Each VariSTAR Type AZU arrester must pass the following production tests: 100% Physical Inspection 100% Leakage Current Test 100% RIV Test

Similar documents
Figure 1. Storm Trapper H. E. arrester, external mount. Figure 2. Storm Trapper H.E. arrester, metal enclosed. use in Storm Trapper H.E. arresters.

COOPER POWER. UltraSIL polymer-housed VariSTAR IEEE surge arresters; normal-duty (5 ka), heavyduty, and riser pole (10 ka) for MV systems to 36 kv

35 kv Class M.O.V.E. DirectConnect elbow arrester

Technical specifications for 5 ka, normal-duty distribution 4.5 kv and 5

UltraSIL polymer-housed VariSTAR surge arresters 5 ka and 10 ka Class 1 IEC for MV systems to 36 kv

METAL-OXIDE SURGE ARRESTER PROTECTION OF DISTRIBUTION SYSTEMS

DynaVar SURGE ARRESTERS

Annexure-1 (CC no )

Surge Protection for Low Voltage Power Systems

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

VariSTAR AZE Station Surge Arresters

TDX Series. Transient Discriminating TM TVSS

MSP Reliability White Paper Bourns, Inc. Hans-Wolfgang Oertel Vice President of Technology

Application Considerations for Gapped Silicon-Carbide Arresters Currently Installed on Utility High Voltage Installations

TVZ: THERMO-FUSE VARISTORS

COOPER POWER. Types GN3E and GN3VE electronically controlled, manually closed sectionalizers SERIES. Sectionalizers Catalog Data CA270001EN

Secondary Surge Arrester Instruction Manual Page 1 of 5

COOPER POWER SERIES. Fusing Equipment Catalog Data CA132064EN. Effective February 2018 Supersedes January 2014 (240-50)

ENGR. MARITES R. PANGILINAN, P.E.E.

Application Techniques CENTERLINE 2100 Motor Control Centers

Figure 1. ELSP Current-Limiting Backup Fuse. INSTALLATION

glossary GE Digital Energy Power Quality Surge Protective Devices (SPDs)

ELSP current-limiting backup fuse

GLOSSARY OF TERMS. Surge and Lightning Protection ERICO Inc.

GE Digital Energy. Power Quality

File Ref: CP No.: CP1205 Rev. 0 Page: 1 of 25 CERTIFIED TEST REPORT. Cooper Power Systems. 28 kv Class 600 Amp 16.2 / 28.

Central Power Research Institute, Medipally PO, Uppal, Hyderabad, Telangana. Discipline Electrical Testing Issue Date

US Catalog March Surge protective devices (SPDs) UL range

Varistor Products Radial Lead Varistors > TMOV and itmov Series

Low Voltage and Medium Voltage Surge Protection

BSPD Surge Protective Devices

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

SOUTH CAROLINA ELECTRIC COOPERATIVES SECONDARY TYPE 1 SURGE PROTECTIVE DEVICE SPECIFICATIONS Updated/Revised: October 6, 2014

The following standards are the basis of design, manufacture, and test of SPD equipment: Guide for Surge Voltages in Low-Voltage AC Power Circuits

for the protection of gas-insulated metal-enclosed switchgear against lightning and switching overvoltages

CERTIFIED TEST REPORT

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Series Wall Mounted Low and Medium Exposure Surge Protective Devices (SPDs)

Externally Gapped Line Arresters Smart Solution for Stable Power Supply

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Externally Gapped Line Arresters Smart Solution for Stable Power Supply

ELSP current-limiting backup fuse

NEW surge protective devices

OVRH catalog Surge protective devices

Surge & Filter Protection Addressing your industrial power quality needs.

Datasheet Stock No: RS Pro

Overvoltage Protection Devices

Quality assurance Test Facilities for Gapless ZnO Surge Arresters in High Voltage Division of CPRI, Bengaluru

Description. Features

Overvoltage Protection Devices

Designing with Thermally Protected TCMOV Varistors for Type 1 and Type 2 UL1449 3rd Edition Applications

SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet

AC Line Voltage Transients and Their Suppression

MONITORING ABSTRACT KEYWORDS. TRANSFORMERS MAGAZINE Special Edition: Bushings, 2017

Mitigation of Voltage Swells I

ETITEC - Lightning and Surge Arresters

MULTI-POLE PHOTOVOLTAIC SYSTEMS. COMPACT and MODULAR Housing

2U Congestion Alert Rack Insert for UK

File E Project 08NK October 2, 2009 REPORT SURGE PROTECTIVE DEVICES (VZCA) GE Zenith Controls Bonham, TX

BA/BB Varistor Series

Ferraz Shawmut TPMOV Principles and Operation

Revised Standards Provide Design Options for Primary and Secondary Protection TELECOM PROTECTION WHITE PAPER

Surge Protection Devices Ex9UE2

Surge Protection Devices Type 1+2

Surge Protective Devices. STV100K Series. Instruction Manual

CONTA-ELECTRONICS. CONTA-PROTECT overvoltage protection

Surge Protective Devices. STV100K Series. Instruction Manual

Remote contact signaling available. visual status indication

Lightning and Surge Arresters

Micro Contactor MA Series

R-LB R-LX Series Installation, Operation & Maintenance Manual

CPS block & CPS nano UL rd Ed. Surge protective devices (SPD)

Lightning and Surge Protection of Photovoltaic Installations. Leutron GmbH 2013 Leinfelden-Echterdingen, Germany

Power supply CP-C 24/5.0

PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment

Buffer module CP-B 24/20.0, ultra-capacitor based Accessory for power supplies (e.g. switch mode power supplies CP range)

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.

8 PHOENIX CONTACT Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA

ZoneMaster Series Surge Protection Devices

T107 - Installation Considerations for AC drives

Integrating Monitoring and Diagnostic Equipment on Aging Transformers

Overvoltage Protective Devices

Data Sheet. Surge protection devices - A technical overview

File E Project 05NK Issued: Revised: REPORT CLASSIFIED FOR USE WITH SPECIFIED EQUIPMENT (XUPD)

Surgelogic Surge Protective Device I-Line Plug-On Unit Series

AN579 Application note

GENERAL UL th EDITION DESIGN-BUILD SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

wietap wietap Overvoltage Protection Tensions running high

GUIDE TO VERIFYING SURGE PROTECTIVE DEVICES INSTALLED IN LIGHTNING PROTECTION SYSTEM INSTALLATIONS ARE COMPLIANT WITH UL 96A.

S Reclosers Form 4C Microprocessor-Based Recloser Control KME (120V) and KME (240V) Analog Current Metering Accessory Design II

Installation Manual. APEX Series. Silicon and MOV Panel Protection. APEX Series

Collector System Design Considerations for Wind Farms. Sean Carr Ernst Camm S&C Electric Co.

Varistor Products Radial Lead Varistors > TMOV and itmov Series

Chapter J. Protection against voltage surges in LV. Contents. General. Overvoltage protection devices. Choosing a protection device

INTRODUCTION TO SPECIFYING SURGE PROTECTION SURGE PROTECTION NOTE 1 INTRODUCTION TERMS PROBABILITY OF SURGES APPEARING:

Technical Requirements for High-voltage DC Power Feeding Interfaces of ICT equipment

File E Project 08NK November 24,2009 REPORT TRANSIENT VOLTAGE SURGE SUPPRESSORS (VZCA/VZCA7)

GENERAL UL th EDITION BID SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

CONNECT AND PROTECT. nvent ERICO Critec SRF N-Series. Surge Reduction Filters

Single-Core PVC 6491X

NEMA 1 / IP40 metal housing. Compact design

Transcription:

Surge Arresters VariSTAR Type AZU Heavy-duty Distribution Class Under-oil MOV Arrester Electrical Apparatus 235-64 GENERAL The Cooper Power Systems VariSTAR Type AZU under-oil MOV arrester is designed in accordance with ANSI/IEEE C62.11 heavy-duty distribution class requirements. It is designed for either horizontal or vertical mounting inside the distribution transformer tank to eliminate the difficulties associated with externally mounted arresters. In recent years, under-oil arresters have gained increased acceptance due to the distinct advantage the under oil environment offers. When placed under oil the MOV arrester benefits from the cooling effect of the circulating oil. In addition, underoil mounting of the arrester eliminates the possibility of shortened arrester life due to high surface contamination, wildlife, vandalism or moisture ingress. The under-oil arrester also offers improved transformer protection since internal mounting eliminates the need for long lead lengths to the arrester. When properly coordinated with a current-limiting fuse, cover retention can be maintained through 50,000 A of available fault current. The VariSTAR Type AZU under-oil MOV arrester is available in ratings of 3 through 27 kv. PRODUCTION TESTS A complete production test program ensures a quality product. Each VariSTAR metal oxide varistor receives a series of 100% electrical tests. Quality is further ensured by a series of destructive tests performed on every batch of varistors. Listed are the tests that are performed on the varistors: 100% Physical Inspection 100% Discharge Voltage Test 100% V1mA/cm 2 100% Leakage Current at 80% of V1mA/cm 2 Voltage Batch High-current Short-duration Test Batch Thermal Stability Test Figure 1. VariSTAR Type AZU100L Heavy-duty Distribution Class Under-oil MOV Arrester. Each VariSTAR Type AZU arrester must pass the following production tests: 100% Physical Inspection 100% Leakage Current Test 100% RIV Test STANDARDS The VariSTAR Type AZU arrester complies with the latest revision of ANSI/IEEE C62.11 IEEE Standard for Metal Oxide Surge Arresters for AC Power Circuits. July 1995 Supersedes 07/92 1995 Cooper Power Systems, Inc. Printed in U.S.A. 1

Features and Detailed Description COOPER POWER SYSTEMS AZU 10 ka VariSTAR 10kV 8.4 MCOV LINE END R HIGH VOLTAGE LINE LEAD #10 (19 strand) copper wire with PVC insulation, 20 inch length. NON-HYGROSCOPIC HANGER High strength, track resistant hanger brackets. (Brackets may be separated for horizontal mounting applications.) INSULATIVE TUBE RADIAL VENTS Unique radial venting design reduces arc energy should an arrester failure occur. MOV DISKS Highly non-linear metal oxide varistors provide exceptional surge protection. IDENTIFICATION INFORMATION Convenient reference for arrester type, MCOV, voltage rating and year and quarter of manufacture. GROUND LEAD #10 (19 strand) copper wire with PVC insulation, 20 inch length. INSULATING WASHER Figure 2. Cutaway illustration of VariSTAR Type AZU100L Arrester. NOTE: Optional design available with adaptor terminals (see Figure 5). TABLE 1 Protective Characteristics Maximum Discharge Voltage Front-of-Wave 8/20 µs Current Wave Arrester Protective (kv crest) Switching Rating MCOV Level* Surge** (kv rms) (kv rms) (kv crest) 1.5 ka 3 ka 5 ka 10 ka 20 ka 40 ka (kv crest) 3 2.55 10.7 8.2 8.7 9.2 10.0 11.3 13.6 7.4 6 5.10 21.4 16.4 17.4 18.4 20.0 22.5 27.1 14.7 9 7.65 32.1 24.5 26.1 27.5 30.0 33.8 40.7 22.1 10 8.40 35.3 27.0 28.7 30.3 33.0 37.2 44.7 24.3 12 10.2 42.8 32.7 34.7 36.7 40.0 45.0 54.2 29.4 15 12.7 53.5 40.9 43.4 45.9 50.0 56.3 67.8 36.8 18 15.3 64.2 49.1 52.1 55.1 60.0 67.6 81.4 44.1 21 17.0 74.9 57.3 60.8 64.3 70.0 78.8 94.9 51.5 24 19.5 84.3 64.4 68.4 72.3 78.8 88.7 106.8 57.9 27 22.0 95.2 72.8 77.3 81.7 89.0 100.2 120.7 65.5 *Based on 10 ka current impulse that results in a discharge voltage cresting in 0.5 µs. **45-60 µs rise time 500 A current surge. TABLE 2 Performance Test Characteristics* Description Duty Cycle High-current, Short-duration Discharge Low-current, Long-duration Discharge *Per latest revision of ANSI/IEEE C62.11. Characteristics 20 current surges of 10 ka crest 8/20 µs waveshape followed by 2 current surges of 40 ka crest 8/20 µs waveshape 2 current surges of 100 ka crest 4/10 µs waveshape 20 current surges of 250 A crest 2000 µs rectangular wave duration 2

TABLE 3 Commonly Applied Voltage Ratings of the Type AZU Arrester System Voltage Recommended Arrester Rating (kv rms) (kv rms) Four-Wire Three-Wire Delta and Wye; Multi- Wye; Solidly Ungrounded Grounded Grounded Wye Nominal Maximum Neutral Neutral 2.4 2.54 3 4.16Y/2.4 4.4Y/2.54 3 6 6 4.16 4.4 6 4.8 5.08 6 6.9 7.26 9 8.32Y/4.8 8.8Y/5.08 6 9 12.0Y/6.93 12.7Y/7.33 9 12 12.47Y/7.2 13.2Y/7.62 9 15 13.2Y/7.62 13.97Y/8.07 10 15 13.8Y/7.97 14.52Y/8.38 10 15 13.8 14.52 18 20.78Y/12.0 22Y/12.7 15 21 22.86Y/13.2 24.2Y/13.87 18 24 23 24.34 27 24.94Y/14.4 26.4Y/15.24 18 27 27.6Y/15.93 29.3Y/16.89 21 34.5Y/19.92 36.5Y/21.08 27 1.7 1.6 1.5 1.4 1.3 1.2 1.1 1 0.9 0.1 1 10 100 1000 10000 TIME (Seconds) Per Unit MCOV Per Unit Voltage Rating Figure 3. Temporary overvoltage curve. No prior duty 100 C ambient. GENERAL APPLICATION RECOMMENDATIONS The rating of an arrester is the power frequency line-to-ground voltage at which the arrester is designed to pass an operating duty-cycle test. Table 3 provides a general application guide for the selection of the proper arrester rating for a given system voltage and system grounding configuration. Cooper Power Systems application engineers are available to make application recommendations. The following information is normally required: 1. System maximum operating voltage. 2. System grounding conditions. A. For four-wire circuits, grounding conditions depend upon whether the system is multi-grounded, has a neutral impedance and whether common primary and secondary neutrals are used. B. For three-wire circuits, grounding conditions depend upon whether the system is solidly grounded at the source, grounded through neutral impedance at the source transformers, or ungrounded. Where unusual conditions exist (high ground resistance, high capacitive load, arc-welding equipment, etc.) the following supplementary information is necessary: 1. The unusual condition. 2. Type of construction, phase spacing, length of line, conductor size. 3. BIL of equipment and line insulation. 4. Phase-sequence components of impedances on the load side of the distribution substation. The impedance of the transformer and the impedance and grounding of supply to the substation all affect the voltage during faults. TEMPORARY OVERVOLTAGE (TOV) CAPABILITY The Temporary Overvoltage (TOV) capability of the VariSTAR Type AZU arrester is shown in Figure 3. 3

235-64 A 1.87 (47 mm) 3.0 (76 mm) TABLE 4 VariSTAR Type AZU Dimensional Information Arrester Dimensions Rating A* B** (kv rms) in. (mm) in. (mm) 3 4.8 (121) 5.0 (126) 6 5.9 (150) 6.1 (155) 9 7.0 (178) 7.2 (184) 10 7.0 (178) 7.2 (184) 12 8.2 (207) 8.4 (212) 15 9.3 (236) 9.5 (241) 18 10.3 (262) 10.5 (266) 21 11.5 (293) 11.7 (298) 24 11.5 (293) 11.7 (298) 27 12.7 (322) 12.9 (327) *Dimension A from Figure 4. **Dimension B from Figure 5. TABLE 5 Catalog Numbers for AZU Arrester With 20 Line/Ground Leads* Arrester Rating Catalog Number Figure 4. Dimensional information of VariSTAR Type AZU100L arresters. 1/4-20 TERMINAL STUDS (BOTH ENDS) 1.87 (47 mm) *See Figure 4. 3 AZU100L003 6 AZU100L006 9 AZU100L009 10 AZU100L010 12 AZU100L012 15 AZU100L015 18 AZU100L018 21 AZU100L021 24 AZU100L024 27 AZU100L027 TABLE 6 Catalog Numbers for AZU Arrester Without Line/Ground Leads* Arrester Rating Catalog Number B 3 AZU101L003 6 AZU101L006 9 AZU101L009 10 AZU101L010 12 AZU101L012 15 AZU101L015 18 AZU101L018 21 AZU101L021 24 AZU101L024 27 AZU101L027 3.0 (76 mm) *With adapter terminals (See Figure 5)..56 (14 mm) Figure 5. Dimensional information of VariSTAR Type AZU101L arresters. 4

235-64 SYMM. ABOUT CL.75 (19 mm) 1.50 (38 mm) 1.895 DIA. (48 mm) 5.0 (127 mm) 3.56 (90 mm) 4.19 (106 mm).375 DIA. (10 mm) 6 PLACES.375 X.562 (10 X 14 mm) SLOT 2 PLACES 2.0 (51 mm).69 (18 mm).50 (13 mm) 1.34 (34 mm) 3.75 (95 mm).75 (19 mm) Figure 6. Dimensional information of mounting bracket..38 (10 mm).20 DIA. (5 mm) 2 PLACES NOTE: Hanger material thickness is 0.125 inches (3 mm). Dimensions given are for reference only. ORDERING INFORMATION To order a Cooper Power Systems VariSTAR Type AZU arrester, determine the arrester rating for the intended application using Table 3 and specify the appropriate catalog number from Table 5. Contact your Cooper Power Systems sales engineer in your location for applications not listed. VariSTAR is a registered trademark of Cooper Power Systems, Inc. 5

Quality from Cooper Industries P.O. Box 1640, Waukesha, WI 53187