Description of the Simotion D4xx Firmware update

Similar documents
SIMOTION Version 4.1 SP5 Update Description

Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

SIMOTION V4.1 SP2 HF3/HF4

FAQ about Drive Technology

Welcome Guideline D435 training case with SIMOTION 4.1 SP1

Instructions on how to update the firmware from V4.3.x to V4.4.x

Welcome. Guideline SIMOTION D4x5-2. Training Case with SIMOTION V4.4

FAQ Communication over PROFIBUS

FAQ 03/2014. How do I go online? SIMOTION & SINAMICS.

FAQ about Drive Technology

FAQ Communication over IE

Service & Support. Which options exist for reading hardware limit switch signals into a technology CPU? Technology CPU.

FAQ about communication via IE

Totally Integrated Automation Application Notes

SIMATIC. Windows Automation Center WinAC Basis V4.1. User Manual. Version: 05/2004 A5E Siemens Automation

Siemens Hardware SIMOTION. Motion Control Getting Started with SIMOTION SCOUT TIA

SIMATIC/SINAMICS. Getting started with SINAMICS V90 PN on S Motion Control. Fundamental safety instructions 1. Introduction

Training document for the company-wide automation solution Totally Integrated Automation (T I A)

ID Title Description of the restriction Solutions for the restriction

SIMATIC. Windows Logic Controller (WinLC) Preface, Contents. Product Overview 1. Setting Up WinLC Software 2

Service & Support. How can the Safety Functions of SINAMICS S120 be activated in an existing STEP 7 Project? Technology CPU.

Notes on Installation and Use

SIMATIC. Automation Systems S7-300 CPU 317T-2 DP: Controlling a SINAMICS S120. Introduction. Preparation 2. Learning units 3. Further Information 4

Technological Data. How Can the Technological Data Coupling Be Used with the Drive? (Available for SIMOTION SCOUT V3.2 or later)

FAQ Communication via IE

High-response valve with integrated digital axis controller (IAC-R) and clocksynchronized PROFIBUS DP/V2 (PROFIdrive profile)

Accessing SINAMICS parameters via OPC server

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

FAQ Communication over PROFIBUS

Updating SIMOTION Devices SIMOTION. SIMOTION SCOUT Updating SIMOTION Devices. Preface. Overview. Updating 2. Restoring 3.

SIMATIC. Windows Automation Center RTX WinAC RTX V4.0. User Manual A5E

Applications & Tools. Control of the Safety Integrated Extended Functions of the SINAMICS S110 via the fail-safe inputs of the CU305 SINAMICS S110

FAQ about S7 communication via IE

6.22 Migration of SIMOTION D4x5 to SIMOTION D4x5-2

Application about Drive Technology

Bumpless Media Redundancy with PROFINET IRT (MRPD) SIMOTION & SINAMICS. Application description July Applications & Tools. Answers for industry.

Getting Started - Startdrive. Startdrive SINAMICS. Introduction 1. Connecting the drive unit to the PC. Creating a project 3

SIMOTION SIMOTION SCOUT V5.1 HF1 SIMOTION C V5.1 HF1 SIMOTION D V5.1 HF1 SIMOTION P V5.1 HF1. and SIMOTION Runtime software for.

Block Library Motor Starter SIRIUS for SIMATIC PCS 7

FAQ about Drive Technology

SIMATIC. Process Control System PCS 7 V7.0 SP1 Software Update With Utilization of New Functions (PCS 7 V6.x to V7.0 SP1) Preface.

Drive System Application

SIMOTION SIMOTION D410. Preface. Description 1. Commissioning (hardware) 2. Configuring SIMOTION D410. Commissioning (software) 4

Communication between HMI and Frequency Converter. Basic Panel, Comfort Panel, Runtime Advanced, SINAMICS G120. Application Example 04/2016

SIEMENS. General conditions and function limitations, notes for configuration and operation

Spring Training Atlanta, GA

SINAMICS S120. Getting Started with the. Drive Concept 1. Prerequisites 2. Creating the Drive Project OFFLINE 3

S7 Graph V 5.0 incl. Service Pack 1 Programming Software for Sequential Control Systems in SIMATIC S7

Applications & Tools. Application to support the acceptance test of the Safety Integrated Functions of SINAMICS G120 SINAMICS G120

SCE Training Curriculum for Integrated Automation Solutions Totally Integrated Automation (TIA)

Tool Calling Interface

SIMATIC. Component based Automation - WinLC PN Addendum to WinAC Basis V3.0. Foreword. Introduction to CBA and WinAC PN 2. Routing with WinLC PN 3

Description and Tutorial for. SIMOCRANE Drive-Based Technology V1.0 SP1 HF2. with Sinamics CU 310-2

How Do You Replace a CPU 41x with the CPU 410-5H Process Automation? SIMATIC PCS 7 FAQ 01/2016

SIMOTION. New functions of version V4.1 SP2

Commissioning PC Stations - Manual. and Quick Start SIMATIC NET. PC software Commissioning PC Stations - Manual and Quick Start.

SIMATIC Automation License Manager Manual 02/2008 A5E

I-Device Function in Standard PN Communication SIMATIC S7-CPU, CP, SIMOTION, SINUMERIK. Configuration Example 08/2015

SIMATIC HMI. Software RemoteOperate V2. Preface. Overview 1. Range of functions of the RemoteOperate software. Hardware and software requirements

Applications & Tools. Controlling distributed I/Os and drives from two controllers via PROFINET (Shared Device via GSD file) SIMATIC & SINAMICS S

Drive System Application

Output Cams and Measuring Inputs SIMOTION. SIMOTION SCOUT Output Cams and Measuring Inputs. Preface. Output Cam TO - Part I. Cam Track TO - Part II

SINAMICS S120 Family New functions in firmware V4.6 and STARTER V4.3 SP2

SINAMICS S120. Getting Started 01/2013 SINAMICS

Siemens Distributor SIMATIC. WinAC MP for MP370 V3.1. Preface, Contents. Product Overview. Transferring WinAC MP to the Multi Panel

SIMOTION. SIMOTION SCOUT Task Trace. Preface 1. Overview 2. Configuring 3. Working with the SIMOTION Task Profiler. Function Manual 05/2009

SIMOTION with SINAMICS S120 Safety Integrated Extended Functions Fail-safe drives connected to SIMOTION D435 Controlled with PROFIsafe via PROFIBUS

View the most recent product information online

Overview of functions

Notes on Installation and Use

SIMOTION. Motion control Output Cams and Measuring Inputs. Preface 1. Fundamental safety instructions 2. Output Cam TO - Part I 3

SINAMICS G120 Family New functions in firmware V4.6 and STARTER V4.3 SP2

Basic Functions for Modular. Machines SIMOTION. Motion Control Basic Functions for Modular Machines. Preface

Applications & Tools. SINAMICS S120: Control of the Safety Integrated Basic Functions via onboard terminals SINAMICS S120


SIMATIC. Windows Logic Controller WinLC RTX 3.1. Preface, Contents. Product Overview 1. Setting Up the WinLC RTX Software

Storage Concept and Data Backup Mechanisms for SIMATIC S7-300

Service & Support. Data Communication between S7 Station and PC Station, using SIMATIC NET OPC Server SIMATIC S7. Function description March 2013

Service & Support. How do I configure extended PROFIsafe on the CU240E-2?

CANopen with SINAMICS G120. SINAMICS G120 with speed setpoint and CAopen interface. FAQ November Service & Support. Answers for industry.

What's new? New functions for. SIMOTION V5.2 SP1 Edition 04/2018 siemens.com/simotion

FAQ about communication via IE

Drive System Application

Applications & Tools. SINAMICS G/S: Commissioningsupport scripts for SINAMICS drives. SINAMICS commissioning auxiliary scripts


SIMATIC. Windows Automation Center. WinAC Basis. Overview. Preface. Product Overview 1. Installing the Components of. WinAC Basis

Totally Integrated Automation (T I A) MODULE A3 Startup PLC- Programming with STEP 7

SINUMERIK 810D / 840Di sl / 840D / 840D sl Upgrade Instructions HMI-Advanced 7.3 SP3 for PCU 50.3

Features SIMOTION V4.1 SP2

Applications & Tools. Configuration of SINAMICS and MICROMASTER Drives with Drive ES in PCS 7 SIMATIC PCS 7. Application Example February 2012

SIMATIC NET for SIMOTION

SINUMERIK. SINUMERIK 840D sl SINUMERIK STEP 7 Toolbox V14 SP1. Preface. Product information. Configuring the NCU. Programming the PLC 3

SIMATIC. S7 and Profibus- DP Configuration Guide G1026

SINUMERIK 840D sl SINAMICS S120. IBN CNC: NCK, PLC, drive. Preface. Introduction 1. Safety information 2. Requirements for commissioning

SINAUT ST7. SINAUT ST7cc Control Center A I. Manual. Introduction to ST7cc. Installation. Preparation. Working with ST7cc Config

SCE Training Curriculum For Integrated Automation Solutions Totally Integrated Automation (TIA)

Upgrade instructions for the SIMOTION I-Device (PROFINET) SIMOTION V4.1 V4.2 or higher. FAQ March Service & Support. Answers for industry.

Windows NT Server Printer Driver Upgrade Instructions

The possibility of combining interface modules allows various bus and network systems to be integrated into the B&R SYSTEM 2005.

How can you display error messages and warnings of a frequency converter on a panel? WinCC flexible RT and Panels FAQ

Transcription:

Description of the Simotion D4 Firmware update Simotion D consists of several individual software components that can be updated separately. The following figure shows the individual software components and the mutual dependencies: D4 controller Simotion kernel version Engineering PC Simotion project Simotion device version CamTool Sinamics integr. CU version Sinamics component version Sinamics device version Technology packages Libraries Engineeringsystem Scout Authorization In general: The kernel version of Simotion D4 must agree with the version of the controller in the Simotion project. The version of the associated technology packages (e.g. TP-Cam) in the Simotion project must match the controller version. The library modules must match the used technology packages. The Simotion project must match the version of Simotion Scout. The update of the project to a more recent Scout version will be performed automatically (after an appropriate prompt) when an older project is opened. A more recent Simotion project cannot be processed with an older Scout version. The version of the integrated Sinamics Control Unit (CU) must match the kernel version of the Simotion. The Sinamics components (e.g. motor modules, SMCs, etc.) must match the version of the integrated Sinamics Control Unit. Note: The compatibility list shows the version dependencies to hardware and software components. Siemens AG 2005 page 1 / 29 version 21.03.2005

Execution sequence of the software update (also serves as the table of contents) 1 Updating the Engineering System... 3 1.1 Updating SIMOTION SCOUT... 3 1.2 Updating SIMOTION CamTool... 5 1.3 Performing the authorization update.... 6 2 Updating the project (offline)... 8 2.1 Updating the user project... 8 2.2 Replacing the Simotion device in the project... 10 2.3 Updating Technology Packages (TP)... 12 2.4 Updating the library... 16 2.5 Selecting the Sinamics device version... 18 2.6 Compiling the project and checking the consistency... 20 3 Updating the D4 device... 21 3.1 Updating the control unit... 21 3.2 Updating SINAMICS components firmware... 22 3.3 Additional tasks for DRIVE-CLiQ motors... 23 4 Restrictions for updating the software to version V3.2... 25 4.1 Adjusting the Protool project... 25 4.2 Error message: Error 1912: PROFIBUS: isochronous operation life sign failure... 27 4.3 Independent conversion of standard telegrams for the Sinamics update... 28 4.4 Placement of the telegrams in the control unit... 28 4.5 Updating the Sinamics firmware in the offline project causes error messages... 28 Notes: A generally valid procedure for the software update is described here. The Readme file for the associated software version must always be observed! Further information for the software handling, such as a new installation, a platform change, etc., is contained in the general documentation for Simotion. Further restrictions are contained on the Simotion SCOUT CD at: \1_Important\German\Randbedingungen\SIMOTION_Randbedingungen_V32.pdf The STARTER commissioning tool is integrated in SIMOTION SCOUT. The restrictions relevant for STARTER are contained on the CD at: \1_Important\German\Randbedingungen\STARTER_Liesmich.wri. The restrictions that affect the configuring of the drives must also be observed. Siemens AG 2005 page 2 / 29 version 21.03.2005

1 Updating the Engineering System 1.1 Updating SIMOTION SCOUT A complete installation of the SIMOTION SCOUT consists of the following programs: SIMOTION SCOUT AuthorsW SIMOTION SCOUT uses as language setting the default language set in the SIMATIC Manager. You make changes to this in the SIMATIC Manager in the Options > Settings... > Language menu. Currently the German, English and Italian languages are available in SCOUT. If other languages are set in the SIMATIC Manager, English is used as SCOUT setting. The AuthorsW program will be automatically updated to the more recent version during the installation. Prerequisites The exact prerequisites for the associated version are contained in the Readme.txt on the installation CD. Examples of the most important prerequisites for the version V3.2 are listed here: You must be logged on to the operating system with administrator rights Computer with Windows 2000 (Service Pack 3) or XP (Service Pack 1) Microsoft Internet Explorer (Version 5.0.1) SIMATIC STEP 7 Version 5.3 SP1 (not for SCOUT Standalone) One of the following cards must be used as software access point o an integrated PROFIBUS card for PG o a PROFIBUS card, e.g. CP5611 for standard PC o a PCMCIA PROFIBUS adapter, e.g. CP5512 for notebook o an Ethernet card Note: The Starter tool for commissioning individual drives, e.g. SINAMICS or MICROMASTER 410/420/440 as self-contained PC application cannot be installed with SIMOTION SCOUT on a computer, because Starter is already contained in SIMOTION SCOUT. Procedure 1. Insert the CD with SIMOTION SCOUT in the CD-ROM drive. 2. Start Windows Explorer and change to the CD-ROM drive. 3. Open the SCOUT_Vx.x/Disk1 directory. 4. Double-click Setup.exe. 5. Follow the instructions of the installation program. Siemens AG 2005 page 3 / 29 version 21.03.2005

Recommendation: Install the authorization as part of this setup. The installation program requests you to insert the authorization diskette in the diskette drive. 6. If a reboot is required during the installation: logon again after the start of the operating system with your user name and administrator rights. 7. After the end of the installation: restart the PC and logon again with your user name and administrator rights. Now every user logged on as main user can start and operate SIMOTION SCOUT. Siemens AG 2005 page 4 / 29 version 21.03.2005

1.2 Updating SIMOTION CamTool Prerequisites The exact prerequisites for the associated version are contained in the Readme.txt on the installation CD. The most important prerequisites are listed here: SIMOTION SCOUT must have already been installed on the system on which you want to install SIMOTION CamTool You must be logged on with administrator rights for the operating system. After the installation, every user (even those without administrator rights) can work with SIMOTION CamTool All other prerequisites correspond to the prerequisites for the SIMOTION SCOUT and are thus already available on the PC Procedure a) Deinstall SIMOTION CamTool: 1. Click in the Windows taskbar on Start > Settings > System Control. The System Control window will open. 2. Double-click Software. The Properties window for the software will open. 3. Mark the SIMOTION SCOUT CamTool entry in the Install/Deinstall register. 4. Click on Add/Delete. The deinstallation program will be started. 5. Perform the deinstallation program. SIMOTION CamTool will be deinstalled. b) Install SIMOTION CamTool 1. Insert the CD with the installation software in the CD-ROM drive. 2. Start the Windows-Explorer and switch to the CD-ROM drive. 3. Open the CamTool\Disk1 directory. 4. Double-click setup.exe. The installation program will be started. 5. Perform the installation program. SIMOTION CamTool will be installed. Siemens AG 2005 page 5 / 29 version 21.03.2005

1.3 Performing the authorization update. To allow the use of SIMOTION SCOUT or CamTool, an appropriate authorization diskette will be provided with the delivered product CD. This diskette contains the authorization for the SIMOTION SCOUT engineering system. Procedure 1. Insert the authorization diskette in the diskette drive. 2. Start the AuthorsW authorization program in the SIMATIC > AuthorsW > AuthorsW start menu. A new window will open. 3. Select in the Manage authorization register the version of the SIMOTION SCOUT to be updated. Siemens AG 2005 page 6 / 29 version 21.03.2005

4. Select Scout in the Authorization > Update menu. The data will be transferred. 5. Once the update has completed, the AuthorsW reports as follows: 6. Close the AuthorsW program. 7. Remove the diskette from the diskette drive. Siemens AG 2005 page 7 / 29 version 21.03.2005

2 Updating the project (offline) 2.1 Updating the user project If the project is opened with a more recent Scout version, the project will be updated automatically (after confirmation). Note: Prior to the update, a backup copy of the original project will be created, because the data storage of the project will also be updated for the update. This ensures that in the event of a failure (mains interruptions, unexpected malfunctions, incorrect operation,...), it will be possible to return to the original project. Procedure 1. When the project opens, a window appears with the notification that the project to be opened was created with a different Scout version and a query will be issued whether the update is to be performed. This prompt must be confirmed with OK. 2. After the conversion, a prompt appears whether the project is to be opened writeprotected. This prompt must be confirmed with No (Do not open write-protected) for a firmware update. Do not open write-protected: The project can be edited. The data between the controller and the project is not consistent. Diagnostic functions cannot be performed directly. The project must be loaded into the controller beforehand. Siemens AG 2005 page 8 / 29 version 21.03.2005

Open write-protected: The project remains consistent. The data in the controller and in the project is identical. Diagnostic functions (status, trace, etc.) can be performed directly. The project does not need to be loaded into the controller beforehand. Note: A project that was last edited with a more recent Scout version cannot be opened from a Scout with a lower version. However, the project can be converted with the more current Scout version to the required software version beforehand (operation: project save in old project format). Opening with the older Scout version is then possible. Siemens AG 2005 page 9 / 29 version 21.03.2005

2.2 Replacing the Simotion device in the project You perform this replacement in the hardware configuration. Procedure 1. Double-click in the project navigator in SIMOTION SCOUT on the SIMOTION device to be replaced. The hardware configuration will open. 2. Open the appropriate folder structure in the hardware catalog. Drag the entry with drag&drop to the previously assigned module rack. Note Ensure that you do not delete the controller to be replaced beforehand! With pressed left mouse button, move the appropriate controller over the controller to be replaced and release the mouse button as shown. Click Yes to confirm the replacement of the controller. 3. Confirm the displayed dialog box with Yes if you want to replace the SIMOTION device. Siemens AG 2005 page 10 / 29 version 21.03.2005

4. Accept the changes of the hardware configuration with Station > Save and compile in the hardware configuration. 5. Close the hardware configuration. Note The data of the SIMOTION device will be transferred immediately to the SIMOTION SCOUT project and the complete project saved. This causes all changes made in the project (e.g. axis configuration, etc.) to be also transferred to the project! Siemens AG 2005 page 11 / 29 version 21.03.2005

2.3 Updating Technology Packages (TP) The replacement of the modules or the import of the project data does not cause the versions of the technology packages (TP) assigned to the individual technology objects (TO) to be automatically transferred to a version valid for the SIMOTION device. This update will be performed in another work step. Prerequisites An update is necessary if you want to replace the version of the SIMOTION device in your existing project. - Project - Scout with the appropriate software version Procedure 1. Mark in the project navigator the required SIMOTION device. 2. Select the Select technology packages item in the context menu. Siemens AG 2005 page 12 / 29 version 21.03.2005

3. If, as last work step, you have replaced the SIMOTION device, the Technology packages from another version dialog window opens. Confirm with OK to release the existing links to the TPs and to assign new TPs. 4. The Select technology packages dialog window then opens. The Select technology packages window opens. Siemens AG 2005 page 13 / 29 version 21.03.2005

Activate the technology packages checkbox. Because the technology packages must have the same version as the kernel, the same version as the kernel is automatically assigned to each technology package in the SIMOTION SCOUT as of V3.0. Note: The CAM_EXT technology package is available as of version V3.2. Consequently, the TP CAM is always adequate for the update of a project with version < V3.2. If you want to extend your project with TP CAM_EXT functions, you must select the TP CAM_EXT. Observe the documentation with regard to TP CAM_EXT (required hardware version and memory size for the used target device). 5. If TOs that indicate an incorrect version are displayed as incorrect version for your project, then click update. If this is not the case, continue with the handling instruction 8. Siemens AG 2005 page 14 / 29 version 21.03.2005

6. The Update technology objects dialog window opens. Confirm with OK. 7. The successful update will be displayed. Confirm with OK. 8. Confirm the Select technology objects dialog window with OK. The update of the TPs has completed. Note If you use libraries in the project, they must also be updated. Siemens AG 2005 page 15 / 29 version 21.03.2005

2.4 Updating the library An update of the associated libraries is required when the version of the SIMOTION device or of the technology objects (TO) has changed in your existing project. Prerequisites - Project - Scout with the appropriate software version Procedure 1. Open the LIBRARIES menu tree in the project navigator. 2. Select a library, open the context menu with the right mouse button and select Properties... Siemens AG 2005 page 16 / 29 version 21.03.2005

3. Open the TPs/TOs menu in the Properties window. Select the Simotion device here ( C230-2 V3.1 in the example figure) and the technology packages ( CAM in the example figure) for which the library is to be valid. Note: Observe the device dependencies shown in the Help (Scout online help) 4. Close the dialog with OK. Siemens AG 2005 page 17 / 29 version 21.03.2005

5. Reselect the library in the project navigator, open the context menu with the right mouse button and start Accept and compile. 6. The update has completed when Accept and compile has been performed without error. 7. Repeat steps 1 to 6 for each additional library in the project. 2.5 Selecting the Sinamics device version Procedure for updating the Sinamics device version 1. Click with the right mouse button on the appropriate device, e.g. SINAMICS Integrated. A context menu will be displayed. Siemens AG 2005 page 18 / 29 version 21.03.2005

2. Select Target device > Device version. 3. The Device version dialog window will open. It lists all devices with the appropriate firmware versions. Select the required firmware version and close the dialog window. Note: You must use the first two entries in the list (SINAMICS S120 Integrated V2.1x or V2.2x) when you use a Simotion D435. Siemens AG 2005 page 19 / 29 version 21.03.2005

2.6 Compiling the project and checking the consistency 1. Save the project. 2. Perform the consistency test. No further error messages may appear here. 3. Once you have updated the Simotion device ( see Chapter 3), you can load the project into the controller. Siemens AG 2005 page 20 / 29 version 21.03.2005

3 Updating the D4 device 3.1 Updating the control unit Each SIMOTION D4 always contains the most current version when delivered. The user can use update to install a newer or older versions. You can obtain the update for the SIMOTION D from your Siemens contact. Prerequisites Windows PC Card reader for CompactFlash Card d435_fw.zip update file Note: This file must be used for all Simotion D devices (also D425 and D445). Procedure Warning: The update action will delete all project data and parameters on the CompactFlash Card! Important: The CompactFlash Card may be removed or inserted only when the controller is switched off. 1. Switch off the power supply for the D4. 2. Remove the CompactFlash Card from the controller. 3. Insert the CompactFlash Card in the module slot of the card reader. 4. Open the Windows Explorer. The CompactFlash Card must be visible in the Windows Explorer as a replacement data medium under some arbitrary drive. 5. Save the KEYS folder on the CompactFlash Card using the Windows Explorer on the PC/PG. This folder may contain license keys for licensed software options. 6. Delete all files and folders on the CompactFlash Card. 7. Unpack the complete d435_fw.zip file with a ZIP unpacker, e.g. "WINZIP", on the CompactFlash Card. Ensure that the settings of the unpacker retain the file structure. 8. Use Windows Explorer to transfer the KEYS folder from the PC/PG to the CompactFlash Card. 9. Remove the CompactFlash Card from the PG/PC. 10. Insert the prepared CompactFlash Card in the D4. 11. Switch on the power supply for the D4. The new firmware will be loaded from the SIMOTION CF into the D4. 12. The project must be reloaded after the controller has been updated. Siemens AG 2005 page 21 / 29 version 21.03.2005

13. Do not forget: The individual SINAMICS components must then be updated separately. ( see Section 3.2) 3.2 Updating SINAMICS components firmware After updating the firmware of the D4 control unit, you must update online the firmware of the individual SINAMICS components. Prerequisites The current firmware version must be stored on the CompactFlash Card in the D4 control unit. ( See Section 3.1) Procedure 1. Go online with the SCOUT on the SINAMICS. 2. Load the Sinamics project data (updated project) into the D4 and perform "Copy RAM to ROM". 3. Use the "Configuration Versions overview Firmware update" dialog box in the SCOUT to select all SINAMICS components and then start the firmware update. 4. After the firmware update, switch the 24V DC power supply off and on. 5. The drive device is operational once again. Siemens AG 2005 page 22 / 29 version 21.03.2005

3.3 Additional tasks for DRIVE-CLiQ motors 1. After performing all items, the following errors and warnings for all axes will be displayed in the alarm window. 2. To correct the errors, the expert list of each drive must be opened. 3. With a right-click in the parameter list, select the "Access level" menu item 4. The access level must be set to "Service (4)". This access level requires a password. Enter the password 37483 and confirm. 5. The following steps 6 to 8 must be performed successively and separately for each Sinamics drive! 6. Set parameter 10 to the "Encoder commissioning (4)" value. 7. Set parameter 440 to the "Accept serial number (1)" value. This automatically resets itself to the value 0. 8. Set parameter 10 to the "Ready (0)" value. Note: If you forget to perform this step, the axis will not be enabled. The Simotion program remains without an error message at the _EnableAxis command. 9. All error messages must now be confirmed in the alarm window. 10. Copy Sinamics_Integrated: RAM ROM 11. Sinamics_Integrated: Load into the PG 12. Go offline 13. Power Off Power On Siemens AG 2005 page 23 / 29 version 21.03.2005

14. If an online connection exists, no further error with regard to the encoder serial number should be present. Siemens AG 2005 page 24 / 29 version 21.03.2005

4 Restrictions for updating the software to version V3.2 4.1 Adjusting the Protool project 1. Open ProTool configuring. 2. Open the properties of the controller and select "Parameters...". 3. Reconnect the controller with the Simotion program and click "OK" twice to confirm. 4. Close the controller properties. Siemens AG 2005 page 25 / 29 version 21.03.2005

5. In the "Edit" menu, select "Restore symbolics" and then save the project. 6. When opening the "The associated symbolics could not be found" dialog (as shown in the examples below), the source names must be replaced. The correct notation for the names must be taken from the user project. The cause for this procedure is a subsequent change of the unit name syntax (uppercase/lowercase) in the Simotion project by the user. If this window does not open, all variables have been found and reconnected. Examples: 7. After a successful restore: transfer the ProTool configuring to the operator panel. Siemens AG 2005 page 26 / 29 version 21.03.2005

4.2 Error message: Error 1912: PROFIBUS: isochronous operation life sign failure Problem description: Life sign failure between Simotion D V3.2 and Sinamics Integrated in the RUN operating state. The problem occurs only at the D4x5 controller when neither of the DP lines was configured equidistant and makes itself apparent with the following alarms: Alarms occur cyclically again after the confirmation. Work-around: One of the two external DP lines must be set equidistant in the hardware configuration, preferably a DP line not previously used in the project (less effect on the project). No DP Slave needs to be configured on this line. The hardware configuration must be compiled without error and loaded into the controller after the change. It is possible to determine, for example, using the number of DP nodes and/or cyclical I/O data, whether the selected DP cycle time cannot be maintained; if necessary, configured nodes (e.g. PG, HMI) must be moved to a different line. Note: This problem will be corrected in version V3.2.0.2 (Hotfix 2). Siemens AG 2005 page 27 / 29 version 21.03.2005

4.3 Independent conversion of standard telegrams for the Sinamics update During the update of the Sinamics device version, sometimes the standard telegrams selected for the drive (e.g. 105 or 106) are changed to "Free telegram configuring with BICO". Work-around: Perform the drive configuration once again and reselect the original telegram. 4.4 Placement of the telegrams in the control unit In Sinamics_Integrated Configuration, the objects (Dos) without PZDs must be placed at the end of the list. No objects (Dos) with PZDs may be placed behind empty modules. After this placement, the comparison with the hardware configuration can be performed. 4.5 Updating the Sinamics firmware in the offline project causes error messages. Various warnings are issued after performing Sinamics_Integrated "Experts" context menu Device version: The "Change device version" function supports only the update of an older drive device version to a newer one. Siemens AG 2005 page 28 / 29 version 21.03.2005

During the update from SINAMICS V2.1 to SINAMICS V2.2, warnings will be displayed, which, however, can be ignored. Siemens AG 2005 page 29 / 29 version 21.03.2005