June 2006 Data Sheet 2.45 Description Moore Industries Signal Isolator/Converter with Display combines smart digital technology with a large display to deliver an accurate signal that is easily monitored in the field. The highly versatile accepts a wide range of current or voltage inputs, then outputs the signal as an isolated, proportional, current. A flexible analog/digital hybrid, this 2-wire (looppowered) transmitter programs in seconds to handle a wide range of signal interface applications: Monitor Signals using its large, accurate display. Isolate Signals to stop erratic process measurements caused by ground loops. Convert Signals so field instruments can interface directly with an indicator, recorder, DCS, PLC or PC-based SCADA system. Divert Signals so the output from one transmitter can be sent to two separate locations. Protect Equipment and Signals by eliminating common electrical paths. Boost Signals so that more instruments can be added to an overburdened loop. Solve Bucking Power Supplies by stopping the conflict caused when a 4-wire transmitter and a DCS both power the same process loop. Figure 1. Program the versatile to accept any one of a wide range of inputs and convert the input into the EGU of your choice. M A PS -PS 1 2 3 4 Isolated, Scaleable, Output Large, Easy-to Read Display Available in explosion-proof enclosures and a variety of other configurations, the installs easily in even the most rugged environments. Features Wide range of signal input choices. There s no need to specify and stock fixed-range instruments as spares. The handles the majority of current/voltage interface applications you are likely to encounter. Custom linearization curves. Easily create your own custom linearization curve tables to accurately convert any non-linear input signals to their linear representations. Easy-to-read, customizable display. The s display features two rows of large characters that can be set to display any EGU. Input/output. The delivers superior protection against the harmful effects of ground loops and other plant noise. RFI/EMI protection. The is resistant to the harmful, unpredictable effects of radio frequency and electromagnetic interference. Enhanced configuration software. From a single screen, you can set all the applicationspecific parameters. VOLTAGE 0-1Vdc 0-5Vdc 1-5Vdc 0-10Vdc Special Ranges CURRENT 0-20mA 0-50mA 10-50mA Special Ranges I n p u t Certifications 2006 Moore Industries-International, Inc. 235-710-10B All product names are registered trademarks of their respective companies. Page 1
Specifications Performance Overall Accuracy: ±0.036% of span (includes input accuracy, output accuracy, and the combined effects of linearity, hysteresis, repeatability and adjustment resolution) Stability: Input to output stability (% of span): 1 year: 0.09%; 3 years: 0.15%; 5 years: 0.20% Minimum Input Span: Current, 1.0mA; Voltage, 250mV Isolation: 500Vac/1000Vdc input to output to case Measurement Cycle: Updates 8 times per second Response Time: 128msec from time input is applied until output settles to the specified output accuracy Step Response: 128msec maximum for the output to change from 10% to 90% of its scale for an input step change of 0% to 100% Input Impedance: Voltage, 1Mohms; Current, 20 ohms Load Effect: Negligible within specified load limits Performance (continued) Display Ripple: 10mVpp, maximum (measured across 250 ohm resistor) Power Supply Effect: 0.002% of span per 1V change Over-Voltage Protection: 48V, maximum on output; 48V reverse polarity protection on output Maximum Input Overrange: Current: 100mA maximum continuous; Voltage on Current Input: ±1.5Vdc peak; Voltage: 18Vdc Load Capability: Supply Voltage 10V = Ohms 0.024A Output Current Limiting: 3.8mA (low) and 21.4mA (high) Type: LCD: Top Row, 10.16mm (0.4 in) high black digits on a reflective background; Bottom Row, 5.72mm (0.225 in) high black digits on a reflective background Format: Two rows of five alphanumeric characters Range: -99999 to 99999 Minimum Display Span: 1.00 Ambient Conditions Weight Operating Range: Transmitter: 40 C to 85 C (40 F to 185 F) Display: 25 C to 85 C (13 F to 185 F) Storage Range: 40 C to 85 C (40 F to 185 F) Effect of Ambient Temperature on Accuracy: ±0.015% of span/ C Relative Humidity: 0-95%, non-condensing RFI/EMI Immunity: 20V/m@20-1000MHz, when tested according to SA standard 33.1 abc; 20V/m@20-100MHz, 1kHz AM@80% when tested according to IEC 1000-4-3-1995 with <0.5% error Common Mode Rejection: 100dB, minimum,@50/60hz Normal Mode Rejection: 60dB, typical,@1vp-p, 50/60Hz HP Housing: 178g (6.3 oz) BH Housing: 1.5kg (3.3 lbs) D-BOX Housing: 688g (1 lb, 8.3 oz) Rugged Enclosures Available We carry a complete line of durable enclosures to protect and complement our high-quality isolators. Choose from our explosion-proof BH housing or our NE 4X and IP66 certified D-BOX housing. Everything You Need is Included... Each order comes with one copy of our Intelligent PC Configuration Software (Windows compatible) and one non-isolated configuration cable. To order additional software or cables: Part Number Part 750-75E05-01 Intelligent PC Configuration Software 803-039-26 Isolated Configuration Cable 803-040-26 Non-Isolated Configuration Cable Page 2
Ordering Information Unit Input Output Power Options Housings Isolator/ Converter with Display PRG Programmable with supplied Configuration Software CURRENT (into 20 ohms) Any range from 2.5mA to 55mA including: 0-20mA 0-50mA 10-50mA VOLTAGE (into 1Mohm) Any range from 0.5V to 11V including: 0-1Vdc 0-5Vdc 1-5Vdc 0-10Vdc (recommended minimum span, 250mV) 4-20 User scaleable with supplied software 10-42DC 10-30DC for -ISC, -ISF, -ISE and -NE options To order, specify: Unit / Input / Output / Power [Housing] Model Number Example: / PRG / 4-20 / 10-42DC [BH2NG] -ISC CSA approved IS -ISF FM approved IS -ISE ATEX IS approved -NE ATEX Type N approved with BH BH2NG 2-Hub, explosion-proof enclosure with glass cover BH3NG 3-Hub, explosion-proof enclosure with glass cover D1LC 1-Hub, low base, clear cover, NE 4X (IP66) enclosure D2LC 2-Hub, low base, clear cover, NE 4X (IP66) enclosure HP Hockey-puck housing and spring clips DN Snap-in mounting for HP case on TS-32 DIN rail FL Mounting flanges on HP suitable for relay track or screw mounting FLD Mounting flanges on HP suitable for 3½ relay track or screw mounting SB2NG 2-Hub, Explosion-Proof enclosure with two, ½-inch NPT entry ports and a glass cover SB2MG 2-Hub, Explosion-Proof enclosure with two, M20 x 1.5 entry ports and a glass cover A suffix indicates SAA/TestSafe (Ex d) Flame-Proof approvals (i.e. BH2NGA) E suffix indicates ATEX (EEx d) Flame-Proof approvals (i.e. BH2NGE) P suffix indicates enclosure comes equipped with base plate and U-bolts for mounting on a 2-inch pipe (i.e. BH2NGP or SB2MGP) Certifications Factory Mutual Approvals FM Global [HP in BH and SB Housings] Explosion-Proof* Class I, Division 1, Groups A*, B, C, D. Dust-Ignition Proof Class II & III, Division 1, Groups E, F, G. NE 4X; IP66; T6 @ 60 C Max. Amb. [HP] Intrinsically Safe Class I, II, III, Division 1, Groups A, B, C, D. Non-Incendive Class I, Division 2, Groups A, B, C, D. Suitable For: Class II, Division 2, Groups F, G. Class III, Division 2. T4A@60 C / T5@40 C Max. Amb. Temp. Canadian Standards Association (CSA) General (Ordinary) Locations Intrinsically Safe [HP]: Class I, Division 1 & 2, Groups A, B, C, D. T4A@60 C / T5@40 C Max. Amb. Temp. TestSafe (Australian) Approvals: Flame-Proof [HP in BH Housing] Ex d IIC T6@60 C European Approvals: CENELEC/ATEX Directive 94/9/EC [HP in BH Housing] Intrinsically Safe II 1G EEx ia IIC T4 Type N II 3G EEx na II T4 T4@60 C Maximum Ambient Temperature Flame-Proof II 2GD EEx d IIC T6@60 C Maximum Ambient Temperature CE Conformant EMC Directive 89/336/EEC EN 61326 * BH HousingGroup A only: Seal all conduits within 18". Specifications and information subject to change without notice. Page 3
PS -PS 1 2 3 4 PS -PS 1 2 3 4 Additional Features Custom Linearization Curves Program your with up to 85 custom linearization points. The ability to plot a custom linearization curve is beneficial when non-linear input signals must be converted to linear output representations. Typical applications include monitoring a non-linear transducer, the level of odd-shaped tanks and flow meter linearization. Monitor Signals Let the make checking the loop easy with its accurate current transmission and large display. And, with an update rate of eight times per second, you can be confident that the display precisely reflects the loop s status. Customized Display The versatile can be programmed to display the input, output or toggle between both. It will also display the engineering unit of your choice (up to five capital letters). PS -PS 1 2 3 4 Long-Term Stability With error rates as low as ±0.09% over a one year period, and ±0.20% for five years, you can schedule calibrations less frequently without sacrificing accuracy. Powerful Isolation Continuous of 500Vac/ 1000Vdc input to output to case will prevent false signals due to ground loops and other noise. Advanced Noise Rejection Filter out 50 or 60Hz noise with our noise rejection feature. Certified Field Enclosures Available Order the in our durable BH enclosure for explosion-proof protection at an affordable price. For applications in rugged environments where explosion-proof protection is not required, choose the NE 4X and IP66 certified D-BOX housing. Convert Signals The takes one process signal type (such as 1-5V) and converts it to a standard, isolated. This allows devices like transmitters and transducers to interface directly with an indicator, recorder, DCS, PLC, or PC-based SCADA system. 4-WIRE 1-5VDC Isolated POWER SUPPLY RECEIVER Solve Bucking Power Supplies When two devices (such as a 4-wire transmitter and a DCS) are trying to source power to a loop, the result is a non-functioning loop. When neither of the devices can be eliminated, the solution is the. It can operate with powered inputs from both sides, thus restoring normal operations to the loop. 4-WIRE 24V 24V DCS Page 4
PS -PS 1 2 3 4 PS -PS 1 2 3 4 PS -PS 1 2 3 4 Stop Ground Noise A difference in potential between a grounded transmitter and a grounded receiving device on the same loop may result in unpredictable ground loop problems, which can lead to signal drift. Use the to break the galvanic path between a field transmitter and an indicator, recorder, DCS, PLC or PC-based SCADA system. This stops the harmful effects of ground loops, motor noise and other electrical interferences. NON- ISOLATED 2-WIRE Ground #1 PS PS Non-isolated Isolated PS ma or PS V POWER SUPPLY POWER SUPPLY RECEIVER Ground #2 Boost Signals If you need to add another instrument to an overloaded loop, use the. It features a high drive capability of 600 ohms (with a 24V power supply) and an input impedance of just 20 ohms. 4-WIRE (into 600 ohms maximum) INTEGRATOR (250 ohms) PID (250 ohms) into 600 ohms 24V RECORDER (250 ohms) Divert and Protect Signals Using the, you can send the output from one transmitter to a second location, protect expensive monitoring/control equipment by eliminating common electrical paths, or create a buffer between devices to allow interruption of one system without impacting the other. ISOLATED 2-WIRE Isolated loop 24V PLC DCS 24V Isolated loop Page 5
One Window. One Minute. One Setup. Configuring the is as simple as point-and-click. All you need is a PC running Windows, our Configuration Software (one copy supplied free with each order), and a configuration cable. In minutes, you can begin configuring your transmitter s: Figure 2. Program the in a minute or less using just this software window. Input type and range (zero and full scale) Output range (, zero and full scale) Noise rejection (50Hz or 60Hz) Direct or reverse output Over or under input range detection Custom instrument tag and serial number Custom input linearization Custom input trimming Fixed output with an easy loop test Damping time for erratic signal compensation (0-20 seconds) Custom LinearizationTables Unusual inputs are not a problem for the. Not when it is so easy to build a custom 85-point linearization table with the Configuration Program s straightforward interface. Output Damping If your sensor is prone to step increases and decreases, use the to lessen the impact on your process. You can program a damping value from 0 to 20 seconds, averaging out sensor fluctuations over the time period setting, and lessening the impact of step changes. On-Screen Setup Confirmation Once programmed, the operating parameters you have selected are constantly displayed in the configuration window. Configuration Alerts Data fields on the configuration window provide alert messages (such as Zero or Full Scale Outside of Conformance Range ) to let you know when you are making a nonstandard or ill-advised selection. Store and Print Files After you ve created a configuration file, it can be downloaded to multiple s, printed out as a hardcopy, or named and stored (on a PC hard drive or other media). Reverse Output Setting Zero Scale Input numerically above Full Scale Input will result in the transmitter s output going up when the input goes down, and vice-versa. When you have chosen this operation, the Output portion of the configuration screen changes to read Reverse Output. Digital Output Trimming A sophisticated yet simple-to-implement software feature allows you to adjust the s output to compensate for inaccuracies in your readout equipment. The Zero Scale Output can be adjusted between 3.797 and 17.400mA. The Full Scale Output adjusts between 7.798 and 21.401mA. Context-Sensitive HELP System Just click on Help, then on the area on the Configuration Screen where you are encountering difficulty, and a concise explanation appears. Page 6
Figure 3. Dimensions of the in a D-BOX Enclosure 130 mm (5.12 in) 116 mm (4.56 in) CONDUIT FITTING BODY BEZEL COVER 118mm (4.65 in) 112mm (4.40 in) 82.6 mm (3.25 in) 64mm (2.50 in) 81mm (3.2 in) INSTRUMENT TAG PS -PS 1 2 3 4 FRONT VIEW SIDE VIEW 84mm (3.30 in) 27mm (1.05 in) Figure 4. Dimensions of the in a BH Enclosure 10mm (.38 in) 129mm (5.06 in) TOP VIEW BOTTOM VIEW 102mm (4.00 in) 84mm (3.30 in) 68mm (2.69 in) PS -PS 1 2 3 4 65mm (2.55 in) 53mm (2.09 in) 124mm (4.90 in) 25mm (1.00 in) SIDE VIEW 66mm (2.60 in) 102mm (4.00 in) FRONT VIEW 57mm (2.25 in) 25mm (1.00 in) GND 1/2 NPT 119mm (4.70 in) 76mm (3.00 in) IDENT TAG Page 7
Signal Isolator/Converter With Display Figure 5. Dimensions of Hockey-Puck with Flange Mount 76mm (3.00 in) 18mm (.70 in) 83mm (3.25 in) 66mm (2.58 in) 61mm (2.4 in) 62mm (2.45 in) PS -PS 1 2 3 4 43mm (1.70 in) 64mm (2.50 in) FRONT VIEW SIDE VIEW Table 1. Terminal Designations. Input Input Output Type Terminals Terminals Terminal Number 1 2 3 4 Left to Right Current Inputs I -I PS -PS Voltage Inputs V -V PS -PS United States info@miinet.com Tel: (818) 894-7111 FAX: (818) 891-2816 Australia sales@mooreind.com.au Tel: (02) 8536-7200 FAX: (02) 9525-7296 Belgium info@mooreind.be Tel: 03/448.10.18 FAX: 03/440.17.97 The Netherlands sales@mooreind.nl Tel: (0)344-617971 FAX: (0)344-615920 China sales@mooreind.sh.cn Tel: 86-21-62491499 FAX: 86-21-62490635 United Kingdom sales@mooreind.com Tel: 01293 514488 FAX: 01293 536852 2006 Moore Industries-International, Inc. Specifications and information subject to change without notice.