MINI MCR-SL-CVS NC

Similar documents
MINI MCR-SL-RPS-I-I. Repeater power supply, active. Data sheet. 1 Description

MINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description

MINI MCR-SL-PT100-UI. Active resistance thermometer measuring transducer. Data sheet. 1 Description

MINI MCR-SL-PT100-UI-200

MINI MCR-SL-MUX-V8-FLK 16

MINI MCR-SL-UI-2I-NC. Extract from the online catalog. Order No.:

MINI MCR-SL-UI-2I(-SP)(-NC)

ETD-BL-1T-OFF-CC- 10S

MINI MCR-SL-PT100-UI(-SP)(-NC)

Extract from the online catalog

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

MINI MCR-SL-UI-REL(-SP)

Extract from the online catalog

MINI MCR-2-U-I4(-PT) 3-way signal conditioner. Data sheet. 1 Description

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description

MACX MCR-SL-(2)I-2)I-ILP(-SP)

MACX MCR-EX-SD LP(-SP)

PSR-PS21. SIL coupling relay. Data sheet. 1 Description

RAD-DAIO6-IFS. I/O extension module, 1 analog input/output, 2 digital wide-range inputs/outputs. INTERFACE Data sheet.

PHOENIX CONTACT - 12/2007

MACX MCR-EX-SL-NAM-R(-SP)

PHOENIX CONTACT - 05/2007

MACX MCR-EX-SL-NAM-2RO(-SP)

Power manual for MACX Analog, MACX Analog Ex, MACX PL, MINI Analog, and MINI Analog Pro signal conditioners. User manual

PHOENIX CONTACT Pin. SUBCON-PLUS M ARCNET, MULTI/MININET (B&R), SYSTEM 2003 (B&R), P-NET SUCONET K1, K2 (EATON/Moeller),

PHOENIX CONTACT - 01/2008

PI-EX-ME-2NAM/COC-24VDC

ETD-BL-1T-230(-PT) Multifunctional time relay with various functions and adjustable times. Data sheet. 1 Description

SUBCON-PLUS-PROFIB...

PI-EX-ME-2NAM/COC-120VAC

MINI MCR-2-RTD-UI(-PT)(-C)

PSR-PC20. SIL coupling relay. Data sheet. 1 Description

PHOENIX CONTACT Features

STEP-PS/1AC/24DC/1.75

Redundancy Module QUINT-DIODE/40

MACX MCR-EX-SL-RPSSI-I(-SP)

RAD-PT100-4-IFS. I/O extension module, 4 temperature inputs (Pt 100) Data sheet. 1 Description

EMD-SL-LL-230. Electronic monitoring relay for level monitoring of conductive liquids. INTERFACE Data sheet _en_04. 1 Description.

MACX MCR-EX-SL-2NAM-T(-SP)

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

PHOENIX CONTACT - 07/2006

PHOENIX CONTACT - 02/2008

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

MACX MCR-EX-SL-RPSS-2I-2I

MINI-PS AC/10-15DC/8

RAD-WHG/WLAN-XD. WirelessHART gateway with integrated WLAN (802.11b/g) INTERFACE Data Sheet 2720_en_C. 2 Features. 1 Description

QUINT-BUFFER/24DC/24DC/40

PSI-MODEM-SHDSL/SERIAL

MACX MCR-EX-SL-RTD-I...

onlinecomponents.com

PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

QUINT-PS-3x AC/24DC/10

PSM-ME-RS485/RS485-P. Repeater for RS wire bus systems. Data sheet. 1 Description

TRIO-DIODE/12-24DC/2X10/1X20

PSR UC/ESAM4/3X1/1X2/B

PSI-MODEM-SHDSL/PB. Broadband PROFIBUS extender, SHDSL PROFIBUS leased line modem. Data sheet _en_03. 1 Description. 1.

EMD-FL-C-10. Electronic monitoring relay for overcurrent and undercurrent monitoring of direct and alternating current in single-phase networks

SATEL-LP-AI4. I/O extension module, 4 analog current inputs. Data sheet. 1 Description

IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

Loop-powered Transmitter for Thermocouple Type K (NiCr-Ni)

UNO-PS/1AC/12DC/30W. Primary-switched power supply unit. Data sheet. 1 Description

PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B

PHOENIX CONTACT - 01/2007

MINI-DC-UPS/12DC/4. Extract from the online catalog. Order No.:

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1

PSR DC/ESP4/2X1/1X2

1-Phase Power Supply, Primary Switch Mode for Use in Potentially Explosive Areas QUINT-PS AC/24DC/5/EX

IB IL 24/48 DOR 2/W-XC-PAC

QUINT-PS/ 1AC/24DC/ 5

QUINT-PS AC/24DC/10

ILBIB24DO16-DSUB. Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

TRIO-PS/1AC/24DC/20. Extract from the online catalog. Order No.:

Extract from the online catalog

QUINT-PS/ 1AC/24DC/20/CO

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

QUINT-DC-UPS/24DC/40. Extract from the online catalog. Order No.:

Interface technology and switching devices

This data sheet is only valid in association with the IL SYS INST UM E user manual.

PHOENIX CONTACT - 11/2007. This data sheet is only valid in association with the IB IL SYS PRO UM E user manual.

QUINT-DC-UPS/24DC/10. Extract from the online catalog. Order No.:

VL BPC 100. Valueline configurable box PC. Data sheet 3063_en_E. 1 Description. 2 Features

PSI-MOS-PROFIB/FO 850 T

Voltage monitoring relays CM-ESS.1 For single-phase AC/DC voltages

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

FL MC 2000E (SM40) LC

STEP-PS/1AC/24DC/2.5. Extract from the online catalog. Order No.: DIN rail power supply of 24 V DC/2.5 A, primary switched, single phase.

Easy Analog RNB130. Technical Information. Primary switched-mode power supply

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

ASI QUINT /2.4 EFD

PHOENIX CONTACT - 10/2009

Termination Board FC-GPCS-SAI16-PF. Features. Assembly. Function. Connection. SAI-1620m HART 24 V DC (I), 24 V DC (II) Fault. Zone 0, 1, 2 Div.

VL BPC MINI. A configurable industrial computer platform. Data sheet 2930_en_F. 1 Description. 2 Features

PSR-SCP- 24DC/SSM/2X1 PSR-SPP- 24DC/SSM/2X1

Transcription:

Constant voltage source Data sheet 105264_en_01 PHOENIX CONTACT 2013-04-03 1 Description Configurable constant voltage source for generating highprecision constant voltages. The voltage supply is also the input voltage. It is between 9.6 V DC and 30 V DC. The DIP switches accessible from the side of the housing allow configuration of the 10 V DC, 7.5 V DC, 5 V DC and 2.5 V DC output voltages. Output and supply (input) are are electrically isolated from one another. Features Configurable constant voltage source Approval for Ex-zone 2 (na) Screw or spring-cage connection can be provided NOTE: Correct usage in potentially explosive areas The module is a category 3 item of electrical equipment. It is absolutely vital to follow the instructions provided here during installation and observe the information in the "Safety regulations and installation notes". Make sure you always use the latest documentation. It can be downloaded from the product at phoenixcontact.net/products. This data sheet is valid for all products listed on the following page:

2 Table of contents 1 Description... 1 2 Table of contents... 2 3 Ordering data... 3 4 Technical data... 4 5 Safety regulations and installation notes... 6 5.1 Installation notes... 6 5.2 Installation in the Ex area (zone 2)... 6 6 Installation... 7 6.1 Structure... 7 6.2 Block diagram... 7 6.3 Power supply... 7 6.4 Assembly... 8 6.5 Connecting the wires... 8 7 Configuration... 9 7.1 Configuration table... 9 8 Adjustment... 9 105264_en_01 PHOENIX CONTACT 2

3 Ordering data Description Type Order No. Pcs. / Pkt. Constant voltage source, input voltage 9.6-30 V DC, output voltage 10 V, 7.5 V, 5 V, 2.5 V DC, electrically isolated, can be configured via DIP switches, screw connection technology, standard configuration Constant voltage source, input voltage 9.6-30 V DC, output voltage 10 V, 7.5 V, 5 V, 2.5 V DC, electrically isolated, can be configured via DIP switches, spring cage connection technology, standard configuration Constant voltage source, input voltage 9.6-30 V DC, output voltage 10 V, 7.5 V, 5 V, 2.5 V DC, electrically isolated, can be configured via DIP switches, spring cage connection technology, standard configuration MINI MCR-SL-CVS-24-5-10-NC 2902822 1 MINI MCR-SL-CVS-24-5-10-SP-NC 2902823 1 MINI MCR-SL-CVS-24-5-10-SP-NC 2902823 1 Accessories Type Order No. Pcs. / Pkt. DIN rail connector (TBUS), 5-pos., for bridging the supply voltage, can be snapped onto NS 35/... DIN rails according to EN 60715 MCR power terminal block for supplying several MINI Analog modules via the T-connector, with screw connection, maximum current consumption of up to 2 A MCR power terminal block for supplying several MINI Analog modules via the T-connector, with spring-cage connection, maximum current consumption of up to 2 A DIN rail power supply unit, primary-switched mode, slim design, output: 24 V DC / 1.5 A DIN rail power supply unit, primary-switched mode, slim design, output: 24 V DC / 1.5 A, ATEX approval Eight MINI analog signal converters with screw connection method can be connected to a control system using a system adapter and system cabling with a minimum of wiring and very low error risk. Fold up transparent cover for MINI MCR modules with additional labeling option using insert strips and flat Zack marker strip 6.2 mm Label for extended marking of MINI MCR modules in connection with the MINI MCR-DKL ME 6,2 TBUS-2 1,5/5-ST-3,81 GN 2869728 10 MINI MCR-SL-PTB 2864134 1 MINI MCR-SL-PTB-SP 2864147 1 MINI-SYS-PS-100-240AC/24DC/1.5 2866983 1 MINI-PS-100-240AC/24DC/1.5/EX 2866653 1 MINI MCR-SL-V8-FLK 16-A 2811268 1 MINI MCR DKL 2308111 10 MINI MCR-DKL-LABEL 2810272 10 105264_en_01 PHOENIX CONTACT 3

4 Technical data Input Voltage input signal Output Max. voltage output signal Configurable/programmable Short-circuit current Ripple Supply Nominal supply voltage Supply voltage range Max. current consumption Power consumption 9.6 V DC... 30 V DC 10 V DC 7.5 V DC 5 V DC 2.5 V DC Yes, preconfigured approx. 32 ma < 20 mv PP 24 V DC 9.6 V DC... 30 V DC (The T connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) < 25 ma (10 V output with 30 ma load at 24 V DC IN) < 65 ma (10 V output with 30 ma load at 9.6 V DC IN) < 50 ma (10 V voltage output with 30 ma load at 12 V DC IN) < 20 ma (10 V voltage output with 30 ma load at 30 V DC IN) < 600 mw (at 24 V IN) < 624 mw (at 9.6 V IN) < 564 mw (At 12 V IN) < 540 mw (At 30 V IN) General data Maximum transmission error 0.1 % (of final value) 0.5 % (Without adjustment) Temperature coefficient, typical < 0.002 %/K Maximum temperature coefficient < 0.01 %/K Electrical isolation Basic insulation according to EN 61010 Surge voltage category II Mounting position Any Degree of protection IP20 Pollution degree 2 Rated insulation voltage 50 V AC/DC Dimensions W / H / D 6.2 mm / 93.1 mm / 102.5 mm Type of housing PBT green Connection data Screw connection Spring-cage conn. Conductor cross section, solid 0.2 mm²... 2.5 mm² 0.2 mm²... 2.5 mm² Conductor cross section, stranded 0.2 mm²... 2.5 mm² 0.2 mm²... 2.5 mm² Stripping length 12 mm 8 mm Ambient conditions Ambient temperature (operation) -20 C... 65 C Ambient temperature (storage/transport) -40 C... 85 C 105264_en_01 PHOENIX CONTACT 4

Conformance with EMC Directive 2004/108/EC Noise immunity according to EN 61000-6-2 When being exposed to interference, there may be minimal deviations. Noise emission according to EN 61000-6-4 Conformance / approvals Conformance ATEX UL, USA / Canada UL, USA / Canada CE-compliant II 3 G Ex na IIC T4 Gc X 508 listed Class I, Div. 2, Groups A, B, C, D T5 applied for 105264_en_01 PHOENIX CONTACT 5

5 Safety regulations and installation notes 5.1 Installation notes The category 3 device is suitable for installation in the zone 2 potentially explosive area. It fulfills the requirements of EN 60079-0:2009 and EN 60079-15:2010. Installation, operation, and maintenance may only be carried out by qualified electricians. Follow the installation instructions described. When installing and operating the device, the applicable regulations and safety directives (including national safety directives), as well as general technical regulations, must be observed. The technical data is provided in this package slip and on the certificates (conformity assessment, additional approvals where applicable). It is not permissible to open or modify the device. Do not repair the device yourself but replace it with an equivalent device. Repairs may only be carried out by the manufacturer. The manufacturer is not liable for damage resulting from violation. The IP20 degree of protection (IEC 60529/EN 60529) of the device is intended for use in a clean and dry environment. Do not subject the device to any load that exceeds the described limits. The device is not designed for use in atmospheres with a danger of dust explosions. 5.2 Installation in the Ex area (zone 2) Observe the specified conditions for use in potentially explosive areas. The device must be installed in a housing (control or distributor box) which meets the requirements of EN 60079-15 and provides at least IP54 (EN 60529) degree of protection. During installation and when connecting the supply and signal circuits, observe the requirements of EN 60079-14. Devices may only be connected to circuits in zone 2 if they are suitable for operation in Ex zone 2 and for the prevailing conditions at the place of use. In potentially explosive areas, terminals may only be snapped onto or off the DIN rail connector and wires may only be connected or disconnected when the power is switched off. The device must be stopped and immediately removed from the Ex area if it is damaged, has been subjected to an impermissible load, has been stored incorrectly, or if it malfunctions. You can download the latest documents for these devices from www.phoenixcontact.net/products. 105264_en_01 PHOENIX CONTACT 6

6 Installation 6.2 Block diagram NOTE: electrostatic discharge! The device contains components that can be damaged or destroyed by electrostatic discharge. When handling the device, observe the necessary safety precautions against electrostatic discharge (ESD) according to EN 61340-5-1 and EN 61340-5-1. OUT OUT OUT U OUT U + 1 5 + GND 1 GND 1 2 6 + 3 7 + 6.1 Structure 4 8 5 Figure 1 4 www.phoenixcontact.com 3 Serial No. Structure 32825 Blomberg, Germany Ord. No.: 29 02 82 2 MINI MCR-SL-CVS-24-5-10-NC IN: 9,6...30V DC OUT: 2,5VDC, 5VDC, 7,5VDC, 10VDC = IN: 9,6...30VDC T 20...+65 C / -4...+149 F 1. Output: constant voltage 2. Potentiometer for adjustment 3. Cover 4. Groove for ZBF 6 zack marker strip 5. Input/supply voltage 6. Connection for DIN rail connector 7. Universal snap-on foot for EN DIN rails 8. DIP switch S1 2 amb ON S1 Constant OFF OUT U GND 1 Voltage Source OUT U GND 1 + 5 1 + - 6 2-7 3 + 8 4 1 6 II 3 G Warning Do n ot seperate when energized 1 5 Ex na II C T4 Gc X 7 1 8 Figure 2 Block diagram 6.3 Power supply Zone 2 NOTE: Never connect the supply voltage directly to the DIN rail connector. It is not permitted to draw power from the DIN rail connector or from individual modules. Supply via the MINI Analog Module Where the total current consumption of the aligned modules does not exceed 400 ma, the power can be supplied directly at the connection terminal blocks of the module. A 400 ma fuse should be connected upstream. Supply via a power terminal block The MINI MCR-SL-PTB power terminal block (Order No. 2864134) or the MINI MCR-SL-PTB-SP power terminal block (Order No. 2864147), which are the same shape, are used to feed the supply voltage to the DIN rail connector. A 2 A fuse should be connected upstream. Supply via a system power supply unit The system power supply unit with 1.5 A output current connects the DIN rail connector to the supply voltage and can thus be used to supply several modules from the mains. MINI-SYS-PS-100-240AC/24DC/1.5 (Order No. 2866983) Potentially explosive areas: MINI-PS-100-240AC/24DC/1.5/EX (Order No. 2866653) 105264_en_01 PHOENIX CONTACT 7

6.4 Assembly Screw connection: A B B C A D E www.interface.phoenixcontact.com SerialNo.XXXXXXXX Figure 4 Screw connection Figure 3 Mounting and removing Insert the wire into the corresponding connection terminal block. Use a screwdriver to tighten the screw in the opening above the connection terminal block. Spring-cage connection: Mount the module on a 35 mm DIN rail according to EN 60715. When using the DIN rail connector, first place it into the DIN rail (see A C). It is used to bridge the power supply. It is also absolutely vital that you snap the module and the DIN rail connector into position in the correct direction: the snap-on foot should be at the bottom and the connector on the left. B A 6.5 Connecting the wires The MINI MCR-SL-CVS-24-5-10... is available in two connection versions: Screw terminal blocks (MINI MCR-SL-CVS-24-5-10- NC) Spring-cage terminal blocks (MINI MCR-SL-CVS-24-5- 10-SP-NC) Figure 5 Spring-cage connection www.interface.phoenixcontact.com Serial No. XXXXXXXX Insert a screwdriver into the opening above the connection terminal block. Insert the wire into the corresponding connection terminal block. 105264_en_01 PHOENIX CONTACT 8

7 Configuration You set the constant output voltage with DIP switch S1 (see table). Standard Configuration If it is an "NC version", the device has the standard configuration: 10 V constant output voltage (all DIP switches in the "off" position). 7.1 Configuration table OUT = ON DIP S1 1 2 10 V 7.5 V 5 V 2.5 V 8 Adjustment A potentiometer is located underneath the cover; this is used for fine adjustment of the analog signals once the configuration of the DIP switches has been modified. The transmission error without adjustment is < 0.5 %. You can use the potentiometer to adjust the error to < 0.1 %. You require measuring equipment with the corresponding accuracy for exact adjustment! The device is adjusted via its output end value: Connect the supply voltage. Set the exact value of the configured output signal with the potentiometer. 105264_en_01 PHOENIX CONTACT GmbH & Co. KG 32823 Blomberg Germany 9 www.phoenixcontact.com