CDD4 Series Room CO2 Transmitter Installation Instructions

Similar documents
CDD Carbon Dioxide Transmitter

CDD4 Duct Carbon Dioxide Transmitter

Installation Guide. Carbon Dioxide (CO 2. ) Detectors. General Information. Mounting WARNING CAUTION. SAE-1011/1012 Space Mount SAE-1011/1012/1062

CDD ModBus Carbon Dioxide Detector

Installation Guide. Section 1 - Room... pg 03. Section 2 - Duct... pg 23. I-CDD3_Modbus Installation. Modbus Gas Transmitters I-CDD3 Series

Carbon Monoxide Sensor - ModBus

AIR41 Series IAQ Transmitter Installation Instructions

TPE 1464 Series Pressure Transducer

CDD3 Space Carbon Dioxide Detector with BACnet

TOXALERT MODEL AIR 2000

Carbon Monoxide Transmitter

Please Read Instruction Carefully Before Installation! Figure 1: A/CO2-DUCT

Differential Liquid/Gas Pressure Transmitter

Precision humidity/temperature control/sensing

PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION!

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION

HT Series Wall Mount with Analog Setpoints, LCD, and Humidistat and Thermostat Control

CDD3 Duct Carbon Dioxide Detector with BACnet

HT Series Wall Mount with Relay Setpoints, LCD, and Humidistat and Thermostat Control

C7110C1001A / C7110D1009A WALL MODULES

HWS Series Wall Mount with Relay Setpoints, LCD, and Humidistat Control

Carbon Monoxide (CO) Gas Detection and Control System

asense m III in industrial wall mounted housing / CO sensor with built-in general purpose controller

BA/BS4S Temperature Sensor Installation & Operating Instructions

Schneider Electric s SCD series of duct mount sensors measure the levels of CO 2. , RH (if equipped) and temperature of air inside a duct.

CDR-RH Room CO 2, Temperature and Humidity Sensors (Controllers)

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

Autoranging True RMS Multimeter User Manual

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

S-14 S-14. Compact Digital Multimeter. Compact Digital Multimeter

Installation manual CF8-W-Disp-AL

Model HU-224/225. Technical Information TI.224/ Humidity Transduce r FOR ADDITIONAL INFORMATION SEE HU-224/225 DATA SHEET

Product Manual SZ2144

Signet Pressure Transmitter

Model CD-AW. Infrared Environmental CO2 Sensor. Operator's manual

+GF+ SIGNET ph/orp Transmitter Instructions

User Manual. PolyGard AT Infrared Carbon Dioxide transmitter Serial No. AT December, PolyGard is a registered trademark of MSR

OPERATING INSTRUCTION

VAT series controller and transmitter. Manual

NSGV Series "90DM3" Carbon Dioxide Detector

H7625A, H7635A Humidity/Temperature Sensors

Your Global Flow Control Partner. Series 50 Valve Status Monitor Operation and Maintenance Manual

Multi-Point Gas Detection and Control System

Precision humidity/temperature sensing/control

Model 305e OEM CO 2 concentration sensor

Installation and Operation Instructions I/CO 2, I/CO 2 -VDC, I/CO 2 -T

H7625B; H7635B,C; H7655B Duct-Mount and Outdoor-Mount Humidity/Temperature Sensors

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

T7560A1036 Digital Wall Module

SERIES CMT CARBON MONOXIDE GAS TRANSMITTER

Zone Pressure Touch (ZPT) Sensor - Standard Range

User's Guide. MiniTec TM Series Model MN25 MultiMeter

Zone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions

Multi-Point Gas Detection and Control System

EPWR Series. RoHS. Product Description. Available Products. Installation Instructions 01

Model R5010. TRMS Digital Multimeter. Instruction Manual

Networkable Dual Duct VAV Controller Specification and Installation Instructions

Zone Pressure Touch Sensor - Standard Range

SmartX Living Space Sensors

+GF+ SIGNET Conductivity/Resistivity Transmitter Instructions

Product Manual SZ2141

AQS51/61-KAM COMBINED CO 2 -/TEMPERATURE DUCT SENSOR/CONTROLLER

PS-AULDP Series. Overview. Applications. Features & Benefits. Datasheet. Ultra Low Air Differential Pressure Transmitters

Multi-Point Gas Detection and Control System

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

AutoRanging Digital MultiMeter

Wireless Remote Controller Kit

Rotork Fairchild PAX1 Linear Actuator User s Manual

CM-220 True RMS AC CLAMP METER INSTRUCTION MANUAL

User's Guide. Digital Multimeter. Model MN42

CONTENTS. Chapter 1...Description. Chapter 2...Installation. Chapter 3...Operation. Chapter 4...Calibration. Chapter 5...

Carbon Dioxide Monitor/Controller With The USB Data Logger

ASI Systems ML5740A Series

ASI Systems ML5720A Series

SEZ7656R1045B / SEZ7656H1045B

MOD-RI Room Interface Modules with Modbus

Analyzer/Controller. ph/orp HART. Model 54e ph/orp ESSENTIAL INSTRUCTIONS WARNINGS RISK OF ELECTRICAL SHOCK

MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions

Model R5010. Instruction Manual. TRMS Digital Multimeter. reedinstruments www.

Hardware Installation. Tracer MP581 Programmable Controller CNT-SVN01C-EN

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

V E1B Snap-in I/O Module

Gas and Air Sensors. Product Specification. CO 2 Engine K30. Sensor Module and OEM Platform. Document PSP 110. Rev 4. Page 1 (11)

V E2B Snap-in I/O Module

DM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER

Instruction Manual CTC-1

SEZ7656E1045B. Installation Guide for BACnet MS/TP RTU Terminal with IAQ Control CONTENTS

Operation and Maintenance Manual

Level-Lance Model 5400A

Mini Digital Multimeter

Owner's Manual. True RMS Multimeter. Model No Safety Operation Maintenance Español

OPERATING INSTRUCTION. Pen-Type Digital Multimeter

Digital Clamp Meter User Manual

Mini Digital Multimeter

2 Table of Contents 1. TABLE OF CONTENTS. 1. Table of Contents Introduction Wiring Diagram Terminals Review...

User Guide True RMS Multimeter Extech EX205T

MicroTrans EQ Signal Processor. Operation & Maintenance Manual

QUICKSTART GUIDE. Infrared Gas Analyzer. Teledyne Analytical Instruments

Component identification

Installation, Start-up and Operating Instructions

Transcription:

CDD4 Series Room CO2 Transmitter Installation Instructions Introduction The CO2 transmitter uses Infrared Technology to monitor CO2 levels and outputs a linear 4-20 ma or 0-5/0-10 Vdc signal. Options include an LCD, control relay, override switch, slide pot setpoint control and resistive temperature sensor. Features include a back-lit LCD and user menu for easy installation Before Installation Read these instructions carefully before installing and commissioning the device. Failure to follow these instructions may result in product damage. Do not use in an explosive or hazardous environment, with combustible or flammable gases, as a safety or emergency stop device or in any other application where failure of the product could result in personal injury. Take electrostatic discharge precautions during installation and do not exceed the device ratings. Mounting The room CO2 transmitter installs directly on a standard electrical box and should be mounted five feet from the floor of the area to be controlled. Do not mount the sensor near doors, opening windows, supply air diffusers or other known air disturbances. Avoid areas where the detector is exposed to vibrations or rapid temperature changes. The cover is hooked to the base at the top edge and must be removed from the bottom edge first. Use a small Phillips screwdriver to loosen the security screw as shown in Figure 1. (Complete removal of this screw is not required). Use the screwdriver to carefully pry each bottom corner if necessary. Tip the cover away from the base and sit it aside as shown in Figure 2. The PCB must be removed from the base to access the mounting holes. Follow usual anti-static procedures when handling the PCB and be careful not to touch the sensors. The PCB is removed by pressing the enclosure base to unsnap the latch near the bottom edge, then the PCB can be lifted out of the base as shown in Figure 3. Sit the PCB aside until the base is mounted on the wall. For added protection, place the PCB in the supplied anti-static bag. Mount the base by screwing to an electrical box or directly to the wall as shown in Figure 4. The mounting hole locations are shown on page 3. After the base is screwed to an electrical box or the wall using the appropriate holes, remove the PCB from the anti-static bag, feed connection wires through center hole and place the top of PCB into the PCB holders on backplate and snap bottom of PCB into place as shown in Figure 4. Make wire connections as per the Wiring Illustrations on Page 2 and install decorative cover by placing the top of the cover into the cover holder on the top of the backplate and snapping the bottom into place as shown in Figure 4. Tighten security screw with a Phillips screwdriver. Figure 1 Figure 2 Figure 3 Figure 4 Cover PCB Backplate Page 1

Wiring Deactivate the 24 Vac/dc power supply until all connections are made to the device to prevent electrical shock or equipment damage. Follow proper electrostatic discharge (ESD) handling procedures when installing the device or equipment damage may occur. Use 22 AWG shielded wiring for all connections and do not locate the device wires in the same conduit with wiring used to supply inductive loads such as motors. Make all connections in accordance with national and local codes. This is a 3-wire sourcing device. Connect the plus dc or the ac voltage hot side to the PWR terminal. The supply common is connected to the COM terminal. The device is reverse voltage protected and will not operate if connected backwards. It has a half-wave power supply so the supply common is the same as the signal common. Several devices may be connected to one power supply and the output signals all share the same common. Use caution when grounding the secondary of a transformer or when wiring multiple devices to ensure the ground point is the same on all devices and the controller. The analog output is available on the CO2 terminal. This signal is switch selectable for either voltage or 4-20 ma active output as shown in Figure 7. In voltage mode the output is selectable for either 0-5 or 0-10 Vdc later during the menu setup (the factory default is 0-5 Vdc). The current output operates in the active mode and does not require a loop power supply (the signal current is generated by the transmitter and must not be connected to a powered input or device damage will result). Figure 5 OUTPUT ma ROLL VOLT TEMP CO2 COM PWR OVERRIDE SETPNT S COM SWITCH N.O. RELAY SAVE MENU CO2 SENSOR 0001248 Figure 6 Wiring for voltage output signal and 24 Vdc power from controller CO2 COM PWR Wiring for all output and external 24 Vac power transformer or external 24 Vac power supply CO2 COM PWR 24 Vac Transformer/ Powersupply Check the controller Analog Input to determine the proper connection before applying power. Both current and voltage signals are referenced to the COM terminal. The analog output signal is typically connected directly to the Building Automation System (B.A.S.) and used as a control parameter or for logging purposes. The optional relay output is on the N.O. RELAY terminals as shown in Figure 8. The relay output is completely isolated and has a Normally Open (NO) signal. This signal can be used to directly control an alarm or ventilation fan. See specifications for contact ratings. The optional override switch is a two-wire dry contact normally open switch contact as shown in Figure 9. The slide pot is a two-wire resistive signal that can vary from 0-10K ohms (for example) with left-to-right slide pot action. Other resistive values are available on request and the slide pot may be configured as normal or reverse acting as shown in Figure 10. The override switch and slide pot options share a single common labelled S. COM and this is not connected to the power supply COM. The two-wire temperature sensor output is available with various RTDs and thermistors to suit all control applications and is available on the TEMP terminals as shown in Figure 11. Figure 7 Figure 8 N.O. RELAY Power Supply Digital Input Alarm Start-up Verify the device is properly wired and connections are tight. Ensure the V/I switch is set for the correct signal type. Apply power and the LCD will indicate the software version number, the output signal type, the relay setpoint (if installed), the CO2 measurement range and then the sensor will begin reading the CO2 level, output the correct analog signal and display the value on the LCD. Figure 9 S COM SWITCH SWITCH Digital Input Page 2

Output Signal The CO2 output is scaled such that 4-20 ma (or 0-5/0-10 Vdc) equals 0 to Out_High. Depending on the model, the factory default is either 0-2000 ppm (CDD4A) or 0-20,000 ppm (CDD4B). Out_High can be changed in the Setup Menu and the output is scaled accordingly. If using voltage output type, the default is 0-5 Vdc (0-10 can be selected in the menu). Figure 10 SETPNT S COM SETPNT Analog Input Operation The output signal is available on the CO2 terminal and is connected to the BAS analog input which reads the signal and calculates the CO2 ppm value using correct scaling for the range and signal type. The CO2 value is used to control output ventilation devices or initiate alarms. The CO2 value is also displayed locally on the optional LCD. If a relay is installed it can control a small fan or alarm by setting the trip value and hysteresis to appropriate values. If a temperature sensor is installed it will be wired to an analog input of the BAS that is set for the specific resistance type. This could be a 10 KΩ thermistor, a 1000 ohm RTD or other sensor values. The BAS reads the resistance signal and converts it to a temperature value. The override switch provides a dry contact closure to a digital input of the BAS. The slide pot can be connected to another analog input and will provide a linear signal such as 0-10 KΩ to be used as a setpoint control. Figure 11 TEMP Analog Input Setup Menu The menu has several items shown below. Some items change depending on the hardware configuration and the CO2 sensor. To enter the menu, press and release the key while in normal operation. This will enter SETUP menu step 1, pressing the key again advances to step 2. Each press of advances the menu item. No values are saved or changed by using. The <ROLL> key is used to make changes to program variables by scrolling through the available options. When a value is changed, use the <SAVE> key to save it to memory and advance to the next menu item as shown is Figure 12. Press and release the key to enter the SETUP menu. If the 2000 ppm CO2 sensor is installed (CDD4A model) Figure 12 ROLL SAVE MENU 1. The default CO2 range is 0-2000 ppm. The span can be changed from 1000 to 7500 ppm in increments of 500. Use the <ROLL> key to change the value and <SAVE> to save. The factory default is 2000 ppm. Out High 2000 ppm If the 20,000 ppm CO2 sensor is installed (CDD4B model) 1. The default CO2 range is 0-20,000 ppm. The span can be changed from 2000 to 20,000 ppm in increments of 500. Use the <ROLL> key to change the value and <SAVE> to save. The factory default is 20,000 ppm. Out High 20000 ppm 2. The default is 0 feet. Change by using the <ROLL> key from 0 to 5000 feet in 500 ft increments. Change for CO2 local altitude correction and press <SAVE> to save a change. Altitude 0 Ft This item is omitted if the 20,000 ppm (CDD4B) dual-channel sensor is installed 3. Automatic Cal Mode default is ON to correct CO2 sensor drift to better than ± 10 ppm per year. Auto Cal Change with the <ROLL> key and save using <SAVE>. ON is recommended for applications ON where the CO2 level will be close to normal (400 ppm) at least once per day. If a building is occupied 24 hours and the CO2 level is fairly constant then this should be set to OFF. Page 3

Items 4, 5 and 6 are only available if the Relay Option is installed, otherwise the menu skips directly to step 7. 4. The relay trip setpoint default is 1000 ppm. It can be changed from 500 to 5000 in 100 ppm increments for the 2000 ppm CO2 sensor or 500 to 15,000 for the 20,000 ppm sensor. Save changes by using the <SAVE> key. Relay SP 1000 ppm 5. The relay hysteresis default is 50 ppm. This can be changed from 25 to 200 in 25 ppm increments for the 2000 ppm sensor or 25 to 500 ppm for the 20,000 ppm sensor. Use <SAVE> to save any change. Relay Hy 50 ppm 6. Use the <ROLL> key to toggle the relay ON or OFF for testing purposes. Press either <SAVE> or to turn the relay off and advance to the next item. Relay Test OFF 7. For voltage, the factory default output type is 0-5 Vdc. Use the <ROLL> key to change the value to 0-10 Vdc if necessary. Press the <SAVE> key to save. If the switch is set to ma, then 4-20 ma is displayed. Out Type 0-5 Vdc 8. Use the <ROLL> key to toggle the output OFF (normal operation), MIN (minimum output) or MAX (maximum output) for testing purposes. Press either <SAVE> or to set it back to OFF and advance to the next item. Output Test OFF This item is omitted if the 2000 ppm (CDD4A) single channel sensor is installed 9. This item is used for 0 ppm gas calibration and is explained in the Calibration section. Calibrat 0 PPM 10. This item is used for 1000 ppm gas calibration and is explained in the Calibration section. Calibrat 1000 PPM This item is omitted if the 2000 ppm CO2 sensor is installed 11. This item is used for 20,000 ppm gas calibration and is explained in the Calibration section. Calibrat 20000PPM Item 12 is only available if the cover is equipped with a viewable LCD, otherwise the menu skips directly to step 13. 12. Use the <ROLL> key to enable or disable the LCD backlight. When enabled the backlight is always on, when disabled it never lights. Press the <SAVE> key to save the setting. The factory default is Enable. BackLite Enable Page 4

13. Press the <SAVE> key to restore calibration to original factory settings. Restore Defaults 14. Press <SAVE> to exit the menu and return to normal operation or to repeat the menu. Menu Exit Calibration Calibration with gas requires a field calibration kit with pressure regulator, necessary tubing and appropriate bottles of CO2 gas. Note that the procedure depends on the device model. The CDD4A requires only a single point. CDD4A Model 1000 ppm calibration to meet specified accuracy due to the Automatic Calibration mode and other technology incorporated into the device. 1000 PPM Calibration Connect the 1000 ppm CO2 gas bottle and apply the gas as before. The CO2 reading on the LCD will begin to approach 1000 ppm. Wait 1 to 2 minutes until the CO2 reading stabilizes. Enter the Setup menu and use the key to advance to Calibrat 1000 PPM. Press and hold the <SAVE> key for 2 seconds and the display will change to Waiting Calibrat then to Waiting 5 minute to indicate that the device is calibrating. Again, this process takes about 5 minutes. When calibration is complete the unit will display the ppm and Cal Done. Press the <SAVE> key to return to normal operation and shut the gas off. CDD4B Model The CDD4B dual-channel sensor with extended range requires a 3-point calibration with 0, 1000 and 20,000 ppm gas (in order). 0 PPM Calibration Turn the regulator knob off and attach it to the Nitrogen gas bottle and hand tighten. Remove the cover of the unit to be calibrated to expose the gas sensor chamber. The tubing from the gas bottle can be connected to either port on the chamber after the plastic cap is removed. Gently remove one cap and connect the tubing, note that strong shock or vibration can affect calibration. Ensure the device has been operating normally for at least five minutes before applying gas. Turn the valve knob on the regulator to start the gas flow. The regulator will restrict the flow rate to the specified 100 ml/min. After a brief period the gas will flow into the chamber. Wait 1 to 2 minutes until the CO2 stabilizes. Enter the Setup menu and use the key to advance to Calibrat 0 PPM. Press and hold the <SAVE> key for 2 seconds and the display will change to Waiting Calibrat then to Waiting 5 minute to indicate that the process of setting the internal calibration is taking place. This takes about 5 minutes while the LCD counts down. Do not disturb the unit or the gas flow. When complete the unit will display the ppm value and Cal Done. Press the <SAVE> key to return to normal operation and shut the gas off. 1000 PPM Calibration Connect the 1000 ppm CO2 gas bottle and apply the gas as before. The CO2 reading on the LCD will begin to approach 1000 ppm. Wait 1 to 2 minutes until the CO2 reading stabilizes. Enter the Setup menu and use the key to advance to Calibrat 1000 PPM. Press and hold the <SAVE> key for 2 seconds and the display will change to Waiting Calibrat then to Waiting 5 minute to indicate that the device is calibrating. Again, this process takes about 5 minutes. When calibration is complete the unit will display the ppm and Cal Done. Press the <SAVE> key to return to normal operation and shut the gas off. 20,000 PPM Calibration Connect the 20,000 ppm CO2 and apply the gas as before. The LCD will begin to approach 20,000 ppm. Wait 1 to 2 minutes until the CO2 reading stabilizes. Enter the Setup menu and use the key to advance to Calibrat 20,000 PPM. Press and hold the <SAVE> key for 2 seconds and the display will change to Waiting Calibrat then to Waiting 5 minute. Again, wait 5 minutes and when calibration is complete the unit will display the ppm and Cal Done. Press the <SAVE> key to return to normal operation and shut the gas off. Disconnect the tubing and replace the cap on the sensor chamber as calibration is complete. Page 5

General Specifications Power Supply...20 28 Vac/dc (non-isolated half-wave rectified) Consumption...100 ma max @ 24 Vdc, 185 ma max @ 24 Vac (with all options) Output Signals...4-20 ma active (sourcing), 0-5 Vdc or 0-10 Vdc (field selectable) Output Drive Capability...550 ohms maximum for current output, 10 Kohm min for voltage output Protection Circuitry...Reverse voltage protected, overvoltage protected Operating Conditions...0-50 C (32-122 F), 0-95 %RH non-condensing Wiring Connections...Screw terminal block (14 to 22 AWG) Sensor Coverage Area...100 m2 (1000 ft2) typical Enclosure...Wall mount enclosure, 3.3 w x 4.7 h x 1.15 d (84 x 119 x 29 mm) CO2 Signal Measurement Type...Non-Dispersive Infrared (NDIR), diffusion sampling Measurement Range...0-2000 ppm (CDD4A) or 0-20,000 ppm (CDD4B), programmable span Standard Accuracy...± 30 ppm + 3% of reading (CDD4A with Auto Cal) ± 75 ppm or 10% of reading (whichever is greater) (CDD4B with dual channel sensor) Temperature Dependence...0.2 %FS per C Stability...< 2 %FS over life of sensor (15 years typical) (CDD4A) < 5 %FS or <10% reading annual (CDD4B) Pressure Dependence...0.135 % of reading per mm Hg Altitude Correction...Programmable from 0-5000 ft via keypad Response Time...< 2 minutes for 90 % step change typical Warm-up Time...< 2 minutes LCD Display Resolution...1 ppm CO2 Size...1.4 w x 0.6 h (35 x 15 mm) alpha-numeric 2 line x 8 characters Optional Temperature Signal Sensing Element...Various RTDs and thermistors available as 2-wire resistance output Optional Relay Output Contact Ratings...Form A contact (N.O.), 2 Amps @ 140 Vac, 2 Amps @ 30 Vdc Relay Trip Point...Programmable via keypad Relay Hysteresis...Programmable via keypad Optional Manual Switch Type...Front panel, momentary pushbutton Ratings...50 ma @12 Vdc, N.O., SPST Optional Setpoint Adjustment Type...Front panel slidepot, 2 wire resistance output Range...0K to 10K Ω standard Custom spans available...1k, 2K, 5K, 10K or 20K Ω Dimensions 84 mm 3.3 29 mm 1.15 119 mm 4.7 58 mm 2.3 82.6 mm 3.25 Page 6 PRINTED IN CANADA Copyright Greystone Energy Systems Inc. All Rights Reserved CDD4-INS-R-001 12/15