asense m III in industrial wall mounted housing / CO sensor with built-in general purpose controller

Similar documents
Installation manual CF8-W-Disp-AL

Installation manual CF3-D, CF3-D-Disp

Please Read Instruction Carefully Before Installation! Figure 1: A/CO2-DUCT

esense Duct (-Disp) Conduit

AQS51/61-KAM COMBINED CO 2 -/TEMPERATURE DUCT SENSOR/CONTROLLER

CDD4 Duct Carbon Dioxide Transmitter

CDD4 Series Room CO2 Transmitter Installation Instructions

Installation Guide. Carbon Dioxide (CO 2. ) Detectors. General Information. Mounting WARNING CAUTION. SAE-1011/1012 Space Mount SAE-1011/1012/1062

CDD Carbon Dioxide Transmitter

2001VT Temp & CO 2. - air quality sensor/controller NOTE!!! Manual for Installation. General. SenseAir AB

TOXALERT MODEL AIR 2000

Carbon Monoxide Sensor - ModBus

DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions

Schneider Electric s SCD series of duct mount sensors measure the levels of CO 2. , RH (if equipped) and temperature of air inside a duct.

Quick Start Guide. SEB-710 I/O Expansion board. Introduction

InBin-P Pressure switches from 5 Pa Pa

RTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions

Product Specification. tsense VAV. CO 2 -, Temperature- and RH- sensor in a housing with colour touch display

Installation Guide. Section 1 - Room... pg 03. Section 2 - Duct... pg 23. I-CDD3_Modbus Installation. Modbus Gas Transmitters I-CDD3 Series

DXTH DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY. Mounting and operating instructions

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

TPE 1464 Series Pressure Transducer

CODE 50108, 50110, 50164, 50165

Model HU-224/225. Technical Information TI.224/ Humidity Transduce r FOR ADDITIONAL INFORMATION SEE HU-224/225 DATA SHEET

CDD ModBus Carbon Dioxide Detector

The unit is designed for connecting to Direct Digital Control (DDC). The linear output functions are pre-programmed as CO 2

RXTP ROOM TEMPERATURE

Operation and Maintenance Manual

RТTH DUAL ROOM SWITCH

1 IF-812 or IF-815 Terminal (Slave) 2 Intended Use. 3 Assembly and Installation _V IF-812/IF-815

RF-RR-C 24V Powered Routers CO 2 and RH & T Sensors

InReg Volume flow controller Pa

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION

Output Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W

User Manual. PolyGard AT Infrared Carbon Dioxide transmitter Serial No. AT December, PolyGard is a registered trademark of MSR

Digital Keypad Introduction

RXTH DUAL ROOM SENSOR / SWITCH

MAXIMA + Series ROTARY LEVEL CONTROL

CONTENTS CONTROLLERS room controllers room units control units PRODUAL 3 CATALOGUE

HPS-M -2 DIFFERENTIAL PRESSURE TRANSMITTER. Mounting and operating instructions

Gas and Air Sensors. Product Specification. CO 2 Engine K30. Sensor Module and OEM Platform. Document PSP 110. Rev 4. Page 1 (11)

InCos-P Pressure sensor 20 Pa Pa

Carbon Monoxide Transmitter

Carbon Monoxide (CO) Gas Detection and Control System

DP DP2500 DP0250

EL7060 Series SERVICE MANUAL

1 IF-810 or IF-811 Terminal (Slave) 2 Intended Use. 3 Assembly and Installation _V IF-810/IF-811

PTC/PT100 board 2.0 Option

VFC. Operating manual TROX air terminal units Type VFC volume flow controllers. General information 2. VFC series volume flow controllers

Installation & Operation Guide

MAXIMA+ Series Rotary Level Indicator

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

BTU-4D/BTU-4D-I Digital Temperature Unit & Sensors. Installation and Operation Manual

MAXIMA + Series ROTARY LEVEL CONTROL

Multi-Point Gas Detection and Control System

The IQ240 panel mount load cell indicator is a precision digital indicator for load cell and strain gauge applications.

NMID. Remote control. SAPIM I/O number. SAPIM I/O number NBRN (RS485) ZM100. Relay, 24 VDC - + UO07 UI11 UI10 UI09 UI08 UI07 UI06 UI05 UI04 UI03 UI02

Instruction Manual. M Pump Motor Controller. For file reference, please record the following data:

Displays Transducers. Displays and transducers

AC300/AC400 SERIES DYNAMIC BRAKING and ADDITIONAL FORM C RELAY. INSTALLATION INSTRUCTIONS Document Number:

NSGV Series "90DM3" Carbon Dioxide Detector

EE360. High-End Moisture in Oil Transmitter. Typical applications. Features EE360 EE360. (+34)

HWS Series Wall Mount with Relay Setpoints, LCD, and Humidistat Control

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

BA Series. Single Action Ballhead. You re on steady ground 1

ZC-OH5 TAMPER-RESISTANT INDOOR/OUTDOOR HOUSING INSTRUCTION MANUAL FOR USE WITH GANZ ZC-D5000 SERIES MINIDOME CAMERAS

14 Pressure Measurement. Measuring Devices Description Pressure range Connection Device Page

Power-Over-Ethernet (PoE) Weatherproof 14 x12 x7 Enclosure with Mounting Plate and Cooling Fan. Model: NB F. Applications and Features

Installing Keypad and Backplate

Installation and Operation Instructions I/CO 2, I/CO 2 -VDC, I/CO 2 -T

Functional configuration Rated input voltage Power ratings Output voltage Output current Part number Non-PFC

DP2500 DP0250. Differential Pressure Transmitter. Product Bulletin

SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS

TRC-190 User s Manual

MODEL: M5DY SEN TRONIC AG CURRENT LOOP SUPPLY. [2] POWER INPUT AC Power M: V AC (Operational voltage range V, Hz)

Free Energy Band RCC30U Room Temperature Controller for Four-pipe Fan Coil Unit

PTC/PT100 board 2.0 Option

Product Specification. CO 2 Engine K30 STA. Sensor Module and OEM Platform

H7625B; H7635B,C; H7655B Duct-Mount and Outdoor-Mount Humidity/Temperature Sensors

256 Kbytes (1771-DRS) 1 Mbyte (1771-DRS1) 4 Mbytes (1771-DRS4) Installation Data

ATR121 Controller with Dual Setpoint

O 2 SENSORS Zirconium Dioxide (ZrO 2 ) Sensor and Interface Selection Guide

H7625A, H7635A Humidity/Temperature Sensors

EE310. High-End Humidity and Temperature Transmitter for Demanding Process Control. Typical applications. Features EE310 EE310

INSTRUCTION SHEET. Eaton Logic Controller ELCB Controllers

H3CA-8H-AC/100/110/120

TRC-190 User s Manual

Instruction Sheet Board Style Low Water Cutoff

ON/OFF HUMIDIFIER CONTROL (ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET OVERVIEW WALL CONTROLLER INSTALLATION (TCY-BH-T-U)

Multi-Point Gas Detection and Control System

BA/BS4S Temperature Sensor Installation & Operating Instructions

PTC/PT100 board 2.0 Option

AI-102. IR Illuminator. Installation Guide. Rev IP Surveillance

RTD-W Installation Instructions

Multi-Point Gas Detection and Control System

Chameleon Stand-alone

lindab we simplify construction UltraLink Technical information

C7110C1001A / C7110D1009A WALL MODULES

RTD-NET Installation Instructions

NEUROLOGIC RESEARCH CORPORATION MODEL 2500

Transcription:

Manual for Installation CO 2 asense m III in industrial wall mounted housing / CO sensor with built-in general purpose controller 9 10 2 1 6 10 8 3 4 5 7 Fig. 1 1 Wall plate 2 PCB (Factory supplied mounted in box) 3 Temperature sensor for internal compensation (not shown) 4 RH sensor for internal compensation (not shown) 5 Carbon monoxide sensor (not shown) 6 Hole for wall plate hooks 7 Snap-in lid 8 Locking screw of the lid (not shown) 9 PG9 cable entry bushing 10 Air holes EM_aSENSE miii_standard_nc_installation_jan'08.doc 1 of 4

85 (3,35) 38,5 (1,5) 10 (0,39) 9,5 (0,37) 142 (3,58) Fig. 2 11 Lidlocking screw 12 Wall plate 13 Screw to hold the wall plate 14 Marking to drill hole for PG7 15 Marking to drill hole for PG9 Wall Mounting Instruction 1. Dismount the wall plate. The sensor is delivered with the wall plate mounted. The wall plate has to be removed before the sensor is mounted onto the wall. Unscrew the screw on the side of the box. See figure 3. 2. Screw the wall plate onto the wall. The sensor should be mounted 1 to 1,8 m above the floor. The wall plate has holes for three screws. Drill holes for 3,5mm screws and put dowel into them. Dowels and screws 3,5 x 25mm are included in a plastic bag 3. Attach the sensor box to the wall plate. It is done by a snap-in fitting. The wall plate has three hooks that fit in holes in the sensor box. Fasten the screw on the side of the box. 4. Electrical cable entry. The box has a factory mounted cable entry bushing in dimension PG9. Never feed more than one cable through each cable entry bushing, or else gas might leak through! The lid can be locked with the screw (11) at the bottom of the sensor box. Please note! Normally the PCB should not be removed from the housing. If for some reason the PCB must be removed it must be handled carefully and protected from electrostatic discharge. EM_aSENSE miii_standard_nc_installation_jan'08.doc 2 of 4

Electrical connections The power supply has to be connected to G+ and G0. G0 is considered as system ground. The same ground reference has to be used for the asense m III unit and for any connected device! Unless different transformers are used, special precautions need to be taken. PLEASE NOTE! The signal ground is not galvanically separated from the asense m III power supply! PLEASE NOTE! The same ground reference has to be used for the asense m III unit and for the control system! Connection Terminal G+ G0 OUT 1 Function Electrical Data Remarks Power (+) Power ground (-) Analogue Output 1 (+) 24 VAC/DC+ (+-20%), 3W 24 VAC/DC- 0-10 VDC or 0-20 ma, 2-10 VDC or 4-20 ma, 2W without output load See note 1! According to positions of OUT1 jumper and start point selection. See note 2! OUT 2 Analogue Output 2 (+) Same as Output 1 According to positions of OUT2 jumper and start point selection. See note 2! M Relay Signal Ground (-) Normally closed Relay Open at alarm situations and power loss OUT4 Analogue Output 4 (+) Connected to G0 via PTC fuse Contact free relay minimum load 1mA/5V rated load 0,5A/125VAC; 1A/24VDC 0-10 VDC or Open Collector Max 0,5A, 55VDC / 40VAC (half-wave rectifier protection) DI1 Digital Input 1 Closed contact current 1mA Open contact voltage max 5V Table I. Electrical terminal connections for asense m III See note 1! Triggered by register OUT3 According to positions of OUT4. See note 2 & 3! Do not apply any voltage on this input! Note 1: The ground terminal is used as negative power supply DC input or AC phase ground G0 (halfwave rectifier). The signal ground M, protected by a PTC resistor, is the same as power ground G0 (permitting a 3-wire configuration). A single transformer may be used for the entire system. Note 2: asense m III can deliver both a voltage or a current loop for OUT1/OUT2. For OUT4 a voltage output or an open collector output is selected with jumper OUT4. To change between voltage and current output mode the hardware jumpers are used. There is one jumper for OUT1 and one for OUT2, so that one output can be a voltage output and the other a current output. Both, voltage output and current output, can have start points 0 % (0-10 VDC or 0-20mA) or 20% (2-10 VDC or 4-20mA) selected from PC software. See the function manual. Note 3: Current of Open Collector is internally returned to G0 terminal. EM_aSENSE miii_standard_nc_installation_jan'08.doc 3 of 4

DI1 Switch for alarm test Jumper for configuring the linear output start point to 0% or 20% start point Jumper to choose communication protocol Jumpers to choose between voltage or current outputs Jumper to choose between open collector or 0-10V linear signal Fig. 3.Terminals and jumpers on asense m III. The darker positions are default settings. No. Label Function (configurable) 3 OUT1 CO-transm. 0 100 ppm 4 OUT2 CO 2 -transm. 0 2000 ppm 6, 7 OUT3 Gas alarm CO >35 ppm or CO 2 >1500 ppm 8 OUT4 Drift disturbing alarm or gas alarm 9, 10 DI 1 Extra terminal.test function (N.O.) If more holes are needed the box has several drill markings for holes in two dimensions, PG7 and PG9. Then fasten the cable entry bushing and seal properly. Never feed more than one cable through each cable entry bushing, or else gas might leak through! The PCB can be removed during the making of holes. The PCB must be handled carefully and protected from electrostatic discharge! If the PCB is in the housing when the hole is made a background calibration, CALb, using the push buttons should be made. See the function and maintenance description. Start-up of the asense m III Connect the power directly after mounting. The unit works best if the sensor is continuously powered. The analogue outputs do not need to be connected before use. An internal delay function prevents the alarm functions of the relay and OUT4 output during 15 minutes after power up. After short power failures the CO measurements need this power up time to stabilize. The alarm outputs may be tested after the 15 minutes delay by shorting the switch DI1. After long power failures the sensor may need several days to restore the measuring functions. NOTE! The CO probe gives incorrect readings near some chemicals, e g silicone. This makes certain environments unsuitable for the sensor. EM_aSENSE miii_standard_nc_installation_jan'08.doc 4 of 4

Installation Manual for All Housings asense VAV CO 2 / temperature sensor with built-in general purpose controller for wall mounting 1 5 Dismounting of the sensor 4 3 2 1 top part 2 lid 3 front part 4 wall plate 5 screw 6 label with settings inside the top part 6 Pull the top part upwards 1 Push the front part with the lid upwards Fold the front part with the lid forwards while keeping the wall plate steady and loose it from the hooks (#1) EM asense-vav (Modbus) all housings installation Oct'08.doc 1 of 11

Mounting of the sensor A The wall plate is screwed onto the wall The screw heads should be max 4 mm B A Put the top tabs of the front part into the top holes of the wall plate. B Press the lower edge of the case onto the wall plate to latch DI1 The top part is pushed under the locking hooks of the wall plate and is secured with a screw Terminals and jumpers on asense VAV standard. The darker positions are default settings. Terminals and jumpers are located under the top part. If for some reason the PCB must be removed it must be handed carefully and protected from electrostatic discharge! Normally, removing the PCB is not required. EM asense-vav (Modbus) all housings installation Oct'08.doc 2 of 11

Dimensions and holes 83(3,26) 31(1,22) 120(4,72) Dimensions of sensor in mm and (inches) 30(1,18) 30(1,18) 29,8(1,17) 7,8(0,31) 4,2(0,16) 2(0,08) Dimensions of mounting plate in mm and (inches) 30(1,18) 52,5(2,07) 25(0,98) EM asense-vav (Modbus) all housings installation Oct'08.doc 3 of 11

asense VAV CO 2 / temperature sensor with built-in general purpose controller for mounting in ventilation ducts 1 2 1 2 3 9 4 5 6 7 1 Sampling probe 6 O-ring 29,2x3,53 (Factory supplied mounted in box) 2 Sealing gasket 7 PCB (Factory supplied mounted in box) 3 Largest locking nob 8 Snap-in lid 4 2 washers BRB 5,3x10x1 9 PG9 cable entry bushing 5 2 screws RXS 4,8x16 8 EM asense-vav (Modbus) all housings installation Oct'08.doc 4 of 11

Mounting of asense VAV on to the duct. 10 11 10 Hole with 25 mm diameter 11 Temperature sensor with 110 mm cable mounted in the sampling probe Mounting Instruction Since there might be a substantial pressure difference in duct mounting applications, it is essential to avoid ambient air from suction into the duct-mounting box. For correct function it is indispensable that the sealing of the box cover, the cable entry bushings, the cable feed through and the duct entrance are absolutely tight. The duct entrance may need extra sealing paste in order to prevent leakage. The PCB must be handed carefully and protected from electrostatic discharge. 1) Electrical cable entry: The box has a factory mounted cable entry bushing in dimension PG9. Never feed more than one cable through each cable entry bushing, or else gas might leak through! 2) Mounting the tube: Drill a hole (10) with 25 mm diameter (or 1 inch) for the sampling probe and two holes with 4 mm diameter for the screws (5) into the air duct and mount the tube (1) with the gasket (2). The sampling probe should be mounted with the largest locking knob on top. The unit can be mounted with the air coming from the left or right. 3) Attaching the sensor box is made to the sampling probe by a snap-in bayonet fitting. First, carefully stick the temperature probe (11) into the sampling probe. (1). Orient the box onto the sampling probe so that the box upside is on the same side as the largest locking knob (3). When the probe is fitted into the notches of the box, then turn the box clockwise until stop (see Figure 1). Position 1 indicates open where the box can be removed from the sampling probe. In position 2 the box is locked to the probe. EM asense-vav (Modbus) all housings installation Oct'08.doc 5 of 11

DI1 Terminals and jumpers on asense VAV standard.the darker positions are default settings. Dimensions 85(3,35) 35(0,38) 10(0,39) 85 (3,35) 40(1,57) 141,8 (5,58) 9,5(0,37) 24(0,94) 22 (0,87) 203,4(8,01) 2,7(0,04) 40,3(1,59) Dimensions of sensor in mm and (inches) 56 (2,2) 6 (0,24) 55 (2,16) 66 (2,6) Dimensions of sampling probe in mm and (inches) EM asense-vav (Modbus) all housings installation Oct'08.doc 6 of 11

asense VAV CO 2 / temperature sensor with built-in general purpose controller mounted in industrial housing 1 4 7 8 8 6 3 2 5 1 Wall plate 5 Snap-in lid 2 PCB (Factory supplied mounted in box) 6 Locking screw of the lid (not shown) 3 Temperature sensor 7 PG9 cable entry bushing 4 Hole for wall plate hooks 8 Air holes EM asense-vav (Modbus) all housings installation Oct'08.doc 7 of 11

9 Lid locking screw 10 Wall plate 11 Screw to hold the wall plate 12 Drill mark for cable entry bushing 13 Drill mark for cable entry bushing Dismounting the wall plate The sensor is delivered with the wall plate mounted. The wall plate has to be removed before the sensor is mounted onto the wall. Unscrew the screw on the side of the box. See figure 3. Wall Mounting Instruction Normally the PCB should not be removed from the housing. If for some reason the PCB must be removed it must be handed carefully and protected from electrostatic discharge. 1) Electrical cable entry: The box has a factory mounted cable entry bushing in dimension PG9. Never feed more than one cable through each cable entry bushing, or else gas might leak through! 2) Screw the wall plate onto the wall: The wall plate has holes for three screws. Drill holes for 3,5mm screws and put dowel into them. Dowels and screws 3,5 x 25mm are included in a plastic bag 3) Attaching the sensor box to the wall plate is done by a snap-in fitting. The wall plate has three hooks that fit in holes in the sensor box. Fasten the screw on the side of the box. 4) The lid can be locked with the screw at the bottom of the sensor box. If for some reason the PCB must be removed it must be handed carefully and protected from electrostatic discharge! Normally, removing the PCB is not required. EM asense-vav (Modbus) all housings installation Oct'08.doc 8 of 11

DI1 Terminals and jumpers on asense VAV standard. The darker positions are default settings. 85 (3,35) 38,5(1,5) 10(0,39) 9,5 (0,37) 85 (3,35) 141,8 (5,58) 40 (1,57) Dimensions of sensor in mm and (inches) 63(2,48) 42(1,65) 66(2,60) 39,9(1,57) Ø5(0,20) Ø5(0,20) 40,5(1,59) 17,5(0,69) 41(1,61) Ø5(0,20) 82(3,23) Dimensions of wall plate in mm and (inches) EM asense-vav (Modbus) all housings installation Oct'08.doc 9 of 11

Electrical connections The power supply has to be connected to G+ and G0. G0 is considered as system ground. The same ground reference has to be used for the asense VAV unit and for any connected device! Unless different transformers are used, special precautions need to be taken. PLEASE NOTE! The signal ground is not galvanically separated from the asense VAV power supply! NOTE! The same ground reference has to be used for the asense VAV unit and for any connected device! If possible keep the sensor powered up after mounting. Connect the analogue output before measuring. Connection Terminal Function Electrical Data Remarks G+ G0 Power (+) Power ground (-) 24 VAC/DC+ (+-20%), 3W 24 VAC/DC- 2W without output load See note 1! OUT 1 Analogue Output 1 (+) 0-10 VDC or 0-20 ma, 2-10 VDC or 4-20 ma, According to positions of OUT1 jumper and start point selection. See note 2! OUT 2 Analogue Output 2 (+) Same as Output 1 According to positions of OUT2 jumper and start point selection. See note 2! M Signal Ground (-) Connected to G0 via PTC fuse See note 1! Relay Relay Normally open Contact free relay minimum load 1mA/5V rated load 0,5A/125VAC; 1A/24VDC Triggered by register OUT3 OUT4 Analogue Output 4 (+) or Open Collector 0-10 VDC Max 0,5A, 55VDC / 40VAC (half-wave rectifier protection) According to positions of OUT4. See note 2 & 3! DI1 DI1 Digital Input 1 Closed contact current 1mA Open contact voltage max 5V Table I. Electrical terminal connections for asense VAV Do not apply any voltage on this input! Note 1: The ground terminal is used as negative power supply DC input or AC phase ground G0 (halfwave rectifier). The signal ground M, protected by a PTC resistor, is the same as power ground G0 (permitting a 3-wire configuration). A single transformer may be used for the entire system. EM asense-vav (Modbus) all housings installation Oct'08.doc 10 of 11

Note 2: asense VAV can deliver both a voltage or a current loop for OUT1/OUT2. For OUT4 a voltage output or an open collector output is selected with jumper OUT4. To change between voltage and current output mode the hardware jumpers are used. There is one jumper for OUT1 and one for OUT2, so that one output can be a voltage output and the other a current output. Both, voltage output and current output, can have start points 0 % (0-10 VDC or 0-20mA) or 20% (2-10 VDC or 4-20mA) selected from PC software. Note 3: Current of Open Collector is internally returned to G0 terminal. DI1 Terminals and jumpers on asense VAV standard. DI1 Terminals and jumpers on asense VAV with communication jumper EM asense-vav (Modbus) all housings installation Oct'08.doc 11 of 11