FX06 Field Controller

Similar documents
Onboard Inputs and Outputs. Remote User Interface. Integral LCD User Interface

FX Input/Output (I/O) Modules XM07 and XM14

FX14 Field Controller

FXVMA Variable Air Volume (VAV) Box Controller

Medium User Interface (MUI) Version 3

FX-PCX Expansion Input/Output Modules Catalog Page Code No. LIT Issued April 17, 2015

TC-9102 Terminal Controller

FX05 Controller. FX05 Controller. Features and Benefits Compatible with standard BAS protocols. LON and N2Open plug-in comm.

PEAK TM. PEAK TM controllers. Mid-Market BAS Smart equipment controllers. HVAC/R controllers

Smart Equipment Controls (SEC)

FX14 Field Controller

TAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta

FX07 Field Controller

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

Input/Output Module (IOM) Series Catalog Page

Network Control Engine Catalog Page

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

Field selectable application type and room module series, via dip-switches on controller

NIEx9. Metasys. BAS network automation Supervisory controllers. Network Integration Engine

Andover ContinuumTM. b3850 Series Terminal Controllers

FEC - FAC. Metasys controllers. Complex BAS Programmable controllers. Catalog Page. Field Equipment Controllers

RCM Room Command Module New Style

Advanced Application Field Equipment Controller (FAC) Catalog Page

Field Equipment Controller (FEC) Series Catalog Page Code No. LIT Issued June 2018

Andover ContinuumTM Infinet II

FX-PCA Advanced Application Programmable Controller Catalog Page

XT-9100 Technical Bulletin

Input/Output Module (IOM) Series Controllers Catalog Page Code No. LIT Issued June 2018

clarity 3 Programmable Controller

Andover ContinuumTM Infinet II

Andover Continuum Infinet II i2865/866 VAV Controllers with Built-in Actuator

BACnet. b3810 Series Local Controllers

Andover ContinuumTM b3865/866 VAV Controllers with Built-in Actuator

LX Series Free Programmable Controllers

PEAK TM. SMART Equipment Controllers. Product bulletin

TAC Xenta 301. Controller, Freely Programmable

Datasheet. ECB-PTU Series. 1/14. BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

AIAS. Technical description

BACnet. b3867 Terminal Controllers

Non-communicating room controllers

Andover ContinuumTM Infinet II

Input/Output Module (IOM) Series Controllers Catalog Page Code No. LIT Issued December 2017

OHIO SEMITRONICS, INC. AC MULTIFUNCTION PROGRAMMABLE TRANSDUCERS & -1000L

Buy American Facility Explorer Products Facility Explorer Product Management Authorized Building Controls Specialists (ABCS)

NAE. Metasys. BAS network automation Supervisory controllers. Network Automation Engine

TC-8900 Controller Units with PM-8900 Power Modules

TALON Network Manager- 2 & 6 Express

FX-PC Series Programmable Controllers and Related Products Product Bulletin

EXOcompact. Freely programmable controller

TX-I/O Product Range. Description. Technical Specification Sheet Document No July 18, 2013

BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

NIE59 Network Integration Engine Figure 1: NIE59 Network Integration Engine

Commercial Comfort System (CCS)

DX-9100 Digital Controller, Version 2

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

FX40 Supervisory Controller

Programmable controller MCX06C

LN Series Remote Input/Output (I/O) Modules

Features Communication Using Commonly Accepted IT Standards, Including Web Services, at the Automation and Enterprise Level Web-Based User Interface

Network Control Engine

Variable Air Volume Modular Assembly (VMA) 1400 Series

ECL Comfort V a.c. and 24 V a.c.

VAV Modular Assembly (VMA) 1410/1420

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

Room unit with PPS2 interface

TEC Zoning Control System for Stand-Alone and BACnet MS/TP Networked Applications

THERMOSTATS & CONTROLLERS

ECON-ZIP-BASE. ZIP Economizer Base Unit. Wiring Diagram USA CANADA LATIN AMERICA / CARIBBEAN

Temperature controller Ducted systems

The Simply Smart Way to Optimize Building Control and Performance

TX-I/O Product Range. Description. Technical Specification Sheet Document No February 20, 2018

TAC Xenta 121-FC Programmable Fan Coil Application

TX-I/O Product Range. Features. Description. Document No January 24, 2007

Specification Sheet For electronically commutated motors

FX-DIS1710 Local Controller Display Installation Instructions Part No , Rev. B Issued April 2016

Fast Route to Reliable Energy Savings ZIP Economizer

TM-2100 Series Room Command Module

PHS Series. PowerHUBB Node - Satellite

NS Series Network Sensors

Modular Room Control (MRC) Series Expansion Board

Network Integration Engine (NIEx9) for Third-Party Integrations Catalog Page

FXVMA VAV Box Controller

MOD-IO9 Modbus Input / Output Modules, Wall Mounted

APP 700 Technical Specification

LX Series Remote Input/Output (I/O) Controller

ECB-300 Series BACnet B-AAC 18-Point Programmable Controllers

Datasheet ECB /6. BACnet B-ASC 10-Point Programmable Controller. Overview

Room unit with PPS2 interface

Non-communicating room controllers

FX-DIS Local Controller Display Technical Bulletin

POL635.XX/XXX POL636.XX/XXX POL638.XX/XXX POL638.70/XXX

TAC Xenta 121-HP Programmable Heat Pump Application

Tracer Controllers. Tracer MP503 Input/Output Module BAS-PRC009-EN. September 2001

SE7600E Series Application Guide

Overview. Seen as an extension of the main HVAC controller when configuring, allowing you to save engineering time.

Controllers for compressor racks with advanced energy saving. PN08 September 2016

Custom Controller Installation Instructions

TM-2100 Series Room Command Module

Datasheet ECB /6. BACnet B-ASC 10-Point Programmable Controller. Overview

Transcription:

Code No. LIT-1900406 Issued October 19, 2012 Facility Explorer FX06 Field Controller The FX06 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning, and Refrigeration (HVACR) applications. The FX06 supports 17 physical inputs and outputs including a wide range of sensors and actuating devices. The FX06 includes an onboard real-time clock to support the start-stop scheduling of equipment, real-time based control sequences, and time stamping events and trend records. With the integral user interface, you can locally monitor and adjust the FX06 s operation. The FX06 also supports a remote panel- or wall-mountable Medium User Interface (MUI) for remote monitoring and adjustment. The FX06 can be fitted with an N2 Open or LONWORKS communication module to integrate the controller into a compatible Building Automation System (BAS). Alternatively, the FX06 can be fitted with an RS-232C serial communication module to transmit event notification messages via Short Messaging Service (SMS) through a Global System for Mobile (GSM) modem. Using the FX Tools software package, you can program the FX06 field controller to operate a wide variety of commercial HVACR equipment; including small refrigeration compressors, close control units, packaged rooftop units, fan coil units, unit ventilators, and chilling or heating ceiling beam installations. Note: This document applies to the LP- FX06Pxx-020C models only. Refer to the FX06 Field Controller Product Bulletin (LIT-12011165) for important product application information. Features freely programmable controller network communication module options: N2 Open, or LONWORKS protocols remote communication services integral Liquid Crystal Display (LCD) user interface with four control buttons optional remote user interface analog outputs models with various output configurations of solid-state triacs and line voltage relays Network Room Module (NRM) FX06 Field Controller Repair Information If the FX06 Field Controller fails to operate within its specifications, replace the unit. For a replacement controller, contact the nearest Johnson Controls representative. Selection Charts FX06 Field Controller Ordering Information LP-FX06P00-020C LP-FX06P20-020C FX06 Compact Field Controller with new style wiring connector: Includes 4 Analog Inputs (AIs), 5 Binary Inputs (BIs), 2 0-10 VDC Analog Outputs, and 6 relay Binary Outputs (BOs) FX06 Compact Field Controller with new style wiring connector: Includes 4 AIs, 5 BIs, 2 0-10 VDC Analog Outputs, 4 BOs, and 2 triac BOs Communication Module Ordering Information LP-NET061-000C N2 Open Communication Module LP-NET062-000C LONWORKS Communication Module LP-NET063-000C RS232C Communication Module User Interfaces Product Code Number LP-DIS60P20-0C LP-DIS60P21-0C LP-KIT007-005C FX06 Accessories (Part 1 of 2) LP-KIT006-020C LP-KIT006-025C LP-KIT100-000C DT-9100-8901 LP-KIT007-001C LP-KIT007-013C LP-KIT007-014C LP-KIT007-020C LP-KIT200-000C Remote Medium User Interface (MUI V3) for FX06 - Panel Mount Remote Medium User Interface (MUI V3) for FX06 - Wall Mount Link cable for the connection of the FX06 to the Panel Mount MUI display or NRM module, 3 m (9.8 ft) Wiring Harness with new style wiring connector, 1.5 m length Wiring Harness with new style wiring connector, 5.0 m length FX Programming Key Power Supply Adapter for Programming Key: 230 VAC/12 VDC (Europe only) Interface cable for standard landline modem, 1.5 m (4.9 ft) Null modem cable for computer connection, 3 m (9.8 ft) Null modem cable for computer connection, 15 m (49.2 ft) Bag of replacement communication wiring connectors (N2 and LON). N2 Commissioning Adapter: Includes port powered RS-232C to RS-485 converter, 3 m (9.8 ft) cable, and mating connectors for FX05, FX06, FX07, FX14, FX15, FX16, and FXVMA. 1 of 5

FX06 Accessories (Part 2 of 2) IU-9100-8401 NP-PWR1209 GSM Modem and Accessories LP-KIT007-002C LP-KIT090-000C LP-KIT090-001C LP-KIT090-003C LP-KIT090-004C LP-KIT090-005C Converter RS-232C/RS-485 (N2) 230 VAC (Europe only) Power Supply Adapter for Programming Key 120 VAC/12 VDC (North America only) Interface Cable for GSM modem to FX06, 1.5 m (4.9 ft) GSM 900/1800 Supreme 10 FastTrack Modem GSM Modem Plug-in Antenna GSM Modem Magnetic Mount Antenna with 2.5 m (8.2 ft) Cable GSM Modem Panel Mount Antenna with 5 m (16.4 ft) Cable GSM Modem Power Adapter, 230 VAC/12 VDC, Wall Plug Room Command Modules, TM Series without Display - 80 x 80 mm (3.15 x 3.15 in.), C TM-2140-0000 TM-2150-0000 TM-2160-0000 TM-2160-0002 TM-2160-0005 TM-2160-0007 TM-2190-0000 TM-2190-0005 Room Sensor Module, temperature sensor only Room Sensor Module, occupancy button and Light-Emitting Diode (LED) Room Sensor Module, 12 to 28 C setpoint dial, occupancy button and LED Room Sensor Module, 12 to 28 C setpoint dial, occupancy button and LED, fan speed override Room Sensor Module, +/- setpoint dial, occupancy button and LED Room Sensor Module, +/- setpoint dial, occupancy button and LED, fan speed override Room Sensor Module, 12-28 C setpoint dial Room Sensor Module, +/- setpoint dial Network Room Modules Ordering Information (Available in Europe) Product Code Size (mm) Service Port Type Features/Options LCD Display Temperature Adjust Dial Fan Speed Selector Button LP-NRM001-000C 80 x 80 Program Key No No No No No LP-NRM002-000C Yes Yes No No No LP-NRM003-000C Yes Yes Yes No No LP-NRM511-000C MUI No No No No Yes 1 LP-NRM502-000C Yes Yes No No No LP-NRM503-000C Yes Yes Yes No No 1. The FX06 controller only supports one connected NRM and therefore the addressing feature is not used. Room Command Modules - Available in North America - TM Series without Display - 120 x 80 mm (4.72 x 3.15 in.), C/ F TM-2141-0000 Room Sensor Module, temperature sensor only TM-2151-0000 Room Sensor Module, occupancy button and LED TM-2161-0000 Room Sensor Module, 54-82 F/12-28 C setpoint dial, occupancy button and LED TM-2161-0002 Room Sensor Module, 54-82 F/12-28 C setpoint dial, occupancy button and LED, fan speed override TM-2161-0005 Room Sensor Module, +/- setpoint dial, occupancy button and LED TM-2161-0007 Room Sensor Module, +/- setpoint dial, occupancy button and LED, fan speed override TM-2191-0000 Room Sensor Module, 54-82 F/12-28 C setpoint dial TM-2191-0005 Room Sensor Module, +/- setpoint dial Network Room Modules Ordering Information (Available in North America) Product Code Features/Options Size, mm (inch) Service Port Type LCD Display Temperature Adjust Dial Fan Speed Selector Button LP-NRM511-000C 80 x 80 mm MUI No No No No Yes 1 LP-NRM552-000C (3.15 x 3.15 in.) Yes Yes No Yes No LP-NRM553-000C Yes Yes Yes Yes No LP-NRM611-000C 120 x 80 mm MUI No No No No Yes 1 LP-NRM652-000C (4.72 x 3.15 in.) Yes Yes No Yes No LP-NRM653-000C Yes Yes Yes Yes No 1. The FX06 controller only supports one connected NRM and therefore the addressing feature is not used. F/ C F/ C Addressable Addressable 2 of 5

Sensor Accessories Product Code Number NS-WALLPLATE-0 Wall plate kit used to mount an 80 x 80 mm (3.15 x 3.15 in.) sensor onto a 51 x 102 mm (2 x 4 in.) wall box Software Ordering Information LP-FXTPRO-0 FX Tools Pro CD-ROM (FX Builder, FX CommPro N2, FX CommPro LON, FX CommPro BACnet, FX Loader, MD Loader) - New User Version LP-FXTPRO-6 FX Tools Pro CD-ROM (FX Builder, FX CommPro N2, FX CommPro LON, FX CommPro BACnet, FX Loader, MD Loader) - Upgrade Version Technical Specifications Analog Inputs (AI) AI1, AI2, AI3, AI4 See Sensor Input Types in this table Software configurable. Application: temperature, humidity, pressure. 16-bit ADC, 13-bit effective resolution. AI Power +5 V at 15 ma max. To power active or ratiometric sensors directly from the controller. AI/AO Power +15 V at 20 ma max. To power active sensors directly from the controller. Sensor Input Types Sensor Type Full Linearization Range Accuracy at 20 C (68 F) - Controller and Sensor (sensor accuracy not included) A99-50 to 100 C (-58 to 212 F) ±0.5 C (±1 F) NTC 10k -40 to 150 C (-40 to 300 F) ±0.5 C (±1 F) PT1000 Extended -50 to 160 C (-58 to 320 F) ±0.5 C (±1 F) Ni1000-45 to 120 C (-49 to 248 F) ±0.5 C (±1 F) (Johnson Controls temperature sensor) Active Voltage 0-10 VDC ±0.05 VDC Active Ratiometric 0.5-4.5 VDC ±0.05 VDC Digital (Binary) Inputs (DI) DI1, DI2, DI3, DI4, DI5 Potential free contacts for status monitoring Status and events Transition Counter at 50 Hz max. Minimum Time ON: 10 ms Minimum Time OFF: 10 ms Digital (Binary) Outputs for Selected Models Relay Outputs Digital (Binary) Outputs (DO) Model Channel Type Remark/Application FX06P0x DO1 - DO6 SPST 3(1)A, 250 VAC Each relay contact is independent with its own terminals power relay FX06P2x DO1, DO2 0.5A/24 VAC triacs 3-point incremental actuators, thermal actuators, and other actuators DO3 - DO6 SPST 3(1)A, 250 VAC power relay Each relay contact is independent with its own terminals. Dielectric strength coil-contacts: 4,000 V RMS for 1 minute Dielectric test voltage on open relay contact:1,000 VAC RMS Maximum relay switching rate at maximum load: 6 operations/minute Average relay contact life: 30,000 operations at maximum load Analog Output (AO) AO1, AO2 0-10 VDC (3 ma max.) Actuators and control devices FX06 Controller Product Codes LP-FX06Pxx-xxxC Power Supply Requirements 24 VAC/VDC ±15%, 50/60 Hz - Safety Extra-Low Voltage (SELV) (Europe) - Class 2 North America Power Consumption Controller: 7 VA maximum (Additional 3VA if MUI is connected) Housing Material ABS + polycarbonate, self-extinguishing: UL 94-5VB flammability rating Protection Class Front Plate (when mounted in panel) IP55; Rear Enclosure IP20, IEC 60529 Ambient Operating Conditions -40 to 50 C (-40 to 122 F), 10 to 95% RH (noncondensing) Note that the integral user interface does not operate below -20 C (-4 F). 3 of 5

Ambient Storage Conditions Dimensions (H x W x D) Weight (with package) -40 to 70 C (-40 to 158 F), 10 to 95% RH (noncondensing) 44 mm (1.7 in.) x 70 mm (2.7 in.) x 95 mm (3.6 in.) 0.32 kg (0.7 lb) including communication module 0.68 Kg (1.5 lb) including communication module and cable set Real-Time Clock Accuracy: Better than ± 200 ms per day at constant ambient temperature of 25 C Backup: Minimum 10 days without power at 25 C Integral LCD Display Resolution -999 to 999 or -99.9 to 99.9 (4 digits for each row) I/O Ratings See the I/O tables in the Technical Specifications section. Power Supply Outputs Connections Cable Length for Inputs Agency Compliance FX06 Controller 24 VAC/DC for panel mount MUI (from controller power supply input) 15 VDC 20 ma power supply for active sensors and PWM output 5 VDC 15 ma power supply for ratio-metric sensors Removable plug connectors. Mating connectors and cables provided with controller or available to order. See FX06 Field Controller Ordering Information and FX06 Accessories. Max. 100 m (330 ft.) with cables 0.6 mm, 22 AWG Europe 2004/108/EEC, EMC Directive: EN 61000-6-3, EN 61000 6 2 2006/95/EEC, Low Voltage Directive: EN 60730. Canada UL Listed (PAZX7), CAN/CSA C22.2 No. 205, Signal Equipment Industry Canada, ICES-003 United States UL Listed (PAZX), UL 916, Energy Management Equipment FCC compliant to CFR 47, Part 15, Subpart B, Class A RS-485 Bus - 9600 Baud Number of Devices Repeaters End-of-Line Termination RS-485/RS-232C Converter for FX CommPro N2 Electrical Isolation in FX06 N2 Open Communication Maximum bus segment length without repeater: 1,200 m (4,000 ft), 0.8/0.6 mm diameter (20/22 AWG) 2 x twisted pair with shield. Use the same cable type throughout segment. Maximum of 32 devices on a bus segment without repeater Maximum 2 repeaters between the master (supervisory) device and any slave (FX controller) device on the network. RP-9100 is recommended. 220 ohm at each end of segment >100 m (300 ft). For segment <100 m (300 ft), only one 220 ohm termination is required. IU-9100 or LP-KIT200-000C. (Other converters must support automatic Data Send Control [DSC]. RTS is not supported by FX CommPro.) 500 V LON Network Topology and Line Terminators Note: LON Communication Daisy chained Bus Topology: two terminators of 100 ohm required - one at each end of the bus. Free (star) topology: single terminator of 50 ohm required at a central point in network. Use the same cable type throughout bus or network. Number of Nodes 64 (if repeaters are not used), FTT-10 nodes only. Cable Type Length with FTT-10 devices Bus Topology Free Topology Belden 85102 2,700 m (8,900 ft) 500 m (1,640 ft) Belden 8471 2,700 m (8,900 ft) 500 m (1,640 ft) Level IV 22 AWG 1,400 m (4,600 ft) 400 m (1,300 ft) For full technical details of LONWORKS networks, refer to the LONMARK Guidelines at www.lonmark.org. Power Supply Memory Type and Size Connection to controller Enclosure IP Class Ambient Limits FX Programming Key Directly powered from the Display Bus port of the FX06 or from an AC/DC adapter 230 V/12 to 15 VDC 2 VA minimum Flash memory 1 MB RS-485, not isolated. Cable (10 cm/4 in.) provided with connector for FX06 front display socket, and a screw terminal block for connection to an RS485 converter. IP40 Operating: 0 to 40 C (32 to104 F), 10-95% RH (noncondensing) Storage: -20 to 70 C (-4 to 158 F), 10-95% RH (noncondensing) Compliance 2004/108/EEC, EMC Directive: EN 61000-6-3, EN 61000 6-2 4 of 5

GSM Connection GSM Modem - Supreme 10 GSM 900 GSM 1800/1900 Voltage Range 5 to 32 VDC Power Supply @25 C Min. Typ. Max. Min. Typ. Max. Input Supply voltage 5 13.2 32 5 13.2 32 Input Peak Supply Current (in @5 V 1.8 A 1.1 A Communication) @13.2 V 0.7 A 0.4 A @32 V 0.4 A 0.2 A Input Average Supply Current (in @5 V 330 ma 220 ma Communication) @13.2 V 130 ma 95 ma @32 V 65 ma 50 ma Input Average Supply Current (in Idle @5 V 31.4 ma 31.4 ma Mode) @13.2 V 13.2 ma 13.2 ma @32 V 5.6 ma 5.6 ma Ambient Operating Conditions -20 to 55 C (-4 to 131 F) Ambient Storage Conditions -25 to 70 C (-13 F to 158 F) Housing Material Aluminum profiled Volume 12.2 cm³ (0.7 in.³) Weight < 130 g (0.3 lb) Dimensions 98 mm (3.9 in.) x 54 mm (2.1 in.) x 25 mm (1 in.) (excluding connectors) Overall Dimensions 110 mm (4.3 in.) x 54 mm (2.1 in.) x 25 mm (1 in.) 5 of 5