage there as well. Signal line Lightning conductor earth tape or power cable (source of noise, high dv/dt) Effective capacitance between conductors, C Capacitively coupled current flows across gap, i=c(dv/dt) Lighting discharge current running down parallel path. Building metal work Power & data cables Capacitive coupling Capacitance between structural protection earth tape and nearby signal (or power) cable allows fast-transient surge energy to flow across gap. Caused by direct lightning strikes to building's lightning conductors. Some of the surge energy is picked up by cabling. Figure 3 Capacitive coupling Signal cable Lightning conductor Earth tape (down conductor) Magnitude of voltage surges Voltage surges on cabling systems, however caused, will be limited in magnitude by the insulation of the cable itself and any electrical or electronic connected to that cable. In other words, if a rising voltage was applied to a cabling system, a point would come where the insulation of either the cable itself, or connected to it would break down and the voltage would "flash over", thus preventing it rising any further. IEC 664 defines practical limits for insulation withstand for cabling system within a building. This standard, in conjunction with IEEE C62.41, in which measurements of induced voltage surges on cabling systems are discussed, tells us the maximum voltage surge that is likely to travel along a cable and, hence, the maximum voltage surge that a surge protection device () will have to divert successfully to protect the connected to the cabling system. IEEE C62.41 tells us that the largest surge that is likely to appear on the main power distribution board for a building is 6,000V and 3,000Amps. Hence, an device fitted here would have a safely divert this surge to protect connected to that distribution board. The standard goes on to explain that the maximum surge currents caused by lightning are limited by the impedance of the cabling system, which is related to the current rating of the circuit. 2

A low impedance 1,000Amp busbar distribution board could possibly carry 3,000Amps of lightning induced current, where as, a higher impedance 30amp twin and earth branch circuit, some distance away from the main incoming distribution board, could only pass 200Amps of lightning current, due to its higher impedance. Figure 5 High voltage supply cables HV to LV Transformer High system exposure voltage surge categories for mains power systems (BS6651:1992, appendix C) Category C (mains) 10kV/10kA Category B (mains) 6kV/3kA Local branch feeder >20m from transformer Category A (mains) 6kV/500A Lightning induced voltage surges can rise from zero to up to 6,000V in around 0.000001 seconds (1 microsecond). Any surge diverting component must operate quickly enough to prevent the voltage surge from passing through. It is for this reason that fuses and circuit breakers do not provide protection. They simply do not work quickly enough. Components used in modern s are usually selected from three main types:- 1. Gas discharge tubes, (Figure 6) 2. Metal oxide varistors, (Figure 7) 3. High sped clamping diodes, (Figure 8) Figure 6 232-5985 GDT waveform and circuit symbol Outbuilding Power Board Branch feeder >20m from transformer Volts Surge protection devices () are designed to safely divert these voltages and current surges away from. For the purposes of specifying s, location categories are used which determine the position in which the can be safely used (Figure 5). For mains power systems,categories A,B and C are used, where as, for data/telephone cables, all s should be designed for use in category C. s designed for use in these areas should be tested to protect against the maximum voltage and current surges they are likely to suffer in their category. s not tested to fit into these categories will only provide limited protection and the they are installed to protect may still suffer damage. time Gas discharge tubes can handle very high surge currents, but are relatively slow to turn on, which means that they let through a lot of surge before they operate. Figure 7 Volts MOV waveform and circuit symbol Surge protection components When selecting surge protection components for use in a surge protector, current technology forces the designer to chose between high current handling capability and high speed operation. Surge protection schemes for buildings need to ensure that dangerous surge currents entering a building are reduced to a safe level stage by stage. The let-through voltage of an in each category is an important parameter when designing protection for in the building. Most modern electronic will meet various safety standards such as BS7002, EN60950 or IEC1010 which provide for the to be able to withstand test voltages for electric strength. The test voltage varies according to the type of and the type of test. Earth products meeting BS7002, with a working voltage of less than 250Vrms are tested at 1500V. Current Metal oxide varistors can handle a fairly high surge currents, but their clamping voltage rises the more surge current that passes through. Figure 8 Volts Zener diode waveform and circuit symbol Note: Surge protection devices have a defined life and will not withstand unlimited numbers of surges. Let-through voltages for mains s should ensure that the is not subject to surges in excess of that for which they are designed. Current High speed clamping diodes can only handle relatively small surge currents, but they do have very accurate voltage clamping performance. 3

Applying a building surge protection scheme Mains When applying surge protection devices to a mains power system, the ability to withstand voltage surges of the system taken as a whole should be considered, i.e. the surge protection device () should be matched to limit any surge voltages to a level considered safe for the weakest component in the system. The should also be designed to safely divert the maximum surge current that the system it is installed on is likely to see, i.e. its installation category should be considered, A, B or C (Figure 5). Category C level protection - first line of defence - should be considered first and foremost - this protection is installed where cables enter the building and is designed to divert most of the surge energy safely to earth. - installed on the incoming power distribution board, modems, CCTV cables etc. Category B level protection - "second line of defence" - removes more of the energy leaving a relatively harmless spike - removes surges picked up inside the building - installed on power distribution sub-panels Category A level protection - "last line of defence" - used to suppress remaining surge energy and absorb RFI for particularly sensitive - installed on the load side of socket outlets, at computer terminals and workstations etc. Generally, most low voltage power systems (240/415V) and the electronic and electrical designed to connect to them, will safely withstand voltage surges of twice their normal peak operating voltage, i.e. around 700V for 240V systems, (8/20µs waveshape), i.e. 8µs rise time and 20µs fall time. IP rating Temperature/ humidity System impairment IP## for internal applications IP 65 for outdoor applications Suitable for environment The should not interfere with the normal operation of the system into which it is connected. Note:Gas discharge tubes should not be connected across mains cables as they can short circuit the supply. * As tested on the connection terminals of the complete, when tested with the 1.2/50µs voltage and 8/20µs current waveforms appropriate to their location, e.g. 6kV/3kA for Category B. ** The let through voltage should protect on all modes. Sometimes only the phase to earth value is quoted. *** Peak surge current is an indication of the lifetime of the complete, e.g. a device that will handle a peak surge of 20kA will withstand many lightning induced currents of 3kA. Installing mains power s There are two types of products. Shunt connecting s are designed for parallel connection to the mains supply, whilst in-line connecting s are designed for series connection between the supply and. Specifications for a mains power Criteria Performance Let-through voltage* <1100V suggested for protecting general office Modes of operation** Phase to neutral, phase to earth, neutral to earth Peak surge current** Cat B > 20kA Cat A > 5kA Leakage current <0.5mA (phase to earth) Indication Visual indication of status, including indication of reduced performance Volt-free contact This should be provided for high risk applications, where remote indication of reduced protection is required 4

Shunt connecting s Long connecting leads will impair the effectiveness of the installation, (1m of 16mm 2 earthing cable can have over 300V generated along it's length when a surge of 6kV/3kA is applied to it). Hence, the should be mounted and connected, as close to the electrical system it is to protect, as is possible. Figure 9 Typical shunt connection details Distribution Board Busbars Connecting Cable Phase, Neutral and Earth Outgoing Way Incoming Switch Feed to protection Example 1. Connection to Distribution Board Connecting Cable Phase, Neutral and Earth Fused spur 20A Fuse Switch Feed to protection Junction Box Example 2. Connection to Fused spur Connecting Cable L,N & E Power terminals Power feed Example 3. Connection to Terminals In-line connecting s Due to the chance of picking up voltage surges in cable runs via inductive and capacitive coupling, in-line connecting s should be connected as close to the to be protected as possible. Figure 10 In-line connecting connection details L N E Fused Power Feed Power Terminals 5

Data When applying surge protection devices to a data/telecomms system, the surge protection device () should be matched to limit any surge voltages to a level considered safe for the weakest component in the system. The should also be designed to safely divert the maximum surge current that it is likely to see on the system it is installed in. All data cables leaving the building are considered to be in Category C, as the slower surges (10/700µs i.e. 10µs rise time, 700µs fall time) seen on data/telecom cables are not attenuated by cable length to the same extent as a mains power surge is by it's cable. The steady state voltage on telephone lines is around 50V, but the voltage applied to produce ringing can rise to a maximum of around 145V. Hence, any surge protection device designed to operate on dial-up PSTN lines, should clamp voltage surges at a maximum of around 290V (let through) with a minimum of around 160V (10/700µs), so that it does not interfere with the ringing voltage. It is important to consider the performance of the complete and claims that devices will react in 10 nanoseconds are misleading because they refer only to the components inside the. The impedance of even the short connections between the terminals of the and its internal components make such a performance impossible. Specifications for a data/telecomms Criteria Performance Let-through voltage* Less than twice the peak operating the voltage of the circuit into which the is installed. For dial-up PSTN lines, let through voltage should be between 160V and 290V Peak surge current** Cat C high 10kA Cat C low 2.5kA System impairment*** The should not interfere with the normal operation of the system into which it is installed Insertion loss Expressed as an equivalent cable run length Bandwidth Normally expressed at the ~ -3dB point in a 50Ω system In-line resistance Note: If the value for in-line resistance is 0, then there is a good chance that the barrier will not operate at all under some conditions, leaving the system unprotected. Voltage standing VSWR is an indication of how wave ratio radio the protector will affect the network Shunt capacitance This will affect the bandwidth Humidity/temperature The max./min. values should be quoted. * As tested on the connection terminals of the complete, when tested with the 10/700µs voltage and 8/20µs current waveforms appropriate to their location, e.g. 5kV/125A for Category C., high. ** Peak surge current is an indication of the lifetime of the complete e.g. a device that will handle a peak surge of 10kA will withstand many lightning induced currents of 125A. *** Oftel, the telecomms watchdog, specifies that connected between the user side of the telecom termination frame and the telephone exchange should comply with Oftel Apparatus Approval Number NS/G/23/L/100005. Installing data/telecomms s Generally, all s designed for protecting data and telephone systems connect in-line. The should be located either as close to the it protects, or as close to the main power earth for the protected as possible. The length of the connection to the electrical earth of the should be no longer than 1m in length. Connection of this earth cable can be made to either the earth terminal of the itself, or to the earth bar of the electrical power supply feeding the. Figure 11 Connection of data/telecomms earth Data Telephone Line Earth Connection Earth Connection Distribution Board Earth Bar Power Supply ENL Power Supply Example 1. Connection to Earth Data Telephone Line Example 2. Connection to Power Board Earth RS components gratefully acknowledges the help and advice of Bowthorpe EMP Ltd and Telematic Ltd in the preparation of this data sheet. The information provided in RS technical literature is believed to be accurate and reliable; however, RS Components assumes no responsibility for inaccuracies or omissions, or for the use of this information, and all use of such information shall be entirely at the user s own risk. No responsibility is assumed by RS Components for any infringements of patents or other rights of third parties which may result from its use. Specifications shown in RS Components technical literature are subject to change without notice. RS Components, PO Box 99, Corby, Northants, NN17 9RS Telephone: 01536 201234 An Electrocomponents Company RS Components 1997