CANBUS Connector Rx and Tx LED to indicate that communication is active Closed circuit terminal (Term) LAN serial port connector

Similar documents
XB800D Series (v.1.0)

MCX08M2 Programmable controller

Controllers for compressor racks with advanced energy saving. PN08 September 2016

EXPANSION PERIPHERAL CVM-R10 C. (Code ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A.

UNIVERSAL CURRENT CONVERTER

Process displays For current and voltage

Programmable controller MCX06C

FEC - FAC. Metasys controllers. Complex BAS Programmable controllers. Catalog Page. Field Equipment Controllers

FX Input/Output (I/O) Modules XM07 and XM14

MDC-20. Maximum Demand predictive Control. Description

Data sheet. MCX15B electronic controller MAKING MODERN LIVING POSSIBLE. REFRIGERATION & air CONDITIONING DIVISION. Danfoss Electronics spa

XEC supercap (v. 1.0)

Measuring transducers MI4x0 series Programmable transducers for RTD sensors MI450

E-STOP relays, safety gate monitors

MCX06C Programmable controller

PEAK TM. PEAK TM controllers. Mid-Market BAS Smart equipment controllers. HVAC/R controllers

Expansion Module HZS 541-1S

MOD-IO9 Modbus Input / Output Modules, Wall Mounted

User s manual. Programmable panel meter IPD

Electronic monitoring relays PMDsrange

I/O EXPANSION MODULES

Strain Gauge Converter

XT-9100 Technical Bulletin

INSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3

Energy Management Modular DC Energy analyzer Type VMU-E and VMU-X

TX-I/O Product Range. Features. Description. Document No January 24, 2007

4 C/O. Contact material AgNi AgNi gold-plated Nominal contact current Inrush current

Compact Coded Magnetic Safety Interlock Switch and Control Units

Time Counters mini "h", DC Version

E-STOP relays, safety gate monitors

Technical data. Dimensions: see page 116. ): 4 kv Rated insulation voltage (U i Over-voltage category: Power supply. Rated operating voltage (Un):

OTB1E0DM9LP I/O distributed module OTB - Ethernet TCP/IP m

Multifunction Transducer MT440

TM3TI8T module TM3-8 inputs temperature

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases

Displays Transducers. Displays and transducers

E-STOP relays, safety gate monitors

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

IQ21x Series Controllers

PTC/PT100 board 2.0 Option

POSITION MONITOR USERS MANUAL POM-M2 / POM-M3. Content

EM2020 Selectable AC transducer A (UK)

LLR-MOD Modbus Light Level and Occupancy Sensor

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

FX-PCX Expansion Input/Output Modules Catalog Page Code No. LIT Issued April 17, 2015

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

Installation manual CF8-W-Disp-AL

MIC-2 MKII, Multi-instrument DATA SHEET

PTC/PT100 board 2.0 Option

Peak/Valley Hold Unit (PVHU) User Manual V3.00

Positive-guided relay outputs: 4 safety contacts (N/O), instantaneous

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

Efficient. Innovative. Sustainable.

PCD3.C90. Date Modification Asked by: Version E/A Bus Connector PCD2.K106 change to PCD3.K106 Müller.R 1.1

Temperature Controller E5C4

Advanced Application Field Equipment Controller (FAC) Catalog Page

Digital hygrometers. FUNction

I-7520: RS-232 to RS-485. Input: RS-232 protocol Output:RS-485/RS-422 Speed: Self Tuner 'inside, auto switching baud rate, 300~ BPS

Version 5 Controls for natural ventilation. WUF 110 / 121 / 150 Actuator interfaces

APP 700 Technical Specification

E-STOP relays, safety gate monitors

Interface Relay CRINT-1x

INTRINSICALLY SAFE INSTRUMENTATION FOR HAZARDOUS AREAS

Hotel Room Controller

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA

Data Manager Installation Guide

RM35UB3. Product data sheet Characteristics. voltage control relay RM35-U - range V AC. Main. Complementary

96x48. gal/h. Digital panel meter 4½-digit DV4. Without setpoints. Sensor supply

02/11/2015

ACUREV Three-Phased DIN-Rail Multifunction Meter FEATURES

TM3TI4 module TM3-4 inputs temperature

RM35TF V AC

PTC/PT100 board 2.0 Option

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

Input/Output Module (IOM) Series Catalog Page

RM17UB3. Product data sheet Characteristics. voltage control relay RM17-U - range V AC. Main. Complementary

ABL8BBU24200 battery control module V DC - 24 V - 20 A - for regulated SMPS

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

RM17UAS. Product datasheet Characteristics. voltage control relay RM17-U - range V DC. Main. Complementary. Price* : 70.

XC1000D SERIES: CONTROLLERS FOR APPLICATIONS UP TO

OTB1E0DM9LP I/O distributed module OTB - Ethernet TCP/IP m

Safe monitoring relays


See instructions to download and install the latest version of LinkBoxMB and the user's manual at

Programmable controller Type MCX06C

Compact Genset Controller, CGC 400 Generator control and protection Engine monitoring and protection Generator and mains breaker control RS485 Modbus

Z-LINE Z201 Z-L LINE. AC Current. to DC ma/v isolator/converter CONVERTERS AND INTERFACES. Electric parameters conv verters

ICP DAS. ICP DAS 2015 M2M WLAN Wireless Solutions

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

Submittal Data Sheet WAGO Node for itm

E-STOP relay, safety gate monitor

Power supply. Interface technology in modular housing DIN rail devices, IM series. Features

EXOcompact. Third generation freely programmable controllers

GSM-PRO2: the perfect communicator GSM-PRO2-GPS. Input and output. Expansion modules

Switched Mode Power Supply Operating manual PAP800

H3CR-F H3CR-F8 H3CR-F-300 H3CR-F8-300

XR100/500 SERIES: CONTROLLERS FOR NT, MT AND LT - RS485 OUTPUT

E-STOP relays, safety gate monitors

MINI MCR-SL-PT100-UI-200

Technical specifications

Transcription:

4.4 IPEX60D 4.4.1 Description of the connections Connector Description Connector for 24Vac/dc power supply Analogue inputs (Pb1 - Pb5, PbC) Potential free digital inputs (DI1 - DI3, DIC) Additional power (+5Vdc, +12Vdc, GND) Analogue outputs (Out1 - Out4, GND) Analogue inputs (Pb6 - Pb7, PbC) Additional power (+5Vdc, +12Vdc, GND) Digital relay outputs 6 NO relays, 2 common CANBUS Connector Rx and Tx LED to indicate that communication is active Closed circuit terminal (Term) LAN serial port connector Dip-switch to set the address of the device. Green LED to indicate the presence of power Red status LED (ALARM) See relative paragraph 1592025700 - EN - rel. 2.0-2011_01_17.doc ipro Series 29/54

4.4.2 Description of the inputs and outputs Input No. Type of Input Description 1 Supply Power 24Vac or 24Vdc(-) 2 Pb1 3 Pb2 4 Pb3 5 Pb4 6 Pb5 7 +12V Additional power +12Vdc 8 +12V Additional power +12Vdc 9 Supply Power 24Vac or 24Vdc(+) 10 DI1 Digital input 1 (potential free contact) 11 DI2 Digital input 2 (potential free contact) 12 DI3 Digital input 3 (potential free contact) 13 DIC Common digital inputs 1 to 3 14 Pbc Common analogue inputs (NTC, PTC, PT1000, DI) 15 GND(-) 16 +5V Additional power +5Vdc Additional power reference 5Vdc and 12Vdc and analogue inputs (0-20mA, 4-20mA, 0-10V, 0-1V, 0-5V) 20 GND(-) Additional power reference 5Vdc, 12Vdc and analogue outputs 21 Out1 Analogue output 1 0-10V 22 Out2 Analogue output 2 0-10V 23 Out3 Analogue output 3 0-10V 24 Pb6 25 GND(-) Additional power reference 5Vdc, 12Vdc and analogue outputs 26 +12V Additional power +12Vdc 27 +5V Additional power +5Vdc 28 Pbc Common analogue inputs (NTC, PTC, PT1000, DI) 29 Pb7 30 CAN Bus CAN Bus connection (+), not open 32 CAN Bus CAN Bus connection (-), not open 33 CAN Bus CAN Bus connection (insulated gnd), not open 40 RL4 Relay 4 normally open contact 41 RL5 Relay 5 normally open contact 42 RL6 Relay 6 normally open contact 43 C Common relays 5, 6 and 3 44 C Common relays 1, 2 and 4 45 RL1 Relay 1 normally open contact 46 RL2 Relay 2 normally closed contact 47 RL3 Relay 3 normally closed contact 1592025700 - EN - rel. 2.0-2011_01_17.doc ipro Series 30/54

4.4.3 Technical specifications 4.4.3.1 Analogue inputs Analogue conversion type: 10-bit A/D converter Number of inputs: 7 Type of analogue input: NTC Dixell (-50T110 C; 10K 1% at 25 C) PTC Dixell(-55T115 C; 990 1% at 25 C) PT1000 Dixell (-100T150 C; 1K at 0 C) Digital input (potential free contact) Voltage: 0 - V, 0-5V, 0-10V (input resistance 3.7K ) Current: 0-20mA, 4-20mA (input resistance 100 Digital input status variation detection time: 100ms (in any case it depends on the cycle time set by the user in the given application) Accuracy: NTC, PTC, PT1000: ±1 C 0-1V: ±20mV 0-5V: ±100mV 0-10V:±200mV 2-20mA, 4-20mA: ±0.30mA Additional power: +12V: 40mA max per terminal +5v: 100mA Any inputs that are powered with a voltage that differs from that supplied by the device (+12V or +5V) must be powered separately with another transformer (do not use the same secondary of the controller's power) in order to prevent the inputs from malfunctioning or being damaged. 4.4.3.2 Digital inputs Opto-insulated potential free contact Number of inputs: 3 Digital input status variation detection time: 100ms (in any case it depends on the cycle time set by the user in the given application) Do not use live contacts in order to prevent the inputs from being damaged. 4.4.3.3 Analogue outputs Non opto-insulated internal power Number of outputs: 3 Type of analogue output: 3 fixed outputs 0-10Vdc (Out1 - Out3) Maximum load: 40mA (Out1 - Out3) 22 Accuracy: Out1 - Out3: ±2% full scale Resolution: 8bit The electrical devices controlled by these analogue outputs must be powered separately with another transformer (do not use the same secondary of the controller's power) in order to prevent the outputs from malfunctioning or being damaged. 4.4.3.4 Digital outputs Relays with NO contacts Number of outputs: 6 Type of output: Relays with normally open contact: Maximum load: 5A(250Vac) SPST 5(2)A Verify the capacity of the output used. There is double insulation between the digital outputs and the low voltage of the rest of the circuit. The common relays of the outputs are separate and split into groups. Different voltages can be used for different groups of relays but the same voltage must be used within each group. 1592025700 - EN - rel. 2.0-2011_01_17.doc ipro Series 31/54

4.4.3.5 Wiring diagrams 4.4.3.6 Mechanical specifications 4 DIN module 4.4.3.7 Electrical specifications Power Supply: Consumption: Connectors: 24Vac +10/-15%, 50/60Hz 20-36Vdc 10VA (Vac), 10W (Vdc) Molex connectors with low voltage wiring SELECOM/CIVILUX connectors for digital outputs (250Vac, 6A max) or with a different order code: Phoenix quick coupling connectors for low voltage STELVIO 90 screw connectors for digital outputs (250Vac, 6A max) 1592025700 - EN - rel. 2.0-2011_01_17.doc ipro Series 32/54

4.4.3.8 Plastic container Mount: On a DIN rail (EN 50022, DIN 43880) Fastened with screws via the removable plastic flaps. Material: PC-ABS Thermoplastic Self-extinguishing: V0 (UL94) Comparative Tracking Index (CTI): 300V Colour: Black 4.4.3.9 Setting the address of the device The address of the device is set via a dip-switch and numbering is binary as shown in the table below: 1592025700 - EN - rel. 2.0-2011_01_17.doc ipro Series 33/54