Emergency Stop Devices (MD Annex I ) Background

Similar documents
Technical Guide. Safety Applications. For Immediate Delivery call KMParts.com at (866) Building Automation. Industrial Automation

FSO Webnair FSO Safety Functions Module. ABB Group February 11, 2015 Slide 1

INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT. LTD.

Original operating instructions Safety relay with relay outputs G1501S / / 2016

Low voltage switchgear and controlgear functional safety aspects

Keystone OM3 - EPI-2 Local Interface Module Installation and Maintenance Instructions

Polymer Electric. Operating Instructions. Control Unit SG-RST 153. Version 0.3

Rotary switches T and switchdisconnectors. reliable switching, disconnection, control and operation

Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016

Original operating instructions Fail-safe inductive sensor GI711S / / 2010

Switch Disconnectors, Main and EMERGENCY-STOP Switches

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Control Cabinet Inverter MOVITRAC B Functional Safety

SAFETY PRESSURE MATS GENERAL PRODUCT FEATURES

Polymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3

Application Technique. Safety Function: Safety Camera with E-stop

Operating Instructions

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

Operating instructions. Speed monitor D / / 2014

Control unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V

FACTORY AUTOMATION. MANUAL VAA-2E-G4-SE Original Instructions Version 1.1

4. CIRCUIT BREAKERS. Functional Emergency Switching

Safe Isolation of Main Circuits with Switch-Disconnectors N or with Molded Case Switches NS

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. MOVITRAC MC07B Functional Safety

CONTROL PANEL WIRING SPECIFICATIONS

SIRIUS Safety Integrated. Modular safety system 3RK3

Control unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~

Operating instructions. Switching amplifier DN0210 DN / / 2015

Safety Manual Safety technology for machines and systems in accordance with the inter national standards EN ISO and IEC 62061

XACA2074 pendant station XAC-A pistol grip - 2 push buttons 1 Emergency stop

3RV1 Circuit-Breakers

C60PV-DC. IEC / EN e. Main characteristics Operating voltage (Ue) 800 V DC Rated insulation voltage (Ui) 1,000 V DC Breaking capacity (Icu)

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

SMS 4 / SMS 5 safety mat Product information

Safety-related controls SIRIUS Safety Integrated

SMVector Additional I/O Module Installation and Operation Manual

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

GB/T / IEC :2006

Mounting and System Description for SSZ-Safety-Switching-Rails

SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016

Operating instructions Safety-monitoring module SSW 301HV. 1. About this document. Content

Installation Instructions for Eaton Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2

MCS-2015 Basic power supply for on-off and emergency 115 VAC Electrak 1 stop. 115 VAC or 230 VAC input. 230 VAC Electrak 10 Electrak 100

SR103AM. User Information for SR103AM. Correct Use

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Electronic Motor DRC Functional Safety

Setpoint Isolators. Technical Manual. HA Issue Parker SSD Drives, a division of Parker Hannifin Ltd. WARRANTY

PowerFlex 700H AC Drive Safe Torque Off Option

NHP SAFETY REFERENCE GUIDE

Operating instructions Safety-monitoring module AES 1235 AES About this document. Content

Varius SUMMARY OF MODELS OF HRC FUSE-LINKS

Mounting and System Description for SSZ-Safety-Bumpers

Balluff smart safety BE ON THE SAFE SIDE. SAFETY OVER IO-LINK

Agilent 34401A 6½ 桁マルチメータ ユーザーガイド

NHP SAFETY REFERENCE GUIDE

User s Manual. ACS550-PD Stock 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual

EMMS-T A00 SIERS. Siemens integrated electrical racking system instruction manual. usa.siemens.com/mvswitchgear

FUSERBLOC UL Fusible disconnect switches UL and CSA 30 to 800 A

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. MOVITRAC MC07B Functional Safety

Please keep these instructions for further reference.

Siemens Industrial s

Model 7705 Control Module

DISCONNECTABLE MOTOR SWITCH AC-3 UP TO 45 kw

Technical Requirements for High-voltage DC Power Feeding Interfaces of ICT equipment

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

User Guide. Cloning interface small option module for Unidrive and Commander GP. Part Number: Issue Number: 3

Sliding shutter control Aluminium shutters

Molded Case Circuit Breakers and Disconnect Switches Auxiliary Contacts for Type NZMH4-...

ES-TN-1H.. E-Stop Safety Modules with Fixed Delay

MSI-RM2 Safety Relays

Automatic Transfer Switch OTM_C20D

Fire Shutter Electrically Operated. Insert address here OPERATING AND MAINTENANCE MANUAL SAFETY, SERVICE & REPAIR. flexability is our strength

ECS servo system MCS servo motors

Operating instructions Safety-monitoring module AES 1235 AES About this document. Content

ELR H3-IES-PT- 24DC/500AC-...

CAPIEL Position Paper WEEE Scope

OPT2011. High-performance distance sensor. Operating Instructions

Applikationen & Tools. Safe switching of IO-Link motor starter combination 3RA27 with safety relay 3SK1. IO-Link. FAQ November 2012

Original operating instructions Fail-safe inductive sensor GF711S / / 2013

Specification Voltage Limiting Device

Please keep these instructions for further reference.

Product Information SIMATIC S Digital Output Module SM 322; DO 16 UC24/48 V

Metal Position Switch

1 Safety instructions. 2 Intended use. 3 Product characteristics. 4 Operation. LB management. Universal rotary dimmer LED

Options for ABB drives. User s manual Emergency stop, stop category 0 (option +Q951) for ACS880-07/17/37 drives

SAFETY RELAY YRB-4EML-31S MAIN FEATURES

Safety Instructions 1-1 Avoid unintended Start General Description 2-2

SR101A. User Information for SR101A. Correct Use

Vista SD Portable Remote Control Pendant

Isolating repeater IRU 420

BT50(T) Safety relay / Expansion relay

Functional Safety for Electronic Control

I/O PCB-AC - Replacement

Operating Instructions

Assembly and Operating Instructions Door Control

EDS94AYAB.;2G. L force Drives. Ä.;2Gä. Manual E94AYAB SM100. Safety module

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

Polymer Electric. Operating Instructions. Control Unit SG-TRS 3X8. Version 1

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

SMARTSCAN INFORMATION

Model 2657A-LIM-3 LO Interconnect Module

Welcome to the overview of ACS880 functional safety, FSO-11 Safety functions module.

Transcription:

Ref. Ares(2015)2362619-05/06/2015 Emergency Stop Devices (MD Annex I 1.2.4.3) Note: this document, as MD WG 2010-03 EN rev.2, has been approved at the Machinery Working Group meeting on 5-6 November 2014. Background According to Art. 5 of the MD 2006/42/EC, machinery can be placed on the market or put into service only when it satisfies the relevant EHSR set out in Annex I of the MD. With regard to the applicable EHSR, Annex I section 1.2.4.3 of the MD 2006/42/EC requires for most machinery 1 to be fitted, with one or more emergency stop devices as shown for example in Fig. 1. Fig. 1: Emergency stop device This document deals only with the design of the emergency stop device, primarily with the mushroom type push button with regard to section 1.2.4.3. The document at hand 1 The second paragraph of section1.2.4.3 of Annex I of the MD 2006/42/EC sets out two exceptions where emergency stop devices are not required.

is not concerned with the location of the devices to be fitted, because this is dependent, for example on the size and configuration of the machinery, the number of operators, the location of the danger zones and the operation positions and maintenance points. With reference to the third paragraph of section 1.2.4.3, which sets out requirements for the design of emergency stop devices, such device must have clearly identifiable, clearly visible and quickly accessible control devices. Quoting the Guide to application of the MD, this is important because, in an emergency situation, a split-second reaction may be crucial. The requirement of the quick accessibility has consequences for both the choice of the type of control device and the number and location of control devices to be fitted. Harmonised standards, applicable to emergency stop devices The following harmonised standards substantiate the design and functioning of the emergency stop device. EN ISO 13850:2006, Safety of machinery emergency stop principles for design, specifies functional requirements and design principles for the emergency stop function on machinery, independent of the type of energy used to control the function. It is applicable to all machinery except for machines, in which the provision of emergency stop would not lessen the risk, and hand-held portable machines and hand-guided machines. It does not deal with functions such as reversal or limitation of motion, deflection, shielding, braking or disconnecting, which can be part of the emergency stop function. Concerning the color scheme of the red push button against a yellow background standardized in EN ISO 13850:2006 section 4.4.5, also standard EN 60073, Basic and safety principles for man-machine interface, marking and identification - Coding principles for indicators and actuators (IEC 60073:2002) can be used. This standard establishes general rules for assigning particular meanings to certain visual, acoustsic and tactile indications. The standard EN 60947-5-5 1997 + A1:2005, Low-voltage switchgear and controlgear - part 5-5: control circuit devices and switching elements - electrical emergency stop device with mechanical latching function is applicable to electrical control circuit 2

devices and switching elements which are used to provide an emergency stop signal. Where electrical switches are used, they should have direct opening action in accordance with EN 60947-5-1, Annex K. Such devices may be either provided with their own enclosure, or installed according to the manufacturer's instructions. Emergency stop devices An emergency stop device as shown in Figure 1 comprises a specific control device linked to the control system that gives a stop command and the components or systems necessary to stop the hazardous functions of machinery as quickly as possible, without creating any further risks. The device fulfills the design requirement of clearly identifiable regarding the color scheme of the red push button against a yellow background, as well as the requirement of clearly visible and quickly accessible. Emergency stop devices with protection measures to prevent unintended activation or damage At a certain type of machinery, mainly mobile machinery or machinery in the construction sector, emergency stop devices are used with protective measures, such as collars or shrouding as sown in Fig. 2, in order to assure its proper function also under demanding conditions. Those measures are sometimes provided to prevent unintentional activation, debris or process materials accumulating on the device and preventing its operation. Fig. 2: Emergency stop device with protection against unintended activation or damage 3

A protective collar must not have any sharp corners or edges or rough surfaces which could lead to injury. Corners and edges should be rounded and surfaces smooth to the touch. The protection collar must not impair the accessibility of the emergency stop device. A full protection collar is in principle not acceptable with regard to Annex I section 1.2.4.3 of the MD 2006/42/EC. However, its particular suitability could be demonstrated by testing. Requirements concerning the acceptable design of protective collars of emergency stop devices are not yet available in the relevant standards. However, it should be noted that the proposed amendment to EN ISO 13850 includes a test method to ensure that the collar does not impair accessibility. Disconnecting device as emergency stop According to market observations, also the disconnecting device as shown in Fig. 3 is used as emergency stop device. Fig. 3: Disconnecting device as emergency stop The supply disconnecting device is sometimes being locally operated to serve the function of emergency stop with regard to EN 60204-1 Safety of machinery Electrical equipment of machines Part 1: General requirements in which it is stated under section 10.7.4 Local operation of the supply disconnecting device to effect emergency stop : 4

The supply disconnecting device may be locally operated to serve the function of emergency stop when: it is readily accessible to the operator; and it is of the type: a) switch-disconnector, with or without fuses, in accordance with IEC 60947-3, utilization category AC-23B or DC-23B; b) disconnector, with or without fuses, in accordance with IEC 60947-3, that has an auxiliary contact that in all cases causes switching devices to break the load circuit before the opening of the main contacts of the disconnector; c) a circuit-breaker suitable for isolation in accordance with IEC 60947-2; d) any other switching device in accordance with an IEC product standard for that device and which meets the isolation requirements of IEC 60947-1 as well as a utilization category defined in the product standard as appropriate for on-load switching of motors or other inductive loads; When also intended for such use, the supply disconnecting device shall be coloured red. If a background exists immediately around the actuator, then this background shall be coloured yellow. See also ISO 13850. This allows supply disconnecting devices that meet these requirements to provide the emergency stop function. Nevertheless, it should be noted, that the supply disconnecting device is regarded as an exception and the normal emergency stop device should be used whenever possible. Stop devices covering the start and the stop-contact Stop devices covering the start and the stop-contact such as the flap stop (Fig. 4), is a special kind of stop device produced normally outside the EU, and used as a normal emergency stop for different machinery, in particular for smaller machines, such as bench drilling machines. 5

Fig. 4: Flap stop device (taken from the original Danish document MD ADCO 2005-19) The flap-stop is a start and stop contact, which is equipped with a yellow flap and a red mushroom-type push button (Fig. 4), covering both the start and the stopcontacts. When the mushroom push button is activated, the flap will press the stop button into a stop command position. The flap can be kept in an open position which cannot assure the availability at all times. The flap stop can therefore not provide the emergency stop function as required in Annex I section 1.2.4.3 of the MD 2006/427EC. Other stop devices Sometimes, Emergency stop device are designed as padlockable stop devices to make the isolation secure. More typically padlocks will be used with devices that can directly isolate equipment from the supply of electricity, such as disconnectors, switchdisconnectors, circuit-breakers etc. Other devices to interrupt the machine movement, such as mats, light curtains, laser scanners etc.) cannot be considered to be an emergency stop device. Those devices are protective devices (as required by EHSR 1.3.7 with 1.4.3 specifying their characteristics). They are part of the safety system for the machine operation and are not an emergency stop devise that should be provided in addition. 6