Pre-programmed room controller with display and communication

Similar documents
RC-CDTO. Pre-programmed room controller with display, communication and three-point control

Pre-programmed room controller with display and communication

STRA-17 Room controller. Installation and maintenance manual. Content

RCF-230CD. Communicating room thermostat for fan-coil applications with on/off outputs

RCF-230CAD. Room controller with communication for fancoil applications with two analogue V DC outputs

RCF-230CAD. Communicating room controller for fan-coil applications with two analogue V DC outputs

Room controller STRA-17

RCF-230CTD. Room controller for fan-coil applications with outputs for two thermal or one 3-position actuator or function for an electric heater

RCF-230CTD. Built-in or external sensor The controller has a built-in sensor. Alternatively, the input for an external PT1000-sensor can be used.

EXOcompact. Third generation freely programmable controllers

WE TAKE BUILDING AUTOMATION PERSONALLY MANUAL RCF

Evolution TH. Pre-configured controller with display, clock and communication. Evolution. Applications. TH version. Sensors

AIAS. Technical description

OP10. Pre-programmed, configurable controller for simple applications

Constant & Variable air volume controllers

TAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta

EXOcompact. Freely programmable controller

HLS34 Modbus FCU/VAV Controllers installation instructions

Field selectable application type and room module series, via dip-switches on controller

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

Semi Flush-mount Room Temperature Controllers with LCD

Room Temperature Controller

FCU-4 FAN COIL CONTROLLER

Room Temperature Controllers

FCU-MULTI Modbus Fan Coil Unit Controller

Semi flush-mounted room temperature controllers with LCD

TAC Xenta 121-FC Programmable Fan Coil Application

Corrigo E. Version 3.0 (ventilation), 3.0 (heating), 1.1 (boiler). Controllers for heating, boiler and ventilation applications in buildings.

Communicative controller for VAV systems

Room Temperature Controller

EC-PU4. Processor unit with 4 communication ports

CONTENTS CONTROLLERS room controllers room units control units PRODUAL 3 CATALOGUE

Temperature controller Ducted systems

Non-communicating room controllers

FCU-4 FAN COIL CONTROLLER

O P T I G O R E A D Y - S T E A D Y - G O Optigo OP5U Manual Copyright AB Regin, Sweden, 2012

Universal Controller

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

Semi flush-mounted room temperature controllers with LCD

UC102 basic version with display and knob UC102BL version with display, knob and backlight UC102DK version without knob and display

TC-8900 Controller Units with PM-8900 Power Modules

7-day room temperature controller

RDF301 RDF CE1N3171en 02 Jun 2010 Building Technologies

Master room unit for RRV controllers

EY-RU : Room operating unit, ecounit

OEM. Room unit QAA822 with2- wire interface. Building Technologies CLIMATIX TM. For use with Climatix controllers

Non-communicating room controllers

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

SE7600E Series Application Guide

Technical data sheet

UCU Room Display. Operation Modes. Features. Applications DATASHEET

Control system. Type FSL-CONTROL II. Modular, stand-alone room control system, specially for decentralised ventilation systems (with bus communication

Room unit with PPS2 interface

TAC Xenta 121-HP Programmable Heat Pump Application

ED-T7. External touch display, 7 inch. Function. Installation The display can be mounted, for example, on the operation panel of the control cabinet.

MOD-RI Room Interface Modules with Modbus

Specification Sheet For electronically commutated motors

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

EYE 200: DDC single-room controller, ecos200

TM-2100 Series Room Command Module

SE8300 Room Controller

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification

Heating Circuit Controller

TM-2100 Series Room Command Module

EY-RU : Room operating unit, ecounit

Room sensors QFA4160 QFA41 D AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

Allure EC-Smart-Comfort Series

SE7600E Series Application Guide

7-day room temperature controller

Weekday / weekend room temperature controller

Automation System TROVIS 5400 District Heating Controller TROVIS 5476

Room thermostat with KNX communications For VAV heating and cooling systems

EY-RU 355: Room operating unit, ecounit355

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

Small distributed I/O module

Allure EC-Smart-Comfort Series

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

EXOcompact Third Generation Manual

MOD-IO9 Modbus Input / Output Modules, Wall Mounted

SmartStruxure SmartStruxure Lite ZENO InnPoint. ZENOcontrols.com. compatible with

Temperature Controller (Heat Pumps)

EY-EM : Remote I/O module, ecolink

RXTP ROOM TEMPERATURE

FXVMA Variable Air Volume (VAV) Box Controller

Heating Circuit Controller

Output Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W

EY-RU : Room operating unit, ecounit

Room unit with PPS2 interface

EY-RU : Room operating unit, ecounit

Product Catalog. Tracer Controller MP501 BAS-PRC008-EN. May 2012

BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

LM24A-MOD. Cable 1 m, 6 x 0.75 mm 2 RJ12 socket

Weekday / weekend room temperature controller

Datasheet. ECB-PTU Series. 1/14. BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

TLR-D42 with OPA-D42 Intelligent PI fan coil controller for modulating actuators. Cabinet mounted base, wall mounted operation terminal.

LLR-MOD Modbus Light Level and Occupancy Sensor

BACnet Product Overview

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

VZ7000 Series. BACnet Commercial Zoning System

Transcription:

revision 01 2014 RC-C3DOC Pre-programmed room controller with display and communication RC-C3DOC is a complete pre-programmed room controller from the Regio Midi series intended to control heating, cooling and CO 2 in a zone control system. Awarded design Communication via RS485 (Modbus, BACnet or EXOline) Fast and safe configuration via Regio tool Simple installation RC-C3DOC is a room controller from the Regio series. It has a display and communication via RS485 (Modbus, BACnet or EXOline) for integration into systems. Regio Regio is a wide series of controllers which handle heating and cooling. The controllers are divided into three different series, Mini, Midi and Maxi. Mini are pre-programmed, stand-alone controllers. Maxi consists of freely programmable controllers with communication. The Midi group, to which RC-C3DOC belongs, are pre-programmed controllers with communication. Applications The Regio controllers are suitable in buildings where you want optimal comfort and low energy consumption, for example offices, schools, shopping centres, airports, hotels and hospitals etc. See application examples on page 4. Design The controllers have a modern design. The design has been awarded the 2007 if product design award. Sensor The controller has a built-in temperature sensor. An external PT1000-sensor can also be used. There is also an input for a CO 2 - sensor. product design award 2007 On/Off or 0...10 V control Backlit display Input for occupancy detector, window contact, condensation detector, CO 2 -sensor and change-over function Easy to install The modular design with a separate bottom plate for wiring makes the whole Regio series easy to install and commission. The bottom plate can be put into place before the electronics are installed. Mounting is directly on the wall or on an electrical connection box. Flexibility with communication RC-C3DOC can be connected to a central SCADA-system via RS485 (EXOline, BACnet or Modbus) and configured for a particular application using the cost-free configuration tool Regio tool. Read more about Regio tool on page 3. Actuators RC-C3DOC can control 0...10 V DC actuators for valves or dampers and/or 24 V AC thermal or On/Off spring return actuators and damper.

Display handling The display has the following indications: Setpoint Indoor / outdoor temp. OFF: The controller is off It is possible to set different parameter values in a parameter menu in the display, using the buttons on the controller. You change parameter values with the INCREASE and DECREASE buttons and confirm changes with the Occupancy button. Control modes RC-C3DOC can be configured for different control modes/control sequences: Heating Heating/Heating Heating/Cooling via change-over Heating/Cooling Heating/Cooling with VAV-control and forced supply air function Heating/Cooling with VAV-control Cooling Cooling/Cooling Forced ventilation STANDBY: Standby indication SERVICE: Setting parameters Occupancy button Heating/Cooling/VAV Changeable value Occupancy indication Current room temperature in C to one decimal point Open window COOL/HEAT: Shows if the unit controls according to the heating or cooling setpoint INCREASE DECREASE Operating modes There are five different operating modes: Off, Unoccupied, Stand-by, Occupied and Bypass. Occupied is the preset operating mode. It can be changed to Stand-by in the parameter menu in the display. The operating modes can be activated via a central command, an occupancy detector or the Occupancy button. Off: Heating and cooling are disconnected. However, frost protection is still active (Factory setting (FS)=8 C). Operating mode Off is activated on open window. Unoccupied: The room where the controller is placed is not used for an extended period, for example during holidays or long weekends. Both heating and cooling are limited to a temperature interval with configurable min/ max temperatures (FS min=15 C, max=30 C). Stand-by: The room is in an energy save mode and is not used at the moment. This can for example be during nights, weekends, evenings etc. The controller is prepared to change operating mode to Occupied if someone enters the room. Both heating and cooling are limited to a temperature interval around the applicable setpoint (FS heating setpoint value=-3 C, cooling setpoint=+3 C). Occupied: The room is in use and is therefore in a comfort mode. The controller regulates the temperature around a heating setpoint (FS=22 C) and a cooling setpoint (FS=24 C). Bypass: The temperature in the room is controlled in the same way as in operating mode Occupied. The output for forced ventilation is also active. Bypass is useful for example in conference rooms, where many people are present at the same time for a certain period of time. When Bypass has been activated by a press on the Occupancy button, the controller will automatically return to the preset operating mode (Occupied or Stand-by) after a configurable time (FS=2 hours). If an occupancy detector is used, the controller will automatically return to the preset operating mode after 10 minutes absence. Bypass can also be activated by a high level of CO 2. CO 2 -control A CO 2 -sensor is connected to AI2. In control modes where VAV (Variable Air Volume) is chosen, the dampers will be affected by the CO 2 -level (UO2/UO3 depending on control mode). On increasing CO 2 -level the damper opens to increase the quantity of air, regardless of the temperature requirements of the controller. The damper starts opening when the CO 2 -level exceeds CO 2 -level for starting opening damper, and is fully open at CO 2 -level for fully opened damper. Occupancy detector By connecting an occupancy detector, RC-C3DOC can switch between Bypass and the preset operating mode (Occupied or Stand-by). The temperature is then controlled according to requirement, which saves energy and keeps the temperature at a comfortable level. The Occupancy button If you press the Occupancy button for less than 5 seconds when the controller is in the preset operating mode, the controller changes to operating mode Bypass. If you press the button for less than 5 seconds when the controller is in Bypass, it changes operating mode to the preset operating mode. 2

When the Occupancy button is held depressed for more than 5 seconds, the controller changes operating mode to Shutdown (Off/Unoccupied), regardless of the current operating mode. Via the display or Regio tool, you can configure which operating mode, Off or Unoccupied, should be activated on Shutdown (FS=Unoccupied). If you press the Occupancy button for less than 5 seconds in Shutdown, the controller returns to Bypass. Control of a third sequence (damper) In control mode Heating/Cooling/VAV, the controller works using three sequences. When the controller is in cooling mode, the output signal is split between UO2 (cooling) and UO3 (VAV), while in heating mode it will control the heat demand via UO1. EC fan control EC fan control is activated when setting UO3 to Control of EC fan in the parameter list or via Regio tool. When the function is activated, UO3 will follow UO1 and UO2 respectively. The function can be activated in the control modes Heating, Heating or Cooling via change-over, Heating/Cooling, Cooling and Cooling/Cooling. Change-over function RC-C3DOC has an input for change-over that automatically resets output UO1 to operate with heating or cooling function. The input can be connected to sensors of the type PT1000 and have the sensor mounted so that it senses the temperature on the supply pipe to the coil. As long as the heating valve is more than 20 % open, or every time a valve exercise is performed, the difference in between the media and room temperature will be calculated. The control mode will change depending on the temperature. As an alternative, a potential-free contact can be used. When the contact is open, the controller works with the heating function and when it is closed with the cooling function. Setpoint In Occupied mode, the controller operates from a heating setpoint (FS = 22 C), or a cooling setpoint (FS = 24 C) that can be changed using the INCREASE and DECREASE buttons. Pressing on INCREASE increases the current setpoint by 0.5 C with each press up to the max. limit (FS = +3 C). Pressing on DECREASE decreases the current setpoint by 0.5 C with each press down to the min. limit (FS = -3 C). Switching between heating and cooling setpoints is done automatically in the controller depending on the heating and cooling requirement. Built-in safety functions RC-C3DOC has an input for a condensation detector which prevents condensation. The controller also has frost protection. It prevents frost damages by ensuring that the room temperature does not drop below 8 C when the controller is in Off-mode. Actuator exercise All actuators are exercised. The exercise takes place at set intervals in hours (FS=23 hours interval). An opening signal is sent to the actuator for as long time as the run time has been configured. Then a closing signal is sent for as long time and the exercise is finished. The exercise is switched off if the interval is set to 0 hours. Configuration and supervision with Regio tool RC-C3DOC is pre-programmed on delivery, but can be configured using Regio tool. Regio tool is a PC-based program that makes it possible to configure and supervise an installation, and change settings, via a clear and easy user interface. The program can be downloaded free of charge from Regin s homepage www.regin.se. Forced ventilation Regio has a built-in function for forced ventilation. When the digital input for an occupancy detector is closed, the controller will enter into Bypass mode and the output for forced ventilation (UO3) will be activated, thereby opening for instance a damper. The function is ended when the forcing interval (settable) has expired. Depending on the configuration of UO3, the output signal will be either 24 V AC (digital) between terminal 20 and output UO3, or 10 V DC (analogue) between terminal G0 and output UO3. Flow calculation AI2 can be configured as a flow calculation input. A flow corresponding to 0 V and one corresponding to 10 V is set, and the flow is then calculated linearly between these two end points. 3

Application examples ROOM 2 ROOM 3 ROOM 4 SCADA RS485 (EXOline alt. Modbus or BACnet) RS485 Window contact Condensation detector IR EXO4 TCP/IP HUB TCP/IP EX8282 EX8282 RS485 RS485 RC-C... RC-C... Temp EX8282 RC-C... ROOM 1 4

Technical data Supply voltage Internal consumption Ambient temperature Storage temperature Ambient humidity Protection class Communication Modbus BACnet Communication speed Display Built-in temperature sensor Material, casing Weight Colour Inputs External room sensor Change-over alt. potential-free contact Occupancy detector Condensation detector alt. window contact Outputs Valve actuator (0...10 V), thermal actuator (pulse On/Off) or On/Off actuator (UO1, UO2) Valve actuator Thermal actuator On/Off actuator Control Damper actuator or EC fan (UO3) Forced ventilation Control 18...30 V AC, 50...60 Hz 2.5 VA 0...50 C -20...+70 C Max 90 % RH IP20 RS485 (EXOline or Modbus with automatic detection/change-over, or BACnet) 8 bits, 1 or 2 stop bits. Odd, even (FS) or no parity. MS/TP 9600, 19200, 38400 bps (EXOline, Modbus and BACnet) or 76800 bps (BACnet only) LCD with background illumination NTC type, measuring range 0...50 C, accuracy ±0.5 C at 15...30 C Polycarbonate, PC 110 g Cover: Polar white RAL9010 Bottom plate: Light gray EMC emissions & immunity standards: This product conforms to the requirements of the EMC Directive 2004/108/EC through product standards EN 61000-6-1 and EN 61000-6-3. RoHS: This product conforms to the Directive 2011/65/EU of the European Parliament and of the Council. PT1000-sensor, 0 50 C. Suitable sensors are Regin s TG-R5/PT1000,TG-UH/PT1000 and TG-A1/PT1000. PT1000-sensor, 0 100 C. Suitable sensor is Regin s TG-A1/PT1000. Closing potential-free contact. Suitable occupancy detector is Regin s IR24-P. Regin s condensation detector KG-A/1 resp. potential-free contact 2 outputs 0 10 V, max 5 ma 24 V AC, max 2.0 A (time-proportional pulse output signal) 24 V AC, Max. 2.0 A Heating, cooling or VAV (damper) 1 output 24 V AC, max 2.0 A, alt. 0...10 V, max. 5 ma Forced ventilation, alt. EC-fan or damper following heating/cooling in sequence Actuator exercise FS = 23 hours interval Terminal blocks Lift type for cable cross-section 2.1 mm 2 Setpoint settings via Regio tool or in the display Basic heating setpoint 5...40 C Basic cooling setpoint 5...50 C Setpoint displacement ±0...10 C (FS = ±3 C) 5

Wiring Terminal Designation Operation 10 G Supply voltage 24 V AC 11 G0 Supply voltage 0 V 12-14 No function 20 GDO 24 V AC out common for DO 21 G0 0 V common for UO (when 0...10 V actuator is used) 22 UO3 Output for forced ventilation damper. 24 V AC, alt. EC fan following heating/ cooling output, alt. damper following cooling in sequence. 23 UO1 Output for 0...10 V valve actuator alt. thermal actuator, alt. On/Off actuator, heating (FS), cooling or heating/cooling via change-over. 24 UO2 Output for 0...10 V valve/damper actuator alt. thermal actuator, alt. On/Off actuator, heating or cooling (FS) 30 AI1 Input for external sensor, alt. change-over sensor 31 A12 Input for CO 2 - sensor, 0...10 V DC, alt. air flow 32 DI1 Input for occupancy detector, alt. window contact, alt. change-over digital 33 DI2/CI Input for Regin s condensation detector KG-A/1 alt. window contact, alt. change-over digital 40 +C 24 V DC out common for UI and DI 41 AGnd Analogue ground 42 A RS485 communication A 43 B RS485 communication B Dimensions 60 68 95 28 mm Product documentation Document Regio Midi manual Installation instruction Regio RC-C3DOC Product sheet TG-R4/PT1000, TG-R5/PT... Product sheet TG-UH/PT... Product sheet CO2RT (-D) Product sheet IR24-P Instruction IR24-P Product sheet KG-A/1 Type Manual for the controllers from the Regio Midi series Installation instruction for RC-C3DOC Information about sensors suitable for RC-C3DOC Information about occupancy detector suitable for RC-C3DOC Information about condensation detector for the Regio controllers All product documentation is available at www.regincontrols.com. Head Office Sweden Phone: +46 31 720 02 00 Web: www.regin.se Mail: info@regin.se