DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for TPSD/A36D Chargers with S2A-205T Option 21P or 57T or 57U. Setup Instructions

Similar documents
A12B DNP 3.0 SERIAL & ETHERNET (TCP/IP) SCADA INTERFACE

DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for A31 Inverters with S2A-383S Option 21P. Setup Instructions

Setup Instructions. This manual is only valid for A12B Chargers equipped with the following: S2A-225C card with software version P225C0630

A36D/TPSD DNP 3.0 & Modbus SCADA INTERFACE

DNP 3.0 & Modbus SCADA INTERFACE INSTRUCTIONS FOR 205T BASED SYSTEMS

A12B / A46 SMNP V3 SCADA INTERFACE INSTRUCTIONS

Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter

ATK3 I/O Module (Modbus Slave)

MB40 & MB45 MODBUS TCP/IP Gateway Handbook

For more information Contact with details of the application.

SCADALink IP100 SCADA Terminal Server QUICK START GUIDE Revision 1.42 June 19, 2012

EVO AT SERIES BATTERY CHARGER AT SERIES BATTERY CHARGER COMMUNICATIONS MANUAL. EVO - Microprocessor Controlled Float Battery Charger JA

ETOR-4. Ethernet/Serial Gateway USER MANUAL

USER S MANUAL. PH232Ex1. #1 RS-232 Serial Port to Ethernet, Terminal Server/Client. Doc No: PH232Ex1-UM-001 IPEX. (IP Electronix)

DKG-210 UNIVERSAL INTERNET GATEWAY UNIT

Docking Stations DS-U1, DS-U2, DS-U4, DS-U4-WL and DS-U Adjustment and configuration procedure for the analog inputs

Industrial Serial Device Server

AP-ENBD User Manual V0.2

CONFIGURATION SOFTWARE

DATRAN XL4 PLUS RTU Quick Start Guide

CJ Series EtherNet/IP TM Connection Guide. OMRON Corporation NX-series EtherNet/IP Coupler Unit P656-E1-01

Site Preparation. for AE250 Inverter Installation Guide. SolarVu

Version 1.0c May 6, 2010 ATK3

Industrial 1-port RS422/485 Modbus Gateway IMG-110T

DataSite Electronic Flow Meter and Remote Terminal Unit

Industrial 2-port RS422/485 Modbus Gateway IMG-120T

ETOR-4 Ethernet/Serial Gateway ETOR-4. Ethernet/Serial Gateway USER MANUAL

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL

EGW1-IA3-MB User s Manual

CAS IKS Gateway (Modbus RTU/TCP and HTML) Manual

Docking Station DS-U4WEB with web server version 1 Instruction Manual

URC Utility Relay Company

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

PWR. Power Module Slots

REL 512 Connectivity With A Harris Westronics RTU Using DNP 3.0

RHF. Railroad High Frequency Battery Charger. Installation and Operation Manual. La Marche Manufacturing Company

Innovative Electronics for a Changing World INDEX

Ethernet to RS-232/485 Gateway

MODBUS TCP/IP TO MODBUS SERIAL GATEWAY. MODEL No: MGate-1024-DC VER 2.0

VENTEV INNOVATIONS BTRM200 Battery Test Remote Monitoring System User Guide V1.0. Innovations BTRM200. Battery Test Remote Monitor User Guide

DNP Points List and Implementation

IntesisBox Modbus Server - BACnet/IP Client

1. Supplied Items. 2. Connecting the DTS SKT. Input side. Input Side

Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual.

Serial to Ethernet Converter

SENS Setup Utility CONFIGURE CHARGERS/SYSTEMS WITH CUSTOM SETTINGS. Operation Manual

KTA-250 Anemometer Alarm Card

MODBUS/TCP TO SIEMENS G110/G120/MM440 APPLICATION

BTRM200 Battery Test Remote Monitor. User Guide

P2 Configuration Guide

ELK-IP232 INSTALLATION AND CONFIGURATION MANUAL. Ethernet to Serial Bridge /07

USER MANUAL FOR FIOA-0402-U-16

MGate MB3000 Modbus Gateway User Manual

NetBiter I/O Extender User Manual

MGate MB3000 Modbus Gateway User s Manual

RS-232/422/485 to Copper or Fiber. Ethernet Converter. User s Manual

Ethernet HMi RAC and Gateway Setup Instructions Rev. 09

TOP Server V5 to MicroLogix Using DNP3 Ethernet Driver

Contents 1 Warnings, Cautions, and Notes Description Features... 1

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx

ACS Stepper _10_Modbus LINEAR SOLUTIONS MADE EASY

Modbus Server - M-Bus (EN ) Gateway for the integration of M-BUS meters with Modbus RTU and TCP based control systems.

Installation and Programming Manual. Niobrara Research & Development Corporation P.O. Box 3418 Joplin, MO USA

TRP-C37M User s Manual

MESR9xx. Vlinx Industrial MODBUS Ethernet to Serial Gateway B&B ELECTRONICS PRODUCT INFORMATION

EnCell Battery Cell Monitor

IntesisBox Modbus Server - Honeywell XLS 80

FNL Modbus TCP Interface

Canlan INSTALLATION MANUAL

TRP-C37M User s Manual

Getting Started with your D3000M Series Module

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

User Manual A08. User Manual

Instruction Manual. Save These Instructions. Centrifugal Compressor Control System. Model Xe-145F Modbus. Instruction Manual

Industrial 1-port RS422/485 Modbus Gateway

SE-330 SERIES (NEW REVISION) MODBUS/TCP INTERFACE

DNP3 Communications Protocol

EQ7000. User Manual. Rev 1.00

Voltage regulator TAPCON 240

1.1 Remote Annunciator Controller (RAC) and 1 Switch (ATC-600/800) via Modbus TCP/IP Ethernet Gateway (PXG-200/400/600E)

Product Specification for SAB-S-MODBUS

Overview. Table of contents

NCOM SERIAL DEVICE SERVER 1XX SERIES USER S MANUAL

TCP/IP TO SERIAL (SINGLE PORT) MODEL No: SerEth-1P VER 2.0

Setting the DCM Switches

Warranty. Warning. Copyright. Contact Us

ZLAN5443A. User Manual

USER MANUAL FOR GS100/GS1003G

STM-1 Mux SONET/SDH Multiplexer User Manual

Advanced Graphical Interface, AGI 100

PRODUCT PROFILE & OUTLINE...6

Texmate Ethernet Supplement NZ216 Revision

IntesisBox Modbus Server KILSEN KSA-7xx. User s Manual 08/2013 r1.2 eng

Industrial 2-port RS422/485 Modbus Gateway

IntesisBox Modbus Server BACnet MSTP and BACnet/IP client

UDA2182 Communications User Guide

TECH NOTES-309. Integrating RACO Verbatim Gateway with the Allen-Bradley ControlLogix Series PLC via Ethernet

TRP-C37. Ethernet to RS232/422/485 Converter. User s Manual. Printed September Rev 1.6

RS232/RS485/RS422 to TCP/IP Converter ITEM NO.: RS007

Serial Connection of HC900 Hybrid Controller to 900CS Control Station

Transcription:

La Marche Manufacturing Company www.lamarchemfg.com DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for TPSD/A36D Chargers with S2A-205T Option 21P or 57T or 57U Setup Instructions This manual is valid for TPSD/A36D Chargers equipped with S2A-205T control card (with software version P205TS0106) and the S2A-383S-3X3X communications card with P383S-21P3-00 configuration or S2A-383DS-4/5x3x cards with P383DS-57TU3-00 configuration. 106 Bradrock Dr. Des Plaines, IL 60018-1967 Instruction Drawing Number: P25-LOPT21P-A36D/TPSD-205T-1 Tel: 847 299 1188 Fax: 847 299 3061 CPN 130064 Revision A01 Rev. Date: 04/18 ECN: 21788

Default Settings The LaMarche Communications Card is shipped with the following default settings: Serial Port Settings Port: RS232 Node Address: 4 Baud Rate: 9600 Data Bits: 8 Stop Bits: 1 Parity: None Ethernet/TCP/Configuration Port Settings Protocol: DNP 3.0 Node Address: 4 IP Address: 192.168.0.6 Subnet: 255.255.255.0 Gateway: 192.168.0.1 TCP Port Number: 20000 Ethernet Type: Copper Interface 10/100 Base-T, Fiber Interface 10/100 Base-FX. PC/Laptop. Required Equipment/Software CAT 5/Ethernet Null-Modem/Crossover cable to connect PC/Laptop to Ethernet Port on Communications Card. To change settings it is necessary to load and install the EasyConnect Software provided by Kalki Communications from the following URL onto your PC/Laptop: https://www.lamarchemfg.com/files/ftp/easyconnect_v4.10.0_setup.zip Setting changes are made through the Ethernet connector on the 383S card. EasyConnect Software Operation EasyConnect is the software that will be used to accomplish the following setting changes. Link Layer Settings (Source Address, Destination Address) SCADA Port Settings (Port Type, Baud Rate, Data Bits, Parity, etc.) Setting the Modbus Address of the Chargers Control Card The communications board utilizes Modbus RTU to read and write settings from the Chargers control board. The settings are polled every 5 seconds. By default they are set as follows: Modbus Address: 1 Modbus Baud Rate: 9600 Modbus Parity Type: None Modbus Port Type: RS232 These settings are required for the two cards to communicate properly. If for some reason the Communications Card is unable to obtain readings from the Control Card the points will go to the offline state. The Modbus Settings may be accessed from the Settings Menu. 2

Changing the DNP 3.0 Link Layer Settings When you have completed the installation of EasyConnect and run it you will be greeted with the following screen: The first step is to upload the settings from the communications board into EasyConnect for modification. Connect the PC/Laptop to the Ethernet Port on the Communications Board. The communications board must be powered. Please note it may take up to 1 minute from the time the board is powered to when it will receive commands. Select Upload as shown below: 3

Select Import to the Configuration (Add as a new device) and the Model should be SYNCS2R1OEM. If you have modified the IP Address of the module to one other than the factory default of 192.168.0.6 you must enter it in the IP Address box. Press Upload to begin the process. Once the Upload is complete you will see a screen as shown below: The above screen shows 3 Channels in the tree view pane. Your application will determine which channel you set up. If you are using RS232 or RS485 to communicate you will interested in Channel-2 DNP 3.0 Serial Slave settings. If you are using TCP to communicate you will be interested in Channel-3 DNP TCP Slave settings. IT IS NOT ADVISED TO MODIFY ANY Channel-1 Modbus RTU Master Settings UNLESS DIRECTED BY LAMARCHE. Channel-1 is used to communicate with the LaMarche Control Card and unintended modification of these settings may prevent the Communications card from receiving and transmitting data to the control card. 4

Channel-2 DNP 3.0 Serial Slave Configuration When using the Serial Ports you must check the 383S card switch settings and make sure switch settings match the DNP Serial Port setting selected in the Communications menu. SW4 (light blue) sets the card to either RS232 or RS485. SW3 (red) selects the RS485 biasing and termination resistor configuration. The silkscreen on the board shows the switch positions for various settings. J2A is the RS232 connection and this port is wired as DTE. TS1 is the RS485 connection. Only one Serial port is active at a time. No configuration is required when using the Ethernet Port. Figure 1 10/100 Base FX Fiber Interface Figure 2 10/100 Base-T Copper Interface 5

Serial Port Configuration (RS232/RS485, Baud Rate, Parity, Data Bits, Stop Bits) Using the mouse point and click on Channel-2 DNP 3.0 Serial Slave in the tree view as shown below. In this view you can select the Channel Type, RS485/RS422 mode, Baud Rate, Data Bits, Stop Bits, Parity and Flow Control. It is not advisable to change any other settings without first consulting with LaMarche or your SCADA Department. ALSO PLEASE LEAVE the Port SETTING ON Com2. Recommended Settings: RS232: Channel Type: RS232 Baud Rate: 9600 RS485: Channel Type: RS485 RS485/RS422 mode: RS485 Data Bits: 8 Baud Rate: 9600 Stop Bits: 1 Data: Bits: 8 Parity: None Stop Bits: 1 Flow Control: None Parity: None Flow Control: Hardware 6

DNP Link Layer Configuration (Source & Destination Address) Using the mouse point and click on Node_2 in the tree view as shown below. In this view you can select the Source Address and Destination Address. Other settings are available however it is not advisable to change any other settings without first consulting with LaMarche or your SCADA Department. Note: The Source Address is the address the Communications card is to reside at. The Destination Address would be that of the Master Station and is not always required unless source validation is utilized. Once you have configured the Serial Port and Link Layer settings you may proceed to the Download Settings to Communications Card section of this manual. 7

Communications Board Configuration Channel-3 DNP TCP Slave Configuration When using the TCP you do not need to concern yourself with the switch settings on the 383s card shown below. 10/100 Base FX Fiber Interface 10/100 Base-T Copper Interface 8

DNP Link Layer Configuration (Source & Destination Address) Using the mouse point and click on Node_3 in the tree view as shown below. In this view you can select the Source Address and Destination Address. Other settings are available however it is not advisable to change any other settings without first consulting with LaMarche or your SCADA Department. Note: The Source Address is the address the Communications card is to reside at. The Destination Address would be that of the Master Station and is not always required unless source validation is utilized. 9

DNP Channel Configuration (TCP Port Number) Using the mouse point and click on Channel-3 DNP TCP Slave in the tree view as shown below. In this view you can select the Port Number. Other settings are available however it is not advisable to change any other settings without first consulting with LaMarche or your SCADA Department. To change the IP, Subnet and Gateway please refer to the section titled Changing the IP Settings. Once you have configured the settings you may proceed to the Download Settings to the Communications Card section of this manual. 10

Downloading the Settings to the Communication Card Step 1: Use the mouse and click on SS1: SYNCHS2R1OEM in the tree view pane. Step 2: Select Download for the Settings menu. 11

Step 3: After you select Download the following dialog will appear. Check the Configuration File Check Box as shown. In the IP Address box enter the IP address of the module if it has been changed to something other than the default of 192.168.0.6. Press the Download button. Step 4: The following dialog should appear when the download is successful. Press the OK button. A Restart is required and is described in the next step. 12

Step 5: Select Restart from the Settings menu as shown below. Step 6: In the IP Address box enter the IP address of the module if it has been changed to something other than the default of 192.168.0.6. Press the Restart button. 13

Step 7: Once the Restart has begun a dialog box as shown below will appear indicating the device is about to restart. Press the OK button. At this point the configuration is now stored on the card and the configuration process is complete. For those that desire to change the IP Settings of the card please refer to the section titled Changing the IP Setting. 14

Changing the IP Settings Step 1: Select IP Configuration from the Settings menu as shown below. Step 2: In the Lan Settings dialog shown below you enter the present IP address in the box just below the SYNCS2R1OEM drop down box. In this case the card is at IP 192.168.0.6. In the IP Address, Subnet and Gateway under the eth0 label you enter the settings you would like the card to take on. In this case the module is presently at 192.168.0.6 and will be changed to an IP of 192.168.0.121 with a Subnet of 255.255.255.0 and a Gateway of 192.168.0.1. Press the OK button when you are done making changes. 15

Step 3: The card is now at the new IP settings. Press the OK button and the board will be restarted automatically and will now be at the new settings. Note: If you have changed them to a different subnet you will have to modify your network adapter card settings to reconnect to the card. 16

17

18

19

20

21

22

23

24

25

26

27

28

DNP V3.0 Point List The tables below identify all the data points provided by the implementation. Binary Output Status Points Object Number: 10 Default Variation reported when variation 0 requested: 2 (Binary Output Status) Control Relay Output Blocks Object Number: 12 Point Name/Description Index 0 Float/EQ Mode Indicator (FLOAT=0, EQUALIZE=1) 1 Temperature Compensation Enable (Enabled=1, Not Enabled=0) Binary Input Points Static (Steady-State) Object Number: 1 Static Variation reported when variation 0 requested: 1 (Binary Input 2 without status) Point Index Name/Description 0 AC Fail Alarm Status (OK=0, ALARM=1) 1 Low Voltage Alarm Status (OK=0, ALARM=1) 2 High Voltage Alarm Status (OK=0, ALARM=1) 3 High Voltage Shutdown Alarm Status (OK=0, ALARM=1) 4 Low DC Current Alarm Status (OK=0, ALARM=1) 5 Ground Detection Enable (Enabled=1, Not Enabled=0) Positive Ground Alarm Status (OK=0, ALARM=1) 6 Point will always read 0 when Ground Detection Enabled (Binary Input Point 5) is 0. Negative Ground Alarm Status (OK=0, ALARM=1) 7 Point will always read 0 when Ground Detection Enabled (Binary Input Point 5) is 0. 8 Summary Alarm Status (OK=0, ALARM=1) Blown DC Protection Alarm Status (OK=0, ALARM=1) 9 Point will always read 0 when Ground Detection Enabled (Discrete Input Point 5) is 1. 10 Local Temperature Probe used for Temperature Compensation (INACTIVE=0, ACTIVE=1) 11 Remote Temperature Probe used for Temperature Compensation (INACTIVE=0, ACTIVE=1) 12 Float/EQ Mode Indicator (FLOAT=0, EQUALIZE=1) 13 Temperature Compensation Enable (Enabled=1, Not Enabled=0) 29

Analog Inputs Static (Steady-State) Object Number: 30 Static Variation reported when variation 0 requested: 4 (16-Bit Analog Input w/o Flag) Point Index Description, Units 0 Heartbeat. Increments continuously to indicate communications between Controller board and communications board are working. None 1 Board Number. Will read 205 for205ts card. None 2 Software Version, Version of software on 205TS card. None 3 DC Output Voltage, Volts 0.1 4 DC Output Current, Amps 0.1 5 Equalize Cycle Time Hours Remaining, Hours, Minutes Note: The last two digits are the minutes. None 6 Auto Equalize Timer, Days None 7 Auto Equalize Timer, Hours, Minutes Note: The last two digits are the minutes. None 8 Low DC Current Alarm Low Limit, Amps Note: Settings below this limit disable the Low DC Current Alarm 0.1 9 Local Temperature Probe Reading, C None 10 Remote Temperature Probe Reading, C None 11 Equalize Timer Mode (0,1 2,3,4) None 12 Equalize Timer Setting (0 to 144) None 13 Low Voltage Alarm Threshold, Volts 0.1 14 High Voltage Alarm Threshold, Volts 0.1 15 High Voltage Shutdown Alarm Threshold, Volts 0.1 16 Low DC Current Alarm Threshold, Amps 0.1 17 Low DC Current Alarm Reset Threshold, Amps 0.1 Scale Factor Analog Outputs Static (Steady-State) Object Number: 40 Static Variation reported when variation 0 requested: 2 (16-Bit Analog Output Status) Point Index Description, Units, Valid Settings/Range 0 Equalize Timer Mode (0,1 2,3,4) None 1 Equalize Timer Setting (0 to 144) None 2 Low Voltage Alarm Threshold, Volts, 0 to 200.0 0.1 3 High Voltage Alarm Threshold, Volts, 0 to 200.0 0.1 4 High Voltage Shutdown Alarm Threshold, Volts, 0 to 200.0 0.1 5 Low DC Current Alarm Threshold, Amps, 0 to 6000.0 0.1 6 Low DC Current Alarm Reset Threshold, Amps, 0 to 6000.0 0.1 Scale Factor 30