TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV)

Similar documents
3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

SECTION METAL-CLAD MEDIUM VOLTAGE SWITCHGEAR (VacClad-W)

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2

SECTION DISTRIBUTION SWITCHBOARDS

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM>

SECTION SWITCHGEAR

SECTION DISCONNECT SWITCHES

ATTACHMENT C. 15kV GENERATOR CIRCUIT BREAKERS & 15KV STATION SERVICES SWITCHGEAR FOR HOLM POWER PLANT GENERATOR LINE BREAKER 52G ADDITION

Power Control Systems

SECTION PANELBOARDS. A. NECA (National Electrical Contractors Association) -Standard of Installation

Elastimold Molded Vacuum Recloser - MVR

Medium-Voltage Circuit Breaker-Type Automatic Transfer Switches and Bypass/Isolation Switches

SECTION ( ) LIGHTING CONTROL PANELBOARD

SECTION SWITCHBOARDS

1. Coordination of series-rated devices is permitted where indicated on Drawings.

SECTION PANELBOARDS

4.3. Switchboards. Contents Description Pow-R-Line Drawout Molded Case Circuit Breaker Switchboards Product Selection...

Medium Voltage Metal-Enclosed Power Capacitor Banks

Featuring Spectra RMS Breakers

SACE Emax 2 Specification guide

SERIES SD3800 / SD3810 SPECIFICATION

1510 MOTOR CONTROLLERS

920 Remote Control (RC) Switches

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A

SECTION 16496E ATS MOLDED CASE WITH ATC 900 CONTROLLER

Metal-enclosed interrupter 5 kv-15 kv usa.siemens.com/siebreak

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum)

ASCO 920 Remote Control (RC) Switches

SECTION MOTOR CONTROL CENTERS

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION MEDIUM VOLTAGE MOTOR CONTROLLERS LIMITAMP WITH POWER MANAGEMENT. A. Medium Voltage Motor Controllers with Power Management

LOW VOLTAGE BYPASS/ISOLATION BREAKER BASED AUTOMATIC TRANSFER SWITCHES SECTION 16496D

Medium Voltage Metal-Enclosed Harmonic Filter Systems

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

Free Standing Emergency Department DGL Project No SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL

SECTION ELECTRICAL CONTROL DEVICES

SECTION ELECTRIC METERING

PDI Modular Compact Remote Power Panel

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM

SECTION MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III 100% CONSTRUCTION DOCUMENTS

Type VR Electrically Operated Ground and Test Device

MOTOR CONTROL CENTER INFINITY SERIES

Meter Enclosure and Equipment Standards

Metal-enclosed interrupter 5 kv-15 kv usa.siemens.com/siebreak

UBC Technical Guidelines Section Edition Primary Unit Substation Page 1 of 14

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application

SUGGESTED SPECIFICATION For Medium Voltage Automatic Closed Transition Transfer Switches

SECTION PANELBOARDS

Maximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches

HID. GE Consumer & Industrial Multilin. High Impedance Differential Module Instruction manual GEK Copyright 2005 GE Multilin

DESCRIPTIVE BULLETIN. SafeGear 5/15 kv, up to 50 ka arc-resistant switchgear

reliable company...caterpillar

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers. 4. Electronic-grade panelboards.

Document C0. Use for:

VisoVac padmount fault interrupter

Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage

AIR COOLED MODULAR RECTIFIER

SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet

Specifications. S&C Line-Rupters. For Line and Cable Switching. Outdoor Transmission (115 kv through 230 kv) Conditions of Sale

Fundamentals of Circuit Breaker Maintenance. AVO Training Institute, Inc. 2018

Metering Devices, Protective Relays, Software and Connectivity. Pre-Wired Control Power, Voltage and CT Inputs

SECTION MEDIUM-VOLTAGE CIRCUIT BREAKER SWITCHGEAR (GAS-INSULATED, VACUUM)

SIEBREAK-VCB 5-15 kv metal-enclosed interrupter switchgear usa.siemens.com/siebreak

This section applies to the design and installation relating to automatic transfer switches (ATS).

Application Techniques CENTERLINE 2100 Motor Control Centers

POWER SYSTEMS STUDY: SIGNIFICANT (OR TOTAL) DELETION OF EXISTING TEXT

DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

Bulletin 1489 Circuit Breakers. Selection Guide

White Paper. UL Standards for Power Control System Equipment

MESP TECHNICAL SPECIFICATION FOR 22 kv METAL ENCLOSED SWITCHGEAR

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD

AHSC MEDIUM VOLTAGE ELECTRICAL SEPARATION

Instrument Current Transformers

SECTION VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD)

Series 2400 Paralleling Switchgear

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5

TRENDS IN SWITCHGEAR SPECIFICATIONS

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching

Medium Voltage Metal-Enclosed Thyristor-Switched Harmonic Filter Banks

Spring Test 5 due 4/26/2013

Switch Disconnectors, Main and EMERGENCY-STOP Switches

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

EMMS-T A00 SIERS. Siemens integrated electrical racking system instruction manual. usa.siemens.com/mvswitchgear

Power-Style QED-2, Series 2 Low Voltage Switchboards

These specifications describe requirements for a power distribution unit (PDU) distributing power to sensitive loads.

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Underground Distribution Switchgear

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS

References. References. Rating (A) Référence

E-Series General Specifications

Refurbishment of Switchgear and Switchgear Devices

ELG4125: System Protection

Transcription:

1.1 DESCRIPTIONS OF WORK A. The Bidder shall furnish and install the equipment as specified herein and as shown on the contract drawings. B. The switchgear and circuit breakers shall be manufactured by single company. C. The 15 kv metal-clad switchgear shall close coupled to the 3000 kva substation transformer as specified in Appendix F. D. Provide software for all protective relays as specified and as shown on drawings. 1.2 RELATED SECTIONS A. Appendix B: Medium Voltage Metal-Clad Paralleling Switchgear B. Appendix D: Primary Unit Substation C. Appendix F: Substation Transformer Vacuum Cast Coil D. Appendix G: Neutral Grounding Resistors E Appendix J: DC Battery System F. Appendix K: Electrical Identification G. Appendix N: Short-Circuit/Coordination Study/Arc Flash Hazard Analysis H. Appendix Q: Basic Electrical Materials and Methods 1.3 REFERENCES A. The metal-clad switchgear and all components shall be designed, manufactured and tested in accordance with the latest applicable standards of NEMA SG-4 and SG- 5, and but not limited to, ANSI/IEEE 37.20.2. 1.4 SUBMITTALS A. The following information shall be submitted to the City Representative: 1. Master drawing index 2. Front view elevation 3. Floor plan 4. Top view 5. Single line diagram ITSF09000227 Appendix E Page 1 of 9

6. Nameplate schedule 7. Component list 8. Conduit entry/exit locations 9. Assembly ratings including: a. Short-circuit rating b. Voltage c. Continuous current d. Basic impulse level for equipment over 600 volts 10. Major component ratings including: a. Voltage b. Continuous current c. Interrupting ratings 11. Cable terminal sizes 12. Product data sheets 13. Busway connection 14. Connection details between close-coupled assemblies 15. Composite floor plan of close-coupled assemblies 16. Key interlock scheme drawing and sequence of operations 17. Descriptive bulletins 19. Final as-built drawings and information for items listed in Paragraph 1.4, and shall incorporate all changes made during the manufacturing process. 19. Wiring diagrams 20. Certified production test reports 21. Installation information including equipment anchorage provisions 22. Seismic certification as specified in APPENDIX S. 1.5 QUALIFICATIONS A. The manufacturer of the assembly shall be the manufacturer of the major components within the assembly. B. For the equipment specified herein, the manufacturer shall be ISO 9001 or 9002 certified. C. The manufacturer of this equipment shall have produced similar electrical equipment for a minimum period of five (5) years. When requested by the City ITSF09000227 Appendix E Page 2 of 9

Representative, an acceptable list of installations with similar equipment shall be provided demonstrating compliance with this requirement. 1.6 OPERATION AND MAINTENANCE MANUALS A. Equipment operation and maintenance manuals shall be provided with each assembly shipped, and shall include instruction leaflets and instruction bulletins for the complete assembly and each major component. B. See Appendix P for additional requirements. 2.1 MANUFACTURERS A. Eaton / Cutler-Hammer or approved equal. B. G.E. or approved equal. 2.2 RATINGS The listing of specific manufacturers above does not imply acceptance of their products that do not meet the specified ratings, features and functions. Manufacturers listed above are not relieved from meeting these specifications in their entirety. Products in compliance with the specification and manufactured by others not named will be considered only if pre-approved by the City Representative ten (10) days prior to bid date. A. The switchgear described in this specification shall be designed for operation on a 12.47 kv, three-phase, three-wire, solidly grounded, 60-hertz system. B. Each circuit breaker shall have the following ratings: Maximum Voltage 15 kv BIL Rated 95 kv Peak Continuous Current (15 kv) 1200 Ampere Short-Circuit Current at rated Maximum kv 18 ka RMS sym Rated Voltage Range Factor K 1.3 Closing and Latching Capability 62 ka Crest Maximum Symmetrical Interrupting ITSF09000227 Appendix E Page 3 of 9

and 3-Second Rating Nominal 3-Phase MVA Class Rated Interrupting Time 23 ka RMS SYM 500 MVA 5 Cycle 2.3 CONSTRUCTION A. The switchgear assembly shall consist of individual vertical sections housing various combinations of circuit breakers and auxiliaries, bolted to form a rigid metal-clad switchgear assembly. Metal side sheets shall provide grounded barriers between adjacent structures and solid removable metal barriers shall isolate the major primary sections of each circuit. Hinged rear doors with tamper proof bolts shall be provided. The switchgear sections shall be provided with infrared sight glasses for IR inspection cameras. IR sight glasses shall be Hawk-IR, catalog No. HWK-100-C-LSF-KT. CLIRVU coated crystal lens. B. The stationary primary contacts shall be silver-plated and recessed within insulating tubes. A steel shutter shall automatically cover the stationary primary disconnecting contacts when the breaker is in the disconnected position or out of the cell. Provide rails to allow withdrawal of each 15 kv circuit breaker for inspection and maintenance without the use of a separate lifting device. 2.4 ENCLOSURES 2.5 BUS A. Switchgear shall be NEMA 3R, non walk-in outdoor enclosure. See Appendix O for additional requirements. A. The main bus shall be copper with fluidized bed epoxy flame-retardant and trackresistant insulation. The bus supports between units shall be flame-retardant, track-resistant, glass polyester. The switchgear shall be constructed so that all buses, bus supports and connections shall withstand stresses that would be produced by currents equal to the momentary ratings of the circuit breakers. Main bus for shall be rated 1200 amperes. Insulated copper main bus shall be provided and have provisions for future extension. All bus joints shall be plated, bolted and insulated with easily installed boots. The bus shall be braced to withstand fault currents equal to the close and latch rating of the breakers. The temperature rise of the bus and connections shall be in accordance with ANSI standards and documented by design tests. ITSF09000227 Appendix E Page 4 of 9

B. A copper ground bus shall extend the entire length of the switchgear. 2.6 WIRING/TERMINATIONS A. The switchgear manufacturer shall provide suitable terminal blocks for secondary wire terminations and a minimum of 10% spare terminals shall be provided. One control circuit cutout device shall be provided in each circuit breaker housing. Switchgear secondary wire shall be #14 AWG, type SIS rated 600 volt, 90 degrees C, furnished with wire markers at each termination. Wires shall terminate on terminal blocks with marker strips numbered in agreement with detailed connection diagrams. B. Incoming line and feeder cable lugs of the type and size to accommodate PG&E supplied cables. 2.7 CIRCUIT BREAKERS A. The circuit breakers shall be horizontal drawout type, capable of being withdrawn on rails. The breakers shall be operated by a motor-charged stored energy spring mechanism, charged normally by a universal electric motor and in an emergency by a manual handle. The primary disconnecting contacts shall be silver-plated copper. B. Each circuit breaker shall contain three vacuum interrupters separately mounted in a self-contained, self-aligning pole unit, which can be removed easily. The vacuum interrupter pole unit shall be mounted on glass polyester supports. A contact wear gap indicator for each vacuum interrupter, which requires no tools to indicate available contact life, shall be easily visible when the breaker is removed from its compartment. The current transfer from the vacuum interrupter moving stem to the breaker main conductor shall be a non-sliding design. The breaker front panel shall be removable when the breaker is withdrawn for ease of inspection and maintenance. C. The secondary contacts shall be silver-plated and shall automatically engage in the breaker operating position, which can be manually engaged in the breaker test position. D. Interlocks shall be provided to prevent closing of a breaker between operating and test positions, to trip breakers upon insertion or removal from housing and to discharge stored energy mechanisms upon insertion or removal from the housing. ITSF09000227 Appendix E Page 5 of 9

The breaker shall be secured positively in the housing between and including the operating and test positions. E. The breakers shall be electrically operated by the following control voltages: 125 volt DC close and 125 volt DC trip. Each breaker shall be complete with control switch and red and green indicating lights to indicate breaker contact position. F. DC control voltage shall be supplied by a station battery as specified in Appendix J, DC Battery System. 2.8 PROTECTIVE RELAYS A. The switchgear manufacturer shall furnish and install, in the metal-clad switchgear, the quantity, type and rating of protection relays as indicated on the drawings and described hereafter in this specification. B. As a minimum, the following Schweitzer SEL 351-7, part number 03517053554XX1, utility grade, multi-function protective relay shall be provided for each Utility Point of Common Coupling (PCC): a. Instantaneous/Time Overcurrent (50/51) Relay, 3-phase, percent adjustable, utilizing ANSI trip curves. b. Under/Over Voltage (27/59) Relay, 3-phase, percent adjustable, percent reset, with time delay. c. Over/Under Frequency (81 O/U) Relay, single phase, percent adjustable, percent reset, with time delay. d. Phase Sequence/Phase Failure (47) Relay (Utility Grade), 3-phase, percent adjustable, with time delay e. Reverse Power (32) Relay, 3-phase, percent adjustable with time delay. f. Reverse Direction Overcurrent (32/51) Relay (Utility Grade), 3- phase, percent adjustable, with time delay. g. Utility Lock-out (86) Relay (Utility Grade), manual reset h. Utility Re-close Lock-out Switch with lockable cover. i. Manual Paralleling Synch Check Relay (25), Industrial Grade j. Automatic Synchronizer (15/25), adjustable sync window and sync window dwell time. k. Manual Paralleling Synch Check (25). ITSF09000227 Appendix E Page 6 of 9

C. Relay programming shall be performed by relay manufacturer s engineering service group. The Bidder shall develop and deliver electronic and printed device configuration setting files for all digital protective relays and data concentrators. The electronic setting files for all SEL protective devices shall be in SEL-5010 Relay Assistant Software (.mdb) and AcSELerator QuickSet SEL-5030 Software (.rdb) file formats. Device settings shall include and not be limited to the following: unique identification names, instrument transformer ratios, protective element pickup thresholds, logic expressions, sequential event recorder lists, event report trigger equations, output contact logic, communications protocol settings, and so forth. Printed settings documentation will include a listing of relay settings, supporting calculations, pertinent fault-study results, and overcurrent coordination curves, as required, in Microsoft Word (.doc) or Adobe Acrobat (.pdf) format. 2.9 AUXILIARY DEVICES A. Ring type current transformers shall be furnished as indicated on the contract drawings. The thermal and mechanical ratings of the current transformers shall be coordinated with the circuit breakers. Their accuracy rating shall be equal to or higher than ANSI standard requirements. The standard location for the current transformers on the bus side and line side of the breaker units shall be front accessible to permit adding or changing current transformers without removing high-voltage insulation connections. Shorting terminal blocks shall be furnished on the secondary of all the current transformers. B. Voltage and control power transformers of the quantity and ratings indicated in the detailed specification shall be supplied. Voltage transformers shall be mounted in drawout drawers contained in an enclosed auxiliary compartment. When required, control power transformers up to 15 kv, 15 kva, single-phase shall be mounted in drawout drawers. Rails shall be provided as applicable for each drawer to permit easy inspection, testing and fuse replacement. Shutters shall isolate primary bus stabs when drawers are withdrawn. C. A mechanical interlock shall be provided to require the secondary breaker to be open before the CPT drawer or CPT primary fuse drawer can be withdrawn. 2.10 UTILITY METERING A. Provide separate utility metering structure complete with hinged sealable door. Bus work shall include provisions for mounting utility company current ITSF09000227 Appendix E Page 7 of 9

2.11 NAMEPLATES transformers and potential transformers as required by the PG&E. A. Engraved nameplates, mounted on the face of the assembly, shall be furnished for all main and feeder circuits as indicated on the drawings. Nameplates shall be laminated plastic, black characters on white background, and secured with screws. Characters shall be 3/16-inch high, minimum. Furnish master nameplate for each switchgear lineup giving information in accordance with IEEE Std. C37.20.2-1999, Section 7.4.1. Circuit nameplates shall be provided with circuit designations as shown on purchaser s single-line diagrams. B. Control components mounted within the assembly, such as fuse blocks, relays, pushbuttons, switches, etc., shall be suitably marked for identification corresponding to appropriate designations on manufacturer s wiring diagrams. 2.12 CORONA FREE DESIGN A. The switchgear shall be corona free by design and shall be tested for partial discharges in accordance with EEMAC standard G11-1. The corona discharges measured during the tests shall be less than 100 picocoulombs. 3.1 FACTORY TESTING A. The following standard factory tests shall be performed on the circuit breaker element provided under this section. All tests shall be in accordance with the latest version of ANSI standards. 1. Alignment test with master cell to verify all interfaces and interchangeability 2. Circuit breakers operated over the range of minimum to maximum control voltage 3. Factory setting of contact gap 4. One-minute dielectric test per ANSI standards 5. Final inspections and quality checks B. The following production test shall be performed on each breaker housing: 1. Alignment test with master breaker to verify interfaces ITSF09000227 Appendix E Page 8 of 9

2. One-minute dielectric test per ANSI standards on primary and secondary circuits 3. Operation of wiring, relays and other devices verified by an operational sequence test 4. Final inspection and quality check C. The manufacturer shall provide three (3) certified copies of factory test reports. ***END OF APPENDIX*** ITSF09000227 Appendix E Page 9 of 9