for the protection of gas-insulated metal-enclosed switchgear against lightning and switching overvoltages
|
|
- Gertrude Chase
- 6 years ago
- Views:
Transcription
1 GAS-INSULATED METAL-ENCLOSED SURGE ARRESTERS (GIS-ARRESTERS) for the protection of gas-insulated metal-enclosed switchgear against lightning and switching overvoltages
2 GIS-Arresters from Siemens GIS arresters Type 3EP2 1-3PKZ for the protection of a gas insulated 123--switch-gear Type 8DN9 (Resonant earthed system, TEAG Jena, Germany) Siemens gas-insulated, metal-enclosed arresters (GIS arresters) provide optimum protection for gas-insulated switchgear (GIS). Two reasons are decisive here. On the one hand, GIS arresters can be installed very close to the object to be protected. This is important for instance when GIS are fed by long cables. Overvoltages, which can be caused by travelling wave occurrences, are limited very effectively in this way. On the other hand, the low self-inductance of GIS arresters provides the best conceivable protection against high rate-of-rise voltages, which are particularly critical for gas-insulated equipment. The first Siemens GIS arresters have been supplied in 197. Since then, they have been designed for an extremely wide range of applications and have been installed worldwide. Today, Siemens possesses extensive know-how concerning GIS arresters, assuring optimum operating properties and the highest possible reliability. Siemens supplies two different series of GIS arresters. In the case of the 3EP2-K type range, the resistors are electrically and mechanically of single-column construction. These arresters are available as single (i.e. one phase per vessel) or three-phase (i.e. three phases per vessel) types. In contrast, the 3EP3-K type range incorporates resistors which are mechanically of three-column while electrically of one-column design. This results in a meandering low-inductance current path and reduces the overall length of the arresters. Common to both type ranges is the fact that they are fitted with safety rupture diaphragms and of course comply with international regulations (e.g. IEC 17). By virtue of suitable choice of material and corresponding paint structure, the Siemens GIS arresters are generally suitable for outdoor installation. Every GIS arrester is fitted with a gas connection. This allows the arrester to be incorporated in an existing gas monitoring system; it is also possible, however, to provide a separate arrester gas monitor. The earth-side end of each individual arrester phase is led out of its tank through an insulated bushing, to which monitoring devices, such as surge counters, spark gaps or leakage current meters can be connected. GIS arresters Type 3EP3 378-PKZ at the transformers in a gas insulated --switch-gear Type 8DQ1 (BEWAG Berlin, Germany)
3 >10 i peak ma Type 3EP2...-3PK (Diameter 392 mm) Nominal system voltage Highest voltage for equipment U m up to 10 up to 170 SF -SF -bushing (SF -Oil-bushing on request) Spring contact Access cover with pressure relief device and filter Enclosure Grading hood Metal-oxide resistors Supporting rods Electrical monitoring devices Gas pressure/density monitoring Arrester Data Height Total weight (max.) Maximum rated voltage U r Maximum nominal discharge current acc. to IEC 99- Maximum classifying current acc. to ANSI/IEEE C2.11 Maximum line discharge class Maximum energy absorbing capability Maximum long duration current impulse, 2 ms Short circuit rating 100 / 10 / / 300 / mm kg kj/ r A
4 >10 i peak ma Type 3EP2...-3PK3 (Diameter 710 mm, three-phase arrester) Nominal system voltage Highest voltage for equipment U m up to 10 up to 170 SF -SF -bushing (SF -Oil-bushing on request) Spring contact Enclosure Access cover with pressure relief device and filter Grading hood Metal-oxide resistors Supporting rods Electrical monitoring devices (each phase separate) Gas pressure/density monitoring Arrester Data Height Total weight (max.) Maximum rated voltage U r Maximum nominal discharge current acc. to IEC 99- Maximum classifying current acc. to ANSI/IEEE C2.11 Maximum line discharge class Maximum energy absorbing capability Maximum long duration current impulse, 2 ms Short circuit rating mm kg kj/ r A
5 >10 i peak ma Type 3EP3...-PK (Diameter 710 mm) Nominal system voltage Highest voltage for equipment U m SF -SF -bushing (SF -Oil-bushing on request) Access cover with pressure relief device and filter Spring contact Enclosure Grading hood Metal-oxide resistors Supporting tube Electrical monitoring devices Gas pressure/density monitoring Arrester Data Height Total weight (max.) Maximum rated voltage U r Nominal discharge current acc. to IEC 99- Maximum classifying current acc. to ANSI/IEEE C2.11 Maximum line discharge class Maximum energy absorbing capability Maximum long duration current impulse, 2 ms Short circuit rating 110 / / / mm kg kj/ r A
6 >10 i peak ma Type 3EP3...-PK (Diameter 900 mm) Nominal system voltage Highest voltage for equipment U m 380 / 00 / 0 SF -SF -bushing (SF -Oil-bushing on request) Access cover with pressure relief device and filter Spring contact Enclosure 2 Grading hood Metal-oxide resistors Supporting tube Gas pressure/density monitoring Electrical monitoring devices Arrester Data Height Total weight (max.) Maximum rated voltage U r Nominal discharge current acc. to IEC 99- Maximum classifying current acc. to ANSI/IEEE C2.11 Maximum line discharge class Maximum energy absorbing capability Maximum long duration current impulse, 2 ms Short circuit rating 211 / 0 10 / / mm kg kj/ r A
7 Optimal operating characteristics and maximal operational reliability Siemens GIS arresters permit versatile connection to any GIS system. Bushings may be of the standard type or customer specific. Gas-to-gas type bushings as well as gas-to oil type bushings for connection to transformers are available. In addition to the standard connection flanges, special flanges or additional adaptor flanges can also be designed, constructed and provided according to customer requirements. GIS arresters Type 3EP3 378-PKZ at the line entrance of a gas insulated --switch-gear Type 8DQ1 (BEWAG Berlin, Germany) Commissioning is possible with the absolute minimum of time and expense. The internal mechanical construction of the arresters has been optimized to the effect that no transport braces have to be removed on site. Opening of the tank, which is usually undesirable, is therefore not necessary. However, an internal disconnecting device is provided, which allows to perform dielectric tests on the GIS without removing the arrester. Installation of the GIS arresters is possible, according to customer requirements, either suspended, upright or horizontal. Siemens GIS arresters are virtually maintenance-free. Apart from the usual checking of possible electrical monitoring devices and the gas monitor, it is only necessary to check the gas humidity after ten years and to change the filter material present in the tank after twenty years of service.
8 For Further Information Please fax this page to the following number: Fax Siemens AG, EV HBA 1323 Berlin Germany Name Position Company/Department Street Town / Country Telephone / Telefax Power system data and requirements Nominal system voltage or highest voltage for equipment U m Earth fault factor (if known) δ <1. 1.< δ <1.7 δ = 3 Earth fault duration (if known) < 10 sec > 10 sec or type of neutral earthing Direct Low-resistance Arc-suppression coil (earth fault compensation) Nominal discharge current Line discharge class Connection to (GIS, transformer,...) Manufacturer / Type Seismic requirements Monitoring devices Any other data / information Power Transmission and Distribution Group High Voltage Division Arrester and Limiters Siemens AG, EV HBA D-1323 Berlin Power Transmission and Distribution Subject to change without prior notice Siemens Aktiengesellschaft 11.97
Plug and Operate Transformer Technology
Plug and Operate Transformer Technology Deepal Shah PFISTERER deepal.shah@pfisterer.com by and Andre Goessler PFISTERER andre.goessler@pfisterer.com 1 THE POWER CONNECTION We have always worked closely
More informationA full range of monitoring solutions for surge arresters
A full range of monitoring solutions for surge arresters Answers for energy. Overview ACI ACM basic ACM advanced Concept Electronic Electronic Electronic Measured variables 3rd harmonic of leakage current
More informationA full range of monitoring solutions for surge arresters Answers for energy.
www.siemens.com/energy/arresters A full range of monitoring solutions for surge arresters Answers for energy. Highly reliable equipment monitoring with added value ACM advanced ACM basic and LCM 500 Overview
More informationGLOSSARY OF TERMS. Surge and Lightning Protection ERICO Inc.
GLOSSARY OF TERMS Surge and Lightning Protection ERICO Inc. Air Termination - shall mean that part of a lightning protection system designed to capture the lightning strike. Normally is mounted on the
More informationCentral Power Research Institute, Medipally PO, Uppal, Hyderabad, Telangana. Discipline Electrical Testing Issue Date
Last Amended on 31.07.2015 Page 1 of 11 I. SWITCHGEAR EQUIPMENT 1. High Voltage switchgear & control gear and AB switches Ratings upto 1200 kv system Switching Impulse Voltage (Dry & Wet) Power Frequency
More informationpower pazifik MV Switchgear Secondary Distribution Networks Fully Gas-Insulated Modular and Compact (RMU) System Up to 36 kv
Manufactured by: MV Switchgear Secondary Distribution Networks Fully Gas-Insulated Modular and Compact (RMU) System Up to 36 kv BO-CGM.3/3 SMART RMU Switchgear in Metro Manila Protection and safety for
More informationEach VariSTAR Type AZU arrester must pass the following production tests: 100% Physical Inspection 100% Leakage Current Test 100% RIV Test
Surge Arresters VariSTAR Type AZU Heavy-duty Distribution Class Under-oil MOV Arrester Electrical Apparatus 235-64 GENERAL The Cooper Power Systems VariSTAR Type AZU under-oil MOV arrester is designed
More informationPower Transmission Division Link between power generation and distribution
Power Transmission Division Link between power generation and distribution Seite 4 High Voltage Substations Schemes, Devices and Types of AIS Installation Content Link between power generation and distribution
More informationAC Line Voltage Transients and Their Suppression
AC Line Voltage Transients and Their Suppression Application Note January 1998 AN9308.2 [ /Title (AN93 08) /Subject (AC Line Voltage Transients and Their Suppression) /Autho r () /Keywords (TVS, Transient
More informationLightning and Surge Protection of Photovoltaic Installations. Leutron GmbH 2013 Leinfelden-Echterdingen, Germany
Lightning and Surge Protection of Photovoltaic Installations 1 Lightning and Surge Protection for PV Installations 2 Safeguard from Risks Ups, that was the insurance policy of my house!! 3 Why Lightning
More informationDeploying surge protective devices (SPDs) in photovoltaic systems. Technical Information
Deploying surge protective devices (SPDs) in photovoltaic systems Technical Information 2 00/09.08 Preface Preface Damages caused by overvoltage s are not only responsible for expensive repair costs; they
More informationENGR. MARITES R. PANGILINAN, P.E.E.
ENGR. MARITES R. PANGILINAN, P.E.E. WHAT IS LOW VOLTAGE INSULATION COORDINATION AND WHY IT IS IMPORTANT WHERE DO SURGES COME FROM HOW DO SPDs WORK/TYPE OF SPDs SPD SPECIFICATIONS SPD COORDINATION /CASCADING
More informationCONNEX. The Plug-in Connection System for Power Transformers and Gas-Insulated Switchgear. the power connection THE PFISTERER GROUP
CONNEX The Plug-in Connection System for Power Transformers and Gas-Insulated Switchgear THE PFISTERER GROUP the power connection CONNEX Safety and Versatility in Substations Power grids are changing dynamically
More informationDesigning with Thermally Protected TCMOV Varistors for Type 1 and Type 2 UL1449 3rd Edition Applications
TCMOV Varistors for Type 1 and Type What is UL 1449? Underwriters Laboratories standard UL 1449 has become the primary safety standard for surge protective devices (SPDs). It describes the materials and
More informationFigure 1. Storm Trapper H. E. arrester, external mount. Figure 2. Storm Trapper H.E. arrester, metal enclosed. use in Storm Trapper H.E. arresters.
Surge Arresters Storm Trapper H.E. (High Energy) Low-Voltage Distribution-class MoV Surge Arrester Electrical Apparatus 235-16 GEnErAL Cooper Power Systems Storm Trapper H.E. (High Energy), lowvoltage
More informationTechnical Specification
EMC TESTS, SEMINARS, HARD AND SOFTWARE Technical Specification No. E-MIG1206-3P.doc Revised: 10.March 2007 1 MIG Tester Type MIG1206-3P 1 MIG Tester Type MIG1206-3P 1 1.1 Introduction 1 2 General 2 2.1
More informationOvervoltage Protection Devices
Siemens AG 2010 Overvoltage Protection Devices /2 Introduction /3 Lightning Arresters, Type 1 /5 Combination Surge Arresters, Type 1 and Type 2 /7 Surge Arresters, Type 2 /11 Surge Arresters, Type 3 /12
More informationSecondary Surge Arrester Instruction Manual Page 1 of 5
Secondary Surge Arrester Instruction Manual Page 1 of 5 GENERAL SAFETY INSTRUCTIONS WARNING: ARRESTER CAN FAIL VIOLENTLY AND CAUSE INJURY AND PROPERTY DAMAGE WHEN APPLIED AT VOLTAGES GREATER THAN 120V.
More informationTechnical Data Sheet Medium Current Power Surge Filters
Technologies Technical Data Sheet Medium Current Power Surge Filters Features High performance surge protector for an operating voltage of 0-220Vac Designed to withstand fault and over-voltage conditions
More informationGas-insulated switchgear type series 8DN8. up to 170 kv, 63 ka, 4000 A. Answers for energy.
Gas-insulated switchgear type series 8DN8 up to 170 kv, 63 ka, 4000 A www.siemens.com/energy Answers for energy. Benefiting from experience Our 8D series of gas-insulated switchgear represents a highly
More informationGHA. Gas-Insulated Circuit-Breaker Switchgear Unit up to 40.5 kv. Gas-Insulated Switchgear. Customer Benefits
01 Gas-Insulated Circuit-Breaker Switchgear Unit up to 40.5 kv PM103255 Energy supply security is our permanent challenge. At Schneider Electric, we are constantly developing and improving our products
More informationLPI SG + SS480 Spark Gap Surge Filters
LPI SG + Spark Gap Surge Filters Features High performance surge protector for an operating voltage of 220-277Vac Encapsulated spark gap and technology capable of operation under fault /overvoltage conditions
More informationCONTA-ELECTRONICS. CONTA-PROTECT overvoltage protection
CONTA-ELECTRONICS CONTA-PROTECT overvoltage protection When choosing the correct device for overvoltage protection, it is important to consider the regulations VDE 110-1, IEC 61643-1, EN 61643-11 and VDE
More informationCoordinated Surge Protection
DEHN + SÖHNE DS641/E/10.05 The Lightning Flood Wave When lightning hits an installation, high impulse currents and impulse voltages come up within conductive systems which can be compared to an enormous
More informationThe Wave Breaking Factor and it s Vital Role in Surge Protection Device Coordination. Hans Slagter, DEHN + SOHNE
The Wave Breaking Factor and it s Vital Role in Surge Protection Device Coordination Hans Slagter, DEHN + SOHNE Earthing, Bonding & Surge Protection Conference, Auckland 2012 Discussion topics 1. Introduction
More informationRole of Surge Arrestors in Electrical Power Systems
International Journal of Advances in Electrical and Electronics Engineering 1 Available online at www.ijaeee.com & www.sestindia.org/volume-ijaeee/ ISSN: 2319-1112 Role of Surge Arrestors in Electrical
More informationLPI SST Surge Filters
LPI SST Surge Filters Features High performance surge protector for an operating voltage of 200-240Vac Designed to withstand fault and over-voltage conditions of up to 85Vac, as per IEC664 Impulse discharge
More informationQuality assurance Test Facilities for Gapless ZnO Surge Arresters in High Voltage Division of CPRI, Bengaluru
Quality assurance Test Facilities for Gapless ZnO Surge Arresters in High Voltage Division of CPRI, Bengaluru Abstract: Surge arrester is one of the important power system network components which is neglected
More informationSession Two: Effective Surge Protection Installation
Abstract Session Two: Effective Surge Protection Installation Phillip Tompson Managing Director, Novaris Pty Ltd This paper provides an outline of how to effectively install surge protection to various
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60099-5 Edition 3.0 2018-01 colour inside Surge arresters Part 5: Selection and application recommendations INTERNATIONAL ELECTROTECHNICAL COMMISSION ICS 29.120.50; 29.240.10
More informationCENTERLINE 2500 Motor Control Centers
CENTERLINE 2500 Motor Control Centers High Performance Motor Control Centers and Switch Gear Meeting IEC 61439-2 Product Description Allen-Bradley CENTERLINE 2500 motor control centers (MCCs) are designed
More informationSurge Protection for Surveillance Systems
Surge Protection for Surveillance Systems 1-in-1 Protection for Network Cameras 2-in-1 Protection for Power and Audio/Video Signals 3-in-1 Protection for Power, Audio/Video and PTZ Control Signals Application:
More informationSurge Protection Devices Ex9UE2
Surge Protection Devices Ex9UE2 Surge Protection Devices Type 2 (Class II, T2, C) Tested according to EN 61643-11 Maximum continuous operational voltage U c from 275 V up to 440 V AC Versions with 1+0,
More information2 Principle of lightning protection
2 Principle of lightning protection The system for protecting a building against the effects of lightning must include: bprotection of structures against direct lightning strokes; bprotection of electrical
More informationPurpose of High Voltage Circuit Switchers
Purpose of High Voltage Circuit Switchers Vertical interrupter circuit switcher without integral disconnect switch (Figure 2) Three-phase Interruption and Protection Circuit switchers have been developed
More informationWhite Paper. AC Surge Protection. Evaluation of Series Element Surge Protective Device for Protection of Electronic Equipment and Systems
White Paper AC Surge Protection Evaluation of Series Element Surge Protective Device for Protection of Electronic Equipment and Systems Richard Odenberg, Research & Advanced Applications, Founder of Transtector
More informationPROTEC Z. High Frequency Transient Surge Suppressors For protection of medium voltage motors, generators and dry type transformers
PROTEC Z High Frequency Transient Surge Suppressors For protection of medium voltage motors, generators and dry type transformers Eliminates interturn insulation failures Extends the life of machine insulation
More informationAIR COOLED MODULAR RECTIFIER
CONTROLLED POWER COMPANY SPECIFICATIONS AIR COOLED MODULAR RECTIFIER Spc1800a1 5JAN1999 SPECIFICATION S-1800-A MODULAR (REMOVABLE AND NON-REMOVABLE MODULES) AIR COOLED RECTIFIER Standard output power range:
More informationZoneMaster Series Surge Protection Devices
ZoneMaster Series Surge Protection Devices New Improved ZoneMaster Series Configurable Hard-Wired Surge Protection Devices Wiremold ZoneMaster Series Surge Protection Devices are fully configurable panel
More informationAC Line Voltage Transients and Their Suppression
Harris Semiconductor No. AN9308.2 January 1998 Harris Suppression Products AC Line Voltage Transients and Their Suppression Author: Martin P. Corbett Introduction The increasing usage of sensitive solid
More informationM ISCELLANEOUS A CCESSORIES O BSTRUCTIONS LIGHTS MISCELLANEOUS ACCESSORIES OBSTRUCTION LIGHTS
M ISCELLANEOUS A CCESSORIES O BSTRUCTIONS LIGHTS MISCELLANEOUS ACCESSORIES OBSTRUCTION LIGHTS G1 Outdoor Surge Protector for AC/Traction network VP range Dimensions (in mm) 19 M8 44 73 diam. 47 6 mm² Electrical
More informationType MVTT 14 and MVTT 15: Static Digital Time delay relays
Type MVTT 4 and MVTT 5: Static Digital Time delay relays Features 000/ setting range Time settings easily selected by means of thumbwheel switches Provide time delayed pick-up, or drop-off Compact construction
More informationTRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA
TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA SURGE PROTECTION DESIGN. Parallel Versus Series Protection. Surge protectors within the scope of this UFC should normally be of the parallel
More informationPROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment
PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment NTSA has developed the ultimate solution for protecting
More informationSpark gap surge arrester for direct current OLE line
Spark gap surge arrester for direct current OLE line System suitable to ensure surge protection to equipment and devices connected to (Overhead Line Electrification) OLE lines operating under direct current.
More informationProgrammable Power Supply with DALI
Programmable Power Supply with DALI Product picture Model Name ㅡ Features : ㅡ Suitable for LED lighting application ㅡ Programmable Power Supply Unit(Adjustable Output Current) ㅡ UL8750/UL1012(Non Class
More informationChapter J. Protection against voltage surges in LV. Contents. General. Overvoltage protection devices. Choosing a protection device
Chapter J Protection against voltage surges in LV 1 2 3 4 Contents General J2 1.1 What is a voltage surge? J2 1.2 The four voltage surge types J2 1.3 Main characteristics of voltage surges J4 1.4 Different
More informationLPI SG + SST Spark Gap Surge Filter
LPI SG + SST Spark Gap Surge Filter Features High performance surge protector for an operating voltage of 220-240Vac Encapsulated spark gap and SST capable of sustaining fault and over-voltage conditions
More informationTel: Web: Lightning and surge protection help pages
Lightning and surge protection help pages Effects of lightning on your home or office Modern Technology has progressed to the point where detecting and preventing surges, has become an exact science -
More information3 Design of the electrical installation protection system
J - Protection against voltage surges in LV 3 Design of the electrical To protect an electrical installation in a building, simple rules apply for the choice of b (s); b its protection system. 3.1 Design
More informationABB AG Calor Emag Medium Voltage Products Gas-insulated switchgear Type ZX2. ABB Gas-insulated switchgear type ZX2 1
ABB AG Calor Emag Medium Voltage Products Gas-insulated switchgear 17.02.2015 Gas-insulated switchgear type ZX2 1 Medium voltage switchgear type ZX2 Single or double busbar systems 12 kv, 2500 A, 40 ka
More informationExternally Gapped Line Arresters Smart Solution for Stable Power Supply
Smart Solution for Stable Power Supply Metal-oxide surge arresters with external series gaps improve the reliability of transmission systems, and help eliminate not only lightning damages of transmission
More informationCirprotec Technical Article No. 5
Lightning and surge protection in waste water purification plants (WWTPs and DWTPs) Cirprotec Technical Article No. 5 2010 CIRPROTEC All rights reserved 2012 CIRPROTEC All rights reserved Cirprotec Technica
More informationApplication Considerations for Gapped Silicon-Carbide Arresters Currently Installed on Utility High Voltage Installations
Application Considerations for Gapped Silicon-Carbide Arresters Currently Installed on Utility High Voltage Installations Dennis W. Lenk, Fellow, IEEE Abstract Utilities have expressed concern recently
More informationMaking the Right Choices In Lightning & Surge Arrestors Some Basics:
Making the Right Choices In Lightning & Surge Arrestors Some Basics: It is a fact that the Highveld region of South Africa and Lesotho have amongst the highest lightning strikes per square km per annum
More informationExternally Gapped Line Arresters Smart Solution for Stable Power Supply
Smart Solution for Stable Power Supply Metal-oxide surge arresters with external series gaps improve the reliability of transmission systems, and help eliminate not only lightning damages of transmission
More informationSurge Protection Devices for. Facility Engineers And Electricians. Today s Information. History of SPD Protection. Why Specify an SPD?
Surge Protection Devices for Facility Engineers And Electricians Peter Walsh, PE 1 Today s Information History of SPD Protection Why Specify an SPD? Codes and Standards Specifications Q & A 2 1 What Products
More informationWe put the now in knowledge Today s solutions built on a century of innovation and expertise
PRODUCT OVERVIEW We put the now in knowledge Today s solutions built on a century of innovation and expertise Knowledge. It s what helps you make the next right decision about your critical assets. And
More informationManual for overvoltage protection for LED luminaires rev 1
Kurtatsch, Italy, February 10, 2017 Manual for overvoltage protection for LED luminaires rev 1 Through the introduction of LED luminaires, substantial improvements have been achieved with respect to conventional
More informationLIGHTNING PROTECTION
The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 8 LIGHTNING PROTECTION Aim is to protect: People Buildings and Contents
More information17 th Edition (BS 7671:2008) incorporating Amendment No 1
20 17th Edition 17 th Edition (BS 7671:2008) incorporating Amendment No 1 Installations designed from the 1 st January 2012 are to comply with Amendment number 1. Geoff Cronshaw The first amendment to
More informationdv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Safety information 1 General 2
dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Operating Instructions Safety information 1 General 2 Mechanical installation 3 Electrical
More informationEquipment protection
Equipment protection Serie K Risk of electrical surges Equipment protection 5.000.000 ightning strikes per day 61% Electrical damages caused by surges 30k verage current of a lightning strike ightning
More informationAnnexure-1 (CC no )
Annexure-1 (CC no. 77627) TECHNICAL SPECIFICATIONS OF EXISTING LIGHTNING ARRESTORS S. No. Description Parameter 1. Type Station class heavy duty zinc oxide gapless 2. Applicable standard IEC-60099-4 /
More informationAB MSAI Research Labs Pvt. Ltd., 201, IInd Floor, Aggarwal Cyber Plaza, Netaji Subhash Place, Pitampura, Delhi
Certificate Number TC-5837 (in lieu of T-3494) Page 1 of 12 Range ing / ELECTRONICS TESTING I. INFORMATION TECHNOLOGY EQUIPMENT 1. Information Technology Equipment (Mobile Phones, Power Adaptors, Laptop/Notebook/
More informationABB AG - EPDS. Gas-insulated switchgear Type ZX2
ABB AG - EPDS Gas-insulated switchgear Medium voltage switchgear Single or double busbar systems 12 kv, 2500 A, 40 ka 24 kv, 2500 A, 40 ka 36 kv, 2500 A, 40 ka Slide 2 Medium voltage switchgear With IAC
More informationSurge Protective Device
SURGE PROTECTIVE DEVICE Surge Protective Device 20 R 320 Type Max. discharge current Imax/Iimp (ka) Number of poles (P) R: with alarm auxiliary contact Blank: without alarm auxiliary contact Max. continuous
More informationOvervoltage Protection
Overvoltage Protection OVR Range FRSOX 0100 03 GB ABB Lightning Protection Group 1 Main causes of transient overvoltages The solution: ABB OVR Surge Protective Device Range Lightning strike A lightning
More informationThis annex is valid from: to Replaces annex dated: Location(s) where activities are performed under accreditation
Location(s) where activities are performed under accreditation Head Office Utrechtseweg 310, Building no. R11 6812 AR Arnhem The Netherlands Location Abbreviation/ location code Utrechtseweg 310, Building
More informationSAMSUNG ELECTRO-MECHANICS CO., LTD
Model Name : Features : ㅡ Suitable for LED lighting application ㅡ UL8750, UL1310 Class 2 ㅡ For use in Dry and Damp Location ㅡ Full-protection provided: OCP/OLP/OTP/SCP ㅡ Non potting product Electrical
More informationVaristor Products Radial Lead Varistors > TMOV and itmov Series
RoHS Description The Littelfuse TMOV and itmov thermally protected varistors represent a new development in integrated circuit protection. Both versions are comprised of radial leaded MOVs (Metal Oxide
More informationCONTENTS 3 EN :2006
3 EN 60950-1:2006 CONTENTS INTRODUCTION...9 0 Principles of safety...9 0.1 General principles of safety...9 0.2 Hazards...10 0.3 Materials and components...14 1 General...15 1.1 Scope...15 1.2 Definitions...17
More informationTRENDS IN SWITCHGEAR SPECIFICATIONS
TRENDS IN SWITCHGEAR SPECIFICATIONS What changes are we seeing in equipment specifications? What s being discussed in client meetings? What s happening in the market to support these requests? EQUIPMENT
More informationResidual overvoltage relay
Page 1 Issued: April 1999 Status: New Data subject to change without notice Features Definite-time residual overvoltage earthfault protection and supervision Two independent operation stages, e.g. one
More informationIncreased Safety for Switchgear Cabinets CI Arresters with Integrated Backup Fuse
Increased Safety for Switchgear Cabinets CI Arresters with Backup Fuse www.dehn-international.com 1 fuse 1 2 fuse monitoring 2 3 Considerable space saving 3 Innovative solution to save space in the switchgear
More informationPRACTICAL EXAMPLES OF OVERVOLTAGE PROTECTION
INTERNAL PROTECTION systems PRACTICAL EXAMPLES OF OVERVOLTAGE PROTECTION INDUSTRIAL INSTALLATIONS 2 1 2 5 5 7 2 2 2 2 4 6 6 7 3 OBJECT: Industrial premises, Industrial complexes, Hospitals, Public buildings
More informationNTC thermistors for inrush current limiting
NTC thermistors for inrush current limiting Summary NTC thermistors for inrush current limiting, as all NTCs, are made of polycrystalline mixed oxide ceramics. They suppress high inrush current surges,
More informationLightning and Surge Arresters
Lightning and Surge Arresters 5/4 Product overview 5/5 Lightning arresters, requirement category I (B) 5/6 Combined arresters, requirement category I (B) and II (C) 5/7 Single-pole surge arrester, requirement
More information1278 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 21, NO. 3, JULY 2006
1278 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 21, NO. 3, JULY 2006 Failure Risk Prediction Using Artificial Neural Networks for Lightning Surge Protection of Underground MV Cables Ángel L. Orille-Fernández,
More informationMedium Voltage Metal-Enclosed Power Capacitor Banks
66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Medium Voltage Metal-Enclosed Power Capacitor Banks General Northeast Power System s (NEPSI's) medium
More informationRMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B
3 136 Synco 700 Extension odules for heating controller RH760B RZ782B RZ783B Extension modules for use with the RH760B heating controller to provide additional auxiliary functions Use Heating plants controlled
More informationAN4275 Application note
AN4275 Application note IEC 61000-4-5 standard overview Introduction The objective of this document is to briefly explain the IEC 61000-4-5 standards and to show the benefits of having a range of protection
More informationSafety instructions Overvoltage protection B81-35
Safety instructions Overvoltage protection B81-35 IECEx BVS 15.0084X Intrinsic safety Document ID: 51001 Contents 1 Area of applicability... 3 2 General information... 3 3 Technical data... 5 4 Application
More informationMV Network Switchgear, Protection and Control
MV Network Switchgear, Protection and Control Ravinder Negi Manager, Services Execution INDIA Schneider Electric, New Delhi. Agenda An Overview MV Network Basic Definitions Circuit breaker Switchgear Control
More informationTechnology Live Workshop
Technology Live Workshop David Pitt Product Manager Eaton Electric Ltd. Technology Live Workshop Subjects to be covered in this Technology Live Workshop: Increased need for installation of transient voltage
More informationRapier GX Gas Enclosed Load Break Switch and Sectionaliser up to 38kV with automation or remote control options ENGINEERING BRILLIANT SOLUTIONS
Rapier GX Gas Enclosed Load Break Switch and Sectionaliser up to 38kV with automation or remote control options ENGINEERING BRILLIANT SOLUTIONS RAPIER GX Gas Enclosed Switch Our new RAPIER GX, pole-mounted
More informationIgnitron Driver Manual (N = cable length in meters -example IG5F2-10 = unit with a 10 meter cable length)
North Star High Voltage 12604 N New Reflection Dr, Marana, AZ 85653 520 780 9030; (206)219-4205 FAX www.highvoltageprobes.com DANGER - Voltages of up to 2.5 kv are generated by this unit Ignitron circuits
More informationSicat CMS. siemens.com/mobility. Catenary monitoring system for overhead contact line systems
The contactless catenary monitoring system Sicat CMS continuously monitors the tensile forces in the contact wire and catenary wire and also acquires and evaluates the information. The filtered information
More information16-Channel Digital Input Termination Card 24Vdc
TDI16BIA 16-Channel Digital Input Termination Card 24Vdc (TDI16BIA) Issue 3 October 2005 INTRODUCTION PURPOSE The TDI16BIA16-channel digital input termination card acts as an interface between the digital
More informationDesign, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter
1 Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter Nee, Staffan Norrga, Remus Teodorescu ISBN-10: 1118851560
More informationALLTEC PROTECTION PYRAMID TM FOR PHOTOVOLTAIC SOLAR FIELD
64 Catalyst Drive Canton, North Carolina, 28716 USA +1.828.646.9290 +1.828.646.9527 (Fax) +1.800.203.2658 (Toll Free) www.alltecglobal.com ALLTEC PROTECTION PYRAMID TM FOR PHOTOVOLTAIC SOLAR FIELD Photovoltaic
More information1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285.
SECTION 26 04 75 - SURGE PROTECTION DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Applicable provisions of the General Conditions, Supplementary General Conditions and Special Conditions shall govern work performed
More informationSurge & Filter Protection Addressing your industrial power quality needs.
Surge & Filter Protection Addressing your industrial power quality needs. BULLETIN 983 INTRODUCING SURGE & FILTER PROTECTION SURGE & FILTER PROTECTION Rockwell Automation is pleased to introduce the Bulletin
More informationBS th Edition wiring regulations Furse overview
BS 7671 18th Edition wiring regulations Furse overview Transient overvoltage protection TRANSIENT OVERVOLTAGE PROTECTION - RISK ASSESSMENT TO BS 7671 Furse electronic systems protection Enhanced solutions
More informationTECHNICAL REPORT. Electromagnetic compatibility (EMC)
TECHNICAL REPORT IEC TR 61000-2-14 First edition 2006-12 Electromagnetic compatibility (EMC) Part 2-14: Environment Overvoltages on public electricity distribution networks IEC 2006 Copyright - all rights
More informationLIGHTNING BOLTS Surge arrestors can prevent lightning from sparking a bad day.
HOWTO BEN LIGHTNING BOLTS Surge arrestors can prevent lightning from sparking a bad day. TEVENS Phoenix Contact Inc.,/ nce of protection ag as recently driven home for one company when its factory ect
More informationMONITORING ABSTRACT KEYWORDS. TRANSFORMERS MAGAZINE Special Edition: Bushings, 2017
MONITORING The difference between safe and reliable on-line bushing monitoring and false alarms often lays in the quality of the sensor design and the installation procedure ABSTRACT On-line monitoring
More informationsiemens.com/energy/transformers FITformer REG The adaptable distribution transformer Answers for energy.
siemens.com/energy/transformers FITformer REG The adaptable distribution transformer Answers for energy. Variable input voltage, constant output voltage Modern networks adapt to prevailing conditions,
More informationDANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.
Installation/Operation Manual TABLE OF CONTENTS Page UNPACKING AND INSTALLATION Unpacking and Preliminary Inspection...2, 3 Model Number...9 LOCATION CONSIDERATIONS Environment, Equipment Performance,
More informationINFORMATION TECHNOLOGY SYSTEMS SPDs FOR COAXIAL CONNECTION. DEHNgate Lightning current and surge arresters
Lightning current and surge arresters Application-specific SPD designs SPD for use in satellite and cable TV systems with measuring output Combined lightning current and surge arrester for high discharge
More information