Operating Instructions Proline Promass A 100 Modbus RS485

Similar documents
Operating Instructions Proline Promass I 100 Modbus RS485

Operating Instructions Proline Promass A 100 EtherNet/IP

Operating Instructions LPGmass Modbus RS485

Operating Instructions Proline Promass F 100 PROFIBUS DP

Operating Instructions Proline Promass F 100 PROFINET

Proline Promass F 100 EtherNet/IP

Proline Promass E 100 Ethernet/IP Coriolis Flowmeter

Operating Instructions Proline Promass G 100 PROFIBUS DP

Proline Prosonic Flow B 200 HART

Operating Instructions Proline Promag H 100 EtherNet/IP

Proline Promass E 500 Coriolis Flowmeter Modbus RS485

Operating Instructions Proline Promass F 300 EtherNet/IP

Operating Instructions Proline Promag P 100 EtherNet/IP

Proline Promass X 300 Coriolis Flowmeter EtherNet/IP

Operating Instructions Proline Promag H 100 PROFINET

Brief Operating Instructions Proline Prosonic Flow B 200

Operating Instructions Proline t-mass T 150 HART

Proline Promass Q 300 Coriolis Flowmeter Modbus RS485

Operating Instructions Proline Promag E 100 EtherNet/IP

Operating Instructions Proline Promag P 100 PROFINET

Proline Promag P 200 HART

Operating Instructions Proline Promag D 400 Modbus RS485

Operating Instructions Proline Promag L 400 Modbus RS485

Operating Instructions Proline Promag D 400 EtherNet/IP

Operating Instructions Nanomass Gas Density

Proline t-mass A 150

Operating Instructions Proline Prowirl F 200 HART

Operating Instructions Proline Promag L 400 HART

Operating Instructions Proline Promag W 400 PROFIBUS DP

Operating Instructions Proline Promag P 300 HART

Proline 500 Digital HART Transmitter with Coriolis Sensor

Operating Instructions Proline Promag P 300 PROFINET

Operating Instructions Dosimag Modbus RS485

Operating Instructions Soliswitch FTE20

Brief Operating Instructions Micropilot NMR84

Brief Operating Instructions Proline 300 HART

Proline 300 Modbus RS485 Transmitter with Coriolis Sensor

Replacing Spare Parts

Brief Operating Instructions Proline 100 PROFINET

Brief Operating Instructions Cerabar M PMC51, PMP51, PMP55

Proline Promass 80. Operating Instructions. Coriolis Mass Flow Measuring System

BA01236F/00/EN/ Products Solutions Services. ToF Adapter FXA291

Proline Promass 83 E, F & O Operating Instructions

Technical Information Promonitor NRF560

SolConeX extra-low voltage flange socket

Special Documentation Liquicap M FMI51, FMI52

DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions

SMARTLINE RM76 Supplementary instructions

Intrinsically safe batch controller Batching Master 110i

Levelflex FMP53. Brief Operating Instructions. Guided Level-Radar

Brief Operating Instructions Proline Promag W 400

Brief Operating Instructions Deltabar S

PTB 01 ATEX Example / Beispiel / Exemple. Type Operating Instructions

MANUAL Vibracon LVL-A7

PTB 01 ATEX 2064 U, IECEx PTB U. Example / Beispiel / Exemple: Type Operating Instructions

SIWAREX JB Aluminum Housing. Instruction Manual Edition 03/2006

Operating manual. Series 450. Compact thermometer. BA01235O/09/en/

English. Operating Manual. Conductive point level switch MLR120. Retain for later reference. Companies / brands of GHM

MANUAL LML-P, LML-S, LML-Ex

Brief Operating Instructions Proline Promag P 200

Proline Promass 83 FOUNDATION Fieldbus

Safety Instructions Micropilot FMR56/57

Brief Operating Instructions itemp TMT82

DR7100 SERIES Supplementary instructions

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B.

Inductive angle sensor with analog output Ri360P1-DSU35TC-ELi-Exi

PHOENIX CONTACT Pin. SUBCON-PLUS M ARCNET, MULTI/MININET (B&R), SYSTEM 2003 (B&R), P-NET SUCONET K1, K2 (EATON/Moeller),

Safety Instructions Levelflex FMP50/51/52/53/54/55/56/57

Proline Promass 80 PROFIBUS PA

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

OPTIFLUX 6000 Handbook

Scanner 2000 Steam Mass Flow Transmitter

Operating Instructions VEGAMET 381

English. Operating manual. Universal transmitter UT125. Save for later reference. Companies / brands of GHM

Proline Prosonic Flow 93T Portable HART

This guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens).

Technical Information Proline Promag E 100

Proline Promass 83 PROFIBUS DP/PA

Assembly. 1 Compact version with valve plug 2 Short tube version with cable 3 Compact version with M12 plug 4 Short tube version with M12 plug

PV Module Installation Instructions

Technical Information Proline Promag D 400

Proline Promass 80. Operating Instructions. Coriolis Mass Flow Measuring System

V E1B Snap-in I/O Module

EX-RC1 Remote I/O Adapter

IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs

CombiTemp TFRN/TFRH. Operating instructions. Temperature sensor. Operating Instructions: EN.

Technical Information Liquipoint FTW23

Liquiphant T FTL20. Technical Information. Level limit switch for liquids

PanelView Plus/VersaView CE Terminals and Display Modules

PNEUMATIC CRIMPER PC 12-8B OPERATING MANUAL

Installation manual plugs and connectors with screw connection (16/32 A)

Type Quickstart (from device Version 2)

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

High Speed Remote I/O Module

TMT470L Temperature Transmitter

Operating Instructions (Translation) 3. Safety Information. 1. Description. 2. Explosion Protection. Supply module Type 17-21BB-170x

KROHNE 12/ GR Installation and Operating Instructions BM 500

SolConeX Wall-Mounted Socket, 16 A

Proline Promass 40. Operating Instructions. Coriolis Mass Flow Measuring System. BA061D/06/en/

Transcription:

BA01179D/06/EN/01.13 71209755 Valid as of version 01.01.zz (Device firmware) Products Solutions Services Operating Instructions Proline Promass A 100 Modbus RS485 Coriolis flowmeter

Proline Promass A 100 Modbus RS485 Make sure the document is stored in a safe place such that it is always available when working on or with the device. To avoid danger to individuals or the facility, read the "Basic safety instructions" section carefully, as well as all other safety instructions in the document that are specific to working procedures. The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser Sales Center will supply you with current information and updates to these Instructions. 2 Endress+Hauser

Proline Promass A 100 Modbus RS485 Table of contents Table of contents 1 Document information... 5 1.1 Document function... 5 1.2 Symbols used... 5 1.2.1 Safety symbols... 5 1.2.2 Electrical symbols... 5 1.2.3 Tool symbols... 6 1.2.4 Symbols for certain types of information... 6 1.2.5 Symbols in graphics... 6 1.3 Documentation... 7 1.3.1 Standard documentation... 7 1.3.2 Supplementary device-dependent documentation... 7 1.4 Registered trademarks... 7 2 Basic safety instructions... 8 2.1 Requirements for the personnel... 8 2.2 Designated use... 8 2.3 Workplace safety... 9 2.4 Operational safety... 9 2.5 Product safety... 9 3 Product description... 10 3.1 Product design... 10 3.1.1 Device version with Modbus RS485 communication type... 10 4 Incoming acceptance and product identification... 11 4.1 Incoming acceptance... 11 4.2 Product identification... 12 4.2.1 Transmitter nameplate... 12 4.2.2 Sensor nameplate... 13 4.2.3 Promass 100 safety barrier - nameplate... 14 4.2.4 Symbols on measuring device... 14 5 Storage and transport... 15 5.1 Storage conditions... 15 5.2 Transporting the product... 15 5.3 Packaging disposal... 16 6 Installation... 17 6.1 Installation conditions... 17 6.1.1 Mounting position... 17 6.1.2 Requirements from environment and process... 19 6.1.3 Special mounting instructions... 20 6.2 Mounting the measuring device... 23 6.2.1 Required tools... 23 6.2.2 Preparing the measuring device... 23 6.2.3 Mounting the measuring device... 24 6.3 Post-installation check... 24 7 Electrical connection... 25 7.1 Connection conditions... 25 7.1.1 Required tools... 25 7.1.2 Requirements for connecting cable... 25 7.1.3 Terminal assignment... 27 7.1.4 Pin assignment, device plug... 29 7.1.5 Shielding and grounding... 30 7.1.6 Preparing the measuring device... 30 7.2 Connecting the measuring device... 30 7.2.1 Connecting the transmitter... 31 7.2.2 Connecting the Safety Barrier Promass 100... 32 7.3 Hardware settings... 33 7.3.1 Enabling the terminating resistor... 33 7.4 Ensuring the degree of protection... 33 7.5 Post-connection check... 34 8 Operation options... 35 8.1 Overview of operation options... 35 8.2 Structure and function of the operating menu... 36 8.2.1 Structure of the operating menu... 36 8.2.2 Operating philosophy... 37 8.3 Access to the operating menu via the operating tool... 38 8.3.1 Connecting the operating tool... 38 8.3.2 FieldCare... 38 9 System integration... 40 9.1 Overview of device description files... 40 9.1.1 Current version data for the device... 40 9.1.2 Operating tools... 40 9.2 Modbus RS485 information... 40 9.2.1 Function codes... 40 9.2.2 Register information... 41 9.2.3 Response time... 41 9.2.4 Modbus data map... 41 10 Commissioning... 44 10.1 Function check... 44 10.2 Establishing a connection via FieldCare... 44 10.3 Configuring the measuring device... 44 10.3.1 Setting the system units... 44 10.3.2 Selecting and setting the medium... 47 10.3.3 Configuring communication interface... 48 10.3.4 Configuring the low flow cut off... 50 10.3.5 Configuring the partial filled pipe detection... 51 Endress+Hauser 3

Table of contents Proline Promass A 100 Modbus RS485 10.4 Advanced settings... 52 10.4.1 Defining the tag name... 52 10.4.2 Calculated values... 52 10.4.3 Carrying out a sensor adjustment... 53 10.4.4 Configuring the totalizer... 54 10.5 Simulation... 55 10.5.1 Parameter overview with brief description... 56 10.6 Protecting settings from unauthorized access... 56 10.6.1 Write protection via write protection switch... 56 11 Operation... 58 11.1 Read device locking status... 58 11.2 Reading measured values... 58 11.2.1 Process variables... 58 11.2.2 Totalizer... 59 11.3 Adapting the measuring device to the process conditions... 60 11.4 Performing a totalizer reset... 60 12 Diagnostics and troubleshooting... 62 12.1 General troubleshooting... 62 12.2 Diagnostic information via light emitting diodes... 62 12.2.1 Transmitter... 62 12.2.2 Safety Barrier Promass 100... 63 12.3 Diagnostic information in FieldCare... 63 12.3.1 Diagnostic options... 63 12.3.2 Calling up remedy information... 64 12.4 Diagnostic information via communication interface... 64 12.4.1 Reading out diagnostic information.. 64 12.4.2 Configuring error response mode... 65 12.5 Adapting the diagnostic information... 65 12.5.1 Adapting the diagnostic behavior... 65 12.6 Overview of diagnostic information... 66 12.7 Pending diagnostic events... 68 12.8 Diagnostic list... 68 12.9 Event logbook... 69 12.9.1 Event history... 69 12.9.2 Filtering the event logbook... 69 12.9.3 Overview of information events... 69 12.10 Resetting the measuring device... 70 12.11 Device information... 70 12.12 Firmware history... 71 14 Repair... 73 14.1 General notes... 73 14.2 Spare parts... 73 14.3 Endress+Hauser services... 73 14.4 Return... 73 14.5 Disposal... 73 14.5.1 Removing the measuring device... 73 14.5.2 Disposing of the measuring device... 74 15 Accessories... 75 15.1 Device-specific accessories... 75 15.1.1 For the sensor... 75 15.2 Communication-specific accessories... 75 15.3 Service-specific accessories... 76 15.4 System components... 76 16 Technical data... 77 16.1 Application... 77 16.2 Function and system design... 77 16.3 Input... 77 16.4 Output... 78 16.5 Power supply... 80 16.6 Performance characteristics... 81 16.7 Installation... 84 16.8 Environment... 84 16.9 Process... 85 16.10 Mechanical construction... 87 16.11 Operability... 88 16.12 Certificates and approvals... 89 16.13 Application packages... 90 16.14 Accessories... 90 16.15 Documentation... 91 17 Appendix... 92 17.1 Overview of the operating menu... 92 13 Maintenance... 72 13.1 Maintenance tasks... 72 13.1.1 Exterior cleaning... 72 13.1.2 Interior cleaning... 72 13.2 Measuring and test equipment... 72 13.3 Endress+Hauser services... 72 4 Endress+Hauser

Proline Promass A 100 Modbus RS485 Document information 1 Document information 1.1 Document function These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal. 1.2 Symbols used 1.2.1 Safety symbols Symbol DANGER A0011189-EN WARNING A0011190-EN CAUTION NOTICE A0011191-EN A0011192-EN Meaning DANGER! This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury. WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury. CAUTION! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in minor or medium injury. NOTICE! This symbol contains information on procedures and other facts which do not result in personal injury. 1.2.2 Electrical symbols Symbol A0011197 A0011198 A0017381 A0011200 A0011199 A0011201 Meaning Direct current A terminal to which DC voltage is applied or through which direct current flows. Alternating current A terminal to which alternating voltage is applied or through which alternating current flows. Direct current and alternating current A terminal to which alternating voltage or DC voltage is applied. A terminal through which alternating current or direct current flows. Ground connection A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system. Protective ground connection A terminal which must be connected to ground prior to establishing any other connections. Equipotential connection A connection that has to be connected to the plant grounding system: This may be a potential equalization line or a star grounding system depending on national or company codes of practice. Endress+Hauser 5

Document information Proline Promass A 100 Modbus RS485 1.2.3 Tool symbols Symbol Meaning Allen key A0011221 Open-ended wrench A0011222 1.2.4 Symbols for certain types of information Symbol A0011182 A0011183 A0011184 A0011193 A0011194 A0011195 A0011196 Meaning Allowed Indicates procedures, processes or actions that are allowed. Preferred Indicates procedures, processes or actions that are preferred. Forbidden Indicates procedures, processes or actions that are forbidden. Tip Indicates additional information. Reference to documentation Refers to the corresponding device documentation. Reference to page Refers to the corresponding page number. Reference to graphic Refers to the corresponding graphic number and page number.,, Series of steps Result of a sequence of actions Help in the event of a problem A0013562 1.2.5 Symbols in graphics Symbol Meaning 1, 2, 3,... Item numbers,, Series of steps A, B, C,... Views A-A, B-B, C-C,... Sections -. A0013441 A0011187 A0011188 Flow direction Hazardous area Indicates a hazardous area. Safe area (non-hazardous area) Indicates a non-hazardous area. 6 Endress+Hauser

Proline Promass A 100 Modbus RS485 Document information 1.3 Documentation The following document types are available: On the CD-ROM supplied with the device In the Download Area of the Endress+Hauser Internet site: www.endress.com Download For a detailed list of the individual documents along with the documentation code ( 91) 1.3.1 Standard documentation Document type Technical Information Brief Operating Instructions Modbus RS485 register information Purpose and content of the document Planning aid for your device The document contains all the technical data on the device and provides an overview of the accessories and other products that can be ordered for the device. Guide that takes you quickly to the 1st measured value The Brief Operating Instructions contain all the essential information from incoming acceptance to initial commissioning. Reference for Modbus RS485 register information The document provides Modbus-specific information for each individual parameter in the operating menu. 1.3.2 Supplementary device-dependent documentation Additional documents are supplied depending on the device version ordered: Always comply strictly with the instructions in the supplementary documentation. The supplementary documentation is an integral part of the device documentation. 1.4 Registered trademarks Modbus Registered trademark of SCHNEIDER AUTOMATION, INC. TRI-CLAMP Registered trademark of Ladish & Co., Inc., Kenosha, USA SWAGELOK Registered trademark of Swagelok & Co., Solon, USA Applicator, FieldCare, Field Xpert TM, HistoROM, Heartbeat Technology TM Registered or registration-pending trademarks of the Endress+Hauser Group Endress+Hauser 7

Basic safety instructions Proline Promass A 100 Modbus RS485 2 Basic safety instructions 2.1 Requirements for the personnel The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements: Trained, qualified specialists must have a relevant qualification for this specific function and task Are authorized by the plant owner/operator Are familiar with federal/national regulations Before beginning work, the specialist staff must have read and understood the instructions in the Operating Instructions and supplementary documentation as well as in the certificates (depending on the application) Following instructions and basic conditions The operating personnel must fulfill the following requirements: Being instructed and authorized according to the requirements of the task by the facility's owner-operator Following the instructions in these Operating Instructions 2.2 Designated use Application and media The measuring device described in these Instructions is intended only for flow measurement of liquids and gases. Depending on the version ordered, the measuring device can also measure potentially explosive, flammable, poisonous and oxidizing media. Measuring devices for use in hazardous areas, in hygienic applications or in applications where there is an increased risk due to process pressure, are labeled accordingly on the nameplate. To ensure that the measuring device remains in proper condition for the operation time: Only use the measuring device in full compliance with the data on the nameplate and the general conditions listed in the Operating Instructions and supplementary documentation. Based on the nameplate, check whether the ordered device is permitted for the intended use in the hazardous area (e.g. explosion protection, pressure vessel safety). Use the measuring device only for media against which the process-wetted materials are adequately resistant. If the measuring device is not operated at atmospheric temperature, compliance with the relevant basic conditions specified in the device documentation provided (on the CD-ROM) is absolutely essential. Incorrect use Non-designated use can compromise safety. The manufacturer is not liable for damage caused by improper or non-designated use. NOTICE Danger of breakage of the measuring tube due to corrosive or abrasive fluids. Housing breakage due to mechanical overload possible! Verify the compatibility of the process fluid with the measuring tube material. Ensure the resistance of all fluid-wetted materials in the process. Observe the specified maximum process pressure. Verification for borderline cases: For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any 8 Endress+Hauser

Proline Promass A 100 Modbus RS485 Basic safety instructions warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties. Residual risks The external surface temperature of the housing can increase by max. 20 K due to the power consumption of the electronic components. Hot process fluids passing through the measuring device will further increase the surface temperature of the housing. The surface of the sensor, in particular, can reach temperatures which are close to the fluid temperature. Possible burn hazard due to fluid temperatures! For elevated fluid temperature, ensure protection against contact to prevent burns. 2.3 Workplace safety For work on and with the device: Wear the required personal protective equipment according to federal/national regulations. For welding work on the piping: Do not ground the welding unit via the measuring device. 2.4 Operational safety Risk of injury. Operate the device in proper technical condition and fail-safe condition only. The operator is responsible for interference-free operation of the device. Conversions to the device Unauthorized modifications to the device are not permitted and can lead to unforeseeable dangers. If, despite this, modifications are required, consult with Endress+Hauser. Repair To ensure continued operational safety and reliability, Carry out repairs on the device only if they are expressly permitted. Observe federal/national regulations pertaining to repair of an electrical device. Use original spare parts and accessories from Endress+Hauser only. 2.5 Product safety This measuring device is designed in accordance with good engineering practice to meet state-of-the-art safety requirements, has been tested, and left the factory in a condition in which they are safe to operate. It meets general safety standards and legal requirements. It also complies with the EC directives listed in the device-specific EC Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device. Endress+Hauser 9

Product description Proline Promass A 100 Modbus RS485 3 Product description 3.1 Product design 3.1.1 Device version with Modbus RS485 communication type 1 2 3 4 1 Important components of a measuring device 1 Transmitter housing cover 2 Main electronics module for Modbus RS485 3 Transmitter housing 4 Sensor A0017609 In the case of the device version with Modbus RS485 intrinsically safe, the Safety Barrier Promass 100 forms part of the scope of supply. 10 Endress+Hauser

Proline Promass A 100 Modbus RS485 Incoming acceptance and product identification 4 Incoming acceptance and product identification 4.1 Incoming acceptance A0015502 1 + 2 1 + 2 A0013843 Is the order code on the delivery note (1) identical to the order code on the product sticker (2)? A0013695 A0015502 A0013698 Are the goods undamaged? A0015502 A0013699 Do the nameplate data match the ordering information on the delivery note? A0015502 A0013697 Is the CD-ROM with the Technical Documentation and documents present? Endress+Hauser 11

Incoming acceptance and product identification Proline Promass A 100 Modbus RS485 If one of the conditions is not satisfied, contact your Endress+Hauser Sales Center. 4.2 Product identification The following options are available for identification of the measuring device: Nameplate specifications Order code with breakdown of the device features on the delivery note Enter serial numbers from nameplates in W@M Device Viewer (www.endress.com/deviceviewer): All information about the measuring device is displayed. For an overview of the scope of the Technical Documentation provided, refer to the following: The "Additional standard documentation on the device" ( 7) and "Supplementary device-dependent documentation" ( 7) sections The W@M Device Viewer: Enter the serial number from the nameplate (www.endress.com/deviceviewer) 4.2.1 Transmitter nameplate 7 1 2 3 4 5 6 Order code: Ser. no.: Ext. ord. cd.: i 8 9 13 12 11 10 2 Example of a transmitter nameplate 1 Manufacturing location 2 Name of the transmitter 3 Order code 4 Serial number 5 Extended order code 6 Electrical connection data, e.g. available inputs and outputs, supply voltage 7 Permitted ambient temperature range (T a ) 8 Degree of protection 9 2-D matrix code 10 Document number of safety-related supplementary documentation ( 91) 11 Manufacturing date: year-month 12 CE mark, C-Tick 13 Firmware version (FW) A0017520 12 Endress+Hauser

Proline Promass A 100 Modbus RS485 Incoming acceptance and product identification 4.2.2 Sensor nameplate 1 2 Order code: Ser. no.: Ext. ord. cd.: 3 4 5 6 Ptest: Material: Tm: Size: 7 8 9 10 11 12 13 14 15 16 17 Ta: Date: Patents 19 18 3 Example of a sensor nameplate 1 Name of the sensor 2 Manufacturing location 3 Order code 4 Serial number (Ser. no.) 5 Extended order code (Ext. ord. cd.) 6 Flange nominal diameter/nominal pressure 7 Test pressure of the sensor 8 Nominal diameter of the sensor 9 Sensor-specific data: e.g. pressure range of secondary containment, wide-range density specification (special density calibration) 10 Material of measuring tube and manifold 11 Medium temperature range 12 Degree of protection 13 Approval information for explosion protection and Pressure Equipment Directive 14 Permitted ambient temperature (T a ) 15 Document number of safety-related supplementary documentation ( 91) 16 CE mark, C-Tick 17 Flow direction 18 Manufacturing date: year-month 19 2-D matrix code A0017923 Order code The measuring device is reordered using the order code. Extended order code The device type (product root) and basic specifications (mandatory features) are always listed. Of the optional specifications (optional features), only the safety and approvalrelated specifications are listed (e.g. LA). If other optional specifications are also ordered, these are indicated collectively using the # placeholder symbol (e.g. #LA#). If the ordered optional specifications do not include any safety and approval-related specifications, they are indicated by the + placeholder symbol (e.g. XXXXXX-ABCDE +). Endress+Hauser 13

Incoming acceptance and product identification Proline Promass A 100 Modbus RS485 4.2.3 Promass 100 safety barrier - nameplate 1 2 Safe area NON intrinsically safe circuit (grey terminals) Promass 100 Safety Barrier 8 3 4 5 6 7 Intrinsically safe circuits (blue terminals) HAZARDOUS area i 9 10 11 4 Example of a Safety Barrier Promass 100 nameplate 1 Non-hazardous area or zone 2/div. 2 2 Serial number, material number and 2-D matrix code of the Safety Barrier Promass 100 3 Electrical connection data, e.g. available inputs and outputs, supply voltage 4 Explosion protection approval information 5 Safety warning 6 Communication-specific information 7 Intrinsically safe area 8 Manufacturing location 9 Document number of safety-related supplementary documentation ( 91) 10 Permitted ambient temperature (T a ) 11 CE mark, C-Tick A0017854 4.2.4 Symbols on measuring device Symbol A0011194 A0011199 Meaning WARNING! This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury. Reference to documentation Refers to the corresponding device documentation. Protective ground connection A terminal which must be connected to ground prior to establishing any other connections. 14 Endress+Hauser

Proline Promass A 100 Modbus RS485 Storage and transport 5 Storage and transport 5.1 Storage conditions Observe the following notes for storage: Store in the original packaging to ensure protection from shock. Do not remove protective covers or protective caps installed on process connections. They prevent mechanical damage to the sealing surfaces and fouling in the measuring tube. Protect from direct sunlight to avoid unacceptably high surface temperatures. Storage temperature: 40 to +80 C ( 40 to +176 F), preferable for +20 C (+68 F) Store in a dry and dust-free place. Do not store outdoors. 5.2 Transporting the product!warning Center of gravity of the measuring device is higher than the suspension points of the webbing slings. Risk of injury if the measuring device slips. Secure the measuring device from rotating or slipping. Observe the weight specified on the packaging (stick-on label). Observe the transport instructions on the stick-on label on the electronics compartment cover. A0015606 Observe the following notes during transport: Transport the measuring device to the measuring point in the original packaging. Lifting gear Webbing slings: Do not use chains, as they could damage the housing. For wood crates, the floor structure enables these to be loaded lengthwise or broadside using a forklift. For measuring device > DN 40 (1½ in): lift the measuring device using the webbing slings at the process connections; do not lift at the transmitter housing. Do not remove protective covers or protective caps installed on process connections. They prevent mechanical damage to the sealing surfaces and fouling in the measuring tube. Endress+Hauser 15

Storage and transport Proline Promass A 100 Modbus RS485 5.3 Packaging disposal All packaging materials are environmentally friendly and 100% recyclable: Measuring device secondary packaging: polymer stretch film that conforms to EC Directive 2002/95/EC (RoHS). Packaging: Wood crate, treated in accordance with ISPM 15 standard, which is confirmed by the affixed IPPC logo. or Carton in accordance with European Packaging Directive 94/62EC; recyclability is confirmed by the affixed RESY symbol. Seaworthy packaging (optional): Wood crate, treated in accordance with ISPM 15 standard, which is confirmed by the affixed IPPC logo. Carrying and mounting hardware: Disposable plastic pallet Plastic straps Plastic adhesive strips Dunnage: Paper cushion 16 Endress+Hauser

Proline Promass A 100 Modbus RS485 Installation 6 Installation 6.1 Installation conditions No special measures such as supports are necessary. External forces are absorbed by the construction of the device. 6.1.1 Mounting position Mounting location To prevent measuring errors arising from accumulation of gas bubbles in the measuring tube, avoid the following mounting locations in the pipe: Highest point of a pipeline. Directly upstream of a free pipe outlet in a down pipe. A0015595 Installation in down pipes However, the following installation suggestion allows for installation in an open vertical pipeline. Pipe restrictions or the use of an orifice with a smaller cross-section than the nominal diameter prevent the sensor running empty while measurement is in progress. 1 2 3 4 5 5 Installation in a down pipe (e.g. for batching applications) 1 Supply tank 2 Sensor 3 Orifice plate, pipe restriction 4 Valve 5 Batching tank A0015596 Endress+Hauser 17

Installation Proline Promass A 100 Modbus RS485 DN Ø orifice plate, pipe restriction [mm] [in] [mm] [in] 1 ¹ ₂₄ 0.8 0.03 2 ¹ ₁₂ 1.5 0.06 4 ¹ ₈ 3.0 0.12 Orientation The direction of the arrow on the sensor nameplate helps you to install the sensor according to the flow direction (direction of medium flow through the piping). Orientation Recommendation A Vertical orientation A0015591 B Horizontal orientation, transmitter head up 1) Exception: A0015589 C Horizontal orientation, transmitter head down 2) Exception: D Horizontal orientation, transmitter head at side A0015590 A0015592 1) Applications with low process temperatures may reduce the ambient temperature. To maintain the minimum ambient temperature for the transmitter, this orientation is recommended. 2) Applications with high process temperatures may increase the ambient temperature. To maintain the maximum ambient temperature for the transmitter, this orientation is recommended. Inlet and outlet runs No special precautions need to be taken for fittings which create turbulence, such as valves, elbows or T-pieces, as long as no cavitation occurs ( 19). A0015597 A0015598 Installation dimensions For the dimensions and installation lengths of the device, see the "Technical Information" document, "Mechanical construction" section 18 Endress+Hauser

Proline Promass A 100 Modbus RS485 Installation 6.1.2 Requirements from environment and process Ambient temperature range Measuring device Safety Barrier Promass 100 40 to +60 C ( 40 to +140 F) 50 to +60 C ( 58 to +140 F) (Order code for "Test, certificate", option JM 40 to +60 C ( 40 to +140 F) If operating outdoors: Avoid direct sunlight, particularly in warm climatic regions. System pressure It is important that cavitation does not occur, or that gases entrained in the liquids do not outgas. Cavitation is caused if the pressure drops below the vapor pressure: In liquids that have a low boiling point (e.g. hydrocarbons, solvents, liquefied gases) In suction lines Ensure the system pressure is sufficiently high to prevent cavitation and outgassing. For this reason, the following mounting locations are recommended: At the lowest point in a vertical pipe Downstream from pumps (no danger of vacuum) A0015594 Thermal insulation In the case of some fluids, it is important that the heat radiated from the sensor to the transmitter is kept to a minimum. A wide range of materials can be used for the required insulation. NOTICE Electronics overheating on account of thermal insulation! Observe maximum permitted insulation height of the transmitter neck so that the transmitter head is completely free. Heating NOTICE Electronics can overheat due to elevated ambient temperature! Observe maximum permitted ambient temperature for the transmitter ( 19). Depending on the fluid temperature, take the device orientation requirements into account. Endress+Hauser 19

Installation Proline Promass A 100 Modbus RS485 Heating options If a fluid requires that no heat loss should occur at the sensor, users can avail of the following heating options: Electrical heating, e.g. with electric band heaters Via pipes carrying hot water or steam Via heating jackets Using an electrical trace heating system If heating is regulated via phase angle control or pulse packages, magnetic fields can affect the measured values (= for values that are greater than the values approved by the EN standard (sine 30 A/m)). For this reason, the sensor must be magnetically shielded: the housing can be shielded with tin plates or electric sheets without a privileged direction (e.g. V330-35A). The sheet must have the following properties: Relative magnetic permeability µr 300 Plate thickness d 0.35 mm (d 0.014 in) Vibrations The high oscillation frequency of the measuring tubes ensures that the correct operation of the measuring system is not influenced by plant vibrations. 6.1.3 Special mounting instructions Outlet run for peripheral device If a pressure and temperature measuring device are installed downstream from the measuring device, make sure there is sufficient distance between the two devices. PT TT 3 5 DN 4 8 DN A0016893 PT TT Pressure transmitter Temperature transmitter Rupture disk Make sure that the function and operation of the rupture disk is not impeded through the installation of the device. The position of the rupture disk is indicated on a sticker beside it. For additional information that is relevant to the process ( 86). The existing connecting nozzles are not designed for a rinse or pressure monitoring function. 20 Endress+Hauser

Proline Promass A 100 Modbus RS485 Installation G E 45 F D i A C 1 RUPTURE DISK 3 2 B A0019676 1 Rupture disk label 2 Rupture disk with 1/2" NPT internal thread with 1" width across flat 3 Transport protection Dimensions in SI units DN A B C D E F G [mm] [mm] [in] [in] [mm] [mm] [mm] [mm] 1 Approx.42 AF 1 ½ NPT 77.0 70.0 47.0 178 2 Approx.42 AF 1 ½ NPT 77.0 70.0 47.0 260 4 Approx.42 AF 1 ½ NPT 83.0 83.0 59.5 385 Dimensions in US units DN A B C D E F G [in] [in] [in] [in] [in] [in] [in] [in] ¹ ₂₄ ¹ ₁₂ ¹ ₈ Approx. 1.65 Approx. 1.65 Approx. 1.65 AF 1 ½ NPT 3.0 2.8 1.85 7.01 AF 1 ½ NPT 3.0 2.8 1.85 10.24 AF 1 ½ NPT 3.3 3.2 2.34 15.16!WARNING Limited functional reliability of the rupture disk. Danger to persons from escaping fluids! Do not remove the rupture disk. When using a rupture disk, do not use a heating jacket. Make sure that the function and operation of the rupture disk is not impeded through the installation of the device. Take precautions to prevent damage and danger to persons if the rupture disk is actuated. Observe information on the rupture disk sticker. Endress+Hauser 21

Installation Proline Promass A 100 Modbus RS485 Wall mounting!warning Incorrect sensor mounting Risk of injury if measuring tube breaks The sensor should never be installed in a pipe in a way that it is freely suspended Using the base plate, mount the sensor directly on the floor, wall or ceiling. Support the sensor on a securely mounted support base (e.g. angle bracket). The following mounting versions are recommended for the installation. Vertical Mounted directly on a wall using the base plate, or Device supported on an angle bracket mounted on the wall A0019631 Horizontal Device standing on a solid support base A0019632 Post retainer The post retainer mounting kit is used to secure the device to a pipe or post (order code for "Accessories", option PR). 22 Endress+Hauser

Proline Promass A 100 Modbus RS485 Installation 1 2 3 4 5 6 7 8 13 mm 10 mm 6 Post retainer mounting kit 1 8 x hexagonal nut M8 0.8 2 4 x threaded bolt M8 150 3 1 x post retaining plate 4 1 x post securing plate 5 4 x spring washer M8 6 4 x hexagon bolt M6 20 7 4 x spring washer M6 8 4 x hexagonal nut M6 0.8 A0019746 Zero point adjustment All measuring devices are calibrated in accordance with state-of-the-art technology. The zero point obtained in this way is printed on the nameplate of the measuring device. Calibration takes place under reference conditions ( 81). Therefore, a zero point adjustment in the field is generally not required! ) Experience shows that zero point adjustment is advisable only in special cases: To achieve maximum measuring accuracy even with very low flow rates Under extreme process or operating conditions, e.g.: high process temperature (> 50 C (122 F) high viscosity (> 100 cst) high process pressure (> 20 bar (290 psi)) 6.2 Mounting the measuring device 6.2.1 Required tools For sensor For flanges and other process connections: Corresponding mounting tools 6.2.2 Preparing the measuring device 1. Remove all remaining transport packaging. 2. Remove any protective covers or protective caps present from the sensor. 3. Remove stick-on label on the electronics compartment cover. Endress+Hauser 23

Installation Proline Promass A 100 Modbus RS485 6.2.3 Mounting the measuring device!warning Danger due to improper process sealing! Ensure that the inside diameters of the gaskets are greater than or equal to that of the process connections and piping. Ensure that the gaskets are clean and undamaged. Install the gaskets correctly. 1. Ensure that the direction of the arrow on the nameplate of the sensor matches the flow direction of the fluid. 2. Install the measuring device or turn the transmitter housing so that the cable entries do not point upwards. A0013964 6.3 Post-installation check Is the device damaged (visual inspection)? Does the measuring device conform to the measuring point specifications? For example: Process temperature ( 85) Process pressure (refer to the chapter on "Material load curves" of the "Technical Information" document) Ambient temperature ( 19) Measuring range ( 77) Has the correct orientation for the sensor been selected? According to sensor type According to medium temperature According to medium properties (outgassing, with entrained solids) Does the arrow on the sensor nameplate match the direction of flow of the fluid through the piping ( 18)? Are the measuring point identification and labeling correct (visual inspection)? Is the device adequately protected from precipitation and direct sunlight? Are the securing screw and securing clamp tightened securely? 24 Endress+Hauser

Proline Promass A 100 Modbus RS485 Electrical connection 7 Electrical connection 7.1 Connection conditions 7.1.1 Required tools For cable entries: Use corresponding tools For securing clamp (on aluminum housing): Allen screw 3 mm For securing screw (for stainless steel housing): open-ended wrench 8 mm Wire stripper When using stranded cables: Crimping tool for wire end ferrule 7.1.2 Requirements for connecting cable The connecting cables provided by the customer must fulfill the following requirements. Electrical safety In accordance with applicable federal/national regulations. Permitted temperature range 40 C ( 40 F)... 80 C (176 F) Minimum requirement: cable temperature range ambient temperature + 20 K Power supply cable Standard installation cable is sufficient. Signal cable Modbus RS485 The EIA/TIA-485 standard specifies two types of cable (A and B) for the bus line which can be used for every transmission rate. Cable type A is recommended. Cable type Characteristic impedance Cable capacitance Wire cross-section Cable type Loop resistance Signal damping Shielding A 135 to 165 Ωat a measuring frequency of 3 to 20 MHz < 30 pf/m > 0.34 mm 2 (22 AWG) Twisted pairs 110 Ω/km Max. 9 db over the entire length of the cable cross-section Copper braided shielding or braided shielding with foil shield. When grounding the cable shield, observe the grounding concept of the plant. Connecting cable between Safety Barrier Promass 100 and measuring device Cable type Maximum cable resistance Shielded twisted-pair cable with 2x2 wires. When grounding the cable shield, observe the grounding concept of the plant. 2.5 Ω, one side Endress+Hauser 25

Electrical connection Proline Promass A 100 Modbus RS485 Comply with the maximum cable resistance specifications to ensure the operational reliability of the measuring device. The maximum cable length for individual wire cross-sections is specified in the table below. Observe the maximum capacitance and inductance per unit length of the cable and the connection values in the Ex documentation ( 91). Wire cross-section Maximum cable length [mm 2 ] [AWG] [m] [ft] 0.5 20 70 230 0.75 18 100 328 1.0 17 100 328 1.5 16 200 656 2.5 14 300 984 Cable diameter Cable glands supplied: M20 1.5 with cable 6 to 12 mm (0.24 to 0.47 in) Spring terminals: wire cross-sections 0.5 to 2.5 mm 2 (20 to 14 AWG) With Safety Barrier Promass 100: Plug-in screw terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG) 26 Endress+Hauser

Proline Promass A 100 Modbus RS485 Electrical connection 7.1.3 Terminal assignment Transmitter Connection version Modbus RS485, for use in non-hazardous areas and Zone 2/Div. 2 Order code for "Output", option M Depending on the housing version, the transmitters can be ordered with terminals or device plugs. Order code for "Housing" Connection methods available Output Power supply Possible options for order code "Electrical connection" Options A, B Terminals Terminals Option A: coupling M20x1 Option B: thread M20x1 Option C: thread G ½" Option D: thread NPT ½" Options A, B Device plug ( 29) Terminals Option L: plug M12x1 + thread NPT ½" Option N: plug M12x1 + coupling M20 Option P: plug M12x1 + thread G ½" Option U: plug M12x1 + thread M20 Options A, B, C Device plug ( 29) Device plug ( 29) Option Q: 2 x plug M12x1 Order code for "Housing": Option A: compact, coated alu Option B: compact hygienic, stainless Option C: ultra compact hygienic, stainless, M12 device plug 26 27 A B 2 1 2 L + _ 1 L 7 Modbus RS485 terminal assignment, connection version for use in non-hazardous areas and Zone 2/Div. 2 1 Power supply: DC 24 V 2 Output: Modbus RS485 A0019528 Order code for "Output" Terminal number Power supply Output 2 (L-) 1 (L+) 27 (B) 26 (A) Option M 24 DC V Modbus RS485 Order code for "Output": Option M: Modbus RS485, for use in non-hazardous areas and Zone 2/Div. 2 Connection version Modbus RS485, for use in intrinsically safe areas (connection via Safety Barrier Promass 100) Order code for "Output", option M: Modbus R485, for use in intrinsically safe areas (connection via Safety Barrier Promass 100) Endress+Hauser 27

Electrical connection Proline Promass A 100 Modbus RS485 Depending on the housing version, the transmitters can be ordered with terminals or device plugs. Order code for "Housing" Connection methods available Output Power supply Possible options for order code "Electrical connection" Options A, B Terminals Terminals Option A: coupling M20x1 Option B: thread M20x1 Option C: thread G ½" Option D: thread NPT ½" A, B, C Device plug ( 29) Option I: plug M12x1 Order code for "Housing": Option A: compact, coated alu Option B: compact hygienic, stainless Option C: ultra compact hygienic, stainless, M12 device plug 62 72 A B 2 10 20 L + _ 1 L 8 Modbus RS485 terminal assignment, connection version for use in intrinsically safe areas (connection via Safety Barrier Promass 100) 1 Intrinsically safe power supply 2 Output: Modbus RS485 A0017053 Order code for "Output" 20 (L-) 10 (L+) 72 (B) 62 (A) Option M Intrinsically safe supply voltage Modbus RS485 intrinsically safe Order code for "Output": Option M: Modbus RS485, for use in intrinsically safe areas (connection via Safety Barrier Promass 100) 28 Endress+Hauser

Proline Promass A 100 Modbus RS485 Electrical connection Safety Barrier Promass 100 1 2 L 1 L+ Power supply 24V DC 26 A Safe area 27 B Modbus RS485 A Power Lift panel for bus termination Communication Safety Barrier Promass 100 A 2 Hazardous area Power supply Modbus RS485 L L+ A B 20 10 62 72 9 Safety Barrier Promass 100 with terminals 1 Non-hazardous area and Zone 2/Div. 2 2 Intrinsically safe area A0016922 7.1.4 Pin assignment, device plug Modbus RS485 Modbus RS485 intrinsically safe with supply voltage (on the device side) 2 Pin Assignment Coding Plug/socket 1 L+ Supply voltage, intrinsically safe A Plug 3 4 1 5 A0016809 2 A Modbus RS485 intrinsically safe 3 B 4 L- Supply voltage, intrinsically safe 5 Grounding/shielding Supply voltage for Modbus RS485, non-hazardous area and Zone 2/Div. 2 (on the device side) 2 Pin Assignment Coding Plug/socket 1 L+ DC24 V A Plug 3 4 1 5 A0016809 2 3 4 L- DC24 V 5 Grounding/shielding Endress+Hauser 29

Electrical connection Proline Promass A 100 Modbus RS485 Modbus RS485, non-hazardous areas and zone 2/Div. 2 (on the device side) 2 Pin Assignment Coding Plug/socket 1 B Socket 1 5 4 3 A0016811 2 A Modbus RS485 3 4 B Modbus RS485 5 Grounding/shielding 7.1.5 Shielding and grounding The shielding and grounding concept requires compliance with the following: Electromagnetic compatibility (EMC) Explosion protection Personal protection equipment National installation regulations and guidelines Observe cable specification ( 25). Keep the stripped and twisted lengths of cable shield to the ground terminal as short as possible. Seamless cable shielding. Grounding of the cable shield To comply with EMC requirements: Ensure the cable shield is grounded to the potential matching line at multiple points. Connect every local ground terminal to the potential matching line. NOTICE In systems without potential matching, the multiple grounding of the cable shield causes mains frequency equalizing currents! Damage to the bus cable shield. Only ground the bus cable shield to either the local ground or the protective ground at one end. 7.1.6 Preparing the measuring device 1. Remove dummy plug if present. 2. NOTICE! Insufficient sealing of the housing! Operational reliability of the measuring device could be compromised. Use suitable cable glands corresponding to the degree of protection. If measuring device is delivered without cable glands: Provide suitable cable gland for corresponding connecting cable ( 25). 3. If measuring device is delivered with cable glands: Observe cable specification ( 25). 7.2 Connecting the measuring device NOTICE Limitation of electrical safety due to incorrect connection! Have electrical connection work carried out by correspondingly trained specialists only. Observe applicable federal/national installation codes and regulations. Comply with local workplace safety regulations. For use in potentially explosive atmospheres, observe the information in the devicespecific Ex documentation. 30 Endress+Hauser

Proline Promass A 100 Modbus RS485 Electrical connection 7.2.1 Connecting the transmitter The connection of the transmitter depends on the following order codes: Housing version: compact or ultracompact Connection version: device plug or terminals A B C 1 2 1 2 3 4 10 Device versions and connection versions A Housing version: compact, aluminum coated B Housing version: compact hygienic, stainless 1 Cable entry or device plug for signal transmission 2 Cable entry or device plug for supply voltage C Housing version: ultra-compact hygienic, stainless, device plug M12 3 Device plug for signal transmission 4 Device plug for supply voltage A0016924 8 mm 8 mm 3 mm 2 1 2 1 2 3 1 2 3 10 (0.4) mm (in) 11 Device versions with connection examples 1 Cable 2 Device plug for signal transmission 3 Device plug for supply voltage A0017844 Endress+Hauser 31

Electrical connection Proline Promass A 100 Modbus RS485 For device version with device plug: only pay attention to Step 6. 1. Depending on the housing version, loosen the securing clamp or fixing screw of the housing cover. 2. Depending on the housing version, unscrew or open the housing cover. 3. Push the cable through the cable entry. To ensure tight sealing, do not remove the sealing ring from the cable entry. 4. Strip the cable and cable ends. In the case of stranded cables, also fit ferrules. 5. Connect the cable in accordance with the terminal assignment or the device plug pin assignment ( 29). 6. Depending on the device version: tighten the cable glands or plug in the device plug and tighten ( 29). 7. Enable the terminating resistor if applicable ( 33). 8. NOTICE! Housing degree of protection voided due to insufficient sealing of the housing. Screw in the screw without using any lubricant. The threads on the cover are coated with a dry lubricant. Reverse the removal procedure to reassemble the transmitter. 7.2.2 Connecting the Safety Barrier Promass 100 In the case of the device version with Modbus RS485 intrinsically safe, the transmitter must be connected to the Safety Barrier Promass 100. 1. Strip the cable ends. In the case of stranded cables, also fit ferrules. 2. Connect the cable in accordance with the terminal assignment ( 29). 3. Where applicable, enable the terminating resistor in the Safety Barrier Promass 100 ( 33). 1 2 3 4 A B A B L- L+ A B L+ L- A B L+ L- 8 5 6 7 A0016804 12 Electrical connection between the transmitter and Safety Barrier Promass 100 1 Control system (e.g. PLC) 2 Observe cable specification 3 Safety Barrier Promass 100: terminal assignment ( 29) 4 Observe cable specification ( 25) 5 Non-hazardous area 6 Non-hazardous area and Zone 2/Div. 2 7 Intrinsically safe area 8 Transmitter: terminal assignment 32 Endress+Hauser

1 2 Proline Promass A 100 Modbus RS485 Electrical connection 7.3 Hardware settings 7.3.1 Enabling the terminating resistor To avoid incorrect communication transmission caused by impedance mismatch, connect the Modbus RS485 cable correctly to the start and end of the bus segment. If the transmitter is used in the non-hazardous area or Zone 2/Div. 2 ON OFF 4 - Bus termination 26 A 3 - Not used 2 - Not used 1 - Write protection 27 B 220 13 Terminating resistor can be enabled via DIP switch on the main electronics module A0017610 If the transmitter is used in the intrinsically safe area A A ON 26 27 A B 220 14 Terminating resistor can be enabled via DIP switch in the Safety Barrier Promass 100 A0017791 7.4 Ensuring the degree of protection The measuring device fulfills all the requirements for the IP66/67 degree of protection, Type 4X enclosure. Endress+Hauser 33

Electrical connection Proline Promass A 100 Modbus RS485 To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following steps after the electrical connection: 1. Check that the housing seals are clean and fitted correctly. Dry, clean or replace the seals if necessary. 2. Tighten all housing screws and screw covers. 3. Firmly tighten the cable glands. 4. To ensure that moisture does not enter the cable entry, route the cable so that it loops down before the cable entry ("water trap"). 5. Insert dummy plugs into unused cable entries. A0013960 7.5 Post-connection check Are cables or the device undamaged (visual inspection)? Do the cables comply with the requirements ( 25)? Do the cables have adequate strain relief? Are all the cable glands installed, firmly tightened and leak-tight? Cable run with "water trap" ( 33)? Depending on the device version: are all the device plugs firmly tightened ( 31)? Does the supply voltage match the specifications on the transmitter nameplate ( 80)? For device version with Modbus RS485 intrinsically safe: does the supply voltage match the specifications on the nameplate of the Safety Barrier Promass 100 ( 80)? Is the terminal assignment or the pin assignment of the device plug ( 29) correct? If supply voltage is present, is the power LED on the electronics module of the transmitter lit green ( 10)? For device version with Modbus RS485 intrinsically safe, if supply voltage is present, is the power LED on the Safety Barrier Promass 100 lit ( 10)? Depending on the device version, is the securing clamp or fixing screw firmly tightened? 34 Endress+Hauser

Proline Promass A 100 Modbus RS485 Operation options 8 Operation options 8.1 Overview of operation options 1 2 A0017760 1 Computer with "FieldCare" operating tool via Commubox FXA291 and service interface (CDI) 2 Control system (e.g. PLC) Endress+Hauser 35

Expert Task-oriented Operator Operation options Proline Promass A 100 Modbus RS485 8.2 Structure and function of the operating menu 8.2.1 Structure of the operating menu For an overview of the operating menu with menus and parameters ( 92) Operating menu for operators and maintenances Display/operat. Locking status Operation Setup Submenu 1 Submenu 2 Maintenance Submenu n Advanced setup Enter access code Parameter 1 Parameter n Submenu 1 Diagnostics Parameter 1 Submenu n Parameter n Submenu 1 Submenu n Operating menu for experts Expert Locking status Access status tooling Enter access code System Sensor Communication Application Diagnostics Function-oriented 15 Taking the example of the "FieldCare" operating tool A0016726-EN 36 Endress+Hauser

Proline Promass A 100 Modbus RS485 Operation options 8.2.2 Operating philosophy The individual parts of the operating menu are assigned to certain user roles. Each user role corresponds to typical tasks within the device lifecycle. Menu User role and tasks Content/meaning Display/operat. task-oriented Role "Operator", "Maintenance" Tasks during operation: Reading measured values Resetting and controlling totalizers Setup Diagnostics "Maintenance" role Commissioning: Configuration of the measurement Configuration of the communication interface "Maintenance" role Fault elimination: Diagnostics and elimination of process and device errors Measured value simulation Submenus for fast commissioning: Setting the individual system units Defining the medium Configuration of the digital communication interface Configuring the low flow cut off Configuring the monitoring of partial and empty pipe detection "Advanced setup" submenu: For more customized configuration of the measurement (adaptation to special measuring conditions) Configuration of totalizers Contains all parameters for error detection and analyzing process and device errors: "Diagnostic list" submenu Contains up to 5 currently pending diagnostic messages. "Event logbook" submenu Contains 20 event messages that have occurred. "Device information" submenu Contains information for identifying the device. "Measured values" submenu Contains all current measured values. "Simulation" submenu Is used to simulate measured values or output values. "Device reset" submenu Resets the device configuration to certain settings Expert function-oriented Tasks that require detailed knowledge of the function of the device: Commissioning measurements under difficult conditions Optimal adaptation of the measurement to difficult conditions Detailed configuration of the communication interface Error diagnostics in difficult cases Contains all the parameters of the device and makes it possible to access these parameters directly using an access code. The structure of this menu is based on the function blocks of the device: "System" submenu Contains all higher-order device parameters that do not pertain either to measurement or the measured value communication. "Sensor" submenu Contains all parameters for configuring the measurement. "Communication" submenu Contains all parameters for configuring the digital communication interface. "Application" submenu Contains all parameters for configuring the functions that go beyond the actual measurement (e.g. totalizer). "Diagnostics" submenu Contains all parameters for error detection and analyzing process and device errors and for device simulation. Endress+Hauser 37

Operation options Proline Promass A 100 Modbus RS485 8.3 Access to the operating menu via the operating tool 8.3.1 Connecting the operating tool Via service interface (CDI) 3 2 1 A0016925 1 Service interface (CDI) of the measuring device 2 Commubox FXA291 3 Computer with "FieldCare" operating tool with COM DTM "CDI Communication FXA291" 8.3.2 FieldCare Function scope FDT-based plant asset management tool from Endress+Hauser. It can configure all smart field units in a system and helps you manage them. By using the status information, it is also a simple but effective way of checking their status and condition. Access takes place via: Service interface CDI ( 38) Typical functions: Configuring parameters of transmitters Loading and saving device data (upload/download) Documentation of the measuring point Visualization of the measured value memory (line recorder) and event logbook For details, see Operating Instructions BA00027S and BA00059S Source for device description files See data ( 40) Establishing a connection Via service interface (CDI) 1. Start FieldCare and launch the project. 2. In the network: Add a device. The Add device window opens. 3. Select the CDI Communication FXA291 option from the list and press OK to confirm. 4. Right-click CDI Communication FXA291 and select the Add device option in the context menu that opens. 38 Endress+Hauser

Proline Promass A 100 Modbus RS485 Operation options 5. Select the desired device from the list and press OK to confirm. 6. Establish the online connection to the device. For details, see Operating Instructions BA00027S and BA00059S User interface A0017402-EN 1 2 3 4 5 6 7 8 Header Picture of device Device tag ( 58) Status area with status signal ( 64) Display area for current measured values ( 58) Event list with additional functions such as save/load, events list and document creation Navigation area with operating menu structure Working area Endress+Hauser 39

System integration Proline Promass A 100 Modbus RS485 9 System integration 9.1 Overview of device description files 9.1.1 Current version data for the device Firmware version 01.02.00 On the title page of the Operating instructions On transmitter nameplate ( 12) Parameter firmware version Diagnostics Device info Firmware version Release date of firmware version 04.2013 --- 9.1.2 Operating tools The suitable device description file for the operating tool is listed in the table below, along with information on where the file can be acquired. Operating tool via service interface (CDI) FieldCare Sources for obtaining device descriptions www.endress.com Download Area CD ROM (contact Endress+Hauser) DVD (contact Endress+Hauser) 9.2 Modbus RS485 information 9.2.1 Function codes Function codes are used to define which read or write action is carried out via the Modbus protocol. The measuring device supports the following function codes: Code Name Description Application 03 Read holding register 04 Read input register Master reads one or more Modbus registers from the device. A maximum of 125 consecutive registers can be read with 1 telegram: 1 register = 2 bytes The measuring device does not make a distinction between function codes 03 and 04; these codes therefore yield the same result. Master reads one or more Modbus registers from the device. A maximum of 125 consecutive registers can be read with 1 telegram: 1 register = 2 bytes The measuring device does not make a distinction between function codes 03 and 04; these codes therefore yield the same result. Read device parameters with read and write access Example: Read mass flow Read device parameters with read access Example: Read totalizer value 40 Endress+Hauser

Proline Promass A 100 Modbus RS485 System integration Code Name Description Application 06 Write single registers Master writes a new value to one Modbus register of the measuring device. Use function code 16 to write multiple registers with just 1 telegram. Write only 1 device parameter Example: reset totalizer 08 Diagnostics Master checks the communication connection to the measuring device. The following "Diagnostics codes" are supported: Sub-function 00 = Return query data (loopback test) Sub-function 02 = Return diagnostics register 16 Write multiple registers 23 Read/Write multiple registers Master writes a new value to multiple Modbus registers of the device. A maximum of 120 consecutive registers can be written with 1 telegram. If the required device parameters are not available as a group, yet must nevertheless be addressed with a single telegram, use Modbus data map ( 41) Master reads and writes a maximum of 118 Modbus registers of the measuring device simultaneously with 1 telegram. Write access is executed before read access. Write multiple device parameters Example: Mass flow unit Mass unit Write and read multiple device parameters Example: Read mass flow Reset totalizer Broadcast messages are only allowed with function codes 06, 16 and 23. 9.2.2 Register information For an overview on Modbus-specific information of the individual device parameters, please refer to the additional document on Modbus RS485 register information ( 91) 9.2.3 Response time Response time of the measuring device to the request telegram of the Modbus master: typically 3 to 5 ms 9.2.4 Modbus data map Function of the Modbus data map The device offers a special memory area, the Modbus data map (for a maximum of 16 device parameters), to allow users to call up multiple device parameters via Modbus RS485 and not only individual device parameters or a group of consecutive device parameters. Grouping of device parameters is flexible and the Modbus master can read or write to the entire data block simultaneously with a single request telegram. Endress+Hauser 41

System integration Proline Promass A 100 Modbus RS485 Structure of the Modbus data map The Modbus data map consists of two data sets: Scan list: Configuration area The device parameters to be grouped are defined in a list in that their Modbus RS485 register addresses are entered in the list. Data area The measuring device reads out the register addresses entered in the scan list cyclically and writes the associated device data (values) to the data area. For an overview of device parameters with their individual Modbus register address, please refer to the additional document on Modbus RS485 register information ( 91) Scan list configuration For configuration, the Modbus RS485 register addresses of the device parameters to be grouped must be entered in the scan list. Please note the following basic requirements of the scan list: Max. entries Supported device parameters 16 device parameters Only parameters with the following characteristics are supported: Access type: read or write access Data type: float or integer Configuring the scan list via FieldCare Carried out using the operating menu of the measuring device: Expert Communication Modbus data map Scan list register 0-15 Scan list No. Configuration register 0 Scan list register 0...... 15 Scan list register 15 Configuring the scan list via Modbus RS485 Carried out using register addresses 5001-5016 Scan list No. Modbus RS485 register Data type Configuration register 0 5001 Integer Scan list register 0...... Integer... 15 5016 Integer Scan list register 15 Reading out data via Modbus RS485 The Modbus master accesses the data area of the Modbus data map to read out the current values of the device parameters defined in the scan list. Master access to data area Via register addresses 5051-5081 42 Endress+Hauser

Proline Promass A 100 Modbus RS485 System integration Data area Device parameter value Modbus RS485 register Data type* Access** Value of scan list register 0 5051 Integer/float Read/write Value of scan list register 1 5053 Integer/float Read/write Value of scan list register............ Value of scan list register 15 5081 Integer/float Read/write * Data type depends on the device parameters entered in the scan list. ** Data access depends on the device parameters entered in the scan list. If the device parameter entered supports read and write access, the parameter can also be accessed via the data area. Endress+Hauser 43

Commissioning Proline Promass A 100 Modbus RS485 10 Commissioning 10.1 Function check Before commissioning the device, make sure that the post-installation and postconnection checks have been performed. "Post-mounting check" checklist ( 24) "Post-connection check" checklist ( 34) 10.2 Establishing a connection via FieldCare For FieldCare connection ( 38) For establishing a connection via FieldCare ( 38) For FieldCare user interface ( 39) 10.3 Configuring the measuring device The Setup menu with its submenus contains all parameters needed for standard operation. Structure of the "Setup" menu Setup System units ( 44) Select medium ( 47) Communication ( 48) Low flow cut off ( 50) Partially filled pipe detection ( 51) 10.3.1 Setting the system units In the System units submenu, you can configure the units of all measured values. Navigation path "Setup" menu Advanced setup System units Structure of the submenu System units Mass flow unit Mass unit Volume flow unit Volume unit Corrected volume flow unit Corrected volume unit Density unit Reference density unit 44 Endress+Hauser

Proline Promass A 100 Modbus RS485 Commissioning Temperature unit Pressure unit Parameter overview with brief description Parameter Description Selection/ User entry Factory setting Mass flow unit Select the unit for mass flow. Result The selected unit applies for: Output Low flow cut off Simulation process variable Unit choose list Country-dependent: kg/h lb/min Mass unit Select the unit for mass. Result The selected unit is taken from: Mass flow unit Unit choose list Country-dependent: kg lb Volume flow unit Select the unit for volume flow. Result The selected unit applies for: Output Low flow cut off Simulation process variable Unit choose list Country-dependent: l/h gal/min (us) Volume Select the unit for volume. Result The selected unit is taken from: Volume flow unit Country-dependent l gal (us) Corrected volume flow unit Select the unit for corrected volume flow. Result The selected unit applies for: Output Low flow cut off Simulation process variable Unit choose list Country-dependent: Nl/h Scf/min Corrected volume unit Select the unit for standard volume. Result The selected unit is taken from: Corrected volume flow unit Unit choose list Country-dependent: Nl Scf Density unit Select the unit for density. Result The selected unit applies for: Output Low value partial filled pipe detection High value partial filled pipe detection Simulation process variable Density adjustment (in the Expert menu) Unit choose list Country-dependent kg/l lb/cf Reference density unit Select the unit for reference density. Result The selected unit applies for: Output Low value partial filled pipe detection High value partial filled pipe detection Simulation process variable Fixed reference density Density adjustment (in the Expert menu) Unit choose list Country-dependent: kg/nl lb/scf Endress+Hauser 45

Commissioning Proline Promass A 100 Modbus RS485 Parameter Description Selection/ User entry Factory setting Temperature unit Select the unit for temperature. Result The selected unit applies for: Output Reference temperature Simulation process variable Unit choose list Country-dependent: C (Celsius) F (Fahrenheit) Pressure unit Select the unit for pipe pressure. Unit choose list Country-dependent: bar a psi a 46 Endress+Hauser

Proline Promass A 100 Modbus RS485 Commissioning 10.3.2 Selecting and setting the medium The Medium selection submenu contains parameters that have to be configured for selecting and setting the medium. Navigation path "Setup" menu Medium selection Structure of the submenu Medium selection Select medium Select gas type Reference sound velocity Temperature coefficient sound velocity Pressure compensation Pressure value External pressure Parameter overview with brief description Parameter Prerequisite Description Selection/ User entry Factory setting Medium selection Select the medium type. Liquid Gas Liquid Select gas type The following option is selected in the Medium selection parameter: Gas Select the gas type for the measurement application. Gas type choose list Air Reference sound velocity The following option is selected in the Select gas type parameter: Others Enter the sound velocity of the gas at 0 C (32 F). 0 to 99 999 m/s 0 m/s Temperature coefficient sound velocity The following option is selected in the Select gas type parameter: Others Enter the temperature coefficient of the sound velocity of the gas. Max. 15-digit, positive floatingpoint number 0 (m/s)/k Pressure compensation The following option is selected in the Medium selection parameter: Gas Enable the automatic pressure correction. Off Fixed value Off Pressure value The following option is selected in the Pressure compensation parameter: Fixed value Enter a value for the process pressure to be used for pressure correction. 0 to 99 999 [bar, psi] Countrydependent: 1.01325 bar 14.7 psi External pressure The following option is selected in the Pressure compensation parameter: External value External value 0 to 99 999 [bar, psi] Countrydependent: 1.01325 bar 14.7 psi Endress+Hauser 47

Commissioning Proline Promass A 100 Modbus RS485 10.3.3 Configuring communication interface The Communication submenu guides you systematically through all parameters that must be configured for selecting and setting the communication interface. Navigation path "Setup" menu Communication Structure of the submenu Communication Bus address Baud rate Data transfer mode Parity Byte order Assign diagnostic behavior Failure mode Parameter overview with brief description Parameter Description Selection/ User entry Factory setting Bus address Enter device address. 1 to 247 247 Baud rate Define data transfer speed. Baud rate list box( 79) 19 200 BAUD Data transfer mode Select data transfer mode. ASCII Transmission of data in the form of readable ASCII characters. Error protection via LRC. RTU Transmission of data in binary form. Error protection via CRC16. Parity Select parity bits. ASCII picklist 0 = even 1 = odd RTU picklist 0 = even 1 = odd 2 = no parity bit/1 stop bit 3 = no parity bit/2 stop bits RTU Even Byte order Select byte transmission sequence. 0-1-2-3 3-2-1-0 1-0-3-2 2-3-0-1 1-0-3-2 48 Endress+Hauser

Proline Promass A 100 Modbus RS485 Commissioning Parameter Description Selection/ User entry Factory setting Assign diagnostic behavior Select diagnostic behavior for MODBUS communication. Off Alarm or warning Warning Alarm Alarm Failure mode Select measured value output behavior when a diagnostic message occurs via Modbus communication. This parameter operates in accordance with the option selected in the Assign diagnostic behavior parameter. NaN value Last valid value NaN º not a number NaN value Endress+Hauser 49

Commissioning Proline Promass A 100 Modbus RS485 10.3.4 Configuring the low flow cut off The Low flow cut off submenu contains parameters that have to be set for configuring the low flow cut off. Navigation path "Setup" menu Low flow cut off Structure of the submenu Low flow cut off Assign process variable On value low flow cut off Off value low flow cutoff Pressure shock suppression Parameter overview with brief description Parameter Prerequisite Description Selection/ User entry Factory setting Assign process variable Select the process variable for low flow cut off. Off Mass flow Volume flow Corrected volume flow Mass flow On value low flow cut off One of the following options is selected in the Assign process variable parameter: Mass flow Volume flow Corrected volume flow Enter the on value for low flow cut off. Max. 15-digit, positive floatingpoint number For liquids: depends on country and nominal diameter Off value low flow cut off One of the following options is selected in the Assign process variable parameter: Mass flow Volume flow Corrected volume flow Enter the off value for low flow cut off. 0 to 100 % 50 % Pressure shock suppression One of the following options is selected in the Assign process variable parameter: Mass flow Volume flow Corrected volume flow Enter the time interval for signal suppression (= active pressure shock suppression). 0 to 100 s 0 s 50 Endress+Hauser

Proline Promass A 100 Modbus RS485 Commissioning 10.3.5 Configuring the partial filled pipe detection The Partially filled pipe detection submenu contains parameters that have to be set for configuring empty pipe detection. Navigation path "Setup" menu Partial filled pipe detection Structure of the submenu Partially filled pipe detection Assign process variable Low value partial filled pipe detection High value partial filled pipe detection Response time part. filled pipe detect. Parameter overview with brief description Parameter Prerequisite Description Selection/ User entry Factory setting Assign process variable Select a process variable to detect empty or partially filled pipes. Off Density Reference density Density Low value partial filled pipe detection One of the following options is selected in the Assign process variable parameter: Density Reference density Enter a lower limit value to activate detection of an empty or partially filled pipe. Max. 15-digit, positive floatingpoint number Countrydependent: 0.2 kg/l 12.5 lb/cf High value partial filled pipe detection One of the following options is selected in the Assign process variable parameter: Density Reference density Enter an upper limit value to activate detection of an empty or partially filled pipe. Max. 15-digit, positive floatingpoint number Countrydependent: 6 kg/l 374.6 lb/cf Response time part. filled pipe detect. One of the following options is selected in the Assign process variable parameter: Density Reference density Enter the time interval until the diagnostic message S862 Partly filled pipe detection is displayed for an empty or partially filled pipe. 0 to 100 s 1 s Endress+Hauser 51

Commissioning Proline Promass A 100 Modbus RS485 10.4 Advanced settings The Advanced setup menu with its submenus contains all parameters needed for specific settings. Navigation path "Setup" menu Advanced setup Overview of the parameters and submenus in the "Advanced setup" menu taking the example of the Web browser Advanced setup Enter access code Device tag ( 52) Calculated values ( 52) Sensor adjustment ( 53) Totalizer 1 to 3 ( 54) 10.4.1 Defining the tag name To enable quick identification of the measuring point within the system, you can enter a unique designation using the Device tag parameter and thus change the factory setting. Navigation path Setup Advanced setup Device tag Parameter overview with brief description Parameter Description Selection/ User entry Factory setting Device tag Enter the name for the measuring point. Max. 32 characters, such as letters, numbers or special characters (e.g. @, %, /) Promass The number of characters displayed depends on the characters used. For information on the tag name in the "FieldCare" operating tool ( 39) 10.4.2 Calculated values The Calculated values submenu contains parameters for calculating the corrected volume flow. Navigation path "Setup" menu Advanced setup Calculated values Structure of the submenu Calculated values Corrected volume flow calculation External reference density Fixed reference density Reference temperature 52 Endress+Hauser

Proline Promass A 100 Modbus RS485 Commissioning Linear expansion coefficient Square expansion coefficient Parameter overview with brief description Parameter Prerequisites Description Selection/input Factory settings Corrected volume flow calculation Select the reference density for calculating the corrected volume flow. Fixed reference density Calculated reference density Reference density according to API 53 External reference density Calculated reference density External reference density Shows external reference density. Floating-point number with sign Country-dependent: 0 kg/nl (0 lb/scf) Fixed reference density The following option is selected in the Corrected volume flow calculation parameter: Fixed reference density Enter the fixed value for the reference density. Positive floatingpoint number with leading sign Country-dependent: 0.001 kg/nl (0.062 lb/scf) Reference temperature The following option is selected in the Corrected volume flow calculation parameter: Calculated reference density Enter the reference temperature for calculating the reference density. Floating-point number with sign Country-dependent: 20 C (68 F) Linear expansion coefficient Square expansion coefficient The following option is selected in the Corrected volume flow calculation parameter: Calculated reference density Enter the linear, medium-specific expansion coefficient for calculating the reference density. For media with a non-linear expansion pattern, use this function to enter a quadratic, mediumspecific expansion coefficient for calculating the reference density. 0 to 1 0.0 0 to 1 0.0 10.4.3 Carrying out a sensor adjustment The Sensor adjustment submenu contains parameters that pertain to the functionality of the sensor. Endress+Hauser 53

Commissioning Proline Promass A 100 Modbus RS485 Navigation path "Setup" menu Advanced setup Sensor adjustment Structure of the submenu Sensor adjustment Installation direction Zero point adjustment Zero point adjustment control Progress Parameter overview with brief description Parameter Description Selection/ User entry Factory setting Installation direction Change the sign of the direction of flow of the fluid. Flow in arrow direction Flow against arrow direction Flow in arrow direction Zero point adjustment control Start the zero point adjustment. Cancel Start Cancel Progress 0 100 % 0 10.4.4 Configuring the totalizer You can configure each totalizer in the three submenus Totalizer 1-3. Navigation path "Setup" menu Advanced setup Totalizer 1-3 Structure of the submenu Totalizer 1-3 Assign process variable Mass unit Volume unit Corrected volume unit Totalizer operation mode Failure mode 54 Endress+Hauser

Proline Promass A 100 Modbus RS485 Commissioning Parameter overview with brief description Parameter Prerequisite Description Selection/ User entry Factory setting Assign process variable - Select process variable for totalizer. Result The selection determines the choose list of the Unit parameter. Off Mass flow Volume flow Corrected volume flow The range of options increases if the measuring device has one or more application packages. Mass flow Mass unit The following option is selected in the Assign process variable parameter: Mass flow Select the unit for mass. Result The selected unit is taken from: Mass flow unit Unit choose list Country-dependent: kg lb Volume unit The following option is selected in the Assign process variable parameter: Volume flow Select the unit for volume. Result The selected unit is taken from: Volume flow unit Unit choose list Country-dependent l gal (us) Corrected volume unit The following option is selected in the Assign process variable parameter: Corrected volume flow Select the unit for standard volume. Result The selected unit is taken from: Corrected volume flow unit Unit choose list Country-dependent: Nl Scf Totalizer operation mode One of the following options is selected in the Assign process variable parameter: Mass flow Volume flow Corrected volume flow Select totalizer calculation mode. Net flow total Forward flow total Reverse flow total Net flow total Failure mode One of the following options is selected in the Assign process variable parameter: Mass flow Volume flow Corrected volume flow Specify the behavior of the totalizer in the event of a device alarm. Stop Actual value Last valid value Stop 10.5 Simulation The Simulation submenu enables you to simulate, without a real flow situation, various process variables in the process and the device alarm mode and to verify downstream signal chains (switching valves or closed-control loops). Endress+Hauser 55

Commissioning Proline Promass A 100 Modbus RS485 Navigation path "Diagnostics" menu Simulation Simulation Assign simulation process variable Value process variable Simulation device alarm 10.5.1 Parameter overview with brief description Parameter Prerequisite Description Selection/ User entry Factory setting Assign simulation process variable - Select a process variable for the simulation process that is activated. Off Mass flow Volume flow Corrected volume flow Density Reference density Temperature Off The range of options increases if the measuring device has one or more application packages. Value process variable A process variable is selected in the Assign simulation process variable parameter. Enter the simulation value for the selected process variable. Depends on the process variable selected - Simulation device alarm - Switch the device alarm on and off. Off On Off 10.6 Protecting settings from unauthorized access The following option exists for protecting the configuration of the measuring device from unintentional modification after commissioning: Write protection via write protection switch 10.6.1 Write protection via write protection switch The write protection switch makes it possible to block write access to the entire operating menu with the exception of the following parameters: External pressure External temperature Reference density All parameters for configuring the totalizer The parameter values are now read only and cannot be edited any more: Via service interface (CDI) Via Modbus RS485 56 Endress+Hauser

Proline Promass A 100 Modbus RS485 Commissioning ON OFF 4 - Bus termination 3 - Not used 2 - Not used 1 - Write protection A0017954 1. Depending on the housing version, loosen the securing clamp or fixing screw of the housing cover. 2. Depending on the housing version, unscrew or open the housing cover. 3. Setting the write protection switch on the main electronics module to the ON position enables the hardware write protection. Setting the write protection switch on the main electronics module to the OFF position (factory setting) disables the hardware write protection. If hardware write protection is enabled, the Hardware locked option is displayed in the Locking status parameter ( 58); if disabled, no option is displayed in the Locking status parameter ( 58) 4. Reverse the removal procedure to reassemble the transmitter. Endress+Hauser 57

Operation Proline Promass A 100 Modbus RS485 11 Operation 11.1 Read device locking status The write protection types that are currently active can be determined using the Locking status parameter. Navigation path "Display/operation" menu Locking status Function scope of "Locking status" parameter Options Hardware locked Temporarily locked Description The write protection switch (DIP switch) for hardware locking is activated on the main electronics module. This prevents write access to the parameters ( 56). Write access to the parameters is temporarily locked on account of internal processes running in the device (e.g. data upload/download, reset etc). Once the internal processing has been completed, the parameters can be changed once again. 11.2 Reading measured values You can read all measured values using the Measured values menu. Navigation path Diagnostics Measured values 11.2.1 Process variables The Process variables submenu contains all the parameters needed to display the current measured values for every process variable. Navigation path "Diagnostics" menu Measured values Process variables Structure of the submenu Process variable Mass flow Volume flow Corrected volume flow Density Reference density Temperature Pressure value 58 Endress+Hauser

Proline Promass A 100 Modbus RS485 Operation Parameter overview with brief description Parameter overview with brief description Parameter Prerequisite Description Display Mass flow Displays the mass flow currently measured Volume flow Displays the volume flow currently calculated Floating-point number with sign Floating-point number with sign Corrected volume flow Displays the corrected volume flow currently calculated Floating-point number with sign Density Displays the density currently measured Floating-point number with sign Reference density Displays the density currently measured at reference temperature Temperature Displays the medium temperature currently measured Pressure value Displays either a fixed or external pressure value Floating-point number with sign Floating-point number with sign Floating-point number with sign 11.2.2 Totalizer The Totalizer submenu contains all the parameters needed to display the current measured values for every totalizer. Navigation path "Diagnostics" menu Measured values Totalizer Structure of the submenu Totalizer 1 to 3 Totalizer value 1 Totalizer overflow 1 Totalizer value 2 Totalizer overflow 2 Totalizer value 3 Totalizer overflow 3 Endress+Hauser 59

Operation Proline Promass A 100 Modbus RS485 Parameter overview with brief description Parameter Prerequisite Description Display Totalizer value 1-3 One of the following options is selected in the Assign process variable parameter of the Totalizer 1-3 submenu: Mass flow Volume flow Corrected volume flow Displays the current totalizer counter value. Floating point number with sign Totalizer overflow 1-3 One of the following options is selected in the Assign process variable parameter of the Totalizer 1-3 submenu: Mass flow Volume flow Corrected volume flow Displays the current totalizer overflow. Integer 11.3 Adapting the measuring device to the process conditions The following are available for this purpose: Basic settings using the Setup menu ( 44) Advanced settings using the Advanced setup menu ( 52) 11.4 Performing a totalizer reset In the Operation submenu, 2 parameters with various options for resetting the three totalizers are available: Control totalizer 1-3 Reset all totalizers Navigation path "Display/operat." menu Operation Function scope of the "Control totalizer" parameter Options Totalize Description The totalizer is started. Reset + hold The totaling process is stopped and the totalizer is reset to 0. Preset + hold Reset + totalize Preset + totalize The totaling process is stopped and the totalizer is set to the defined start value in the Preset parameter. The totalizer is reset to 0 and the totaling process is restarted. The totalizer is set to the defined start value in the Preset parameter and the totaling process is restarted. Function scope of the "Reset all totalizers" parameter Options Reset + totalize Description Resets all totalizers to 0 and restarts the totaling process. This deletes all the flow values previously totalized. 60 Endress+Hauser

Proline Promass A 100 Modbus RS485 Operation "Operation" submenu Operation Control totalizer 1 Preset value 1 Control totalizer 2 Preset value 2 Control totalizer 3 Preset value 3 Reset all totalizers Parameter overview with brief description Parameter Prerequisite Description Selection/ User entry Factory setting Control totalizer 1-3 A process variable is selected in the Assign process variable parameter of the Totalizer 1-3 submenu. Control totalizer value. Totalize Reset + hold Preset + hold Reset + totalize Preset + totalize Totalize Preset value 1-3 A process variable is selected in the Assign process variable parameter of the Totalizer 1-3 submenu. Specify start value for totalizer. Floating-point number with sign Country-dependent: 0 kg 0 lb Reset all totalizers - Reset all totalizers to 0 and start. Cancel Reset + totalize Cancel Endress+Hauser 61

Diagnostics and troubleshooting Proline Promass A 100 Modbus RS485 12 Diagnostics and troubleshooting 12.1 General troubleshooting For output signals Problem Possible causes Remedy Green power LED on the main electronics module of the transmitter is dark Green power LED on the main electronics module of the transmitter is dark Green power LED on Safety Barrier Promass 100 is dark Green power LED on Safety Barrier Promass 100 is dark Device measures incorrectly. Supply voltage does not match that specified on the nameplate. Power supply cable connected incorrectly Supply voltage does not match that specified on the nameplate. Power supply cable connected incorrectly Configuration error or device is operated outside the application. Apply the correct supply voltage ( 31). Check the terminal assignment. Apply the correct supply voltage ( 31). Check the terminal assignment ( 29). 1. Check and correct parameter configuration. 2. Observe limit values specified in the "Technical Data". For access Problem Possible causes Remedy No write access to parameters Hardware write protection enabled Set the write protection switch on the main electronics module to the OFF position ( 56). No connection via Modbus RS485 Modbus RS485 bus cable connected incorrectly Check the terminal assignment. No connection via Modbus RS485 Device plug connected incorrectly Check the pin assignment of the device plug ( 29). No connection via Modbus RS485 No connection via Modbus RS485 No connection via service interface Modbus RS485 cable incorrectly terminated Incorrect settings for the communication interface Incorrect configuration of USB interface on PC or driver not installed correctly. Check terminating resistor ( 33). Check the Modbus RS485 configuration ( 48). Observe the documentation for the Commubox. FXA291: Document "Technical Information" TI00405C 12.2 Diagnostic information via light emitting diodes 12.2.1 Transmitter Various light emitting diodes (LEDs) on the main electronics module of the transmitter provide information on device status. LED Color Meaning Power Off Supply voltage is off or too low. Green Supply voltage is ok. 62 Endress+Hauser

Proline Promass A 100 Modbus RS485 Diagnostics and troubleshooting Alarm Off Device status is ok. Flashing red Red A device error of diagnostic behavior "Warning" has occurred. A device error of diagnostic behavior "Alarm" has occurred. Boot loader is active. Communication Flashing white Modbus RS485 communication is active. 12.2.2 Safety Barrier Promass 100 Various light emitting diodes (LEDs) on the Safety Barrier Promass 100 provide status information. LED Color Meaning Power Off Supply voltage is off or too low. Green Supply voltage is ok. Communication Flashing white Modbus RS485 communication is active. 12.3 Diagnostic information in FieldCare 12.3.1 Diagnostic options Any faults detected by the measuring device are displayed on the home page of the operating tool once the connection has been established. XXXXXXX 1 XXXXXXX 2 3 A0014014-EN 1 2 3 Status area with status signal Diagnostic information Remedy information with Service ID Furthermore, diagnostic events that have occurred can be viewed in the Diagnostics menu: Via parameters Via submenu ( 68) Endress+Hauser 63